Documente Academic
Documente Profesional
Documente Cultură
Fire Alarm signal Manual Initiation 12.3.4.2.1 Initiation of the required fire alarm system shall be by both of Automatic Not required:
initiation the following means: Manual Control MASJID (with or without Imam House) <300 Occupants
Panel
(1) Manual means in accordance with 9.6.2.1(1), unless Required:
otherwise permitted by one of the following: MASJID (with or without Imam House) >300 Occupants
(a) The requirement of 12.3.4.2.1(1) shall not apply where
initiation is by means of an approved automatic fire detection ASSEMBLY with less than 300 Occupants
system in accordance with 9.6.2.1(2) that provides fire (AUDITORIUMS, THEATER AS PER NFPA 101)
detection throughout the building.
(b) The requirement of 12.3.4.2.1(1) shall not apply where ASSEMBLY with more than 300 Occupants (AUDITORIUMS,
initiation is by means of an approved automatic sprinkler THEATER AS PER NFPA 101)
Also see 12.3.4.2.1(1) above and 12.3.4.2.2 below ASSEMBLY with more than 300 Occupants (AUDITORIUMS,
Also see 12.3.6, 12.4.3.3.4, 12.7.5.3.7.1, and 12.7.12 in NFPA THEATER AS PER NFPA 101)
101
9.6.2.10.1 Where required by another section of this Code, single-station Stand alone smoke alarms battery operated required in MASJID
and multiple-station smoke alarms shall be in accordance with (with or without Imam House) <300 Occupants
NFPA 72 unless otherwise provided in 9.6.2.10.3, 9.6.2.10.4,
9.6.2.10.6, or 9.6.2.10.7.
12.4.8.4 Special Amusement Buildings GA_6.3 – Detector Coverage shall comply with latest edition of NFPA 72.
Where the nature of the special amusement building is such Revisions_2015 Exemption: Void space less than or equal to 400mm in
that it operates in reduced lighting levels, the building shall be (7.0) depth/height shall not require detection.
protected throughout by an approved automatic smoke
detection system in accordance with Section 9.6
Carbon Monoxide N 12.3.4.4.1 New assembly occupancies shall be provided with carbon
Alarms and monoxide detection and warning equipment in accordance
Carbon Monoxide with Section 9.12 in the locations specified as follows:
Detection (1) On the ceilings of rooms containing permanently installed
Systems. fuel-burning appliances or fuel-burning fireplaces
(2) Centrally located within occupiable spaces served by the
first supply air register from permanently installed fuelburning
HVAC systems
(3)* Centrally located within occupiable spaces adjacent to an
attached garage
GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
Revisions_2015 type and location of all initiating devices with labels on that
(6.0) floor with a “YOU ARE HERE” indication and shall be provided
on each floor of every building located within the firefighting
lobby and smoke-stop lobby or common lobby in close
proximity to the exit staircase.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
Fire alarm system 14.3.4.1.1 Educational occupancies shall be provided with a fire alarm Superscripts Definition-a system or portion of a combination system that Automatic and Manual system required in all occupancy
/ fire warning system in accordance with Section 9.6. Description consists of components and circuits arranged to monitor and classification
equipment annunciate the status of fire alarm or supervisory signal-
initiating devices and to initiate the appropriate response to
those signals
14.3.4.1.2 The requirement of 14.3.4.1.1 shall not apply to buildings GA_6.3 – Fire alarm systems shall be provided for all buildings and
meeting all of the following criteria: Revisions_2015 structure that provide public access. See Guidelines for Fire
(1) Buildings having an area not exceeding 1000 ft2 (93 m2) (1.0) Alarm System for reference.
(2) Buildings containing a single classroom GA_6.3 – Fire alarm systems shall be of the conventional type or
(3) Buildings located not less than 30 ft (9.1 m) from another Revisions_2015 addressable type or combination of both. This shall be QCD
building (2.0) approved for use in the State of Qatar.
GA_6.3 – Fire Alarm Systems shall be designed and installed in
Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
(3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation Δ 14.3.4.2.1 Initiation of the required fire alarm system, other than as Automatic Required
initiation permitted by 14.3.4.2.3, shall be by manual means in Manual Control
accordance with 9.6.2.1(1). Panel
14.3.4.2.3 Manual fire alarm boxes shall be permitted to be eliminated in GA_6.3 – Fire alarm control unit/panel shall be provided inside each
accordance with 14.3.4.2.3.1 or 14.3.4.2.3.2. Revisions_2015 building and located in any of the following:
(5.0) 5.1 Within a designated Fire Command Center
5.2 In the ground floor level at main entrance/reception lobby
5.3 In a continuous attended location where above mentioned
are not available.
