design degree of utilisation, web post fail- Licensee PAGEPress, Italy
the beam. As the web post failure may occur
ure may occur before the section reaches Fire Research 2017; 1:27
before the section reaches the limiting tem-
on
the critical temperature of members in doi:10.4081/fire.2017.27
perature, usually an increase in the fire pro-
bending (Figure 3). This is due to the fact
tection may be required for members with
that the temperature of the web-post in a
web openings in comparison to its equiva-
e
cellular beam increases at a faster rate com- lar beams as their use has increased.
lent solid section. The aim of this work is to us
pared to its equivalent (similar web size) The fire resistance design of cellular
present an experimental study of unloaded
solid beam. If the temperature of the web- beams was controversial in last decade,
solid and cellular beams with circular holes
post increases faster than expected, the cel- with most of the debate being concerned
in fire conditions with and without intumes-
al
lular beam failure may occur by local buck- with their requirements for intumescent
cent fire protection. These preliminary tests
ling instability of the web-post between the
results are the basis for generating an ele- protection. The mentioned empirical pre-
ci
to assess cellular beams with intumescent the basis of the fire resistance test results on
modulus of steel reduces rapidly in compar-
protection and give experimental results for beams coated with intumescent products.6
ison to its strength, which results in more
m
will need a higher fire protection compared about the same time giving a more general
the behaviour of equivalent solid beams,
to an equivalent solid beam. Also, a special method of calculating the increased DFTs.
when a fire protection is used, an increase in
care is needed when the intumescent coat- The cellular beams parameters used in AD
the fire protection thickness may be
ing is applied around the hole to avoid the 269 were: the ration of Span/depth, distance
required for members with web openings.
intumescent contraction, applying for between holes and its diameter (S/do), the
Traditionally the design guidance Fire
example an over coating. web-post width, the web hight to thickness
Protection for Structural Steel in Buildings
from the Association for Specialist Fire ratio and the degree of utilization at cold
Protection (ASFP), known as the Yellow design.7
Book, until its 3rd edition,5 indicates that a From the fact that different intumescent
Introduction 20% increase in thickness of passive fire coatings behaved differently, a testing pro-
Cellular beams are widely used in protection material should be used for cedure was developed to allow coatings
multi-storey buildings, especially to members with web openings (the 20% manufactures to test their products on a set
achieve long spans and the same time pro- being 20% increase in thickness from that of specified cellular beams.8 This methodol-
viding passage for ducts, cables and other required for the solid section). This 20% ogy required that one loaded cellular beam
technical installations. These beams are rule is for passive fire protection thickness, and four short unloaded cellular beams
steel sections with distributed circular open- and has therefore been widely used for int- were tested. From the tests, the tempera-
ings that are produced by cutting and weld- tures of the web posts and bottom flanges
ing hot rolled steel sections (Westok mescent coating thickness (DFT) on cellu- were measured and the ratios of web post
temperature to bottom flange temperature temperatures depends on type and thickness widths and section factors to be evaluated,
calculated for each web post width. This of the intumescent fire protection. instrumented with thermocouples around
data allows to draw a regression line of the It is recognised that the intumescent fire the holes, web post and bottom flange, as
ratios in function of web post widths and the protection thickness required to provide a standardized in prEN 13381-9.10 The sec-
failure temperature is converted to the given fire resistance to a cellular beam tions must be fabricated with welded plates
required protection thickness using the depends on its web thickness, the hole to ensure a constant thickness, and a differ-
multi-temperature loading tables defined shape and dimensions, the width of the web ent set of standard cellular sections are
for different fire resistant times and sections post, the degree of the beam asymmetry and specified for 60, 90 and 120 minutes fire
factors of the beam taken as 1400 divided the structural utilisation factor, as well as resistance assessment.
by the web thickness. the protection efficiency of the intumescent This MTA shall be carried out on the
After a great effort from the coatings coating.8 web and bottom flange separately generat-
manufactures to produce the DFT tables for The assessment method of cellular ing an elemental multi-temperature analysis
cellular beams, and with the used of beams beams protected with intumescent coatings (EMTA). The assessment procedure is used
with rectangular and elongated holes, a needs a multi-temperature analysis (MTA) to establish: i) The thermal performance
more general protocol (engineering based) of the coating assessment on solid beams, based on testing unloaded steel sections; ii)
was established valid for rectangular and for each fire protection period, performed the temperature ratio between the web post
oval holes. This does not require the loaded accordingly to EN 13381-8.13 The solid and the web reference temperature; and iii)
beam to be tested and the major difference beam assessment provide a DFT baseline the EMTA from EN 13381-8 shall be
is that the web post temperatures are com- against which a suitable enhancement for reassessed and reported against elemental
pared to the temperature of a plain web, cellular beams is added. Each fire test is A/V for each fire resistance period (Figure
instead of the bottom flange.9 This assess- carried out using five cellular beam sec- 3).
