Documente Academic
Documente Profesional
Documente Cultură
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient.
Before carrying out any work on the equipment the user should be familiar with the contents of this
manual, and read relevant chapters carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Date: 2011-08-05
Preface
DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high -voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high
voltage generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the power supply. It
takes a few seconds for the voltage to discharge.
Date: 2011-08-05
Preface
CAUTION!
Earthing
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when the power supply to the equipment is
on, as this may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check
the supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
We reserve all rights to this document an d to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corr ections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Date: 2011-08-05
Preface
Date: 2011-08-05
Table of Contents
Table of Contents
Preface....................................................................................................I
1 Introduction ........................................................................................ 1
Date: 2011-08-05
Table of Contents
2.6 Performance........................................................................................................ 9
2.6.1 Metering Scope and Accuracy .............................................................................................. 10
2.7 Certifications..................................................................................................... 10
4 Supervision ...................................................................................... 21
4.1 Overview............................................................................................................ 21
5 Hardware........................................................................................... 41
Date: 2011-08-05
Table of Contents
5.1 Overview............................................................................................................ 41
5.2 CPU Module (NR4102) on Slot B01(Mandatory) ............................................. 45
6 Settings........................................................................................... 117
6.1 Overview...........................................................................................................117
6.2 Device_Settings for PCS-9705A/B/C..............................................................117
Date: 2011-08-05
Table of Contents
Date: 2011-08-05
Table of Contents
Date: 2011-08-05
Table of Contents
Date: 2011-08-05
Table of Contents
Date: 2011-08-05
Table of Contents
Date: 2011-08-05
1 Introduction
1 Introduction
1.1 Application
PCS-9705 series bay control units (abbreviated BCUs) are mainly applied to measurement and
control of data and signals for bay level of substation. They are object-orientedly designed under
the same hardware and software platform.
Typical application of PCS-9705 series BCUs in SAS is shown in the following figure.
GPS Antenna
Digital Relays
Remote Monitoring
System(DRRMS)
PCS-9700 HMI System IEC60870-5-101,
Anti -maloperation IEC60870-5-104,
DNP 3.0, etc. IEC 60870-5-103
Operator Engineer Workstation
Server A Server B
运
报警
行
主 GPS 时钟 同步装
同
从 置
RCS-9798A/ B
取消
秒脉冲
步
(Optional ) Printer
Station Level RTU
Protection Management Unit
(Optional ) RCS-9785C/ D
Clock
Synchronization
Unit
PCS-9881/PCS-9882
Station Bus: MMS , GOOSE( Interlocking),SNTP
Ethernet Switch
Third-Party IED,
Energy meters, DFR, etc
PCS-9881/PCS-9882
Ethernet Switch Process Bus: SV, GOOSE Tripping/ Binary Input, GMRP IEEE 1588
PCS-221 PCS-222 PCS-221 PCS-222
Merging Unit Intelligent Interposing Relay Set Merging Unit Intelligent Interposing Relay Set
Process Level
Optical Fiber Optical Fiber
1.2 Functions
PCS-9705 series BCUs have an object oriented design, i.e., the user can find a proper sub-type of
bay control unit for an object inside the substation to be monitored and/or controlled. To achieve
this goal, some sub-type bay control units with different functions and/or different configurations
are founded under the same hardware and software platform; the following tables present the
details:
Device models
PCS-9705A PCS-9705B PCS-9705C
Module types
DC analog inputs 8 or 16 8 or 16 8 or 16
Date: 2011-08-05
1 Introduction
Device models
PCS-9705A PCS-9705B PCS-9705C
Module types
DC analog outputs 0 4 0
Synchronism 1 0 2
Note! Only one of the 3 optional sampling methods can be chosen at one time:
1) Conventional sampling method via AI(AC) module(e.g.:NR4402) equipped in slot B02 and slot
B03.
Note! 120 binary inputs are not compatible with GOOSE mode. When GOOSE module is
Circuit breaker.
PCS-9705A Each side of Transformer.
Tap position acquisition/regulation of transformers
Date: 2011-08-05
1 Introduction
1.3 Features
The devices make use of a fully-closed chassis with a complete panel, have completely
separated spaces for electronic and electrical systems. The traditional motherboard wiring
mode is cancelled. At the same time, its software features corresponding anti-interference
measures which enhance their anti-interference capacity; and their electromagnetic radiation
also satisfy relevant standards.
PCS-9705 series BCUs make use of new PowerPC hardware platform, 16 bits parallel A/D
converter, 320*240 graphic dot matrix LCD, and real time multi-task operating system for
industrial purpose so as to realize high-capacity, high-precision, fast, real time information
processing. With high-precision parallel A/D converter, synchronization sampling can be
conducted for all the AC signals to ensure the accuracy of analog quantity measurement
which is up to the 15th harmonic component.
Software and hardware clock synchronization are both adopted with 1ms timing accuracy to
ensure the resolution of Sequence Of Events (abbreviated SOE).
Large scale LCD provides graph and text HMI which makes operation convenient.
The devices are equipped with duplex Ethernet with 100M optical fiber or twisted pair cable.
The devices make use of back plug-in module structure. Electrical and electronic circuits are
strictly separated, which enhances EMC immunity performance.
PCS-9705 series BCUs support IEC61850, IEC60870-5-103 and DNP 3.0 protocols. Please
refer to the Chapter “Communication”for more details of these communication protocols.
Date: 2011-08-05
1 Introduction
Date: 2011-08-05
2 Technical Data
2 Technical Data
(Operating condition)
Digital substation <25W
(Quiescent condition)
Digital substation <30W
Date: 2011-08-05
2 Technical Data
(Operating condition)
Date: 2011-08-05
2 Technical Data
Date: 2011-08-05
2 Technical Data
Date: 2011-08-05
2 Technical Data
Overvoltage category Ⅲ
2.6 Performance
Date: 2011-08-05
2 Technical Data
2.7 Certifications
ISO9001:2000
ISO14001:2004
OHSAS18001:1999
ISO10012:2003
CMMI L4
Date: 2011-08-05
2 Technical Data
Date: 2011-08-05
2 Technical Data
Date: 2011-08-05
3 Operation Theory
3 Operation Theory
Maintenance mode: If the corresponding isolator link is closed, the binary input 1(i.e.
[BI_Maintenance]) will be set as “1”, now this device is in the maintenance mode. The
“ALARM”LED on the front panel of this device is off. The “HEALTHY”LED on the front panel
of this device is lit on as green.
For the details about the maintenance mode, please refer to the Section “Operation
Theory”->“Binary Input”.
Fault mode: When this device has detected a major self-check failure or after a parameter
modification, this device is in the fault mode. The “ALARM”LED on the front panel of this
device will be lit on as yellow. The “HEALTHY”LED on the front panel of this device will be off.
The execution of binary output is blocked, but the analog values and binary inputs can also be
sent to SCADA/RTU.
Acquisition of AC voltage and current coming from the electrical network is done via AI(AC) board.
Note! Only one of the 3 optional sampling methods can be chosen at one time:
1) Conventional sampling method via AI(AC) module(e.g.:NR4402) equipped in slot B02 and slot
B03.
Date: 2011-08-05
3 Operation Theory
with the correct time, the following changes within the debounce time are ignored. The debouncing
time can be set with a range of 0~60000ms. The event is time tagged at the instant of the first
transition. This device checks the state of binary input every 0.625 millisecond.
There are two types of binary input: physical binary input which indicates the apparatus switching
position and virtual binary input. The state of the physical binary input can be displayed in the
menu “Status”and can be sent to SCADA/RTU as states or as changes of state depending on the
protocol. The binary input can be written into the SOE record.
Some of the first 5 binary inputs on BI module on slot B04 are used for specific usages. These
binary inputs are called as Special Purpose Binary Input:
Binary input 1:
The binary input 1(i.e.:[BI_Maintenance]) can only be energized locally by closing the
corresponding isolator link, and this device will show corresponding prompt message via LCD
display to remind the operator that this device is in the maintenance mode when it is
energized.
The application of the binary input [BI_Maintenance] for IEC103 protocol is to block
communication between this device and SCADA (I.e.: HMI system) or remote terminal unit
(RTU).
Please refer to the “GOOSE Function Manual”for the application of [BI_Maintenance] for
IEC61850 protocol.
Binary input 2:
The binary input 2(i.e.: [BI_Block_Dis]) is used for releasing the interlocking function of this
Date: 2011-08-05
3 Operation Theory
device. When [BI_Block_Dis] is set as “1”, the interlocking function of the device will be
disabled.
Binary input 3:
Note! The following 2 special purpose binary inputs are inapplicable to PCS-9705B.
Binary input 4:
If the [BI_Rmt/Loc] is “0”, i.e. this device works in Local Control Mode, when the
[BI_Manual_Synchro] is “1”, the function of synchronism-check for circuit breaker
(abbreviated CB) closing is started.
When all the synchronism-check criteria are met, the CB is closed by manual control.
For PCS-9705B, Binary input 4 is named as [BI_Spare1], and it is applied as the 1st reserved
binary input for possible special purpose in the future.
If the [BI_Rmt/Loc] is “0”, i.e. this device works in Local Control Mode, when the
[BI_Manual_Synchro1] is “1”, the function of synchronism-check for closing the 1st CB is
started.
When all the synchronism-check criteria are met, the 1st CB wiil be closed by manual control.
Binary input 5:
For PCS-9705A, Binary input 5 is named as [BI_Spare1], and it is applied as the 1st reserved
binary input for possible special purpose in the future.
For PCS-9705B, Binary input 5 is named as [BI_Spare2], and it is applied as the 2nd
reserved binary input for possible special purpose in the future.
If the [BI_Rmt/Loc] is “0”, i.e. this device works in Local Control Mode, when the
[BI_Manual_Synchro2] is “1”, the function of synchronism-check for closing the 2nd CB is
started.
When all the synchronism-check criteria are met, the 2nd CB wiil be closed by manual control.
Binary input 6:
For PCS-9705A, Binary input 6 is named as [BI_Spare2], and it is applied as the 2nd
reserved binary input for possible special purpose in the future. The 1st tap position binary
Date: 2011-08-05
3 Operation Theory
For PCS-9705B, Binary input 6 is named as [BI_Spare3], and it is applied as the 3rd reserved
binary input for possible special purpose in the future.
For PCS-9705C, Binary input 6 is named as [BI_Spare1], and it is applied as the 1st reserved
binary input for possible special purpose in the future.
3.7 Records
Please refer to the Section “Human-Machine Interface”->“Understand the HMI Menu Tree”
->“Records”for more details.
3.8 Interlocking
Before a switching command, output is executed, the interlocking logic of this device will check
whether the preprogrammed interlocking logic equations are met to permit the operation or not.
The logic interlocking function is enabled by setting the parameter [En_Trpn_Blk] and/or
[En_Clsn_Blk] to “1”. Interlocking logic equations can be configured straight forwardly upon the
devices to meet the customer’ s specific requirements via adding configurable logic by the
interlocking configuration tool with a user-friendly interface.
The interlocking conditions depend on the circuit configuration and apparatus position status at
any given time.
If the setting [En_Hardware_Blk] is set as “1”, hardware interlocking is enabled. This function is
based on software interlocking logic function and provides one more output contact for every
remotely-controlled apparatus as user purpose which is built in the BO(IL) module(i.e. interlocking
module). When executing a switching command output, if the interlocking logic conditions are met,
besides internal software interlocking corresponds remote trip or remote closing contact, this
device also provides an additional normal open contact for the remotely-controlled apparatus via
Date: 2011-08-05
3 Operation Theory
BO(IL) module.
3.9 Synchronism-check
This feature only aims at remote closing 1 if this device has 1 group of synchronism-check for CB
closing (only appropriate for PCS-9705A) or aimed at remote closing 1 and 2 if this device (only
appropriate for PCS-9705C) has 2 groups of synchronism-check for CB closing.
The BCU synchronism-check function is designed to check whether the voltages with respect to
phase angle, frequency and magnitude on both sides of the CB are in synchronism to ensure that
CB closing can be done safely.
3 configurable synchronism-check modes are designed: No check mode, Dead check mode and
Synchronism-check mode.
Please refer to the Chapter “Settings” for the function links and synchronism settings of
PCS-9705A and PCS-9705C.
Note! 4 remote control commands are optional: Normal telecontrol, No check mode,
When Binary input 3 ([BI_Rmt/Loc ]) is set as “1”, if the remote control command adopts “No
check mode”, “Dead check mode” or “Synchronism-check mode”, the settings
[Link_DeadChk] and [Link_SynChk] in the menu “Function_Links”will be invalid. Whether “No
check mode”, “Dead check mode”or “Synchronism-check mode”will take effect is determined
by the remote control command from SCADA.
When Binary input 3 ([BI_Rmt/Loc]) is set as “1”, if the remote control command adopts “Normal
remote control”, and then whether “No check mode”, “Dead check mode” or
“Synchronism-check mode”will take effect is determined by the settings [Link_DeadChk] and
[Link_SynChk] in the menu “Function_Links”of PCS-9705.
When Binary input 3 ([BI_Rmt/Loc]) is set as “0”, whether “No check mode ”, “Dead check
mode” or “Synchronism-check mode” will take effect is determined by the settings
[Link_DeadChk] and [Link_SynChk] in the menu “Function_Links”of PCS-9705.
Date: 2011-08-05
3 Operation Theory
When this device is set to work in No check mode and receives a closing command, the CB will be
closed without synchronism-check and dead check.
When this device is set to work in Synchronism-check mode, synchronism-check criteria must be
met to close CB. From receiving a closing command, this device will continuously check whether
the 2 voltages (Incoming voltage and reference voltage) involved in dead check can meet the
synchronism-check criteria. If the synchronism-check criteria are not met in [t_Reset_SynChk],
after [t_Reset_SynChk], this device will not check the synchronism-check criteria any longer, the
failure of synchronism-check will be confirmed and an alarm signal [Alm_SynChkFail] will be
issued and it can be sent to SCADA.
If the synchronism-check criteria are met during the time [t_Reset_SynChk], the CB will be
closed.
When this device is set to work in Dead check mode, dead check criteria must be met to close CB.
Dead check mode is determined by the setting [Opt_Mode_DeadChk]. From receiving a closing
command, this device will continuously check whether the 2 voltages (Incoming voltage and
reference voltage) involved in dead check can meet the dead check criteria. If the dead check
criteria are not met in [t_Reset_SynChk], after [t_Reset_SynChk], this device will not check the
dead check criteria any longer, the failure of dead check will be confirmed and an alarm signal
[Alm_SynChkFail] will be issued and it can be sent to SCADA.
If the dead check criteria are met during the time [t_Reset_SynChk], the CB will be closed.
Manual closing as well as remote closing can be checked by the function with the same settings.
Clock synchronization: PCS-9705 can realize clock synchronization through timing message
sent by the monitoring system. It can also realize synchronization of the device’
s clock and
the standard time by receiving IRIG-B or PPS signals from an external timing device(e.g.:
RCS-9785C or RCS-9785D).
Date: 2011-08-05
3 Operation Theory
The hardware faults include the faults of RAM,E 2PROM, and binary output circuits.
The LED HEALTHY can not be lit on again automatically after a fault clearing . The device needs to
be reset or powered on manually.
3.13 Regulation
If AO module is equipped in slot B10, PCS-9705B can receive regulation messages from local
SCADA system or remote control centers, and then send DC voltage/current output to DCS
system to regulate the active power output of the specified generator.
User can also simulate regulation by operating on the menu of this device, i.e.: to operate on the
menu of PCS-9705B to send DC voltage/current output to DCS system.
Please refer to the Chapter “Settings”for more details about the regulation function.
Note! When AO module is equipped in slot B10 and [Opt_Type_ReguX] (X=1,2,3,4) is set
Date: 2011-08-05
3 Operation Theory
Date: 2011-08-05
4 Supervision
4 Supervision
4.1 Overview
Alarm signals are displayed in the submenu “Status”->“Superv_State”.
Please refer to the “GOOSE Function Manual”for the application of GOOSE alarm signals for
details.
[Opt_TimeSyn] Function
Date: 2011-08-05
4 Supervision
Please refer to the Chapter “Settings”for more details about the settings
[U0_Alm_ROV], [En_Alm_ROV], [U1n_VT_U0] and [U2n_VT_U0].
[U0_Alm_ROV] in the menu “Settings”->“System_Settings” is
expressed as a percentage.
If the [En_Alm_ROV] is enabled and the primary 3U0 voltage input (i.e.:
[3U0Ext_Pri] displayed in the submenu
“Analog”->“Measurements”->“Primary_Values”in PCS-9705A) is higher
than [U0_Alm_ROV]*[U1n_VT_U0] for more than 10s, and then
[Alm_ROV] will be issued and it can be sent to SCADA.
3 Alm_ROV
When [3U0Ext_Pri] is lower than [U0_Alm_ROV]*[U1n_VT_U0] for more
than 1s, the alarm signal [Alm_ROV] will disappear.
If the [En_Alm_ROV] is enabled and the secondary 3U0 voltage input
(i.e.: [3U0Ext_Sec] displayed in the submenu
“Analog”->“Measurements”->“Secondary_Values” in PCS-9705A) is
higher than [U0_Alm_ROV]*[U2n_VT_U0] for more than 10s, and then
[Alm_ROV] will be issued and it can be sent to SCADA.
When [3U0Ext_Sec] is lower than [U0_Alm_ROV]*[U2n_VT_U0] for
more than 1s, the alarm signal [Alm_ROV] will disappear.
Only one of the 3 optional sampling methods can be chosen at one time:
1) Conventional sampling method via AI(AC) module(e.g.:NR4402)
equipped in slot B02 and slot B03.