15.3.4.2.3.2* Manual fire alarm boxes shall be permitted to be GA_6.3 – Manual call points shall be located within 1.5M of each fire
eliminated where both of the following conditions apply: Revisions_2015 exit. The initiating device shall be located such that no part of
(1) The building is protected throughout by an approved, (8.0) any floor is further than 30M from the nearest manual call
supervised automatic sprinkler system in accordance with point
Section 9.7.
(2) Provision is made at a central point to manually activate the
evacuation signal or to evacuate only affected areas.
cont. of cont. of Audible / 9.6.3.5.6 Visible signals shall not be required in elevator cars
Occupant Visible 9.6.3.7 Audible alarm notification appliances shall be of such character
Notification and so distributed as to be effectively heard above the average
ambient sound level that exists under normal conditions of
occupancy
9.6.3.8 Audible alarm notification appliances shall produce signals that
are distinctive from audible signals used for other purposes in a
given building.
Positive Alarm 14.3.4.3.1.3 Positive alarm sequence shall be permitted in
sequence accordance with 9.6.3.4.
9.6.3.4 Where permitted by Chapters 11 through 43, a positive alarm
sequence shall be permitted, provided that it is in accordance
with NFPA 72
Presignal system Not addressed
Voice 14.3.4.3.1.2 The occupant notification required by 14.3.4.3.1.1 shall utilize Mass Notification Not required:
Announcements an emergency voice/alarm communication system in Kindergarten
accordance with 9.6.3 where the building has an occupant load
of more than 100.
9.6.3.9 Automatically transmitted or live voice evacuation or relocation Permitted
instructions shall be permitted to be used to notify occupants Preparatory
and shall comply with either 9.6.3.9.1 or 9.6.3.9.2. Primary
GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
Revisions_2015 type and location of all initiating devices with labels on that
(6.0) floor with a “YOU ARE HERE” indication and shall be provided
on each floor of every building located within the firefighting
lobby and smoke-stop lobby or common lobby in close
proximity to the exit staircase.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
Fire alarm system 18.3.4.1 Health care occupancies shall be provided with a fire alarm Superscripts Definition-a system or portion of a combination system that Automatic and Manual system required in Type A & Type B
/ fire warning system in accordance with Section 9.6. Description consists of components and circuits arranged to monitor and occupancy classification
equipment annunciate the status of fire alarm or supervisory signal-
initiating devices and to initiate the appropriate response to Not required in Type C occupancy classification.
those signals
GA_6.3 – Fire alarm systems shall be provided for all buildings and
Revisions_2015 structure that provide public access. See Guidelines for Fire
(1.0) Alarm System for reference.
GA_6.3 – Fire alarm systems shall be of the conventional type or
Revisions_2015 addressable type or combination of both. This shall be QCD
(2.0) approved for use in the State of Qatar.
GA_6.3 – Fire Alarm Systems shall be designed and installed in
Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
(3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation 18.3.4.2.1 Initiation of the required fire alarm systems shall be by manual Automatic Required
initiation means in accordance with 9.6.2 and by means of any required Manual Control
sprinkler system waterflow alarms, detection devices, or Panel
detection systems, unless otherwise permitted by 18.3.4.2.2
and 18.3.4.2.3.
GA_6.3 – Manual call points shall be located within 1.5M of each fire
Revisions_2015 exit. The initiating device shall be located such that no part of
(8.0) any floor is further than 30M from the nearest manual call
point
Automatic 18.3.4.5.1 Detection systems, where required, shall be in accordance with Smoke / Heat Required
detection Section 9.6. Detectors
18.3.4.5.2 Detection in Spaces Open to Corridors. See 18.3.6.1. GA_6.3 – Detector Coverage shall comply with latest edition of NFPA 72.
18.3.4.5.3* Nursing Homes. An approved automatic smoke detection Revisions_2015 Exemption: Void space less than or equal to 400mm in
system shall be installed in corridors throughout smoke (7.0) depth/height shall not require detection.
compartments containing patient sleeping rooms and in spaces
open to corridors as permitted in nursing homes by 18.3.6.1,
unless otherwise permitted by one of the following:
(1) Corridor systems shall not be required where each patient
sleeping room is protected by an approved smoke detection
system.
(2) Corridor systems shall not be required where patient room
doors are equipped with automatic door-closing devices with
integral smoke detectors on the room side installed in
accordance with their listing, provided that the integral
detectors provide occupant notification.
9.6.7.7 Where the system serves more than one building, each building
shall be annunciated separately
9.6.7.8 Where permitted by another section of this Code, the alarm
zone shall be permitted to coincide with the permitted area for
smoke compartments.
