HOW TO USE:
FUNCTION PARAMETERS:
Press SET 5 seconds to enter the main menu settings, press the + -
Switch P0 ... P6, or long press the SET button for 10 seconds without
motion controller automatically confirm return.
Press SET 5 seconds display P0, press SET to set the operating
mode, press the + - switched to heating mode [H] [C] for cooling mode
press SET to return, long press SET or automatic confirmation button for
10 seconds without motion controller carry out.
P1 hysteresis setting:
Press SET 5 seconds display P0, press + - Switch to P1, press SET to set
back the difference, press + - to set hysteresis 0.1 to 15, press SET to return
after the completion of, or long press the SET button for 10 seconds
without motion controller automatically confirm completion.
Cooling mode: When the temperature measurement value ≥ set value, the
relay, refrigeration starts; when the temperature measured value ≤ set value
- the difference between the return, the relay off, cooling off.
Heating mode: When the temperature measurement value ≤ set value, the
relay, the heater starts; when the temperature measured value ≥ set value +
return difference, the relay off, the heater is turned off.
To avoid misuse of others led to the setting temperature is too high risk
that the thermostat is set to a maximum limit function, define the scope of
the thermostat setting to control the maximum temperature set point.
Press SET 5 seconds display P0, press + - Switch to P2, press SET to set
the maximum limit, press + - to set up the set temperature, the maximum is
110, according to a SET return is completed, long press SET or 10 No
keystrokes second controller automatically confirm completion.
For example: Set the maximum temperature set point is 60 to 60 ? can only
be set if you want a higher temperature set point temperature to expand the
scope, you need to adjust the upper limit setting.
Press SET 5 seconds display P0, press + - Switch to P3, press SET to set a
minimum limit, press + - to set the minimum temperature can be set to a
minimum value of -50, press SET to return after the completion of, or long
press SET 10 seconds, the controller automatically confirm no keystrokes
to complete.
For example: Set the minimum temperature set point 2 can only be set to 2
? temperature set point if you want to expand the scope of lower
temperatures, you need to change the setting lower limit.
P4 temperature correction:
Press SET 5 seconds display P0, press + - Switch to P4, press SET to
correct, press + - to set the correction value, press SET to return upon
completion, or long press the SET button for 10 seconds without motion
controller automatically confirm completion .
When the cooling or heating needs work delay, delay function can be
opened to protect the life of equipment.
Press SET 5 seconds display P0, press + - Switch to P5, press SET to set
the delay start time is in minutes, press the + - Set 0-10 minutes, press SET
to return after the completion, or 10 seconds long press SET No keystrokes
controller automatically confirm completion
Cooling mode: the first powered, if the current temperature ≥ set value, the
cooler will not start cooling immediately after the set delay time required to
run start.
Heating mode: the first powered, if the current temperature ≤ set value, the
heater will not start heating immediately after the set delay time required to
run start.
When downtime cooler or heater starts between two adjacent delay start
time is greater than the set value, the cooler starts immediately.
For example, the state set the delay under refrigeration for 5 minutes after
boot cooler startup delay, five minutes after opening the refrigerator to
reach the desired temperature when cooling is stopped, then the start time,
the next time the refrigerator immediately start the timer is complete work
unfinished end timing to wait timed to work, delay in the LED blinks.
In the temperature controller XH-W1209 menu will move with buttons + and – to select
the value or raising or lowering the temperature.
The red LED display indicates when the relay is activated.Always shines as long as the
relay is activated.If the relay is switched off LED off.
PO Heating or Cooling ?
If you set Cooling (C) temperature controller will be activated relay when temperature
falls to the setpoint.
If you set Heating (H) temperature controller will be activated relay when temperature
raise to setpoint.
P1 – Hysteresis or Return diference set
This device model can value set by 0.1C and the lowest value is 0.1C.This is a very
useful feature for precise operation of the temperature controller.For example, if you set
the value of 1C and the desired temperature on the thermostat 20C relay will be
deactivated at 21C (20C+1C). The relay is activated again when the temperature drops
to 20C.
You can set a maximum temperature limit, less than 110 degrees.
Very good feature that lets you set your thermostat by certified accurate thermometer.
If you do not have a certified thermometer leave the value at 0C. Calibration allows you
to adjust the temperature in 0.1 increments.
In this step, you set the start delay in minutes 1-10 min.If you set 1min relay is activated
The menu P6 initially turns OFF to ON and press the SET,then set the temperature at
which the alarm is activated. When is alarm activated display not showing temperature
only – - -.
Other info
The device has a low consumption of 25-35 mA at rest 50-75 mA when the relay is
activated.Be careful if the power supply voltage lower than 10V relay is not activated
although the LED shining