2) IEC60044-8 digital sampling method via slot B02 AI(ECVT)
module(e.g.:NR4201B).
3) IEC61850-9-2 digital sampling method via slot B03 NET-DSP
module(e.g.:NR4136A).
In conventional sampling method, this alarm signal is ineffective and will
4 Alm_SmplCh
not be issued.
In IEC60044-8 digital sampling method via slot B02 AI(ECVT) module, if
any of the following events occurs, this alarm signal will be produced to
issue an alarm and it can be sent to SCADA:
1) The optical fiber linked to AI(ECVT) module is pulled out.
2) The AI(ECVT) module can not receive any data.
In IEC61850-9 -2 digital sampling method via slot B03 NET-DSP module, if
any of the following events occurs, this alarm signal will be produced to
Date: 2011-08-05
4 Supervision
5 Alm_Pwr_BI_B04 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
6 Alm_Pwr_BI_B05 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
7 Alm_Pwr_BI_B06 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
8 Alm_Pwr_BI_B07 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
12 GAlm_ADisc_SL_XX
13 GAlm_ADisc_B03_PL_XX
14 GAlm_BDisc_B03_PL_XX
15 GAlm_AStorm_B03_PL
XX=01,02… 16.
16 GAlm_BStorm_B03_PL
Please refer to the “PCS-9611 and PCS-9705 GOOSE Function
17 GAlm_General_B03
Instruction Manual”for the application of GOOSE alarm signals for
18 GAlm_ADisc_B09_PL_XX details.
19 GAlm_BDisc_B09_PL_XX
20 GAlm_AStorm_B09_PL
21 GAlm_BStorm_B09_PL
22 GAlm_General_B09
If some frames are lost in SV message received by this device through the
23 SVAlm_FrameLoss_X SV receiving link X(X=1,2,3,4), this alarm signal will be issued and it can
be sent to SCADA.
Date: 2011-08-05
4 Supervision
Note! This alarm signal will only be effective when slot B03
Date: 2011-08-05
4 Supervision
If no valid SV message is
received via the SV receiving
link X(X=1,2,3,4). of SV
25 SVAlm_NetA_X
network A, this alarm signal
will be issued and it can be
sent to SCADA.
Date: 2011-08-05
4 Supervision
When this device is set to work in Dead check mode, dead check criteria
must be met to close CB. Dead check mode is determined by the setting
[Opt_Mode_DeadChk]. From receiving a closing command, this device
29 Sig_Ok_SynChk
will continuously check whether the 2 voltages (Incoming voltage and
reference voltage) involved in dead check can meet the dead check
criteria. If the dead check criteria are not met in [t_Reset_SynChk], after
[t_Reset_SynChk], this device will not check the dead check criteria any
longer, the failure of dead check will be confirmed and an alarm signal
[Alm_SynChkFail] will be issued and it can be sent to SCADA.
If the dead check criteria are met during the time [t_Reset_SynChk],
[Sig_Ok_DeadChk] will be issued and the CB will be closed.
actual value of XX will differ according to the number of BI module in this device. (i.e.: If
only 3 BI modules are configured, [Alm_Pwr_BI_B04], [Alm_Pwr_BI_B05] and
[Alm_Pwr_BI_B06] will be displayed in the submenu “Status”->“Superv_State”, but
[Alm_Pwr_BI_B07],[Alm_Pwr_BI_B08],[Alm_Pwr_BI_B09] will be hidden).
Note! In the above table, [Alm_VTS] can be generated with a delay of 2.5s when meeting
2) Any phase sequence secondary voltage is less than 30V with the presence of any phase
currents (I.e., the secondary value of anyone of the phase A/B/C current is in excess of
0.06In).
Where:
If any of these 2 conditions is met and lasts for 2.5s, an alarm signal named [Alm_VTS] will
be issued. If both of these 2 conditions are not met for 10s, [Alm_VTS] will disappear.
Date: 2011-08-05
4 Supervision
[Opt_TimeSyn] Function
Date: 2011-08-05
4 Supervision
Please refer to the Chapter “Settings”for more details about the settings
[U0_Alm_ROV], [U1n_VT_U0] and [U2n_VT_U0].
[U0_Alm_ROV] in the menu “Settings”->“System_Settings” is
expressed as a percentage.
If the primary 3U0 voltage input (i.e.: [3U0Ext_Pri] displayed in the
submenu “Analog”->“Measurements”->“Primary_Values2” in
PCS-9705B) is higher than [U0_Alm_ROV]*[U1n_VT_U0] for more than
10s, and then [Alm_ROV1] will be issued and it can be sent to SCADA.
2 Alm_ROV1
When [3U0Ext_Pri] is lower than [U0_Alm_ROV]*[U1n_VT_U0] for more
than 1s, the alarm signal [Alm_ROV1] will disappear.
If the secondary 3U0 voltage input (i.e.: [3U0Ext_Sec] displayed in the
submenu “Analog”->“Measurements ”->“Secondary_Values2” in
PCS-9705B) is higher than [U0_Alm_ROV]*[U2n_VT_U0] for more than
10s, and then [Alm_ROV1] will be issued and it can be sent to SCADA.
When [3U0Ext_Sec] is lower than [U0_Alm_ROV]*[U2n_VT_U0] for
more than 1s, the alarm signal [Alm_ROV1] will disappear.
Please refer to the Chapter “Settings”for more details about the settings
[U0_Alm_ROV], [En_VT4_U0], [U1n_VT_U0] and [U2n_VT_U0].
[U0_Alm_ROV] in the menu “Settings”->“System_Settings” is
expressed as a percentage.
If [En_VT4_U0] is disabled, i.e.: the 4th group voltage inputs (Pin
19~pin24:“U10”~ “U12n” on AI(AC) module) is disabled to receive.3
external zero sequence voltage inputs, [Alm_ROV2] will not be issued.
If [En_VT4_U0] is enabled, i.e.:the 4th group voltage inputs (Pin
19~pin24:“U10”~ “U12n” on AI(AC) module) is enabled to receive.3
external zero sequence voltage inputs, and [Ua_Pri_Grp4] (displayed in
Please refer to the Chapter “Settings”for more details about the settings
[U0_Alm_ROV], [En_VT4_U0], [U1n_VT_U0] and [U2n_VT_U0].
Date: 2011-08-05
4 Supervision
Please refer to the Chapter “Settings”for more details about the settings
[U0_Alm_ROV], [En_VT4_U0], [U1n_VT_U0] and [U2n_VT_U0].
[U0_Alm_ROV] in the menu “Settings”->“System_Settings” is
expressed as a percentage.
If [En_VT4_U0] is disabled, i.e.: the 4th group voltage inputs (Pin
19~pin24:“U10”~ “U12n” on AI(AC) module) is disabled to receive.3
external zero sequence voltage inputs, [Alm_ROV4] will not be issued.
If [En_VT4_U0] is enabled, i.e.:the 4th group voltage inputs (Pin
19~pin24:“U10”~ “U12n” on AI(AC) module) is enabled to receive.3
external zero sequence voltage inputs, and [Uc_Pri_Grp4] (displayed in
Only one of the 3 optional sampling methods can be chosen at one time:
1) Conventional sampling method via AI(AC) module(e.g.:NR4402)
Date: 2011-08-05
4 Supervision
9 Alm_SmplCh4 If any of the following events occurs, this alarm signal will be produced to
issue an alarm and it can be sent to SCADA:
1) The optical fiber linked to the RX4 input channel of AI(ECVT) module
is pulled out.
Date: 2011-08-05
4 Supervision
2) The AI(ECVT) module can not receive any data via the RX4 input
channel.
10 Alm_Pwr_BI_B04 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
11 Alm_Pwr_BI_B05 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
12 Alm_Pwr_BI_B06 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
13 Alm_Pwr_BI_B07 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
16 Alm_DC_IoutX SCADA.
Date: 2011-08-05
4 Supervision
22 GAlm_AStorm_B03_PL details.
23 GAlm_BStorm_B03_PL
24 GAlm_General_B03
25 GAlm_ADisc_B09_PL_XX
26 GAlm_BDisc_B09_PL_XX
27 GAlm_AStorm_B09_PL
28 GAlm_BStorm_B09_PL
29 GAlm_General_B09
If some frames are lost in SV message received by this device through the
SV receiving link X(X=1,2,3,4), this alarm signal will be issued and it can
be sent to SCADA.
30 SVAlm_FrameLoss_X
Note! This alarm signal will only be effective when slot B03
31 Alm_TimeSyn_B03
If slot B03 is equipped with NET-DSP module and the setting
[En_GPSSynSample_B03] is set as “1”, the clock synchronization
method of this device will only be determined by [Opt_TimeSyn_B03].
[Opt_TimeSyn_B03] Function
Date: 2011-08-05
4 Supervision
If no valid SV message is
received via the SV receiving
link X(X=1,2,3,4). of SV
32 SVAlm_NetA_X
network A, this alarm signal
will be issued and it can be
sent to SCADA.
actual value of XX will differ according to the number of BI module in this device. (i.e.: If
only 3 BI modules are configured, [Alm_Pwr_BI_B04], [Alm_Pwr_BI_B05] and
[Alm_Pwr_BI_B06] will be displayed in the submenu “Status”->“Superv_State”, but
[Alm_Pwr_BI_B07],[Alm_Pwr_BI_B08],[Alm_Pwr_BI_B09] will be hidden).
Date: 2011-08-05
4 Supervision
[Opt_TimeSyn] Function
Date: 2011-08-05
4 Supervision
Only one of the 3 optional sampling methods can be chosen at one time:
1) Conventional sampling method via AI(AC) module(e.g.:NR4402)
equipped in slot B02 and slot B03.
2) IEC60044-8 digital sampling method via slot B02 AI(ECVT)
module(e.g.:NR4201B).
3) IEC61850-9-2 digital sampling method via slot B03 NET-DSP
module(e.g.:NR4136A).
In conventional sampling method, this alarm signal is ineffective and will
not be issued.
In IEC60044-8 digital sampling method via slot B02 AI(ECVT) module, if
any of the following events occurs, this alarm signal will be produced to
4 Alm_SmplCh1
issue an alarm and it can be sent to SCADA:
1) The optical fiber linked to the RX1 input channel of AI(ECVT) module
is pulled out.
2) The AI(ECVT) module can not receive any data via the RX1 input
channel.
In IEC61850-9 -2 digital sampling method via slot B03 NET-DSP module, if
any of the following events occurs, this alarm signal will be produced to
issue an alarm and it can be sent to SCADA:
1) The optical fiber linked to the SV(i.e.: Sampled Valued) sampling port
of NET-DSP module is pulled out.
2) The NET-DSP module can not receive any data.
Date: 2011-08-05
4 Supervision
8 Alm_Pwr_BI_B04 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
9 Alm_Pwr_BI_B05 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
10 Alm_Pwr_BI_B06 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
11 Alm_Pwr_BI_B07 connected to positive pole of binary input auxiliary power, this alarm signal
will be produced to issue an alarm and it can be sent to SCADA.
19 GAlm_BStorm_B03_PL
20 GAlm_General_B03
21 GAlm_ADisc_B09_PL_XX
22 GAlm_BDisc_B09_PL_XX
23 GAlm_AStorm_B09_PL
24 GAlm_BStorm_B09_PL
Date: 2011-08-05
4 Supervision
25 GAlm_General_B09
If some frames are lost in SV message received by this device through the
SV receiving link X(X=1,2,3,4), this alarm signal will be issued and it can
be sent to SCADA.
26 SVAlm_FrameLoss_X
Note! This alarm signal will only be effective when slot B03
[Opt_TimeSyn_B03] Function
Date: 2011-08-05
4 Supervision
If no valid SV message is
received via the SV receiving
link X(X=1,2,3,4). of SV
28 SVAlm_NetA_X
network A, this alarm signal
will be issued and it can be
sent to SCADA.
actual value of XX will differ according to the number of BI module in this device. (i.e.: If
only 3 BI modules are configured, [Alm_Pwr_BI_B04], [Alm_Pwr_BI_B05] and
[Alm_Pwr_BI_B06] will be displayed in the submenu “Status”->“Superv_State”, but
[Alm_Pwr_BI_B07],[Alm_Pwr_BI_B08],[Alm_Pwr_BI_B09] will be hidden).
Note! In the above table, [Line1_Alm_VTS] can be generated with a delay of 2.5s when
2) Any phase sequence secondary voltage of Busbar 1 is less than 30V with the presence of
any phase currents (I.e., the secondary value of anyone of the phase A/B/C current is in
Date: 2011-08-05
4 Supervision
excess of 0.06In).
Where:
If any of these 2 conditions is met and lasts for 2.5s, an alarm signal named [Line1_Alm_VTS]
will be issued. If both of these 2 conditions are not met for 10s, [Line1_Alm_VTS] will
disappear.
Note! In the above table, [Line2_Alm_VTS] can be generated with a delay of 2.5s when
2) Any phase sequence secondary voltage of Busbar 2 is less than 30V with the presence of
any phase currents (I.e., the secondary value of anyone of the phase A/B/C current is in
excess of 0.06In).
Where:
If any of these 2 conditions is met and lasts for 2.5s, an alarm signal named [Line2_Alm_VTS]
will be issued. If both of these 2 conditions are not met for 10s, [Line2_Alm_VTS] will
disappear.
Date: 2011-08-05
4 Supervision
Date: 2011-08-05
5 Hardware
5 Hardware
5.1 Overview
The PCS-9705 series BCUs adopt modularized hardware design. Different functional
modules are shown in the following table.
1) 3* NR4501
2) 4* NR4501
3) 5* NR4501
BI module 4) 6* NR4501
5) 4* NR4501+ 1* NR4504
6) 4* NR4501+ 2* NR4504
7) 5* NR4501+ 1* NR4504
AO module 0 or 1 NR4411A
Note! The BO module and the BO(IL) module share the same board: NR4521. If an
Note! The medium of the Ethernet interface of the CPU module and GOOSE module is
optional. Different subtypes of the CPU module and GOOSE module correspond to
different Ethernet interface medium.
Date: 2011-08-05
5 Hardware
Note! The hardware configuration of this device must be definitely declared in the
There are 20 slots in the rear panel of PCS-9705, these slots are named as B01~B 20 from
left to right by the rear view of PCS-9705.
AI(DC) module B10 or B11 can be equipped with the AI(DC) module.
(Optional) AI(DC) module can only be installed in B10 or B11.
BO(IL) module B12 ~ B13 can be equipped with the BO(IL) module.
(Optional) BO(IL) module can only be installed in B12~B13.
The following figure shows the front panel of the PCS-9705A, PCS-9705B and PCS-9705C.
Date: 2011-08-05
5 Hardware
1 11
HEALTHY
2
ALARM
12 PCS-9705
3 13 EN BAY CONTROL UNIT
U
4 14
5 15
6 16 ENT
7 17
D JUS
T
8 18
9 19
- +
10 20
ESC
The following figure shows the rear panel of the PCS-9705A without GOOSE module and
adopts conventional sampling method .
For PCS-9705B and PCS-9705C without GOOSE module and adopt conventional sampling
method, the rear panels are are similar to PCS-9705A, but the AI(AC) modules of them are
different from each other.
Note! In engineering applications, the number of the modules equipped in PCS-9705 may
Figure 5.1-2 An example of rear panel of PCS-9705A (CPU module adopts NR4102C; with 6 BI modules, 1
AI(DC) modules, 2 BO(IL) modules, 6 BO modules)
The following figure shows the rear panel of the PCS-9705A with GOOSE module and
adopts conventional sampling method.
For PCS -9705B and PCS-9705C with GOOSE module and adopt conventional sampling
method, the rear panels are are similar to PCS-9705A, but the AI(AC) modules of them are
different from each other.
Date: 2011-08-05
5 Hardware
Figure 5.1-3 An example of rear panel of PCS-9705A (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 3 NR4501 BI modules, 1 AI(DC) module, 2 BO(IL) modules, 3 BO modules)
The following figure shows the rear panel of the PCS-9705A with GOOSE module and
adopt s IEC60044-8 digital sampling method via slot B02 AI(ECVT) module(e.g.:NR4201B).
For PCS-9705B and PCS -9705C with GOOSE module and adopt IEC60044-8 digital
sampling method via slot B02 AI(ECVT) module, the rear panels are similar to PCS-9705A.
Figure 5.1-4 Rear panel of PCS-9705A (CPU module adopts NR4102J; GOOSE module adopts NR4126A; 4
NR4501 BI modules, 1 NR4504 BI module, 0 AI(DC) module, 2 BO(IL) modules, 3 BO modules are adopted
for example)
The following figure shows the rear panel of the PCS-9705A with GOOSE module and
adopts IEC61850-9-2 digital sampling method via slot B03 NET-DSP module(e.g.:NR4136A).
For PCS-9705B and PCS-9705C with GOOSE module and adopt IEC61850-9-2 digital
sampling method via slot B03 NET-DSP module, the rear panels are similar to PCS-9705A.
Date: 2011-08-05
5 Hardware
Figure 5.1-5 Rear panel of PCS-9705A (CPU module adopts NR4102J; GOOSE module adopts NR4126A; 4
NR4501 BI modules, 1 NR4504 BI module, 0 AI(DC) module, 2 BO(IL) modules, 3 BO modules are adopted
for example)
The CPU module is the kernel part of this equipment, and contains a powerful microchip processor
and some necessary electronic elements. This powerful processor performs all of the functions for
this device: calculation, control, communication and user interface functions.
Calculations
Basing on the analog inputs, the CPU module can calculate the measurement values, such as
active power, reactive power and power factor etc. All these values can be sent to a SAS or a
RTU through the communication interfaces.