Fire safety 18.3.4.4 Operation of any activating device in the required fire alarm GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions system shall be arranged to accomplish automatically any Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
control functions to be performed by that device. (See 9.6.5.) (9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
Fire alarm system 28.3.4.1 A fire alarm system in accordance with Section 9.6, except as Superscripts Definition-a system or portion of a combination system that Hotel:
/ fire warning modified by 28.3.4.2 through 28.3.4.7, shall be provided. Description consists of components and circuits arranged to monitor and Complying with NFPA 72, Required
equipment annunciate the status of fire alarm or supervisory signal- Dormitory and Accommodation:
initiating devices and to initiate the appropriate response to Complying with NFPA 72, Required
those signals
11.8.4.1* High-Rise Building. GA_6.3 – Fire alarm systems shall be provided for all buildings and
A fire alarm system using an approved emergency voice/alarm Revisions_2015 structure that provide public access. See Guidelines for Fire
communication system shall be installed in accordance with (1.0) Alarm System for reference.
Section 9.6. GA_6.3 – Fire alarm systems shall be of the conventional type or
Revisions_2015 addressable type or combination of both. This shall be QCD
(2.0) approved for use in the State of Qatar.
GA_6.3 – Fire Alarm Systems shall be designed and installed in
Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
(3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation 28.3.4.2 The required fire alarm system shall be initiated by each of the Automatic Required
initiation following: Manual Control Hotel: All classification
(1) Manual means in accordance with 9.6.2 Panel Dormitory and Accommodation: All classification
28.3.4.7.2 Where required by 28.3.4.7.1, carbon monoxide alarms or Superscripts Hotel: The CO sensitivity shall meet the requirements of UL
carbon monoxide detectors shall be installed in the Description std. 2043 (or other applicable / accepted certifying bodies).
following locations:
(1) Outside of each separate guest room or guest suite sleeping
area in the immediate vicinity of the sleeping rooms
(2) on every occupiable level of a guest room and guest suite
Voice N 28.3.4.4.1 Risk Analysis for Mass Notification. Mass Notification Required:
Announcements A risk analysis in accordance with Section 9.14 shall be Hotels: Class B - Medium Rise
performed for grades K through 12, college, or university Class C - High Rise Building
dormitories with an occupant load greater than 100 to Dormitory and Accommodation: High Rise
determine whether a mass notification is required.
N 28.3.4.4.2 Applicable portions of an existing risk analysis shall be Permitted:
permitted to be used when a new building is added to the Dormitory and Accommodation: Medium Rise
campus
N 11.8.4.3 High-Rise Buildings Not Required:
Risk Analysis for Mass Notification systems: For high-rise Hotels: Class A - Low rise Building
buildings with a total occupant load of 5000 or more persons, Dormitory and Accommodation: Low Rise
or where the floor of an occupiable story is greater than 420 ft
(128 m) above the lowest level of fire department vehicle
access, a risk analysis in accordance with Section 9.14 shall be
performed to determine whether a mass notification system is
required.
N 9.14.1.1 Where required by Chapters 11 through 43, a risk analysis for
mass notification systems shall be provided in accordance with
the requirements of Chapter 24 of NFPA 72 and the provisions
of 9.14.2 through 9.14.4
N 9.14.1.2 Where a mass notification system is required by the risk
analysis in 9.14.1.1, the system shall be in accordance with the
requirements of Chapter 24 of NFPA 72.
11.8.4.2.2 The requirement of 11.8.4.2.1 shall not apply where the fire
department radio system is approved as an equivalent system.
9.6.7.4.1 Where permitted by another section of this Code, fire alarm Superscripts Zone Chart or Fire Evacuation Plan required, shall be as-built
zones shall be permitted to exceed 22,500 ft2 (2090 m2), and Description drawing plan of the building and required in each of every floor
the length of a zone shall be permitted to exceed 300 ft (91 m) of the common area's (e.g. lift lobby, corridor, etc.) whereas
in any direction. noticeable to the occupant / tenant / public. The plan shall
9.6.7.4.2 Where the building is protected by an automatic sprinkler indicate all manual initiating device, exit sign, and other
system in accordance with 9.7.1.1(1), the area of the fire alarm applicable fire measure.
zone shall be permitted to coincide with the allowable area of
the sprinkler system.
9.6.7.4.3 Where the building is protected by a water mist system in GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
accordance with 9.8.1 and Table 9.8.1, the area of the fire Revisions_2015 type and location of all initiating devices with labels on that
alarm zone shall be permitted to coincide with the allowable (6.0) floor with a “YOU ARE HERE” indication and shall be provided
area of the water mist system. on each floor of every building located within the firefighting
9.6.7.4.4 Unless otherwise prohibited by another section of this Code, lobby and smoke-stop lobby or common lobby in close
where a building not exceeding four stories in height is proximity to the exit staircase.
protected by an automatic water mist system in accordance
with 9.8.1, the water mist system shall be permitted to be
annunciated on the fire alarm system as a single zone.