ment procedure was also on the basis for the tions, which enables a range of web post
ly
establishment of the European standard
prEN13381-9.10
on
e
Materials and Methods
Assessment of cellular beams pro-
us
tected with intumescent coatings
al
The questions raised about the tempera-
ture of the web post being higher than a
ci
Test program
The set of experimental tests performed
at the Polytechnic Institute of Bragança to
evaluate the behaviour of solid and cellular
beams with and without fire protection is
the presented in Table 1. The table shows
the set of performed experimental tests con-
sidering solid beams with and without intu-
mescent protection and also cellular beams
with and without intumescent fire protec-
tion. Figure 4 shows different steps of the
coating application process. The aim was to
Figure 4. Application of the primer and intumescent coating to the profiles.
ly
length and in case of the cellular sections
the circular holes cut directly from the web,
on
resulting in a section with the same height,
as represented in the Figure 5. Figure 5. Test setup, position and numbering of the thermocouples.
e
Experimental setup and element
instrumentation
The fire resistance tests were performed
us
on a fire furnace with interior dimensions of
al
1x1x1 m3, insulated with refractory bricks
and ceramic fibber. It is a gas furnace with
ci
plate thermocouple.
For the analysis of the steel temperature
m
Figure 6. Tests P12 and P15 before (left) and after (right) the test.
unprotected beams the thermocouples wires
were welded to the steel surface, but for the
sections with fire protection, the thermo-
N
lular beams in smaller than its equivalent intumescent fire protection, the temperature
Results and Discussion solid beam. The web post average tempera- evolution is presented in Figure 10. The
The steel temperature evolution of the ture after a fire exposure of 15 and 30 min curves present a higher non-uniformity of
tests was measured by the attached thermo- is equal to 655.5 and 812.3ºC for the solid the temperature in the elements, when com-
couples. The flange temperature is deter- beam P1, and equal to 640.2 and 799.4ºC in pared to the unprotected beams.
mined by the thermocouples T9 to T12 and the case of the cellular beam P9, respective- A comparison is presented in Table 1 for
the web post temperatures by the thermo- ly. The average temperature in the flanges all tested beams, regarding the fire exposure
couples T1, T2 and T3. The data obtained for the same fire exposure periods are 650.7 time, in completed minutes, to reach a refer-
from T7 and T8 can be used to verify the and 811.7ºC for the solid beam P1, and ence temperature of 550ºC, and the beam
non-uniform temperature distribution 638.3 and 801.3ºC in the cellular beam P9, temperature for 30 minutes of fire exposure.
across the section due to the three-side fire respectively. Considering the global mean temperature of
exposure. During the test some of the ther- For the case of solid (P3 and P4) and the beams, the time to reach a temperature
cellular beams (P13 and P16) tested with of 550ºC is 36 and 49 minutes for the solid
mocouple temperatures presented some
unrealistic fluctuations, possibly due to an
intermittent contact to steel and as a conse-
quence were disregarded from the follow-
ing graphs and analysis.
The temperature results from the unpro-
tected solid and cellular beams are present-
ed in Figure 8.
Considering for comparison the results
of the tests P1 and P9, a solid and a cellular
ly
beam tested simultaneously, one can com-
pare the evolution of the mean temperature
on
of the web post temperature (WT), from T1
to T3, and the mean flange temperature
(FT), from T9 to T12, presented in Figure 9.
e
In both elements, the temperature of the cel- us
Figure 7. Tests P4 and P3 before (left) and after (right) the test.
al
ci
er
m
m
co
on
N
beams P3 and P4, respectively, but for the paint. The experimental temperature results time of 25 minutes is achieved for solid
cellular beams P13 and P16 the time show intumescent coating efficiency when beams, while for cellular beams with a hole
decreases significantly to 28 minutes in applied to solid beams and also for cellular diameter of 160 mm the increase is equal to
both beams. beams, resulting from its application an 17 minutes.