Communication management
The CPU module can effectively manage the communication procedure and reliably send out
some useful information through its two Ethernet communication interfaces. A 20-pin interface
for the connection with the HMI module is contained in this module too. If an event has
occurred (such as SOE, CB tripping event etc.), this module will send out the relevant event
information through these interfaces, and make it be easily observable by the user.
Clock Synchronization
This module has a local clock chip and an interface to receive clock synchronized
signals(IRIG-B) from an external clock source. Based on the timing message (from SAS or
Date: 2011-08-05
5 Hardware
RTU) or the IRIG-B signal, this module can make the local clock synchronize with the
standard clock.
Generally speaking, the CPU module in PCS-9705 adopts the board named as NR4102.
4 types of CPU modules(i.e.: NR4102C, NR4102D, NR4102J, NR4102K)are optional as shown
in the following 4 figures.
Each type of BCU may be equipped with any one of these 4 CPU modules.
The 1st type of CPU module (NR4102C) as shown in the following figure has 2 electrical Ethernet
ports, but has no fiber Ethernet port.
The connectors of all the 4 types of the CPU modules have the same connectors as shown in the
following table.
1 SYN+
EIA RS-485 standardized interface for clock synchronization, PPS
2 SYN-
and IRIG-B signals are permitted.
3 SHLD
4 Reserved.
5 Reserved.
6 Reserved.
7 Reserved.
Date: 2011-08-05
5 Hardware
Pin connection definition of the RJ-45 socket of NR4102C/ NR4102D/NR4102J/NR4102K are the
same as shown in the following table.
Table 5.2-2
4 NC Not connected
5 NC Not connected
7 NC Not connected
8 NC Not connected
The 2nd type of CPU (NR4102D) as shown in the following figure has 4 electrical Ethernet ports,
but has no fiber Ethernet port.
4 RJ-45 Ethernet connectors are on the front of this kind of CPU board.
The 3rd type of CPU (NR4102J) as shown in the following figure has 2 SC type fiber Ethernet
Date: 2011-08-05
5 Hardware
The 4th type of CPU (NR4102K) as shown in the following figure has 2 ST type fiber Ethernet
ports and 2 electrical Ethernet ports.
Date: 2011-08-05
5 Hardware
Generally speaking, the AI(ECVT) module in PCS-9705 adopts the board named as NR4201B.
The AI(ECVT) module is a digital sampling module applied in a digital substation for sampling the
current and voltage from the electronic transformer through merging units. The communication
protocol is abided by the IEC60044-8 standard protocol strictly.
The AI(ECVT) module of PCS-9705 will send these analog inputs to the CPU module for further
treatment.
Note! The width of AI(AC) module and PWR module is double of other modules. An AI(AC)
module or a PWR module occupies 2 slots while any other module only occupies 1 slot.
Date: 2011-08-05
5 Hardware
The AI(AC) module is an analog input unit. It contains voltage transformers and current
transformers. It can transform these high AC input values to relevant low AC output value, which
are suited to the analog inputs of the CPU module. It also can be thought as a bridge between the
CPU module and the external analog signals that come into this device. The transformers are
used both to step-down the currents and voltages to levels appropriate to this devices’electronic
circuit and to provide effective isolation between this device and the power system. A low pass
filter circuit is connected to each transformer (CT and VT) secondary circuit for reducing the noise
of each analog AC input signal.
Note! The rated value of the input current transformer is optional: 1A or 5A. The rated
value of the CT must be definitely declare d in the technical scheme and the contract.
Note! Because the rated value of the input current transformer is optional, it is necessary
to check that whether the rated values of the current transformer inputs are in
accordance with the demand of the practical engineering before putting the device into
operation.
Generally speaking, the AI(AC) module in PCS-9705 adopts the board named as NR4402.
There are 3 types of AI(AC) modules providing various numbers of CT and VT separately
applicable to difference types of BCUs.
Note! In the above figure, P01 means the 1st pin. P02 ,… , P26 have similar meaning.
Date: 2011-08-05
5 Hardware
In the figures about pin description of this instruction manual, P01, P02, … have
similar meanings, too.
1 Ia
Current input of phase A.
2 Ian
3 Ib
Current input of phase B.
4 Ibn
5 Ic
Current input of phase C.
6 Icn
7 3I0
The input of the zero sequence current.
8 3I0n
9 Not used.
10 Not used.
11 Not used.
12 Not used.
13 Ua
14 Uan
17 Uc
18 Ucn
19 3U0
The input of the zero sequence voltage.
20 3U0n
22 Un_syn breaker.
23 Not used.
24 Not used.
25 Not used.
26 Not used.
Date: 2011-08-05
5 Hardware
1 U1
Voltage input of phase A.
2 Un1
3 U2
Group 1 Voltage input of phase B.
4 Un2
5 U3
Voltage input of phase C.
6 Un3
7 U4
Voltage input of phase A.
8 Un4
9 U5
Group 2 Voltage input of phase B.
10 Un5
11 U6
Voltage input of phase C.
12 Un6
13 U7
Voltage input of phase A.
14 Un7
15 U8
Group 3 Voltage input of phase B.
16 Un8
17 U9
Voltage input of phase C.
18 Un9
Date: 2011-08-05
5 Hardware
20 Un10
21 U11
Voltage input of phase B.
22 Un11
23 U12
Voltage input of phase C.
24 Un12
25 U13
The input of the zero sequence voltage.
26 Un13
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
Date: 2011-08-05
5 Hardware
1 Ia1
Current input of phase A.
2 Ia1n
5 Ic1
Current input of phase C.
6 Ic1n
7 Ia2
Current input of phase A.
8 Ia2n
11 Ic2
Current input of phase C.
12 Ic2n
15 Ua1
Date: 2011-08-05
5 Hardware
Uc2 2nd CB )
23
24 Un2
Generally speaking, the NET-DSP in PCS-9705 adopts the board named as NR4136A.
The NET-DSP module is a digital sampling module applied in a digital substation for sampling the
current and voltage from the electronic transformer through merging units. The communication
protocol is abided by the IEC61850-9-2 standard protocol strictly.
The NET-DSP module of PCS-9705 will send these analog inputs to the CPU module for further
treatment.
The NET-DSP module can also be used to transmit or receive the binary inputs via GOOSE
network. It can also trip or close the corresponding CB according to the control commands from
manual operation on PCS-9705 or from SCADA/RTU.
Note! The GOOSE function of slot B09 GOOSE module and slot B03 NET-DSP module
are the same, they can be appiled at the same time, and they can be adopted
independently. But the NET-DSP module supports the IEC61850-9-2 digital sampling
method while slot B09 GOOSE module does not support.
As shown in the following figure, the NET-DSP module (NR4136A) has 6 LC type optical Ethernet
ports(TX1/RX1, TX2/RX2, TX3/RX, TX4/RX4, TX5/RX5, TX6/RX6) for receiving or transmitting
the sampled values or GOOSE command.
Date: 2011-08-05
5 Hardware
NR4136A
TX1
RX1
TX2
RX2
TX3
RX3
TX4
RX4
TX5
RX5
TX6
RX6
IEC60044-8
Communication port
IRIG-B
As shown in the following figure, there are 2 ST type optical Ethernet ports:
2) IRIG-B: applied to receive the clock synchronization input signals. It corresponds to the clock
synchronization method “IRIG-B(Fiber optic)”.
Two types of BI modules are provided in this device: NR4501 and NR4504.
Date: 2011-08-05
5 Hardware
Note! If the GOOSE module is adopted, B09 must be configured with the GOOSE module,
1 common negative connection of all the binary inputs of this board (i.e.:the 22nd terminal
Opto-_X(X=1,2,3,4,5,6).
Each binary input is processed by a well-designed debouncing technique to avoid any hazardous
behavior (multiple state changes during a given duration). A separate debounce and chatter time
(i.e.: [t_DPU_BI001],… ,[t_DPU_BI120], please refer to the Chapter “Settings”for more details)
may be set for each of the binary input.
The auxiliary power supervision input terminal should be connected to the positive pole of a binary
input auxiliary power.
If the PwrSuperv_X(X=1,2,3,4,5,6) terminal of the NR4501 BI module on BXX (XX=B04, B05, B06,
B07) is not connected to positive pole of binary input auxiliary power, [Alm_Pwr_BI_BXX] (XX=B04,
B05, B06, B07, B08, B09) will be produced to issue an alarm and it can be sent to SCADA.
7 common negative connections of this module, each of them corresponds to 2 binary inputs of
this module.
Each binary input is processed by a well-designed debouncing technique to avoid any hazardous
behavior (multiple state changes during a given duration). A separate debounce and chatter time
(i.e.: [t_DPU_BI081],… , [t_DPU_BI106], please Chapter “Settings”for more details) may be set
for each of the binary input.
Date: 2011-08-05
5 Hardware
Note!
NR4501A and NR4501D share the same pin definition, only their working voltages of all the binary
inputs are different.
For NR4501A, the rated working voltage of all the binary inputs is 110~250Vdc.
For NR4501D, the rated working voltage of all the binary inputs is 24~48Vdc.
Note!
In application, the last letter “A”(of NR4501A) and “D”(of NR4501D) will be printed on the module,
but the last letter is omitted in the figures in this instruction manual.
Date: 2011-08-05
5 Hardware
The following table shows the pin description of the NR4501BI module on B04 of PCS-9705A.
6 BI_Spare1 The 1st reserved binary input for possible special purpose in the future.
BI_Spare2 The 2nd reserved binary input for possible special purpose in the future.
7
(Tap Pos1) The 1st tap position binary input can be connected to this terminal.
Date: 2011-08-05
5 Hardware
22 Opto-_1 Common negative connection of all the binary inputs of this module.
Note! The rated voltage of binary input is optional: 24V, 48V, 110V, 220V, 125V or 250V,
which must be definitely declared in the technical scheme and the contract. It is
necessary to check whether the rated voltage of BI module meets the demand of the
engineering before putting the relay into operation.
Date: 2011-08-05
5 Hardware
The following table shows the pin description of the NR4501 BI module on B04 of PCS-9705B.
Date: 2011-08-05
5 Hardware
3 BI_Block_Dis (1:released,
0:unreleased)
The 1st reserved binary input for possible special purpose in the
5 BI_Spare1
future.
The 2nd reserved binary input for possible special purpose in the
6 BI_Spare2
future.
The 3rd reserved binary input for possible special p urpose in the
7 BI_Spare3
future.
22 Opto-_ 1 Common negative connection of all the binary inputs of this module.
Date: 2011-08-05
5 Hardware
The following table shows the pin description of the NR4501 BI module on B04 of PCS-9705C.
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
Date: 2011-08-05
5 Hardware
A binary input for enabling the telecontrol (1: enable remote control,
4 BI_Rmt/Loc
0:enable local control)
The 1st reserved binary input for possible special purpose in the
7 BI_Spare1
future.
Date: 2011-08-05
5 Hardware
22 Opto-_1 Common negative connection of all the binary inputs of this module.
The following table shows the pin description of the NR4501 BI module on B05 of PCS-9705A.
Date: 2011-08-05
5 Hardware
22 Opto-_ 2 Common negative connection of all the binary inputs of this module.
The terminal definition of the NR4501 BI module on B05 of PCS-9705B and PCS-9705C are the
same.
The following figure shows the NR4501 BI module on B05 of PCS-9705B and PCS-9705C.
Date: 2011-08-05
5 Hardware
The following table shows the pin description of the NR4501 BI module on B05 of PCS-9705B and
PCS-9705C.
Table 5.6-5 Pin description of NR4501 BI module on B05 of PCS-9705B and PCS-9705C
Date: 2011-08-05
5 Hardware
22 Opto-_ 2 Common negative connection of all the binary inputs of this module.
The terminal definition of the NR4501 BI module on B06 of PCS-9705A, PCS-9705B and
PCS-9705C are the same.
The following table shows the pin description of the NR4501 BI module on B06 of PCS-9705.
Date: 2011-08-05
5 Hardware
22 Opto-_ 3 Common negative connection of all the binary inputs of this module.
The terminal definitions of the NR4501 BI module on B07 of PCS-9705A, PCS-9705B and
PCS-9705C are the same.
Date: 2011-08-05
5 Hardware
The following table shows the pin description of the NR4501 BI module on B07 of PCS-9705.
Date: 2011-08-05
5 Hardware
22 Opto-_ 4 Common negative connection of all the binary inputs of this module.
For PCS-9705A, PCS-9705B and PCS-9705C, the terminal definitions of B08 and B09 are the
same.
2) B08 is equipped with NR4501 BI module while B09 is empty with no BI module.
3) B08 is equipped with NR4504 BI module while B09 is empty with no BI module.
4) B08 is equipped with NR4501 BI module while B09 is equipped with NR4504 BI module.
5) B08 is equipped with NR4504 BI module while B09 is equipped with NR4501 BI module.
The following figure shows the slot B08 NR4501 BI module in the above scheme “2)”and the slot
B08 NR4501 BI module, the slot B09 NR4504 BI module scheme “4)”.
Date: 2011-08-05
5 Hardware
Figure 5.6-8 Slot B08 NR4501 BI module and slot B09 NR4504 BI modulein scheme “2)”and scheme “4 )”
Note!
NR4504A and NR4504D share the same pin definition, only their working voltages of all the binary
inputs are different.
For NR4504A, the rated working voltage of all the binary inputs is 110~250Vdc.
For NR4504D, the rated working voltage of all the binary inputs is 24~48Vdc.
Note!
In application, the last letter “A”(of NR4504A) and “D”(of NR4504D) will be printed on the module,
but the last letter is omitted in the figures in this instruction manual.
The following table shows the pin description of slot B08 NR4501 BI module in scheme “2)”and
scheme “4)”.
Date: 2011-08-05
5 Hardware
Table 5.6-8 Pin description of slot B08 NR4501 BI module in scheme “2)”and scheme “4)”
22 Opto-_5 Common negative connection of all the binary inputs of this module.
The following table shows the pin description of slot B09 NR4504 BI module in scheme “4)”.
Table 5.6-9 Pin description of slot B09 NR4504 BI module in scheme “4)”
Date: 2011-08-05
5 Hardware
22 Reserved.
The following figure shows the slot B08 NR4504 BI module in the above scheme “3)”and the slot
B08 NR4504 BI module, the slot B09 NR4501 BI module scheme “5)”.
Date: 2011-08-05
5 Hardware
Figure 5.6-9 Slot B08 NR4504 BI module and slot B09 NR4501 BI module in scheme “3)”and scheme “5)”
The following table shows the pin description of slot B08 NR4504 BI module in scheme “3)”and
scheme “5)”.
Table 5.6-10 Pin description of slot B08 NR4504 BI module in scheme “3)”and scheme “5)”
Common negative connection of the binary inputs BI82 and BI83 (Pin
6 Opto-_6
4 and Pin 5) of this module.
Common negative connection of the binary inputs BI84 and BI85 (Pin
9 Opto-_7
7 and Pin 8) of this module.
Date: 2011-08-05
5 Hardware
Common negative connection of the binary inputs BI86 and BI87 (Pin
12 Opto-_8
10 and Pin 11) of this module.
Common negative connection of the binary inputs BI88 and BI89 (Pin
15 Opto-_9
13 and Pin 14) of this module.
Common negative connection of the binary inputs BI90 and BI91 (Pin
18 Opto-_10
16 and Pin 17) of this module.
Common negative connection of the binary inputs BI92 and BI93 (Pin
21 Opto-_11
19 and Pin 20) of this module.
22 Reserved.
The following table shows the pin description of slot B09 NR4501 BI module in scheme “5)”.
Table 5.6-11 Pin description of slot B09 NR4501 BI module in scheme “5)”
Date: 2011-08-05
5 Hardware
22 Opto-_12 Common negative connection of all the binary inputs of this module.
For scheme “6)”(Both B08 and B09 are equipped with NR4501 BI module) , the BI modules are
shown in the following figure.
Figure 5.6-10 NR4501 BI module on slot B08 and slot B09 in scheme “6”
The following table shows the pin description of slot B08 NR4501 BI module in scheme “6)”.
Table 5.6-12 Pin description of slot B08 NR4501 BI module in scheme “6)”
Date: 2011-08-05
5 Hardware
22 Opto-_5 Common negative connection of all the binary inputs of this module.
The following table shows the pin description of slot B09 NR4501 BI module in scheme “6)”.
Table 5.6-13 Pin description of slot B09 NR4501 BI module in scheme “6)”
Date: 2011-08-05
5 Hardware
22 Opto-_6 Common negative connection of all the binary inputs of this module.
For scheme “7)”(Both B08 and B09 are equipped with NR4504 BI module) , the BI modules are
shown in the following figure.
The following table shows the pin description of slot B08 NR4504 BI module in scheme “7)”.
Table 5.6-14 Pin description of slot B08 NR4504 BI module in scheme “7)”
Date: 2011-08-05
5 Hardware
Common negative connection of the binary inputs BI82 and BI83 (Pin
6 Opto-_6
4 and Pin 5) of this module.
Common negative connection of the binary inputs BI84 and BI85 (Pin
9 Opto-_7
7 and Pin 8) of this module.
Common negative connection of the binary inputs BI86 and BI87 (Pin
12 Opto-_8
10 and Pin 11) of this module.
Common negative connection of the binary inputs BI88 and BI89 (Pin
15 Opto-_9
13 and Pin 14) of this module.
Common negative connection of the binary inputs BI90 and BI91 (Pin
18 Opto-_10
16 and Pin 17) of this module.
Common negative connection of the binary inputs BI92 and BI93 (Pin
21 Opto-_11
19 and Pin 20) of this module.
22 Reserved.
The following table shows the pin description of slot B09 NR4504 BI module in scheme “7)”.
