SYSTEMS OUTPUT
CONTROL UNIT ANNUNCIATION NOTIFICATION REQUIRED FIRE SAFETY CONTROL

Recall Elevators to Primary Recall Floor "Ground Floor"

Recall Elevators to Alternate Recall Floor "1st Floor"

Release Magnetically Hold- Open Smoke/Fire Doors


Indicate General Supervisroy Signal on Mimic Panel

Activate the Staircase Pressurization Fan Shutdown


Indicate General Trouble Signal on Mimic Panel
Activate Common Supervisory Signal Indicator
CAUSE AND EFFECT MATRIX

Activate Common Trouble Signal Indicator

Indicate Fire Alarm Signal on Mimic Panel


Actuate Audible Common Trouble Signal
Activate Common Alarm Signal Indicator

Activate the Staircase Pressurization Fan


(One method to define and determine the required

Activate the Lobby Pressurization Fan

Release to Open of the Sliding Door


Actuate Audible Supervisory Signal
sequence of operations of life safety systems & fire

Activate Voice Evacuation System

Shutdown All Air Handling Units


Display/Print Change of Status
protection systems)

Actuate Audible Alarm Signal

Shut-down Elevator Power


Activate Building Alarm
SYSTEMS INPUT A B C D E F G H I J K L N O P Q R S T U V

1 Manual Call Point Activation O O x x x x x x x x x x


2 Smoke Detector Activation O O x x x x x x x x x x
3 Heat Detector Activation O O x x x x x x x x x x
4 Smoke Detector Activation - Lift Machine Room O O x x x x x x x x x x
5 Heat Detector Activation - Lift Machine Room O O x x x x x x x x x x x
6 Elevator Lobby Smoke Detector Activation - Ground Floor (GF) O O x x x x x x x x x x
7 Elevator Lobby Smoke Detector Activation - Any Floor except GF O O x x x x x x x x x x
8 Flow Switch Activation O O x x x x x x x x x x
9 Zone Control Valve Activation (Tamper Switch) O O x x
`

10 Smoke Duct Detector Activation O O x x x x x x x x x x


11 Pressurizaion Fan Smoke Duct Detector Activation O O x x x x x x x x x x x
12 Detector Removal From Base O O x x
13 Electric Pump Running Status O O x x
14 Electric Pump Phase Reversal O O x x
15 Electric Pump Phase Loss O O x x
16 Electric Pump Fail to Start O O x x
Electric Pump Power Disconnect O O x x
17 Electric Pump Controller Trouble O O x x
18 Diesel Pump Running Status O O x x
21 Diesel Pump not in Auto Mode O O x x
22 Diesel Pump Controller Trouble O O x x
19 Diesel Pump Battery Missing/Charger Trouble O O x x
20 Diesel Pump Engine Trouble O O x x
Low Fuel Level O O x x
23 Tamper Switches/Valves Activation O O x x
24 Low Level in Fire Water Tank O O x x
Kitchen Hood System Alarm Signal O O x x x x x x x x x x
Kitchen Hood Microswitch Removed O O x x
25 FM200 System Alarm Signal O O x x x x x x x x x x
26 FM200 System Trouble Signal O O x x
27 FM200 System Supervisory Signal

28 Foam System Alarm Signal O O x x x x x x x x x x


29 Foam System Trouble Signal O O x x
30 Foam System Supervisory Signal O O x x
31 Deluge System Alarm Signal O O x x x x x x x x x x
32 Deluge System Trouble Signal O O x x
33 Deluge System Supervisory Signal O O x x
34 Fire Alarm AC Power Failure O O x x
35 Fire Alarm System Low Battery O O x x
36 Loss Phase O O x x
37 Open Circuit O O x x
38 Ground Fault O O x x
39 Notification Appliance Circuit Shorted O O x x
40 Generator Running Status O O x x
41 Generator General Trouble Status O O x x
42 Generator not in Auto Mode O O x x