The intumescent coating expansion of increase fire the resistance time in both Tests performed in cellular beams with
the cellular beams P13 and P16, protected cases. Considering for example the time web posts of 80 and 100 mm does not show
with a DFT of intumescent coating close to required for the steel to reach 550ºC, with any significate temperature difference nei-
1000 mm, measured at the web post and the application of a nominal thickness of ther in relation to the fire resistance time.
after the test end was equal to 30 mm. The 1000 mm, an increase of the fire resistance For both beams, when is applied a nominal
expansion measured at the web of the solid
beams P3 and P4, with a DFT equal to 1047
mm and 1187 mm, respectively, was signifi-
cantly higher, resulting in 85 and 75 mm,
respectively. The carbonaceous char layer
thickness of these beams can be seen in
Figure 11, verifying generally a smaller
expansion in the case of cellular beams, a
decrease of this expansion close to the beam
edge and also around the hole edge. Also,
due the intumescent char contraction
around the hole of the beam P16 one can
verify a small area of steel without fire pro-
tection, leading to a faster steel temperature
ly
increase. This behaviour suggests that, to
Figure 9. Evolution of the mean temperature registered on the web post and flanges of test
on
achieve the same fire protection level as for
P1 and P9.
e
us
Conclusions
al
This work presents the results of a set of
experimental tests on protected and unpro-
ci
paint and prEN13381-9 for the analysis of Figure 10. Temperature evolution results of intumescent protected solid and cellular
cellular beams protected with intumescent beams.
Figure 11. Intumescent coating expansion of test P4 (left), P13 (middle) and P16 (right) after test.
DFT equal to 1000 mm, the temperature of http://www.steelconstruction.info/imag Fire Protection; 2010.
550ºC is achieved after 28 minutes. For es/8/87/Steel_construction_- 9. ASFP. Fire protection for structural
longer fire exposure periods a slight differ- _Fire_Protection.pdf steel in buildings (the yellow book). 5th
ence can be already verified. 3. Wang P, Wang X, Liu M, Zhang L. ed. Kingsley: Association for Specialist
The intumescent char expansion shows Web-post buckling of fully and partially Fire Protection; 2014.
a localized effect, a known edge or board protected cellular steel beams at elevat- 10. CEN. prEN 13381-9: Test methods for
effect that limits the char expansion in the ed temperatures in a fire. Thin-Walled determining the contribution to the fire
case of tested cellular beams. Also, specifi- Struct 2016;98:29-38.
resistance of structural members Part 9:
cally in beam P16, a small contraction of 4. Wong VYB, Burgess IW, Plank RJ.
Contribution of fire resistance to steel
the intumescent char around the circular Behaviour of composite floor beam
with web openings at high tempera- beams with web opening. Brussels,
hole was occur, leaving a small area of steel
tures. In: E. Batista PV, L. de Lima Belgium: European Committee for
directly exposed to fire. These two
(Eds.). SDSS’Rio 2010 Stability and Standardization; 2013.
behaviours lead to a need of higher DFTs
values for cellular beams in comparison to ductility of steel structures. Rio de 11. Bailey C. Indicative fire test on a cellu-
equivalent beams to achieve the same fire Janeiro, Brazil, 2010. Available from: lar and solid web steel beam.
protection. https://fire-research.group. Manchester; Manchester Centre for
This study is being extended to a wider shef.ac.uk/Downloads/BW_SDSS_Rio Civil and Constructional Engineering:
parametric analysis considering different _2010.pdf 2003.
cellular beams geometries and intumescent 5. ASFP. Fire protection for structural 12. Bailey C. Indicative fire tests to investi-
coatings thicknesses to allow for a general steel in buildings (the yellow book). 3th gate the behaviour of cellular beams
elemental multi-temperature analysis ed. Kingsley: Association for Specialist protected with intumescent coatings.
(EMTA). Fire Protection; 2004. Fire Safety J 2004;2004:689-709.
6. Nadjai A, Vassart O, Ali F, et al.
ly
13. CEN. EN13381-8 Test methods for
Performance of cellular composite floor
determining the contribution to the fire
on
beams at elevated temperatures. Fire
References Safety J 2007;42:489-97.
resistance of structural members. Part 8:
1. Pachpor PD, Mittal ND, Gupta LM, 7. SCI. Structural fire design: off-site Applied reactive protection to steel
members. Brussels, Belgium: European
e
Deshpand NV. Finite element analysis applied thin film intumescent coatings.
and comparison of castellated and cellu- 2nd ed. Ascot: Steel Construction
us Committee for Standardization; 2010.
lar beam. Adv Mat Res 2011;264- Institute; 2005. 14. CEN. EN1363-1: Fire resistance tests.
265:694-9. 8. ASFP. Fire protection for structural General requirements. Brussels,
2. TATASteel, BCSA. Steel construction steel in buildings (the yellow book). 4th Belgium: European Committee for
al
fire protection. 2013. Available from: ed. Kingsley: Association for Specialist Standardization; 1999.
ci
er
m
m
co
on