Table 5.6-15 Pin description of slot B09 NR4504 BI module in scheme “7)”
Common negative connection of the binary inputs BI95 and BI96 (Pin
6 Opto-_13
4 and Pin 5) of this module.
Date: 2011-08-05
5 Hardware
Common negative connection of the binary inputs BI97 and BI98 (Pin
9 Opto-_14
7 and Pin 8) of this module.
22 Reserved.
Note! The medium of the Ethernet interface of the CPU module and GOOSE module is
optional. Different subtypes of the CPU module and GOOSE module correspond to
different Ethernet interface medium.
The GOOSE module is used to transmit or receive the binary inputs via GOOSE network. It can
also trip or close the corresponding CB according to the control commands from manual operation
on PCS-9705 or from SCADA/RTU.
Note! The GOOSE function of slot B09 GOOSE module and slot B03 NET-DSP module
are the same, they can be appiled at the same time, and they can be adopted
independently. But the NET-DSP module supports the IEC61850-9-2 digital sampling
Date: 2011-08-05
5 Hardware
Generally speaking, the GOOSE module in PCS-9705 adopts the board named as NR4126.
2 types of GOOSE modules(i.e.: NR4126A, NR4126C) are optional as shown in the following 2
figures.
Each type of BCU may be equipped with any one of these 2 GOOSE modules.
As shown in the following figure, the 1st type of GOOSE module (NR4126A) has 2 SC type optical
Ethernet ports for receiving or transmitting the GOOSE command.
As shown in the following figure, the 2nd type of GOOSE module (NR4126C) has 2 ST type optical
Ethernet ports for receiving or transmitting the GOOSE command.
Date: 2011-08-05
5 Hardware
In PCS-9705B, B10 can be equipped with the AO module if B10 is not equipped with AI(DC)
module.
Generally speaking, the AO module in PCS-9705 adopts the board named as NR4411A.
AO module can send out up to 4 channels of 0~10V and 4~20mA output to DCS system to
regulate the active power output of the specified generator.
The DC analog output type can be configured by the settings [Opt_Type_ReguX] (X=1,2,3,4).
Please refer to the Chapter “Settings”for more details.
Date: 2011-08-05
5 Hardware
5 Reserved.
6 Reserved.
11 Reserved.
Date: 2011-08-05
5 Hardware
12 Reserved.
17 Reserved.
18 Reserved.
In PCS-9705B, B10 can not be equipped with the AI(DC) module if B10 is already equipped with
AO module.
Generally speaking, the AI(DC) module in PCS-9705 adopts the board named as NR4410.
AI(DC) module is a transducer input module used to interface transducer signals from transducers
(e.g.: temperature or humidity transducers).
AI(DC) module offers 8 channels of DC analog inputs and no binary input signal.
3 types of DC signals:0~250V, 0~10V and 4~20mA can be acquired, which can be selected by
setting 3 groups of jumpers on the AI(DC) module.
Note! Analog inputs between 0~4mA DC can also be processed, and all the analog inputs
between 0~4mA DC will be processed as 4mA, so we can also say that 0~20mA analog
DC input can be processed.
4~20mA DC
ON OFF ON
(or: 0~20mA DC)
Date: 2011-08-05
5 Hardware
inputs.
B11
NR4410
AI1+ 1
AI1- 2
GND 3
AI2+ 4
AI2- 5
GND 6
AI3+ 7
AI3- 8
GND 9
AI4+ 10
AI4- 11
GND 12
AI5+ 13
AI5- 14
GND 15
AI6+ 16
AI6- 17
GND 18
AI7+ 19
AI7- 20
AI8+ 21
AI8- 22
Pin connections on the connector of the AI(DC) module on B11 are introduced in the following
table.
Date: 2011-08-05
5 Hardware
B10
NR4410
AI9+ 1
AI9- 2
GND 3
AI10+ 4
AI10- 5
GND 6
AI11+ 7
AI11- 8
GND 9
AI12+ 10
AI12- 11
GND 12
AI13+ 13
AI13- 14
GND 15
AI14+ 16
AI14- 17
GND 18
AI15+ 19
AI15- 20
AI16+ 21
AI16- 22
Pin connections on the connector of the AI(DC) module on B10 are introduced in the following
table.
Date: 2011-08-05
5 Hardware
Generally speaking, the BO(IL) module in PCS-9705 adopts the board named as NR4521.
Note! The BO module and the BO(IL) module share the same board: NR4521. If an
BO(IL) module is an interlocking module which provides a normal open contact for every
remotely-controlled object when the setting [En_Hardware_Blk] is set as “1”.
When executing a switching command output, if the interlocking logic conditions are met, besides
internal software interlocking corresponds remote trip or remote closing contact, this device also
provides an additional normal open contact for the remotely-controlled object.
Date: 2011-08-05
5 Hardware
If a contact is closed, it means that the interlocking criterion of corresponding binary output is met.
If a contact is open, it means that the interlocking criterion of corresponding binary output is not
met.
Note! Each BO(IL) module can only provide up to 11 open contact corresponds to each
binary output, since there are 13 binary outputs in this device, so the last 2 binary outputs
does not have corresponding contacts in the BO(IL) module.
2 BO(IL) modules are recommended to be configured in this device at the same time: one in slot
B12 and the other in slot B13.
Please refer to the following 2 figures and 2 tables for more details.
Pin connections of the BO(IL) module on B13 are shown in the following table.
Date: 2011-08-05
5 Hardware
1 BO_BlkTrp1+
No.1 interlocking criteria status output contact for tripping.
2 BO_BlkTrp1-
3 BO_BlkTrp2+
No.2 interlocking criteria status output contact for tripping.
4 BO_BlkTrp2-
5 BO_BlkTrp3+
No.3 interlocking criteria status output contact for tripping.
6 BO_BlkTrp3-
7 BO_BlkTrp4+
No.4 interlocking criteria status output contact for tripping.
8 BO_BlkTrp4-
9 BO_BlkTrp5+
No.5 interlocking criteria status output contact for tripping.
10 BO_BlkTrp5-
11 BO_BlkTrp6+
No.6 interlocking criteria status output contact for tripping.
12 BO_BlkTrp6-
13 BO_BlkTrp7+
No.7 interlocking criteria status output contact for tripping.
14 BO_BlkTrp7-
15 BO_BlkTrp8+
No.8 interlocking criteria status output contact for tripping.
16 BO_BlkTrp8-
17 BO_BlkTrp9+
No.9 interlocking criteria status output contact for tripping.
18 BO_BlkTrp9-
20 BO_BlkTrp10- tripping.
22 BO_BlkTrp11- tripping.
Date: 2011-08-05
5 Hardware
Pin connections of the BO(IL) module on B12 are shown in the following table.
1 BO_BlkCls1+
No.1 interlocking criteria status output contact for closing
2 BO_BlkCls1-
3 BO_BlkCls2+
No.2 interlocking criteria status output contact for closing
4 BO_BlkCls2-
5 BO_BlkCls3+
No.3 interlocking criteria status output contact for closing
6 BO_BlkCls3-
7 BO_BlkCls4+
No.4 interlocking criteria status output contact for closing
8 BO_BlkCls4-
9 BO_BlkCls5+
No.5 interlocking criteria status output contact for closing
10 BO_BlkCls5-
Date: 2011-08-05
5 Hardware
11 BO_BlkCls6+
No.6 interlocking criteria status output contact for closing
12 BO_BlkCls6-
13 BO_BlkCls7+
No.7 interlocking criteria status output contact for closing
14 BO_BlkCls7-
15 BO_BlkCls8+
No.8 interlocking criteria status output contact for closing
16 BO_BlkCls8-
17 BO_BlkCls9+
No.9 interlocking criteria status output contact for closing
18 BO_BlkCls9-
19 BO_BlkCls10+
No.10 interlocking criteria status output contact for closing
20 BO_BlkCls10-
21 BO_BlkCls11+
No.11 interlocking criteria status output contact for closing
22 BO_BlkCls11-
Generally speaking, the BO module in PCS-9705 adopts the board named as NR4521.
The BO module is a well-done binary output module used for tripping or closing output or for any
signaling purpose.
A normal open contact is presented via terminal 21-22 (i.e.:BO_CtrlX, X=1,2,3,4,5,6) designated
as ROS (remote operation signal). Whenever any of the normal open contacts of the binary output
relay is closed, the normal open contact ROS of ROS relay will close to issue a signal indicating
that this device is undergoing a remote operation. If none of the normal open contact of the binary
output relay is closed, the normal open contact ROS keeps open state.
One more group of all the 13 pairs of binary outputs can be provided by the BO module configured
in B14~B16. The allocations of the binary outputs on the BO module configured in B14~B16 are
the same as the binary outputs on the BO module configured in B17~B19.
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B19 are shown in the following table.
1 BO_CtrlTrp1+
Tripping output 1
2 BO_CtrlTrp1-
3 BO_CtrlCls1+
Closing output 1
4 BO_CtrlCls1-
5 BO_CtrlTrp2+
Tripping output 2
6 BO_CtrlTrp2-
7 BO_CtrlCls2+
Closing output 2
8 BO_CtrlCls2-
9 BO_CtrlTrp3+
Tripping output 3
10 BO_CtrlTrp3-
Date: 2011-08-05
5 Hardware
11 BO_CtrlCls3+
Closing output 3
12 BO_CtrlCls3-
13 BO_CtrlTrp4+
Tripping output 4
14 BO_CtrlTrp4-
15 BO_CtrlCls4+
Closing output 4
16 BO_CtrlCls4-
17 BO_CtrlTrp5+
Tripping output 5
18 BO_CtrlTrp5-
19 BO_CtrlCls5+
Closing output 5
20 BO_CtrlCls5-
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B18 are shown in the following table.
1 BO_CtrlTrp6+
Tripping output 6
2 BO_CtrlTrp6-
3 BO_CtrlCls6+
Closing output 6
4 BO_CtrlCls6-
5 BO_CtrlTrp7+
Tripping output 7
6 BO_CtrlTrp7-
7 BO_CtrlCls7+
Closing output 7
8 BO_CtrlCls7-
9 BO_CtrlTrp8+
Tripping output 8
10 BO_CtrlTrp8-
Date: 2011-08-05
5 Hardware
11 BO_CtrlCls8+
Closing output 8
12 BO_CtrlCls8-
13 BO_CtrlTrp9+
Tripping output 9
14 BO_CtrlTrp9-
15 BO_CtrlCls9+
Closing output 9
16 BO_CtrlCls9-
17 BO_CtrlTrp10+
Tripping output 10
18 BO_CtrlTrp10-
19 BO_CtrlCls10+
Closing output 10
20 BO_CtrlCls10-
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B17 are shown in the following table.
1 BO_CtrlTrp11+
Tripping output 11
2 BO_CtrlTrp11-
3 BO_CtrlCls11+
Closing output 11
4 BO_CtrlCls11-
5 BO_CtrlTrp12+
Tripping output 12
6 BO_CtrlTrp12-
7 BO_CtrlCls12+
Closing output 12
8 BO_CtrlCls12-
9 BO_CtrlTrp13+
Tripping output 13
10 BO_CtrlTrp13-
11 BO_CtrlCls13+
Closing output 13
12 BO_CtrlCls13-
13
Reserved.
14
15
Reserved.
16
17
Reserved.
18
19
Reserved.
20
Remote operation signal output of this module. Whenever
21 BO_Ctrl3+
any of the binary output relay is closed, this contact will close
to issue an annunciation signal indicating that this device is
22 BO_Ctrl3-
undergoing a remote operation.
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B16 are shown in the following table.
1 BO_CtrlTrp1 +
Tripping output 1
2 BO_CtrlTrp1-
3 BO_CtrlCls1 +
Closing output 1
4 BO_CtrlCls1-
5 BO_CtrlTrp2 +
Tripping output 2
6 BO_CtrlTrp2-
7 BO_CtrlCls2 +
Closing output 2
8 BO_CtrlCls2-
9 BO_CtrlTrp3 +
Tripping output 3
10 BO_CtrlTrp3-
Date: 2011-08-05
5 Hardware
11 BO_CtrlCls3 +
Closing output 3
12 BO_CtrlCls3-
13 BO_CtrlTrp4 +
Tripping output 4
14 BO_CtrlTrp4-
15 BO_CtrlCls4 +
Closing output 4
16 BO_CtrlCls4-
17 BO_CtrlTrp5 +
Tripping output 5
18 BO_CtrlTrp5-
19 BO_CtrlCls5 +
Closing output 5
20 BO_CtrlCls5-
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B15 are shown in the following table.
1 BO_CtrlTrp6+
Tripping output 6
2 BO_CtrlTrp6-
3 BO_CtrlCls6+
Closing output 6
4 BO_CtrlCls6-
5 BO_CtrlTrp7+
Tripping output 7
6 BO_CtrlTrp7-
7 BO_CtrlCls7+
Closing output 7
8 BO_CtrlCls7-
9 BO_CtrlTrp8+
Tripping output 8
10 BO_CtrlTrp8-
11 BO_CtrlCls8+
Closing output 8
12 BO_CtrlCls8-
13 BO_CtrlTrp9+
Tripping output 9
14 BO_CtrlTrp9-
15 BO_CtrlCls9+
Closing output 9
16 BO_CtrlCls9-
17 BO_CtrlTrp10+
Tripping output 10
18 BO_CtrlTrp10-
19 BO_CtrlCls10+
Closing output 10
20 BO_CtrlCls10-
Date: 2011-08-05
5 Hardware
Pin connections of the BO module on B14 are shown in the following table.
1 BO_CtrlTrp11+
Tripping output 11
2 BO_CtrlTrp11-
3 BO_CtrlCls11+
Tripping output 11
4 BO_CtrlCls11-
5 BO_CtrlTrp12 +
Tripping output 12
6 BO_CtrlTrp12-
7 BO_CtrlCls12 +
Tripping output 12
8 BO_CtrlCls12-
9 BO_CtrlTrp13 +
Tripping output 13
10 BO_CtrlTrp13-
11 BO_CtrlCls13 +
Tripping output 13
12 BO_CtrlCls13-
Date: 2011-08-05
5 Hardware
13
Reserved.
14
15
Reserved.
16
17
Reserved.
18
19
Reserved.
20
Remote operation signal output of this module. Whenever
21 BO_Ctrl6+
any of the binary output relay is closed, this contact will close
to issue an annunciation signal indicating that this device is
22 BO_Ctrl6-
undergoing a remote operation.
Generally speaking, the PWR module in PCS-9705 adopts the board named as NR4301.
The PWR module is the power supply module used to provide the correct internal voltages and full
isolation between terminal and the battery system. An in -line fuse is wired in the PWR module for
short circuit protection.
Note! The width of AI(AC) module and PWR module is double of other modules. An AI(AC)
module or a PWR module occupies 2 slots while any other module only occupies 1 slot.
Date: 2011-08-05
5 Hardware
NR4301
BO_ COM 1
BO_ FAIL 2
BO_ ALM 3
BO_ Resv1+ 4
BO_ Resv1- 5
BO_ Resv2+ 6
BO_ Resv2- 7
BO_ Resv3+ 8
BO_ Resv3- 9
BO_ Resv4+ 10
BO_ Resv4- 11
BO_ Resv5+ 12
BO_ Resv5- 13
BO_ Resv6+ 14
BO_ Resv6- 15
BO_ Resv7+ 16
BO_ Resv7- 17
BO_ Resv8+ 18
BO_ Resv8- 19
PWR+ 20
PWR- 21
GND 22
A 22-pin connector is fixed on the front of the PWR module. The terminal definition of the
connector is described as below.
Pin connections on the PWR module are shown in the following table.
4 BO_Resv1+
Reserved as user-defined binary output 1
5 BO_Resv1-
6 BO_Resv2+
Reserved as user-defined binary output 2
7 BO_Resv2-
8 BO_Resv3+
Reserved as user-defined binary output 3
9 BO_Resv3-
10 BO_Resv4+
Reserved as user-defined binary output 4
11 BO_Resv4-
Date: 2011-08-05
5 Hardware
12 BO_Resv5+
Reserved as user-defined binary output 5
13 BO_Resv5-
14 BO_Resv6+
Reserved as user-defined binary output 6
15 BO_Resv6-
16 BO_Resv7+
Reserved as user-defined binary output 7
17 BO_Resv7-
18 BO_Resv8+
Reserved as user-defined binary output 8
19 BO_Resv8-
Note! It is only permitted to withdraw or insert the PWR module or some other modules
Note! The following figures show the rear panel definition of this device with the modules
as many as possible. But in engineering applications, this device may be equipped with
fewer modules.
Note! The CPU module may adopt NR4102C, NR4102D, NR4102J, NR4102K. The
GOOSE module may adopt NR4126A, NR4126C. For the sake of convenience, the
following figures will not show every subtype of the CPU module and the GOOSE
module.
Note! The following modules must be equipped in every subtype of this device.
The following figure shows the rear panel definition of PCS-9705A without GOOSE module and
adopts conventional sampling method .
Date: 2011-08-05
5 Hardware
Figure 5.13-1 An example of rear panel of PCS-9705A (CPU module adopts NR4102D; with 4 NR4501 BI
modules, 2 NR4504 BI modules, 2 AI(DC) modules, 2 BO(IL) modules, 6 BO modules , with no AO module)
The following figure shows the rear panel definition of PCS-9705A with GOOSE module and
adopts conventional sampling method.
Date: 2011-08-05
5 Hardware
Figure 5.13-2 An example of rear panel of PCS-9705A (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 4 NR4501 BI modules, 1 NR4504 BI module, 1 AI(DC) module, 2 BO(IL) modules, 3
BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705A with GOOSE module and
adopts digital sampling method via slot B02 AI(ECVT) module(e.g.:NR4201B).