9.6.7.7 Where the system serves more than one building, each building
shall be annunciated separately
9.6.7.8 Where permitted by another section of this Code, the alarm
zone shall be permitted to coincide with the permitted area for
smoke compartments.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
Fire Alarm signal Manual Initiation 30.3.4.2.1 Initiation of the required fire alarm system shall be by manual Automatic Not required:
initiation means in accordance with 9.6.2, unless the building complies Manual Control Residential Dwellings & Villas
with 30.3.4.2.2. Panel
30.3.4.2.2 Initiation of the required fire alarm system by Required:
manual means shall not be required in buildings four or fewer Low Rise Apartment
stories in height, containing not more than 16 dwelling units, Medium Rise Apartment Type A
and protected throughout by an approved, supervised Medium Rise Apartment Type B
automatic sprinkler system installed in accordance with High Rise Apartment
Voice 9.6.3.9 Automatically transmitted or live voice evacuation or relocation Mass Notification Not required:
Announcements instructions shall be permitted to be used to notify occupants Residential Dwellings & Villas
and shall comply with either 9.6.3.9.1 or 9.6.3.9.2. Low Rise Apartment
Medium Rise Apartment Type A
9.6.3.9.1 Automatically transmitted or live voice evacuation or Permitted:
relocation instructions shall be in accordance with NFPA 72 Medium Rise Apartment Type B
11.8.4.2.2 The requirement of 11.8.4.2.1 shall not apply where the fire
department radio system is approved as an equivalent system.
9.6.7.1 Where alarm annunciation is required by another section of Superscripts Main Graphic Annunciator or Main Mimic Panel required, shall
this Code, it shall comply with 9.6.7.2 through 9.6.7.8 Description be building as-built drawing plan, used red coloured LED's to
9.6.7.2 Alarm annunciation at the control center shall be by means of indicate graphically the building, the floor, location of initiating
audible and visible indicators. device that is in alarm. This shall be located in Fire Command
9.6.7.3 For the purposes of alarm annunciation, each floor of the Center or where the the Main Fire Alarm Control Panel is
building, other than floors of existing buildings, shall be located.
considered as not less than one zone, unless otherwise
permitted by 9.6.7.4.4, 9.6.7.4.5, 9.6.7.4.6, or another section
of this Code.
9.6.7.4 Where a floor area exceeds 22,500 ft2 (2090 m2), additional Zone Chart / Fire Required:
fire alarm zoning shall be provided, and the length of any single Evacuation Plan Low Rise Apartment
fire alarm zone shall not exceed 300 ft (91 m) in any direction, Medium Rise Apartment Type A
except as provided in 9.6.7.4.1 through 9.6.7.4.6, or as Medium Rise Apartment Type B
otherwise modified by another section of this Code. High Rise Apartment
9.6.7.7 Where the system serves more than one building, each building
shall be annunciated separately
9.6.7.8 Where permitted by another section of this Code, the alarm
zone shall be permitted to coincide with the permitted area for
smoke compartments.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
High‐Rise Building. A building where the floor of an occupiable
story is greater than 75 ft (23 m) above the lowest level of fire
3.3.37.7* department vehicle access. (SAF‐FUN)
36.1.2.2 Subclassification of Occupancy.
(1) Class A, all mercantile occupancies having an aggregate
gross area of more than 30,000 ft2 (2800 m2) or occupying
more than three stories for sales purposes
(2) Class B, as follows:
(a) All mercantile occupancies of more than 3000 ft2 (280 m2),
but not more than 30,000 ft2 (2800 m2), aggregate gross area
and occupying not more than three stories for sales purposes
(b) All mercantile occupancies of not more than 3000 ft2 (280
m3) gross area and occupying two or three stories for sales
purposes
(3) Class C, all mercantile occupancies of not more than 3000
ft2 (280 m2) gross area and used for sales purposes occupying
one story only
CO Alarms and CO Not addressed
Detection
Systems.