Date: 2011-08-05
5 Hardware
Figure 5.13-3 An example of rear panel of PCS-9705A (CPU module adopts NR4102J; GOOSE module
adopts NR4126A; with 4 NR4501 BI modules, 1 NR4504 BI module, 1 AI(DC) module, 2 BO(IL) modules, 3
BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705A with GOOSE module and
adopts digital sampling method via slot B03 NET-DSP module(e.g.:NR4136A).
Date: 2011-08-05
5 Hardware
Figure 5.13-4 An example of rear panel of PCS-9705A (CPU module adopts NR4102J; GOOSE module
adopts NR4126A; with 5 NR4501 BI modules, 1 AO module,1 AI(DC) module, 2 BO(IL) modules, 3 BO
modules)
The following figure shows the rear panel definition of PCS-9705B without GOOSE module and
adopts conventional sampling method .
Date: 2011-08-05
5 Hardware
Figure 5.13-5 An example of rear panel of PCS-9705B (CPU module adopts NR4102C; with 4 NR4501 BI
modules, 2 NR4504 BI modules, 1 AI(DC) module, 2 BO(IL) modules, 6 BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705B with GOOSE module and
adopts conventional sampling method .
Date: 2011-08-05
5 Hardware
Figure 5.13-6 An example of rear panel of PCS-9705B (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 4 NR4501 BI modules, 1 NR4504 BI module, 1 AI(DC) module, 2 BO(IL) modules, 3
BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705B with GOOSE module and
adopts digital sampling method via slot B02 AI(ECVT) module(e.g.:NR4201B).
Date: 2011-08-05
5 Hardware
Figure 5.13-7 An example of rear panel of PCS-9705B (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 4 NR4501 BI modules, 1 NR4504 BI module , 1 AO module, 1 AI(DC) module, 2 BO(IL)
modules, 3 BO modules)
The following figure shows the rear panel definition of PCS-9705B with GOOSE module and
adopts digital sampling method via slot B03 NET-DSP module(e.g.:NR4136A).
Date: 2011-08-05
5 Hardware
Figure 5.13-8 An example of rear panel of PCS-9705B (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 5 NR4501 BI modules, 1 AO module, 1 AI(DC) module, 2 BO(IL) modules, 3 BO
modules)
The following figure shows the rear panel definition of PCS-9705C without GOOSE module and
adopts conventional sampling method .
Date: 2011-08-05
5 Hardware
Figure 5.13-9 An example of rear panel of PCS-9705C (CPU module adopts NR4102K; with 4 NR4501 BI
modules, 2 NR4504 BI modules, 1 AI(DC) module, 2 BO(IL) modules, 3 BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705C with GOOSE module and
adopts conventional sampling method .
Date: 2011-08-05
5 Hardware
Figure 5.13-10 An example of rear panel of PCS-9705C (CPU module adopts NR4102J; GOOSE module
adopts NR4126A; with 4 NR4501 BI modules, 1 NR4504 BI module, 1 AI(DC) module, 2 BO(IL) modules, 3
BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705C with GOOSE module and
adopts digital sampling method via slot B02 AI(ECVT) module(e.g.:NR4201B).
Date: 2011-08-05
5 Hardware
Figure 5.13-11 An example of rear panel of PCS-9705C (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 4 NR4501 BI modules, 1 NR4504 BI module, 1 AI(DC) module, 2 BO(IL) modules, 3
BO modules, with no AO module)
The following figure shows the rear panel definition of PCS-9705C with GOOSE module and
adopts digital sampling method via slot B03 NET-DSP module(e.g.:NR4136A).
Date: 2011-08-05
5 Hardware
Figure 5.13-12 An example of rear panel of PCS-9705C (CPU module adopts NR4102K; GOOSE module
adopts NR4126C; with 5 NR4501 BI modules, 1 AO module, 1 AI(DC) module, 2 BO(IL) modules, 3 BO
modules)
Date: 2011-08-05
6 Settings
6 Settings
6.1 Overview
The settings of this device locate in the “Settings”menu.
The settings are used to determine the characteristic of operation mode of this device. It is
necessary to configure the settings of this device according to engineering demands before
putting this device into service. If the settings are not configured correctly, this device may work
abnormally (such as when communication is interrupted etc.).
Note! If a CPU module is replaced, it is necessary to configure all the settings again
The following table shows the parameter description of the “Device_Settings”of PCS-9705A/B/C.
The setting is used to set the voltage level of binary input module.
“0”:24V,
“1”:48V,
“2”:110V,
1 Un_BinaryInput
“3”:220V.
If low-voltage BI module is equipped, 24V or 48V can be set according
to the actual requirement, and if high-voltage BI module is equipped,
110V or 220V can be set according to the actual requirement.
Date: 2011-08-05
6 Settings
(1) (point(s)
25 SampleRate_B03 4000 [1200:4800]
per second)
Date: 2011-08-05
6 Settings
The following table shows the parameters description of the “Comm_Settings”of PCS-9705A.
“0”: Chinese,
1 Language
“1”: English.
Date: 2011-08-05
6 Settings
[Opt_TimeSyn] Function
15 Opt_TimeSyn
Adopt pulse per second (PPS) clock
“0”:
synchronization via RS-485 differential
PPS(RS-485)
level via slot B01 CPU module.
Date: 2011-08-05
6 Settings
(The 3rd
Point-to-point section)x256+(the 4th The 4th section
SNTP mode section (In this example:
is selected (In this example: 102)
100×256+102=25702)
Broadcast
SNTP mode 255×256+255=65535 255
is selected
Date: 2011-08-05
6 Settings
Note! This setting will be hidden when slot B09 is empty. Only
The setting only represents the time period when the device sends
measurement data to SCADA.
When the setting is set as “0s”, it means that the device will not send
20 Cycle_Measmt measurement data periodically forwardly, but the time inquiry issued by
SCADA still being responded by the device. This setting may be set
according to actual field condition and can be set as “0s” when the
communication function is not used.
Date: 2011-08-05
6 Settings
“0”: Disable the NET B link of the slot NET-DSP module, and then the slot
NET-DSP module module can only work in single SV network mode.
Note! This setting will only be effective when slot B03 NET-DSP
Note! This setting will only be effective when slot B03 NET-DSP
module(NR4136A) is equipped.
[Opt_TimeSyn_B03] Function
Date: 2011-08-05
6 Settings
This setting is applied to configure the digital sampling rate of slot B03
NET-DSP module.
25 SampleRate_B03 Note! This setting will only be effective when slot B03 NET-DSP
Date: 2011-08-05
6 Settings
useless.
Only when this device is used in digital substation and adopts fiber-optical
sampling via AI(ECVT) module or NET-DSP module(i.e.: the setting
[Opt_Mode_CT/VT] is set as “1”or “2”), this setting can be enabled.
Each bit of 0-0x3fffff represents the state of one of the 22 channels in FD3
32 Cfg_SmplCh_ECVT
format. Bit 1 is the least significant bit, and Bit 22 is the most significant
bit.
If a bit is set as “1”, it means the state of this channel will be considered in
calculation, the state of this channel will not be considered in calculation.
In PCS-9705B and PCS-9705C, there are 36 settings in “Comm_Settings”, the first 31 settings
Date: 2011-08-05
6 Settings
The following table shows the parameters description of the “Comm_Settings”of PCS-9705B and
PCS-9705C.
9 Uc of Group 3
10 Ua of Group 4
11 Ub of Group 4
12 Uc of Group 4
Date: 2011-08-05
6 Settings
The following table shows the parameters description of the “Function_Links”of PCS-9705A.
Date: 2011-08-05
6 Settings
criterion.)
If [ Link_DeadChk] is “0”and [Link_SynChk] is “1”,
Synchronism-check mode will be selected.
(Synchronism -check mode: The mode only to check the
2 Link_DeadChk
synchronism-check criterion.)
If [ Link_DeadChk] is “1”and [Link_SynChk] is “1”,
Dead check will be executed fisrly, if dead check criterion is not met,
then synchronism-check will be executed.
The following table shows the parameters description of the “Function_Links”of PCS-9705B.
Date: 2011-08-05
6 Settings
The following table shows the parameters description of the “Function_Links”of PCS-9705C.
Date: 2011-08-05
6 Settings
… …
different.
Date: 2011-08-05
6 Settings
“0”:50Hz
“1”:60Hz.
The following table shows the parameters description of the “System_Settings”of PCS-9705A.
these refer to
3 U2n_VT_Measmt Rated secondary reference voltage.
phase-to-phase
voltages.
Determined by
[Opt_U_SynChk] in the
submenu
4 U1n_VT_Syn Rated primary incoming voltage.
“Syn_Settings”of the
menu “Settings”.
If [Opt_U_SynChk] is
Date: 2011-08-05
6 Settings
Date: 2011-08-05
6 Settings
2 Options to be selected:
1 Opt_SysFreq 50Hz “0”:50Hz
“1”:60Hz.
The following table shows the parameters description of the “System_Settings”of PCS-9705B.
This device can work under different system frequencies. This setting
is used to set the rated frequency that this device works under.
1 Opt_SysFreq 2 Options to be selected:
“0”:50Hz;
“1”:60Hz.
Date: 2011-08-05
6 Settings
Corresponding
The 2nd group rated to the input of
4 U1n_VT2
primary busbar voltage. the 2nd group
voltage input via
pin 7~pin12
The 2nd group rated (“U4”~ “U6n”on
5 U2n_VT2 secondary phase AI(AC) module
voltage. of PCS-9705B).
Corresponding
The 3rd group rated to the input of
6 U1n_VT3
primary busbar voltage. the 3rd group
voltage input via
pin 13~pin18
The 3rd group rated (“U7”~ “U9n”on
7 U2n_VT3 secondary busbar AI(AC) module
voltage. of PCS-9705B).
Corresponding
Date: 2011-08-05
6 Settings
Date: 2011-08-05
6 Settings
2 Options to be selected:
1 Opt_SysFreq 50Hz “0”:50Hz
“1”:60Hz.
Date: 2011-08-05
6 Settings
The following table shows the parameters description of the “System_Settings”of PCS-9705C.
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
Date: 2011-08-05
6 Settings
Determined by
[Opt_U_SynChk] in the
Rated primary incoming voltage of
4 Line1_U1n_VT_Syn submenu
the 1st CB.
“Settings”->“Syn_Settings”.
If [Opt_U_SynChk] is set as
“0”, “1 ”and “2”, these 2
parameters will adopt phase
voltages.
If [Opt_U_SynChk] is set as
Rated secondary incoming voltage
5 Line1_U2n_VT_Syn “3”, “4 ”and “5”, these 2
of the 1st CB.
parameters will adopt
phase-to-phase voltages.
6 Line1_I1n_CT_Measmt Rated primary current of the 1st CB. Note! All of these
Determined by
[Opt_U_SynChk] in the
Rated primary incoming voltage of submenu
10 Line2_U1n_VT_Syn
the 2nd CB. “Settings”->“Syn_Settings”.
If [Opt_U_SynChk] is set as
“0”, “1 ”and “2”, these 2
parameters will adopt phase
voltages.
Rated secondary incoming voltage If [Opt_U_SynChk] is set as
11 Line2_U2n_VT_Syn
of the 2nd CB. “3”, “4 ”and “5”, these 2
parameters will adopt
phase-to-phase voltages.
12 Line2_I1n_CT_Measmt Rated primary current of the 2nd CB. Note! All of these
Date: 2011-08-05
6 Settings
Date: 2011-08-05
6 Settings
Date: 2011-08-05
6 Settings
“Analog”->“Measurements”->“Synchrocheck”in PCS-9705A.
Date: 2011-08-05
6 Settings
If the dead check criteria are met during the time [t_Reset_SynChk], the
CB will be closed.
Date: 2011-08-05
6 Settings
Date: 2011-08-05
6 Settings
0 Ua
1 Ub
2 Uc
12 Opt_U_SynChk 3 Uab
4 Ubc
5 Uca
Date: 2011-08-05
6 Settings
voltage automatically.
Date: 2011-08-05
6 Settings
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
1 Line1_U_UV_SynChk
2 Line1_U_Diff_SynChk
3 Line1_f_Diff_SynChk
4 Line1_df/dt_SynChk
5 Line1_phi_Diff_SynChk
The settings [Line1_XX] have the same functions as
6 Line1_t_Reset_SynChk corresponding settings [XX] in Table 6.9-2.
7 Line1_Opt_Mode_DeadChk [XX] of PCS-9705A are applied for the CB
8 Line1_En_VTS_Blk_DeadChk synchronism-check.
[Line1_XX] of PCS-9705C are applied for the 1st CB
9 Line1_En_VTS_Blk_SynChk
synchronism-check in 1½ CB arrangement.
10 Line1_t_Close_CB
11 Line1_phi_Comp_Diff
12 Line1_Opt_U_SynChk
13 Line1_U_DeadChk
14 Line1_U_LiveChk
Date: 2011-08-05
6 Settings
1 Line2_U_UV_SynChk
2 Line2_U_Diff_SynChk
3 Line2_f_Diff_SynChk
4 Line2_df/dt_SynChk
5 Line2_phi_Diff_SynChk
The settings [Line2_XX] have the same functions as
6 Line2_t_Reset_SynChk corresponding settings [XX] in Table 6.9-2.
7 Line2_Opt_Mode_DeadChk [XX] of PCS-9705A are applied for the CB
8 Line2_En_VTS_Blk_DeadChk synchronism-check.
[Line2_XX] of PCS-9705C are applied for the 2nd CB
9 Line2_En_VTS_Blk_SynChk
synchronism-check in 1½ CB arrangement.
10 Line2_t_Close_CB
11 Line2_phi_Comp_Diff
12 Line2_Opt_U_SynChk
13 Line2_U_DeadChk
14 Line2_U_LiveChk
… … … … …
Note! 120 Binary inputs and GOOSE module can not be chosen at the same time. When
GOOSE module is chosen, PCS-9705 can only support up to 100 binary inputs.
Note! “DPU”is the abbreviation of “the debouncing time of Delay Pick Up”.
Binary input state is processed by well-designed anti-jitter technique. Every binary input is
corresponding to a parameter named as [t_DPU_BIXX] (XX=1,… ,120), i.e. the signal state
change confirmation time. The default value is 20ms. It can be set up to be longer to ensure a fine
binary signal input according to the specific application.
Date: 2011-08-05
6 Settings
The 1st terminal of each BI module is the Power supervision (PwrSuperv) terminal.
If the PwrSuperv_X(X=1,2,3,4,5,6) terminal of the BI module on slot BXX (BXX=B04, B05, B06,
B07, B08, B09) is not connected to positive pole of binary input auxiliary power,
[Alm_Pwr_BI_BXX] (BXX=B04, B05, B06, B07, B08, B09) will be issued and it can be sent to
SCADA.
[t_VBI]: The signal state change confirmation time for all the virtual double point binary inputs.
PCS-9705 supports up to 16 virtual double point binary inputs (i.e.: [Sig_DP01]… [Sig_DP16]
displayed in the submenu “Test”->“Internal_Signal”).
If a double point binary input changes to 0x00 or 0x11(i.e.: double point information error occurs),
the anti-jitter technique will be applied. [t_VBI] will be regarded as the debouncing time for all the
virtual double point binary inputs of PCS-9705.
If a double point binary inputs changed to 0x01 or 0x10(i.e.: no double point information error), the
anti-jitter technique will not be applied.
… … … … …
But if this device is not equipped with the maximum number of BO boards, only the
[t_Hold_TrpXX], [t_Hold_ClsXX] which correspond to existing tripping/closing outputs are
meaningful.
Date: 2011-08-05
6 Settings
[Num_TapPos], i.e. Numbers of tap position in the above table is set as the maximum
number of transformer tap position. If the [Num_TapPos] is less than 23, binary input
(6+[Num_TapPos]) to 28 is used as conventional binary input purpose.
For example, [Num_TapPos] is 23, the transformer tap-position is 10, and then binary input
28 to 6 indicate as “00000000000001000000000”.
For another example, if [Num_TapPos] is 20 and currently, the transformer tap-position is 10,
then binary input (6+20) to 28, i.e. binary input 26 to 28 is used as conventional binary input
purpose, and binary 25 to 6 indicate as “00000000001000000000”.
Binary inputs 1 to 5 are for other applications, only binary inputs 6 to 28 are for the tap position
indication.
1) When [Code_TapPos] is set as 0, binary inputs 6 to 28 are not used for tap position
indication (abbreviated TPI).
Binary input 6 is the least significant bit and binary input 11 is the most significant bit. The first
4 bits are in binary numbers while the 5th bit and the 6th bit represent ten and twenty
respectively.
E.g.1: If the transform tap position is 5, then binary inputs 6 to 11 (the bits start from right
Date: 2011-08-05
6 Settings
E.g.2: If the transform tap position is 15, then binary inputs 6 to 11 (the bits start from right
side) are indicating as “01 0101”.
E.g.3: If the transform tap position is 25, then binary inputs 6 to 11 (the bits start from right
side) are indicating as “10 0101”.
3) When [Code_TapPos] is set as 2, the transformer tap-positions are connected to binary inputs
6 to 18 in sequence.
Binary input 6 is the least significant bit and binary input 18 is the most significant bit. The 13
bits are separated into 2 segments, the first segment of binary inputs 6 to 15 denote unit
positions, i.e.0~9; the second segment of binary inputs 16 to 18 denote the tap positions
lower than 10, between 11 and 19 and over 20 respectively.
E.g.1: If the transformer tap-position is 5, then binary inputs 6 to 18 (the bits start from right
side) indicate as “0010000100000”.
E.g.2: If the transformer tap-position is 15, then binary inputs 6 to 18 (the bits start from
right side) indicate as “0100000100000”.
E.g.3: If the transformer tap-position is 25, then binary inputs 6 to 18 (the bits start from
right side) indicate as “1000000100000”.
E.g.1: If binary input 6 is set as 1 and binary inputs 7 to 28 are all set as 0, it indicate the tap
position is 1.
E.g.2: If binary input 28 is set as 1 and binary inputs 6 to 27 are all set as 0, it indicate the tap
position is 23.
Application
Name
[Code_TapPos]=0 [Code_TapPos]=1 [Code_TapPos]=2 [Code_TapPos]=3
Date: 2011-08-05
6 Settings
Application
Name
[Code_TapPos]=0 [Code_TapPos]=1 [Code_TapPos]=2 [Code_TapPos]=3
BI 1 BI_Maintenance
BI 2 BI_Block_Dis
BI 3 BI_Rmt/Loc
BI 4 BI_Manual_Synchro
BI 5 BI_Spare1
BI 6 BI_Spare2 1 0
BI 7 Binary input 7 2 1
BI 8 Binary input 8 4 2
BI 9 Binary input 9 8 3
BI 10 Binary input 10 10 4
BI 11 Binary input 11 20 5
BI 29 Binary input 29
… …
Date: 2011-08-05
6 Settings
Application
Name
[Code_TapPos]=0 [Code_TapPos]=1 [Code_TapPos]=2 [Code_TapPos]=3
BI XX Binary input XX
[t_DPU_TapPos]: Debouncing time limit of tap position, it has the same meaning with binary
input jitter-free time limit of status.
[En_Slide_TapPos]:
“0”: The BCU will not block the tap positioning function.
[t_Slide_TapPos]:
The time setting of tripping for dealing with the slide of transformer tap position.
Note! This submenu is only valid in the PCS-9705B which sends DC voltage/current
output to DCS system to regulate the active power output of the specified generator via
AO module.
Parameters in the “Regulation_Settings”menu of PCS-9705B are listed in the following table.
[Opt_Type_ReguX]
X=1,2,3,4
Date: 2011-08-05
6 Settings
This setting is applied to set the DC analog output type for regulation.
0 4~20mA
1 0~10V
… … … … …
Date: 2011-08-05
6 Settings
Mode:
If this setting is set as “0”, “Online Anti-maloperation Mode”is
disabled.
If this setting is set as “1”, “Online Anti-maloperation Mode”is
enabled.
If this setting is set as “2”, PCS-9705 will receive the
Remote/Local status signal(e.g.:[En_CC_Ctrl]) of the remote
terminal unit (RTU, e.g.:RCS-9698G or RCS-9698H)
If the Remote/Local status signal is “1”, it means that the RTU is in
“Remote” status and the control commands from the control
centers are effective, and then in PCS-9705, “Online
Anti-maloperation Mode”will be disabled.
If the Remote/Local status signal is “0”, it means that the RTU is in
“Local” status and the control commands from local
anti-maloperation system are effective, then in PCS-97 05, “Online
Anti-maloperation Mode”will be enabled.
Date: 2011-08-05
6 Settings
“Status”->“Interlock_Status”. (XX=01~13)
… …
“1”: Closing output XX of the BO module is controlled by the
interlocking logic. (XX=01~13) If the interlocking conditions are
met (i.e.: [Sig_En_CtrlClsXX]=1), closing output XX has output,
otherwise (i.e.: [Sig_En_CtrlClsXX]=0) closing output XX has no
output.
28 En_Cls13_Blk
“0”: Closing output XX of the BO module is not controlled by the
interlocking logic. (XX=01~13) Whether the interlocking
conditions are met or not, closing output XX has output.
Note! This submenu is only valid in the PCS-9705 which acquires DC voltage/current
intput from transducers (e.g.: temperature or humidity transducers) via AI(DC) module.
… … … … …
Note! In the above table, XX=01,02,03,,… ,08 if only 1 AI(DC) module is equipped in slot
B11; XX=01,02,03,… ,16 if 2 AI(DC) modules are equipped in slot B11 and B10.
[Opt_Type_TransducerXX]
This setting is applied to set the DC analog transducer type, and.It cooperates with the
jumpers on the AI(DC) module to match the DC analog input.
0 0~10V
1 4~20mA
Date: 2011-08-05
6 Settings
2 0~250V
Note! The function is used to maintain this device and has already been set by the
Note! This submenu is only valid in the PCS-9705 which acquires DC voltage/current
intput from transducers (e.g.: temperature or humidity transducers) via AI(DC) module.
This menu consists of the parameters to adjust the accuracy of DC analog input manually.
Note! The function is used to maintain this device and has already been set by the
Date: 2011-08-05
7 Human Machine Interface
This chapter will describe HMI, menu tree and LCD display of the equipment. In addition, how to
input settings using keypad is described in detail.
7.1 Overview
7.1.1 Design
The human-machine interface consists of an HMI module which allows communication to be as
simple as possible for the user. The HMI module includes:
A 320×240-dot matrix backlight LCD visible in dim lighting conditions for monitoring status,
fault diagnostics and setting, etc.
Two LED indicators on the front panel of this device for denoting the status of this equipment.
A 2-keys multifunctional knob keyboard on the front panel of the device for full access to the
device.
1 11
HEALTHY
2
ALARM
12 PCS-9705
3 13 EN BAY CONTROL UNIT
U
M
4 14
5 15
6 16 ENT
7 17
D JUS
A
8 18
9 19
- +
10 20
ESC
7.1.2 Functionality
The HMI module helps to draw your attention to something that has occurred which may
activate a LED or a report display on the LCD.
Using the menus user can navigate through menu commands and locate the data of interest.
Date: 2011-08-05
7 Human Machine Interface
U
A
T
Figure 7.1-2 Knob keypad on the front panel
The knob keyboard is located in the front of the device panel, which is convenient for users to
obtain data and the fixed value through operation.
The knob keyboard has two multifunctional keys, each of which can be knobbed and confirmed in
two directions.
By pressing the above “(ENT)”key we can confirm the current operation and access the next
menu;
By Pressing the below “(ESC)”key we can cancel the current operation, and return to the former
menu.
By tunring the above “(MENU)”knob we can switch between different pages of current submenu.
The following figure shows the LED indicators on the front panel of the device.
HEALTHY
ALARM
The following table shows the description of LED indicators on the front panel of the device.
Steady Green Lit when the equipment is in service and ready for operation.
Date: 2011-08-05
7 Human Machine Interface
NOTE:
“ALARM”LED is turned on as long as alarm exists. When alarm signals disappear, it will be
turned off.
Under normal condition, this device will display the measured value of this device; meanwhile, it
will display the system time, GPS clock status and the last byte of the IP.
The following figure shows an example of the LCD display of PCS-9705 when there is some alarm
signals.The LCD display may differ according to different alarm signals.
Date: 2011-08-05
7 Human Machine Interface
Under normal condition, press “MENU”or knob the “MENU”button will enter the “MainMenu”of
PCS-9705.
Note! The following figures show the menu trees of PCS-9705 with the submenus as many
Date: 2011-08-05
7 Human Machine Interface
GOOSE_Outputs GOOSE_Interlock
Local_Cmd
Tap_Position IEC 103_Interlock
Interlock _Status
Download Clock
Superv_State Clear_Interlock _File
Language
Clear_Statistics
AR_Sig
Manual_ Control
Records
Disturb_Records
Superv_Events
IO_Events
Device_Logs Information
Control_Logs Version_Info
Clear_Records
Date: 2011-08-05
7 Human Machine Interface
Date: 2011-08-05
7 Human Machine Interface
Interlock_Info
Inputs
Contact_Inputs GOOSE_Interlock
Local_Cmd
GOOSE_Inputs IEC 103_Interlock
Records
Superv_Events
IO_Events
Information
Device_Logs
Control_Logs Version_Info
Clear_Records
7.3.2 Analog
This menu is mainly used to display the real time sampling value of current, voltage and phase
angle. This menu and “Status”menu can fully reflects of the running environment of the device. As
long as the displayed values consist with the actual running situation, basically, the device can
work normally. This menu is set to greatly facilitate the debugging and maintenance of people on
site.
Locate the cursor on “Analog”by turning the knob of the “MENU”and press the “MENU”key to
access the submenu “Measurements”.
Locate the cursor on “Measurements”by turning the knob of the “MENU”and press the “MENU”
key to access the submenus.
The submenus in the “Measurements”menu of PCS-9705A are listed in the following table.
Date: 2011-08-05
7 Human Machine Interface
8 GOOSE_Analog Display the original analog values sampled by the GOOSE module.
The submenus in the “Measurements”menu of PCS-9705B are listed in the following table.
1 Primary_Values1 Display the 1st group primary value of the AC analog inputs.
2 Primary_Values2 Display the 2nd group primary value of the AC analog inputs.
3 Secondary_Values1 Display the 1st group primary value of the AC analog inputs.
4 Secondary_Values2 Display the 2nd group primary value of the AC analog inputs.
6 Harmonics1 Display the 1st group harmonic voltages (Harmonic orders: 1-15).
7 Harmonics2 Display the 2nd group harmonic voltages (Harmonic orders: 1-15).
8 DC_Input_Pri_Val Display the primary values of the DC analog inputs via transducer.
9 DC_Input_Sec_Val Display the secondary values of the DC analog inputs via transducer.
10 GOOSE_Analog Display the original analog values sampled by the GOOSE module.
11 Regulation_Outputs
Note! If this device does not have regulation functions, this
The submenus in the “Measurements”menu of PCS-9705C are listed in the following table.
Date: 2011-08-05
7 Human Machine Interface
6 Harmonics1 Display the 1st group harmonic voltages (Harmonic orders: 1-15).
7 Harmonics2 Display the 2nd group harmonic voltages (Harmonic orders: 1-15).
10 DC_Input_Pri_Val Display the primary values of the DC analog inputs via transducer.
11 DC_Input_Sec_Val Display the secondary values of the DC analog inputs via transducer.
12 GOOSE_Analog Display the original analog values sampled by the GOOSE module.
1 Ia_Pri
3 Ic_Pri
5 Ua_Pri
7 Uc_Pri
Date: 2011-08-05
7 Human Machine Interface
9 Ubc_Pri
10 Uca_Pri
1 Ua_Pri_Grp1
2 Ub_Pri_Grp1 The primary values of the three-phase voltages of the 1st group.
3 Uc_Pri_Grp1
4 Uab_Pri_Grp1
5 Ubc_Pri_Grp1 The primary values of the 3 phase-to-phase voltages of the 1st group.
6 Uca_Pri_Grp1
8 U1_Pri_Grp1 The primary value of the positive-sequence voltage of the 1st group.
9 U2_Pri_Grp1 The primary value of the negative-sequence voltage of the 1st group.
10 Ua_Pri_Grp2
11 Ub_Pri_Grp2 The primary values of the three-phase voltages of the 2nd group.
12 Uc_Pri_Grp2
13 Uab_Pri_Grp2
14 Ubc_Pri_Grp2 The primary values of the 3 phase-to-phase voltages of the 2nd group.
15 Uca_Pri_Grp2
Date: 2011-08-05
7 Human Machine Interface
17 U1_Pri_Grp2 The primary value of the positive-sequence voltage of the 2nd group.
18 U2_Pri_Grp2 The primary value of the negative-sequence voltage of the 2nd group.
1 Ua_Pri_Grp3
2 Ub_Pri_Grp3 The primary values of the three-phase voltages of the 3rd group.
3 Uc_Pri_Grp3
4 Uab_Pri_Grp3
5 Ubc_Pri_Grp3 The primary values of the 3 phase-to-phase voltages of the 3rd group.
6 Uca_Pri_Grp3
8 U1_Pri_Grp3 The primary value of the positive-sequence voltage of the 3rd group.
9 U2_Pri_Grp3 The primary value of the negative-sequence voltage of the 3rd group.
10 Ua_Pri_Grp4
11 Ub_Pri_Grp4 The primary values of the three-phase voltages of the 4th group.
12 Uc_Pri_Grp4
13 Uab_Pri_Grp4
14 Ubc_Pri_Grp4 The primary values of the 3 phase-to-phase voltages of the 4th group.
15 Uca_Pri_Grp4
17 U1_Pri_Grp4 The primary value of the positive-sequence voltage of the 4th group.
18 U2_Pri_Grp4 The primary value of the negative-sequence voltage of the 4th group.
Date: 2011-08-05
7 Human Machine Interface
“Analog”->“Measurements”->“Secondary_Values”in PCS-9705A.
1 Ia_Sec
3 Ic_Sec
5 Ua_Sec
7 Uc_Sec
8 Uab_Sec
10 Uca_Sec
Date: 2011-08-05
7 Human Machine Interface
1 Ua_Sec_Grp1
2 Ub_Sec_Grp1 The secondary values of the three-phase voltages of the 1st group.
3 Uc_Sec_Grp1
4 Uab_Sec_Grp1
The secondary values of the 3 phase-to-phase voltages of the 1st
5 Ubc_Sec_Grp1
group.
6 Uca_Sec_Grp1
8 U1_Sec_Grp1 The secondary value of the positive-sequence voltage of the 1st group.
9 U2_Sec_Grp1 The secondary value of the negative-sequence voltage of the 1st group.
10 Ua_Sec_Grp2
11 Ub_Sec_Grp2 The secondary values of the three-phase voltages of the 2nd group.
12 Uc_Sec_Grp2
13 Uab_Sec_Grp2
The secondary values of the 3 phase-to-phase voltages of the 2nd
14 Ubc_Sec_Grp2
group.
15 Uca_Sec_Grp2
17 U1_Sec_Grp2 The secondary value of the positive-sequence voltage of the 2nd group.
1 Ua_Sec_Grp3
2 Ub_Sec_Grp3 The secondary values of the three-phase voltages of the 3rd group.
3 Uc_Sec_Grp3
4 Uab_Sec_Grp3
The secondary values of the 3 phase-to-phase voltages of the 3rd
5 Ubc_Sec_Grp3
group.
6 Uca_Sec_Grp3
Date: 2011-08-05
7 Human Machine Interface
8 U1_Sec_Grp3 The secondary value of the positive-sequence voltage of the 3rd group.
9 U2_Sec_Grp3 The secondary value of the negative-sequence voltage of the 3rd group.
10 Ua_Sec_Grp4
11 Ub_Sec_Grp4 The secondary values of the three-phase voltages of the 4th group.
12 Uc_Sec_Grp4
13 Uab_Sec_Grp4
The secondary values of the 3 phase-to-phase voltages of the 4th
14 Ubc_Sec_Grp4
group.
15 Uca_Sec_Grp4
17 U1_Sec_Grp4 The secondary value of the positive-sequence voltage of the 4th group.
18 U2_Sec_Grp4 The secondary value of the negative -sequence voltage of the 4th group.
1 Pa_Sec
3 Pc_Sec
4 Qa_Sec
6 Qc_Sec
7 Sa_Sec
9 Sc_Sec
10 Cosa
12 Cosc
Date: 2011-08-05
7 Human Machine Interface
Note! In the following table, all the values refer to the primary/secondary values of circuit
In 1½ CB arrangement, the circuit current values are calculated by the vector summation of
the measured values of the 2 circuit breakers (Side CB and Center CB).
1 Line_Ia_Sec
The secondary values of three-phase currents of the circuit in 1½ CB
2 Line_Ib_Sec
arrangement.
3 Line_Ic_Sec
4 Line_Pa_Sec
The secondary values of three-phase active power of the circuit in 1½
5 Line_Pb_Sec
CB arrangement.
6 Line_Pc_Sec
7 Line_Qa_Sec
The secondary values of three-phase reactive power of the circuit in 1½
8 Line_Qb_Sec
CB arrangement.
9 Line_Qc_Sec
Date: 2011-08-05
7 Human Machine Interface
12 Line_Cosa
14 Line_Cosc
16 Line_Ia_Pri
The primary values of three-phase currents of the circuit in 1½ CB
17 Line_Ib_Pri
arrangement.
18 Line_Ic_Pri
21 Line_Pa_Pri
The primary values of three-phase active power of the circuit in 1½ CB
22 Line_Pb_Pri
arrangement.
23 Line_Pc_Pri
24 Line_Qa_Pri
The primary values of three-phase reactive power of the circuit in 1½ CB
25 Line_Qb_Pri
arrangement.
26 Line_Qc_Pri
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
1 Line1_Ia_Sec
3 Line1_Ic_Sec
5 Line1_Ub_Sec
Date: 2011-08-05
7 Human Machine Interface
6 Line1_Uc_Sec
8 Line1_Uab_Sec
10 Line1_Uca_Sec
11 Line1_U1_Sec The secondary value of the positive-sequence voltage of the 1st CB.
12 Line1_U2_Sec The secondary value of the negative-sequence voltage of the 1st CB.
13 Line1_3I0Cal_Sec Line1_Ia _Sec, Line1_I b_Sec and Line1_I c_Sec (i.e. Line1_3 I0Cal_Sec =
Line1_Ia _Sec + Line1_I b_Sec + Line1_I c_Sec).
17 Line1_P_Sec The secondary value of the active power of the 1st CB.
18 Line1_Q_Sec The secondary value of the reactive power of the 1st CB.
19 Line1_S_Sec The secondary value of the apparent power of the 1st CB.
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
1 Line1_Pa_Sec The secondary values of three-phase active power of the 1st CB.
Date: 2011-08-05
7 Human Machine Interface
2 Line1_Pb_Sec
3 Line1_Pc_Sec
4 Line1_Qa_Sec
5 Line1_Qb_Sec The secondary values of three-phase reactive power of the 1st CB.
6 Line1_Qc_Sec
7 Line1_Sa_Sec
8 Line1_Sb_Sec The secondary values of three-phase apparent power of the 1st CB.
9 Line1_Sc_Sec
10 Line1_Cosa
12 Line1_Cosc
13 Line1_P_Sec The secondary value of the active power of the 1st CB.
14 Line1_Q_Sec The secondary value of the reactive power of the 1st CB.
15 Line1_S_Sec The secondary value of the apparent power of the 1st CB.
1) Side CB;
2) Center CB.