Extinguishing See 36.3.4.2(3), 36.4.4.7.2 and 36.4.5.4.2 above
system operation Also see 9.7.2.2 below
Also see 36.3.5, 36.4.4.13, and Δ 36.4.5.5 in NFPA 101 for
extinguishing system requirements and 36.3.6 for additional
extinguishing system provisions
FAS supervisory Extinguishing 9.7.2.1.1 Where supervised automatic sprinkler systems are required by
signal initiation system another section of this Code, supervisory attachments shall be
supervision installed and monitored for integrity in accordance with NFPA
72 and a distinctive supervisory signal shall be provided to
indicate a condition that would impair the satisfactory
operation of the sprinkler system
9.7.2.1.2 Supervisory signals shall sound and shall be displayed either at
a location within the protected building that is constantly
attended by qualified personnel or at an approved, remotely
located receiving facility
Also see 36.3.5, 36.4.4.13, and Δ 36.4.5.5 in NFPA 101 for
extinguishing system requirements and 36.3.6 for additional
extinguishing system provisions
Occupant Audible / Visible 36.3.4.3.1 Class A Mercantile Occupancies Audible / Visible Required
Notification During all times that the mercantile occupancy is occupied, the
required fire alarm system, once initiated, shall perform one of
the following functions:
(1) It shall activate an alarm in accordance with 9.6.3
throughout the mercantile occupancy.
(2) Positive alarm sequence in accordance with 9.6.3.4 shall be
permitted.
9.6.3.5.6 Visible signals shall not be required in elevator cars
9.6.3.7 Audible alarm notification appliances shall be of such character
and so distributed as to be effectively heard above the average
ambient sound level that exists under normal conditions of
occupancy
9.6.3.8 Audible alarm notification appliances shall produce signals that
are distinctive from audible signals used for other purposes in
a given building.
Positive Alarm See 36.3.4.3.1 (2), 36.4.4.7.3.1(1), and 36.4.5.4.3 above
sequence 9.6.3.4 Where permitted by Chapters 11 through 43, a positive alarm
sequence shall be permitted, provided that it is in accordance
with NFPA 72
Presignal system Not addressed
N 9.14.3.1 The emergency action plan, risk assessment report, and
accompanying documentation shall be submitted to the
authority having jurisdiction by the registered design
professional (RDP). The format and content of the
documentation shall be acceptable to the authority having
jurisdiction.
N 9.14.3.2* Where required by the authority having jurisdiction, an
independent review of the emergency action plan, risk
assessment, and the accompanying documentation by one or
more individuals possessing expertise in risk characterization
for accidental and intentional hazards shall be performed.
N 9.14.4 The completed emergency action plan in accordance with
Section 4.8 shall be used for the design of the mass
notification/emergency communications system.
Other provisions See 36.3.4.3.1 (1), 36.4.4.7.3.1(2), and 36.4.5.4.3 above Fire Telephone Not required:
(Two way Class C
11.8.4.2 High‐Rise Building communication Required:
Two‐way telephone service shall be in accordance with system) Class A
11.8.4.2.1 and 11.8.4.2.2. Class B
Δ 11.8.4.2.1 Two‐way telephone communication service shall be provided
for fire department use. This system shall be in accordance
with NFPA 72. The communications system shall operate
between the emergency command center and every elevator
car, every elevator lobby, and each floor level of exit stairs.
11.8.4.2.2 The requirement of 11.8.4.2.1 shall not apply where the fire
department radio system is approved as an equivalent system.
9.6.4.4 For other than existing installations, where fire alarm systems
are required to provide emergency forces notification,
supervisory signals and trouble signals shall sound and be
visibly displayed either at an approved, remotely located
receiving facility or at a location within the protected building
that is constantly attended by qualified personnel.
9.7.2.2.1 Where supervision of automatic sprinkler systems is required
by another section of this Code, waterflow alarms shall be
transmitted to an approved, proprietary alarm‐receiving
facility, a remote station, a central station, or the fire
department
Also see 36.3.4.2(3), 36.4.4.7.2, and 36.4.5.4.2 above.
Also see 36.3.5, 36.4.4.13, and Δ 36.4.5.5 in NFPA 101 for
extinguishing system requirements and 36.3.6 for additional
extinguishing system provisions
Annunciator Graphic Not required:
Annunciator / Class C
Mimic Panel Required:
Class A
Class B
Superscripts Main Graphic Annunciator or Main Mimic Panel required,
Description shall be building as‐built drawing plan, used red coloured LED's
to indicate graphically the building, the floor, location of
initiating device that is in alarm. This shall be located in Fire
Command Center or where the the Main Fire Alarm Control
Panel is located.
Zone Chart / Fire Required
Evacuation Plan
Superscripts Zone Chart or Fire Evacuation Plan required, shall be as‐built
Description drawing plan of the building and required in each of every floor
of the common area's (e.g. lift lobby, corridor, etc.) whereas
noticeable to the occupant / tenant / public. The plan shall
indicate all manual initiating device, exit sign, and other
applicable fire measure.
GA_6.3 – 10.1 Primary Power Supply shall be an alternating current (AC)
Revisions_2015 supply from an authorized electricity provided and shall be
(10.0) exclusive to the alarm system.
‐ The primary power supply should be from the building
Power Supplies emergency mains supply if such supply is available.
‐ The primary power supply shall be direct from the electrical
distribution board and the circuit shall not be used for any
other purpose.
‐ The protective isolating device controlling this circuit shall be
clearly labeled to indicate that it controls the fire alarm
system.
‐ It shall terminate inside the fire alarm panel or its integral
power supply unit. No external intermediary switch shall be
provided between the protective isolation device at the
electrical distribution board and the fire alarm panel / integral
power supply unit
10.2 Secondary Power supply shall be in the form of the
following:
‐ Storage batteries, with an automatic charge. It shall be
capable of operating the alarm system in the event of failure of
the primary power supply and vice versa.
‐ Emergency Power Supply System (EPSS), if provided, shall be
compliant to the latest edition of NFPA 70, 72 and 110
complete with power line diagram to show the automatic
transfer switch.
10.3 A fault warning shall be given in the event of failure of
either primary or secondary power supply
10.4 A battery charger of appropriate type and rating shall be
provided to keep the storage batteries under constant voltage
charge.
‐ The charger shall incorporate automatic control features with
output designed to charge and maintain the batteries within
the limits specified by the battery manufacturer, taking into
account any quiescent load imposed by the associated system.
‐ The charger shall be designed and rated to so that a battery
discharged to its final voltage can be recharged to at least 80%
of its rated capacity within 24 hours and its rated capacity
within another 48 hours.
Applications:
General Offices / City / Municipal Halls / Courthouses /
Doctors/Dentist Offices / Meeting Rooms (<50 Seating
Capacity) / Barber Shops / Salons / Service Facilities
(Newstand, Lunch counters <50 persons) / Classroom /
Instructional Laboratories <50 seating capacity / Birth
Centers / Ambulatory out-patient clinics <4 patients
Fire alarm system 38.3.4.1 A fire alarm system in accordance with Section 9.6 shall be Superscripts Definition-a system or portion of a combination system that Required in all occupancy classification
/ fire warning provided in all business occupancies where any one of the Description consists of components and circuits arranged to monitor and
equipment following conditions exists: annunciate the status of fire alarm or supervisory signal-
(1) The building is three or more stories in height. initiating devices and to initiate the appropriate response to
(2) The occupancy is subject to 50 or more occupants above or those signals
below the level of exit discharge. GA_6.3 – Fire alarm systems shall be provided for all buildings and
(3) The occupancy is subject to 300 or more total occupants. Revisions_2015 structure that provide public access. See Guidelines for Fire
(1.0) Alarm System for reference.
11.8.4.1* High-Rise Building. GA_6.3 – Fire alarm systems shall be of the conventional type or
A fire alarm system using an approved emergency voice/alarm Revisions_2015 addressable type or combination of both. This shall be QCD
communication system shall be installed in accordance with (2.0) approved for use in the State of Qatar.
Section 9.6.
GA_6.3 – Fire Alarm Systems shall be designed and installed in
Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
(3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation 38.3.4.2 Initiation of the required fire alarm system shall be by any one Automatic Required
initiation of the following means: Manual Control
(1) Manual means in accordance with 9.6.2.1(1) Panel
GA_6.3 – Manual call points shall be located within 1.5M of each fire
Revisions_2015 exit. The initiating device shall be located such that no part of
(8.0) any floor is further than 30M from the nearest manual call
point
Automatic See 38.3.4.2(2) above Smoke / Heat Required
detection Detectors
9.6.2.6* For fire alarm systems using automatic fire detection or GA_6.3 – Detector Coverage shall comply with latest edition of NFPA 72.
waterflow detection devices to initiate the fire alarm system in Revisions_2015 Exemption: Void space less than or equal to 400mm in
accordance with Chapters 11 through 43, not less than one (7.0) depth/height shall not require detection.
manual fire alarm box, located as required by the authority
having jurisdiction, shall be provided to initiate a fire alarm
signal.
A.9.6.2.6 The manual fire alarm box required by 9.6.2.6 is intended to
provide a means to manually activate the fire alarm system
when the automatic fire detection system or waterflow devices
are out of service due to maintenance or testing, or where
human discovery of the fire precedes automatic sprinkler
system or automatic detection system activation. Where the
fire alarm system is connected to a monitoring facility, the
manual fire alarm box required by 9.6.2.6 should be connected
to a separate circuit that is not placed “on test” when the
detection or sprinkler system is placed on test. The manual fire
alarm box should be located in an area that is accessible to
occupants of the building and should not be locked.
CO Alarms and CO
Detection
Systems.
Extinguishing See 38.3.4.2(3) above
system operation Also see 9.7.2.2 below
Also see 38.3.5 in NFPA 101 for extinguishing system
provisions.