Date: 2011-08-05
7 Human Machine Interface
3 Line2_Ib_Sec
4 Line2_Ic_Sec
5 Line2_Ua_Sec
7 Line2_Uc_Sec
9 Line2_Uab_Sec
11 Line2_Uca_Sec
12 Line2_U1_Sec The secondary value of the positive-sequence voltage of the 2nd CB.
13 Line2_U2_Sec The secondary value of the negative-sequence voltage of the 2nd CB.
14 Line2_3I0Cal_Sec Line2_Ia _Sec, Line2_I b_Sec and Line2_I c_Sec (i.e. Line2_3I0Cal_Sec =
Line2_Ia _Sec + Line2_I b_Sec + Line2_I c_Sec).
18 Line2_P_Sec The secondary value of the active power of the 2nd CB.
19 Line2_Q_Sec The secondary value of the reactive power of the 2nd CB.
20 Line2_S_Sec The secondary value of the apparent power of the 2nd CB.
1) Side CB;
2) Center CB.
Date: 2011-08-05
7 Human Machine Interface
1 Line2_Pa_Sec
2 Line2_Pb_Sec The secondary values of three-phase active power of the 2nd CB.
3 Line2_Pc_Sec
4 Line2_Qa_Sec
5 Line2_Qb_Sec The secondary values of three-phase reactive power of the 2nd CB.
6 Line2_Qc_Sec
7 Line2_Sa_Sec
8 Line2_Sb_Sec The secondary values of three-phase apparent power of the 2nd CB.
9 Line2_Sc_Sec
10 Line2_Cosa
12 Line2_Cosc
13 Line2_P_Sec The secondary value of the active power of the 2nd CB.
14 Line2_Q_Sec The secondary value of the reactive power of the 2nd CB.
15 Line2_S_Sec The secondary value of the apparent power of the 2nd CB.
Date: 2011-08-05
7 Human Machine Interface
The secondary value of the 1st harmonic voltage of the 1st group voltage
1 U1stH_Grp1
input.
The secondary value of the 3rd harmonic voltage of the 1st group
2 U3rdH_Grp1
voltage input.
The secondary value of the 5th harmonic voltage of the 1st group voltage
3 U5thH_Grp1
input.
The secondary value of the 7th harmonic voltage of the 1st group voltage
4 U7thH_Grp1
input.
The secondary value of the 9th harmonic voltage of the 1st group voltage
5 U9thH_Grp1
input.
The secondary value of the 11th harmonic voltage of the 1st group
6 U11thH_Grp1
voltage input.
The secondary value of the 13th harmonic voltage of the 1st group
7 U13thH_Grp1
voltage input.
The secondary value of the 15th harmonic voltage of the 1st group
8 U15thH_Grp1
voltage input.
The secondary value of the 1st harmonic voltage of the 2nd group
9 U1stH_Grp2
voltage input.
The secondary value of the 3rd harmonic voltage of the 2nd group
10 U3rdH_Grp2
voltage input.
The secondary value of the 5th harmonic voltage of the 2nd group
11 U5thH_Grp2
voltage input.
The secondary value of the 7th harmonic voltage of the 2nd group
12 U7thH_Grp2
voltage input.
The secondary value of the 9th harmonic voltage of the 2nd group
13 U9thH_Grp2
voltage input.
The secondary value of the 11th harmonic voltage of the 2nd group
14 U11thH_Grp2
voltage input.
The secondary value of the 13th harmonic voltage of the 2nd group
15 U13thH_Grp2
voltage input.
The secondary value of the 15th harmonic voltage of the 2nd group
16 U15thH_Grp2
voltage input.
Date: 2011-08-05
7 Human Machine Interface
The secondary value of the 1st harmonic voltage of the 3rd group
1 U1stH_Grp3
voltage input.
The secondary value of the 3rd harmonic voltage of the 3rd group
2 U3rdH_Grp3
voltage input.
The secondary value of the 5th harmonic voltage of the 3rd group
3 U5thH_Grp3
voltage input.
The secondary value of the 7th harmonic voltage of the 3rd group
4 U7thH_Grp3
voltage input.
The secondary value of the 9th harmonic voltage of the 3rd group
5 U9thH_Grp3
voltage input.
The secondary value of the 11th harmonic voltage of the 3rd group
6 U11thH_Grp3
voltage input.
The secondary value of the 13th harmonic voltage of the 3rd group
7 U13thH_Grp3
voltage input.
The secondary value of the 15th harmonic voltage of the 3rd group
8 U15thH_Grp3
voltage input.
The secondary value of the 1st harmonic voltage of the 4th group voltage
9 U1stH_Grp4
input.
The secondary value of the 3rd harmonic voltage of the 4th group
10 U3rdH_Grp4
voltage input.
The secondary value of the 5th harmonic voltage of the 4th group
11 U5thH_Grp4
voltage input.
The secondary value of the 7th harmonic voltage of the 4th group
12 U7thH_Grp4
voltage input.
The secondary value of the 9th harmonic voltage of the 4th group
13 U9thH_Grp4
voltage input.
The secondary value of the 11th harmonic voltage of the 4th group
14 U11thH_Grp4
voltage input.
The secondary value of the 13th harmonic voltage of the 4th group
15 U13thH_Grp4
voltage input.
The secondary value of the 15th harmonic voltage of the 4th group
16 U15thH_Grp4
voltage input.
1) Side CB;
Date: 2011-08-05
7 Human Machine Interface
2) Center CB.
“the 1st group voltage input”mainly refers to the voltage input of the 1st CB in 1½
CB arrangement, it can be the Center CB or the Side CB.
The secondary value of the 1st harmonic voltage of the 1st group voltage
1 Line1_U1stH
input.
The secondary value of the 3rd harmonic voltage of the 1st group
2 Line1_U3rdH
voltage input.
The secondary value of the 5th harmonic voltage of the 1st group voltage
3 Line1_U5thH
input.
The secondary value of the 7th harmonic voltage of the 1st group voltage
4 Line1_U7thH
input.
The secondary value of the 9th harmonic voltage of the 1st group voltage
5 Line1_U9thH
input.
The secondary value of the 11th harmonic voltage of the 1st group
6 Line1_U11thH
voltage input.
The secondary value of the 13th harmonic voltage of the 1st group
7 Line1_U13thH
voltage input.
The secondary value of the 15th harmonic voltage of the 1st group
8 Line1_U15thH
voltage input.
1) Side CB;
2) Center CB.
“the 2nd group voltage input”mainly refers to the voltage input of the 2nd CB in 1½
CB arrangement, it can be the Center CB or the Side CB.
1 Line2_U1stH The secondary value of the 1st harmonic voltage of the 2nd group
Date: 2011-08-05
7 Human Machine Interface
voltage input.
The secondary value of the 3rd harmonic voltage of the 2nd group
2 Line2_U3rdH
voltage input.
The secondary value of the 5th harmonic voltage of the 2nd group
3 Line2_U5thH
voltage input.
The secondary value of the 7th harmonic voltage of the 2nd group
4 Line2_U7thH
voltage input.
The secondary value of the 9th harmonic voltage of the 2nd group
5 Line2_U9thH
voltage input.
The secondary value of the 11th harmonic voltage of the 2nd group
6 Line2_U11thH
voltage input.
The secondary value of the 13th harmonic voltage of the 2nd group
7 Line2_U13thH
voltage input.
The secondary value of the 15th harmonic voltage of the 2nd group
8 Line2_U15thH
voltage input.
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
1 Line1_Ia_Pri
3 Line1_Ic_Pri
4 Line1_Ua_Pri
6 Line1_Uc_Pri
Date: 2011-08-05
7 Human Machine Interface
8 Line1_Ubc_Pri
9 Line1_Uca_Pri
10 Line1_U1_Pri The primary value of the positive-sequence voltage of the 1st CB.
11 Line1_U2_Pri The primary value of the negative-sequence voltage of the 1st CB.
13 Line1_P_Pri The primary value of the active power of the 1st CB.
14 Line1_Q_Pri The primary value of the reactive power of the 1st CB.
15 Line1_S_Pri The primary value of the apparent power of the 1st CB.
16 Line2_Ia_Pri
18 Line2_Ic_Pri
19 Line2_Ua_Pri
21 Line2_Uc_Pri
22 Line2_Uab_Pri
24 Line2_Uca_Pri
25 Line2_U1_Pri The primary value of the positive-sequence voltage of the 2nd CB.
26 Line2_U2_Pri The primary value of the negative-sequence voltage of the 2nd CB.
28 Line2_P_Pri The primary value of the active power of the 2nd CB.
29 Line2_Q_Pri The primary value of the reactive power of the 2nd CB.
30 Line2_S_Pri The primary value of the apparent power of the 2nd CB.
Date: 2011-08-05
7 Human Machine Interface
The frequency difference between reference side and incoming side for
2 f_Diff
CB synchronism-check.
The df/dt difference between reference side and incoming side for CB
3 df/dt
synchronism-check.
1) Side CB;
2) Center CB.
“the 1st CB”mainly refers to the 1st CB in 1½ CB arrangement, it can be the Side
CB or the Center CB.
The frequency difference between reference side and incoming side for
2 Line1_f_Diff
the 1st CB synchronism-check.
The df/dt difference between reference side and incoming side for the
3 Line1_df/dt
1st CB synchronism-check.
The frequency difference between reference side and incoming side for
6 Line2_f_Diff
the 2nd CB synchronism-check.
Date: 2011-08-05
7 Human Machine Interface
The df/dt difference between reference side and incoming side for the
7 Line2_df/dt
2nd CB synchronism-check.
Note! This submenu is only valid in the PCS-9705 which acquires DC voltage/current
intput from transducers (e.g.: temperature or humidity transducers) via AI(DC) module.
The primary value of the No.1 DC analog inputs on the AI(DC) module
1 PriVal_dcmA01
on slot B11.
The primary value of the No.2 DC analog inputs on the AI(DC) module
2 PriVal_dcmA02
on slot B11.
The primary value of the No.3 DC analog inputs on the AI(DC) module
3 PriVal_dcmA03
on slot B11.
The primary value of the No.4 DC analog inputs on the AI(DC) module
4 PriVal_dcmA04
on slot B11.
The primary value of the No.5 DC analog inputs on the AI(DC) module
5 PriVal_dcmA05
on slot B11.
The primary value of the No.6 DC analog inputs on the AI(DC) module
6 PriVal_dcmA06
on slot B11.
The primary value of the No.7 DC analog inputs on the AI(DC) module
7 PriVal_dcmA07
on slot B11.
The primary value of the No.8 DC analog inputs on the AI(DC) module
8 PriVal_dcmA08
on slot B11.
The primary value of the No.1 DC analog inputs on the AI(DC) module
1 PriVal_dcmA01
on slot B11.
The primary value of the No.2 DC analog inputs on the AI(DC) module
2 PriVal_dcmA02
on slot B11.
The primary value of the No.3 DC analog inputs on the AI(DC) module
3 PriVal_dcmA03
on slot B11.
4 PriVal_dcmA04 The primary value of the No.4 DC analog inputs on the AI(DC) module
Date: 2011-08-05
7 Human Machine Interface
on slot B11.
The primary value of the No.5 DC analog inputs on the AI(DC) module
5 PriVal_dcmA05
on slot B11.
The primary value of the No.6 DC analog inputs on the AI(DC) module
6 PriVal_dcmA06
on slot B11.
The primary value of the No.7 DC analog inputs on the AI(DC) module
7 PriVal_dcmA07
on slot B11.
The primary value of the No.8 DC analog inputs on the AI(DC) module
8 PriVal_dcmA08
on slot B11.
The primary value of the No.1 DC analog inputs on the AI(DC) module
9 PriVal_dcmA09
on slot B10.
The primary value of the No.2 DC analog inputs on the AI(DC) module
10 PriVal_dcmA10
on slot B10.
The primary value of the No.3 DC analog inputs on the AI(DC) module
11 PriVal_dcmA11
on slot B10.
The primary value of the No.4 DC analog inputs on the AI(DC) module
12 PriVal_dcmA12
on slot B10.
The primary value of the No.5 DC analog inputs on the AI(DC) module
13 PriVal_dcmA13
on slot B10.
The primary value of the No.6 DC analog inputs on the AI(DC) module
14 PriVal_dcmA14
on slot B10.
The primary value of the No.7 DC analog inputs on the AI(DC) module
15 PriVal_dcmA15
on slot B10.
The primary value of the No.8 DC analog inputs on the AI(DC) module
16 PriVal_dcmA16
on slot B10.
Note! This submenu is only valid in the PCS-9705 which acquires DC voltage/current
intput from transducers (e.g.: temperature or humidity transducers) via AI(DC) module.
Date: 2011-08-05
7 Human Machine Interface
The secondary value of the No.1 DC analog inputs on the AI(DC) module
1 SecVal_dcmA01
on slot B11.
The secondary value of the No.2 DC analog inputs on the AI(DC) module
2 SecVal_dcmA02
on slot B11.
The secondary value of the No.3 DC analog inputs on the AI(DC) module
3 SecVal_dcmA03
on slot B11.
The secondary value of the No.4 DC analog inputs on the AI(DC) module
4 SecVal_dcmA04
on slot B11.
The secondary value of the No.5 DC analog inputs on the AI(DC) module
5 SecVal_dcmA05
on slot B11.
The secondary value of the No.6 DC analog inputs on the AI(DC) module
6 SecVal_dcmA06
on slot B11.
The secondary value of the No.7 DC analog inputs on the AI(DC) module
7 SecVal_dcmA07
on slot B11.
The secondary value of the No.8 DC analog inputs on the AI(DC) module
8 SecVal_dcmA08
on slot B11.
The secondary value of the No.1 DC analog inputs on the AI(DC) module
9 SecVal_dcmA09
on slot B10.
The secondary value of the No.2 DC analog inputs on the AI(DC) module
10 SecVal_dcmA10
on slot B10.
The secondary value of the No.3 DC analog inputs on the AI(DC) module
11 SecVal_dcmA11
on slot B10.
The secondary value of the No.4 DC analog inputs on the AI(DC) module
12 SecVal_dcmA12
on slot B10.
13 SecVal_dcmA13 The secondary value of the No.5 DC analog inputs on the AI(DC) module
Date: 2011-08-05
7 Human Machine Interface
on slot B10.
The secondary value of the No.6 DC analog inputs on the AI(DC) module
14 SecVal_dcmA14
on slot B10.
The secondary value of the No.7 DC analog inputs on the AI(DC) module
15 SecVal_dcmA15
on slot B10.
The secondary value of the No.8 DC analog inputs on the AI(DC) module
16 SecVal_dcmA16
on slot B10.
Note! This submenu is only valid in the PCS-9705 which adopts GOOSE analog sampling
The original sampled value of the No. XX analog input received by the
1 GAI_XX
GOOSE module.
Note! This submenu is only valid in the PCS-9705B which sends DC voltage/current
output to DCS system to regulate the active power output of the specified generator via
AO module.
Date: 2011-08-05
7 Human Machine Interface
7.3.3 Status
This menu is mainly used to display the state of binary inputs (including binary inputs via
opto-coupler and GOOSE binary inputs) and alarm signals in the device. This menu and “Analog”
menu fully reflects the running environment of the device. As long as the displayed values consist
with the actual running situation, basically, the device can work normally. This menu is set to
greatly facilitate the debugging and maintenance of people on site.
Locate the cursor on “Status”by turning the knob of the “MENU”and press the “MENU”key to
access the submenus.
The following table shows the submenus description of the submenu “Status”in PCS-9705A.
The following table shows the submenus description of the submenu “Status”in PCS-9705B/C.
The details of the submenu “Status”in PCS-9705A/B/C is introduced in the following 3 sections.
The following table shows the submenus description of the submenu “Status”->“Inputs” in
PCS-9705A/B/C.
Date: 2011-08-05
7 Human Machine Interface
The following table shows the submenus description of the submenu “Status”->“Outputs” in
PCS-9705A.
26 signals to indicate the interlock result state of each telecontrol are listed
in this submenu :
[Sig_En_CtrlTrp01]… [Sig_En_CtrlTrp13];
[Sig_En_CtrlCls01]… [Sig_En_CtrlCls13].
The items in this submenu are applied together with [En_Trpn_Blk] and
[En_ClsXX_Blk] in the submenu “Settings”->“Interlock_Settings”.
(XX=01~13)
When the [En_TrpXX_Blk]=“1”: Tripping output XX of the BO module is
controlled by the interlocking logic. (XX=01~13) If the interlocking conditions
are met (i.e.: [Sig_En_CtrlTrpXX]=1), tripping output XX has output,
3 Interlock_Status otherwise (i.e.: [Sig_En_CtrlTrpXX]=0) tripping output XX has no output.
When the [En_Trpn_Blk]=“0”: Tripping output XX of the BO module is not
controlled by the interlocking logic. (XX=01~13) Whether the interlocking
conditions are met or not, tripping output XX has output.
When the [En_Clsn_Blk]=“1”: Closing output XX of the BO module is
controlled by the interlocking logic. (XX=01~13) If the interlocking conditions
are met (i.e.: [Sig_En_CtrlClsXX]=1), closing output XX has output,
otherwise (i.e.: [Sig_En_CtrlClsXX]=0) closing output XX has no output.