FAS supervisory Extinguishing 9.7.2.1.1 Where supervised automatic sprinkler systems are required by
signal initiation system another section of this Code, supervisory attachments shall be
supervision installed and monitored for integrity in accordance with NFPA
72 and a distinctive supervisory signal shall be provided to
indicate a condition that would impair the satisfactory
operation of the sprinkler system
Occupant Audible / Visible 38.3.4.3 During all times that the building is occupied (see 7.2.1.1.3), the Audible / Visible Required
Notification required fire alarm system, once initiated, shall perform one of
the following functions:
(1) It shall activate a general alarm in accordance with 9.6.3.
(2) A positive alarm sequence in accordance with 9.6.3.4 shall
be permitted.
Voice N 38.3.4.5* Risk Analysis for Mass Notification systems: A risk analysis in Mass Notification Not required:
Announcements accordance with Section 9.14 shall be performed for business Class A - Low Rise Building
occupancies containing a classroom where the building is
owned, rented, leased, or operated by a college or university to
determine whether a mass notification system is required.
11.8.4.2.2 The requirement of 11.8.4.2.1 shall not apply where the fire Required:
department radio system is approved as an equivalent system. Class C- High Rise Building
Emergency forces 38.3.4.4 Emergency forces notification shall be provided and shall
notification include notifying both of the following:
(1) Fire department in accordance with 9.6.4
(2) Approved local emergency organization, if provided
9.6.4.1 Where required by another section of this Code, emergency
forces notification shall be provided to alert the municipal fire
department and fire brigade (if provided) of fire or other
emergency
Annunciator 30.3.4.3.2 See 38.3.5 in NFPA 101 for extinguishing system provisions. Graphic Not required:
Annunciator / Class A - Low Rise Building
Mimic Panel Permitted:
Class B - Medium Rise Building Type A
GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
Revisions_2015 type and location of all initiating devices with labels on that
(6.0) floor with a “YOU ARE HERE” indication and shall be provided
on each floor of every building located within the firefighting
lobby and smoke-stop lobby or common lobby in close
proximity to the exit staircase.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
Fire alarm system 40.3.4.1 fire alarm system shall be required in accordance with Section Superscripts Definition-a system or portion of a combination system that Required in all occupancy classification, complying with
/ fire warning 9.6 for industrial occupancies, unless the total occupant load of Description consists of components and circuits arranged to monitor and NFPA 72
equipment the building is under 100 persons and unless, of these, fewer annunciate the status of fire alarm or supervisory signal-
than 25 persons are above or below the level of exit discharge. initiating devices and to initiate the appropriate response to
those signals
GA_6.3 – Fire alarm systems shall be provided for all buildings and
Revisions_2015 structure that provide public access. See Guidelines for Fire
(1.0) Alarm System for reference.
GA_6.3 – Fire alarm systems shall be of the conventional type or
Revisions_2015 addressable type or combination of both. This shall be QCD
(2.0) approved for use in the State of Qatar.
GA_6.3 – Fire Alarm Systems shall be designed and installed in
Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
(3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation Δ 40.3.4.2 Initiation of the required fire alarm system shall be by any of Automatic Required
initiation the following means: Manual Control
(1) Manual means in accordance with 9.6.2.1(1) Panel
(2) Approved automatic fire detection system in accordance GA_6.3 – Fire alarm control unit/panel shall be provided inside each
with 9.6.2.1(2) throughout the building, plus a minimum of one Revisions_2015 building and located in any of the following:
manual fire alarm box in accordance with 9.6.2.6 (5.0) 5.1 Within a designated Fire Command Center
(3) Approved, supervised automatic sprinkler system in 5.2 In the ground floor level at main entrance/reception lobby
accordance with 9.6.2.1(3) throughout the building, plus a 5.3 In a continuous attended location where above mentioned
minimum of one manual fire alarm box in accordance with are not available.
9.6.2.6
Manual Call Point Required
FAS supervisory Extinguishing 9.7.2.1.1 Where supervised automatic sprinkler systems are required by
signal initiation system another section of this Code, supervisory attachments shall be
supervision installed and monitored for integrity in accordance with NFPA
72 and a distinctive supervisory signal shall be provided to
indicate a condition that would impair the satisfactory
operation of the sprinkler system
Occupant Audible / Visible 40.3.4.3.1 The required fire alarm system shall meet one of the following Audible / Visible Required
Notification criteria:
(1) It shall provide occupant notification in accordance with
9.6.3.
(2) It shall sound an audible and visible signal in a constantly
attended location for the purposes of initiating emergency
action.
See 40.3.4.3.4 above.
9.6.3.5.1 Areas not subject to occupancy by persons who are hearing
impaired shall not be required to comply with the provisions
for visible signals
9.6.3.5.5 Visible signals shall not be required in exit stair enclosures.
Required:
Class C - High Hazard Industrial Occupancy
Other provisions Fire Telephone Not required:
(Two way Class A - Low Hazard - Special Purpose Industrial Occupancy
communication Class A - Ordinary Hazard - Special Purpose Industrial
system) Occupancy
Class B - Low Hazard - General Industrial Occupancy
Class B - Ordinary Hazard - General Industrial Occupancy
Required:
Class C - High Hazard Industrial Occupancy
Emergency forces 9.7.2.2.1 Where supervision of automatic sprinkler systems is required
notification by another section of this Code, waterflow alarms shall be
transmitted to an approved, proprietary alarm-receiving
facility, a remote station, a central station, or the fire
department.
Also see 40.3.4.2(3) above.
Annunciator Graphic Not required:
Annunciator / Class A - Low Hazard - Special Purpose Industrial Occupancy
Mimic Panel Class A - Ordinary Hazard - Special Purpose Industrial
Occupancy
Class B - Low Hazard - General Industrial Occupancy
Class B - Ordinary Hazard - General Industrial Occupancy
Required:
Class C - High Hazard Industrial Occupancy
GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
Revisions_2015 type and location of all initiating devices with labels on that
(6.0) floor with a “YOU ARE HERE” indication and shall be provided
on each floor of every building located within the firefighting
lobby and smoke-stop lobby or common lobby in close
proximity to the exit staircase.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection
42.3.4.1.3 Storage occupancies protected throughout by an approved GA_6.3 – Fire Alarm Systems shall be designed and installed in
automatic sprinkler system in accordance with Section 9.7 shall Revisions_2015 accordance with the latest edition of NFPA 72 except as clearly
not be required to have a fire alarm system. (3.0) modified by these requirements. Where ambiguities in either
these requirements of the NFPA 72 exist, it shall be the
responsibility of the engineering endorsing the fire safety plans
to obtain clarification from the Qatar Civil Defence
Department.
GA_6.3 – All fire alarm system shall have the following:
Revisions_2015 4.1 Main fire alarm control unit/panel (addressable /
(4.0) conventional type)
4.2 Main Indicating Mimic Panel shall use red coloured Light
Emitting Diode (LED) to indicate graphically the building, the
floor, location and the initiating device that is in alarm; or if
provided with PC based workstation, an information stating
that graphic user interface (GUI) is integrated in the
software/application in lieu of the Main Indicating Mimic Panel.
Fire Alarm signal Manual Initiation Δ 42.3.4.2 Initiation of the required fire alarm system shall be by any of Automatic Not required:
initiation the following means: Manual Control Class A - Low Hazard & Class B - Ordinary Hazard
(1) Manual means in accordance with 9.6.2.1(1) Panel Required:
(2) Approved automatic fire detection system in accordance Class C - High Hazard
with 9.6.2.1(2) throughout the building, plus a minimum of one GA_6.3 – Fire alarm control unit/panel shall be provided inside each
manual fire alarm box in accordance with 9.6.2.6 Revisions_2015 building and located in any of the following:
(3) Approved, supervised automatic sprinkler system in (5.0) 5.1 Within a designated Fire Command Center
accordance with 9.6.2.1(3) throughout the building, plus a 5.2 In the ground floor level at main entrance/reception lobby
minimum of one manual fire alarm box in accordance with 5.3 In a continuous attended location where above mentioned
9.6.2.6 are not available.
CO Alarms and CO
Detection
Systems.
Extinguishing See 42.3.4.2(3) and 42.8.3.4.2(3) above
system operation Also see 9.7.2.2 below
FAS supervisory Extinguishing 9.7.2.1.1 Where supervised automatic sprinkler systems are required by
signal initiation system another section of this Code, supervisory attachments shall be
supervision installed and monitored for integrity in accordance with NFPA
72 and a distinctive supervisory signal shall be provided to
indicate a condition that would impair the satisfactory
operation of the sprinkler system
GA_6.3 – Zone Chart shall clearly depict the location of all fire zones, the
Revisions_2015 type and location of all initiating devices with labels on that
(6.0) floor with a “YOU ARE HERE” indication and shall be provided
on each floor of every building located within the firefighting
lobby and smoke-stop lobby or common lobby in close
proximity to the exit staircase.
Fire safety GA_6.3 – Fire alarm wiring shall be in accordance with the latest edition
functions Revisions_2015 of NFPA 70 & 72. Where fire alarm wires are exposed and
(9.0) subject to possible damage from normal use of the occupancy,
they shall be provided with mechanical protection