When the [En_Clsn_Blk]=“0”: Closing output XX of the BO module is not
controlled by the interlocking logic. (XX=01~13) Whether the interlocking
conditions are met or not, closing output XX has output.
The following table shows the submenus description of the submenu “Status”->“Outputs” in
PCS-9705B/C.
Date: 2011-08-05
7 Human Machine Interface
26 signals to indicate the interlock result state of each telecontrol are listed
in this submenu :
[Sig_En_CtrlTrp01]… [Sig_En_CtrlTrp13];
[Sig_En_CtrlCls01]… [Sig_En_CtrlCls13].
The items in this submenu are applied together with [En_TrpXX_Blk] and
[En_Cl sXX_Blk] in the submenu “Settings”->“Interlock_Settings”.
(XX=01~13)
When the [En_TrpXX_Blk]=“1”: Tripping output XX of the BO module is
controlled by the interlocking logic. (XX=01~13) If the interlocking conditions
are met (i.e.: [Sig_En_CtrlTrpXX]=1), tripping output XX has output,
1 Interlock_Status otherwise (i.e.: [Sig_En_CtrlTrpXX]=0) tripping output XX has no output.
When the [En_TrpXX_Blk]=“0”: Tripping output XX of the BO module is not
controlled by the interlocking logic. (XX=01~13) Whether the interlocking
conditions are met or not, tripping output XX has output.
When the [En_ClsXX_Blk]=“1”: Closing output XX of the BO module is
controlled by the interlocking logic. (XX=01~13) If the interlocking conditions
are met (i.e.: [Sig_En_CtrlClsXX]=1), closing output XX has output,
otherwise (i.e.: [Sig_En_CtrlClsXX]=0) closing output XX has no output.
When the [En_ClsXX_Blk]=“0”: Closing output XX of the BO module is not
controlled by the interlocking logic. (XX=01~13) Whether the interlocking
conditions are met or not, closing output XX has output.
7.3.4 Records
This menu is used for displaying all kinds of records, so that the operator can load to view and use
as the reference of analyzing accidents and maintaining the device. All the records are stored in
non-volatile memory, it can still record the reports even if it losses its power.
Locate the cursor on “Records”by turning the knob of the “MENU”and press the “MENU”key to
access the submenus.
The following table shows the submenus description of the submenu “Records”in PCS-9705A.
Date: 2011-08-05
7 Human Machine Interface
PCS-9705A).
When the total number in this submenu reaches 64, “Disturb_Records”
memory area will be full. If a new item is issued now, the item will be
deleted, and then the latest item will be stored.
The SOE state changes records of this device are displayed in this menu.
When the total number of SOE state change records reaches 1024,
3 IO_Events “IO_Events”memory area will be full. If the device receives a new SOE
state change now, the oldest SOE state change record will be deleted, and
then the latest SOE state change record will be stored and displayed.
The control commands records of this device are displayed in this menu.
When the total number of control command records reaches 256,
5 Control_Logs “Control_Logs” memory area will be full. If the device receives a new
control command now, the oldest control command record will be deleted,
and then the latest control command record will be stored and displayed.
The following table shows the submenus description of the submenu “Records”in PCS-9705B.
Date: 2011-08-05
7 Human Machine Interface
The SOE state changes records of this device are displayed in this menu.
When the total number of SOE state change records reaches 1024,
2 IO_Events “IO_Events”memory area will be full. If the device receives a new SOE
state change now, the oldest SOE state change record will be deleted, and
then the latest SOE state change record will be stored and displayed.
The control commands records of this device are displayed in this menu.
When the total number of control command records reaches 256,
4 Control_Logs “Control_Logs” memory area will be full. If the device receives a new
control command now, the oldest control command record will be deleted,
and then the latest control command record will be stored and displayed.
The regulation commands records of this device are displayed in this menu.
When the total number of regulation command records reaches 256,
“Regulation_Logs”memory area will be full. If the device receives a new
5 Regulation_Logs control command now, the oldest control command record will be deleted,
and the n the latest control command record will be stored and displayed.
Please refer to the Section “Operation Theory”->“Regulation”for more
details.
The following table shows the submenus description of the submenu “Records”in PCS-9705C.
Date: 2011-08-05
7 Human Machine Interface
deleted, and then the latest control command record will be stored and
displayed.
The SOE state changes records of this device are displayed in this menu.
When the total number of SOE state change records reaches 1024,
2 IO_Events “IO_Events”memory area will be full. If the device receives a new SOE
state change now, the oldest SOE state change record will be deleted, and
then the latest SOE state change record will be stored and displayed.
The control commands records of this device are displayed in this menu.
When the total number of control command records reaches 256,
4 Control_Logs “Control_Logs” memory area will be full. If the device receives a new
control command now, the oldest control command record will be deleted,
and then the latest control command record will be stored and displayed.
7.3.5 Settings
This menu is mainly used for viewing and modifying the parameter and settings of the device.
Locate the cursor on “Settings”by turning the knob of the “MENU”and press the “MENU”key to
access the submenus.
Please refer to the Chapter “Settings”for more details of the menu “Settings”.
7.3.6 Local_Cmd
Locate the cursor on “Local_Cmd”by turning the knob of the “MENU”and press the “MENU”key
to access the submenus.
The following table shows the submenus description of the submenu “Local_Cmd” in
PCS-9705A/B/C.
Date: 2011-08-05
7 Human Machine Interface
After accessing this submenu, the device will issue the request for
downloading files.
Now this device can receives files (e.g.:Interlocking configuration files,
1 Download
GOOSE configuration files) from outside computers.
This device will fail to receive files from outside computers after exiting
this menu.
Clear all the statistic data in the all the 4 submenus in the menu “Test”:
1) “AR_Counter” if auto-reclosing function is supported. (Only for
3 Clear_Statistics
PCS-9705A)
2) “CBTrip_Counter”
5 Manual_Regulation
In this submenu, any of the analog output on the AO modules can be
operated manually to regulate the active power output of the specified
generator.
7.3.7 Information
Locate the cursor on “Information”by turning the knob of the “MENU”and press the “MENU”key
to access the submenu “Version_Info”.
Locate the cursor on “Version_Info”by turning the knob of the “MENU”and press the “MENU”key
to access the version information inrerface.
Date: 2011-08-05
7 Human Machine Interface
Note! It’
s only a sample which is used to explain the indication of the software version
menu. The software version of the device of the practical engineering should be taken as
final and binding.
7.3.8 Test
Locate the cursor on “Test”by turning the knob of the “MENU”and press the “MENU”key to
access the submenus.
The following table shows the submenus description of the submenu “Test”in PCS-9705A/B/C.
Date: 2011-08-05
7 Human Machine Interface
Note! Correct password must be inputted to access the submenus “Comm_Test” and
The following sections will introduce the submenu “Comm_Test”, “Interlock_Info”in details.
The following table shows the submenus description of the submenu “Test”->“Comm_Test”in
PCS-9705A/B/C.
Date: 2011-08-05
7 Human Machine Interface
After accessing this submenu, the device will start to test every
1 All Test
item in “Trip_Test”, “Alarm_Test”, “Binary_Test”automatically.
The following table shows the submenus description of the submenu “Test”->“Interlock_Info”in
PCS-9705A/B/C.
7.3.9 Clock
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
Note! Generally speaking, this device can automatically receive the clock synchronization
signal and to ensure the accuracy of the internal clock of this device, so it is unnecessary
to use this submenu to adjust time.
7.3.10 Language
This menu is mainly used for setting LCD display language of this device.
1: Chinese
2: English.
Date: 2011-08-05
7 Human Machine Interface
1.
2.English
Note! The LCD interface provided in this chapter is only a reference and available for
explaining specific definition of LCD. The displayed interface of the actual device may be
some different from it, so you shall be subject to the actual device.
Date: 2011-08-05
7 Human Machine Interface
Date: 2011-08-05
8 Communication
8 Communication
8.1 General
This section outlines the remote data communication interfaces of this device. It should be noted
that the descriptions contained within this section do not aim to fully detail the protocol itself. The
relevant documentation for the protocol should be referred to for this information. This section
serves to describe the specific implementation of the protocol in this device.
xxx.xxx.xxx. xxx
Section 3
Section 2
Section 1
Section 0
Where:
Equipment address has above relationship described as an equation with section 1 and section 0
of IP address.
Date: 2011-08-05
8 Communication
Note! In subsequent paragraphs, the master station (e.g.: SCADA) is referred to as the
controlling station.
8.3.3.1 Initialization
There is a running database for each SCADA link. At initialization, a GI is performed on the
application in order to initialize these databases.
Date: 2011-08-05
8 Communication
The GI sequence consists of different requests to this device application in order to get the value
and state of all data (binary input, measurement, counter, step position indication).
The Outstation Interrogation function is used for updating the controlling station after initialization
procedure of the internal station, or when the controlling station detects loss of information, or
when the link layer connection has been re-established. The general interrogation function of the
controlling station requests this device to transmit the actual values of all addressed datapoints.
This device marks the end of the general interrogation procedure by sending an indication to the
controlling station when the protocols allow it.
The controlling station must continue to send correct clock synchronization commands.
A bay can be in Local Control Mode or Remote Control Mode. When it is in Local Control
Mode it can not be controlled remotely and when it is in Remote Control Mode, it can not be
controlled locally.
The mode switching is associated with a binary input 3 named [BI_Rmt/Loc] on the PWR board.
Please refer to the Section “Operation Theory”->“Binary Input”for details.
The data, which can be sent to SCADA, is detailed in the paragraphs below.
Binary inputs can be sent as states or as changes of state depending on the protocol. A binary
input can be associated with a single point or a double point. Multipoint status is not treated.
8.3.4.2 Measurements
According to the protocol, this may be done by a specific message or by a binary input.
Date: 2011-08-05
8 Communication
A control is transmitted to handling of control sequence function. At the end of the control
sequence an acknowledgement is sent to SCADA if protocol allows it.
8.3.5.2 Synchronization
8.4.1 Overview
The IEC61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
Date: 2011-08-05
8 Communication
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC61850 implementation obtain this document set.
This device supports IEC61850 server services over TCP/IP communication protocol stacks. The
TCP/IP profile requires this device to have an IP address to establish communications. These
addresses are located in the submenu “Comm_Settings”. See Section
“Settings”->“Comm_Settings”for further details.
1) MMS protocol
IEC61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual MMS protocol services are mapped to IEC61850 abstract services in
IEC61850-8-1.
2) Client/server
3) Peer-to-peer
A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IED
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the
combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.
Date: 2011-08-05
8 Communication
for performing various functions, such as reading, writing, control commands, and reporting.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains information
about the IED logical device.
The GGIO logical node is available in this device to provide access to digital status points
(including general I/O inputs and warnings) and associated timestamps and quality flags. The data
content must be configured before the data can be used. GGIO provides digital status points for
access by clients. It is intended that clients use GGIO in order to access digital status values from
in this device. Clients can utilize the IEC61850 buffered reporting features available from GGIO in
order to build sequence of events (abbreviated SOE) logs and HMI display screens. Buffered
reporting should generally be used for SOE logs since the buffering capability reduces the
chances of missing data state changes. All needed status data objects are transmitted to HMI
clients via buffered reporting, and the corresponding buffered reporting control block (abbreviated
BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the others in MMXN, MSQI and so on. Each MMXU logical node provides data
from an IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2
provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog
data objects are transmitted to HMI clients via unbuffered reporting periodically, and the
corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical
nodes provide the following data for each source:
Date: 2011-08-05
8 Communication
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. In this device, most of the public services, the common
settings, control values and some device oriented data objects are available here. The public
services may be BRCB, URCB and GSE control blocks and similar global defines for the whole
device; the common settings (the logic nodes LPHD also contain some related common settings)
include all the setting items of communication settings , system settings and some of the setting
items, which can be configured to 2 or more logical nodes. In LLN0, the item Loc is a device
control object, this Do item indicates the local operation for complete logical device, when it is true,
all the remote control commands to the IED will be blocked and those commands make effective
until the item Loc is changed to false. Besides the logical nodes we describe above, there are
some other logical nodes below in the IEDs:
This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as r.m.s. values for current and voltage or power flows out of the acquired voltage
MMXU: and current samples. These values are normally used for operational purposes such as
power flow supervision and management, screen displays, state estimation, etc. The
requested accuracy for these functions has to be provided.
This LN shall be used to “enable”a switching operation if the interlocking conditions are
fulfilled. One instance per switching device is needed. At least all related switchgear
positions have to be subscribed. The interlocking algorithm is a local issue.
This LN is used for the interlocking function at station level and/or at bay level.
All interlocking rules referring to a bay are included in this LN. Releases or
blockings of requested commands are issued. In the case of status changes
affecting interlocking, blocking commands are issued.
All interlocking rules referring to the station are included in this LN. Releases
or blockings of requested commands are issued. Information with the LN bay
interlocking is exchanged.
This LN is used for the sequences and imbalances, for example for stability purpose.
MSQI: This LN is used to acquire values from CTs and VTs and to calculate the sequences and
imbalances in a three/multi-phase power system.
Date: 2011-08-05
8 Communication
The voltage phasor difference from both sides of an open breaker is calculated and
compared with predefined switching conditions (synchrocheck). Included is the case
that one side is dead (example: energizing a dead line) and the case that the phasor on
one side can be actively controlled by “higher”or “lower”(means synchronising).
RSYN:
Synchronizing or synchronism-check device is a device that operates when two AC
circuits are within the desired limits of frequency, phase-angle and voltage, to permit or
to cause the paralleling of these two circuits (IEEE C37.2-1996).
To avoid stress for the switching device and the network, closing of the circuit breaker is
allowed by the synchrocheck only, if the differences of voltage, frequency and phase
angle are within certain limits.
ATCC: This LN provides automatic function to keep the voltage of a busbar within a specific
range using tap changers. This node operates the tap changer automatically according
to given setpoints or by direct operator commands (manual mode).
Physical device information, the logical node to model common issues for physical
LPHD:
device.
Generic automatic process control, it is used to model in a generic way the
GAPC: processing/automation of functions, for example the sequence control functions for this
device.
Switch controller. This class is used to control all switching conditions of XCBR and
CSWI: XSWI. A remote switching command (for example select-before-operate) arrives here
firstly.
Breaker control. The XCBR logical node is directly associated with the breaker control
XCBR:
feature.
This is the position of the breaker. If the breaker control logic
indicates that the breaker, or any single pole of the breaker, is
XCBR1.ST.Pos: closed, then the breaker position state is “on”. If the breaker
control logic indicates that the breaker is open, then the breaker
position state is “off”.
This is the state of the block open command logic. When true,
XCBR1.ST.BlkOpn:
breaker open commands from IEC61850 clients will be rejected.
This is the state of the block close command logic. When true,
XCBR1.ST.BlkCls: breaker close commands from IEC61850 clients will be
rejected.
This is where IEC61850 clients can issue open or close
commands to the breaker. Select Before Operate (abbreviated
XCBR1.CO.Pos:
SBO) with enhanced security is the only supported IEC61850
control model.
Date: 2011-08-05
8 Communication
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of binary status values (in GGIO) and analog measured/calculated values
(in MMXU, MMTR and MSQI). The reporting control blocks can be configured in CID files, and
then be sent to the IED via an IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 2: Quality-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of event record or other files from this device.
8.4.4.3 Timestamps
The Universal Time Coordinated (abbreviated UTC) timestamp associated with all IEC61850 data
items represents the latest change time of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Date: 2011-08-05
8 Communication
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block”to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE link
settings in device.
This device supports IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-9705 series bay control units.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must
be correct to achieve the successful transfer of data. It is critical that the configured datasets at
the transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Date: 2011-08-05
8 Communication
Table 8.4-1
Client / Server
Services PCS-9705
Subsrciber /Publisher
Client-Server Roles
SCSMS Supported
Note!
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared.
O: Optional.
Y: Supported by this device.
N: Currently not supported by this device.
Table 8.4-2
M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
Reporting
Date: 2011-08-05
8 Communication
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M16 Time M M Y
Note!
C2: Shall be "M" if support for LOGICAL-NODE model has been declared.
C3: Shall be "M" if support for DATA model has been declared .
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time
models has been declared.
Date: 2011-08-05
8 Communication
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared.
M: Mandatory.
Table 8.4-3
Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O N
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Date: 2011-08-05
8 Communication
Reporting
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M Y
S24-3 data-update M Y
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M Y
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
S35 SendGOOSEMessage M Y
S36 GetGoReference O N
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M Y
Control
S51 Select O N
S52 SelectWithValue M Y
Date: 2011-08-05
8 Communication
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O N
File transfer
S58 SetFile O Y
S59 DeleteFile O N
Time
SNTP M Y
This device supports IEC61850 logical nodes as indicated in the following table. Note that the
actual instantiation of each logical node is determined by the product order code.
Table 8.4-4
Nodes PCS-9705
PDIF: Differential -
PDIS: Distance -
Date: 2011-08-05
8 Communication
Nodes PCS-9705
PTOF: Overfrequency -
PTOV: Overvoltage -
PTUC: Undercurrent -
PTUV: Undervoltage -
PTUF: Underfrequency -
RREC: Autoreclosing -
Date: 2011-08-05
8 Communication
Nodes PCS-9705
IARC: Archiving -
MMTR: Metering -
Date: 2011-08-05
8 Communication
Nodes PCS-9705
ZBAT: Battery -
ZBSH: Bushing -
ZCON: Converter -
ZGEN: Generator -
ZMOT: Motor -
ZREA: Reactor -
8.5.1 Overview
The descriptions given here are intended to accompany th is device. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this device, and also specifies what data is available from this device via DNP3.0.
The device operates as a DNP3.0 slave and supports subset level 2 of the protocol, plus some of
the features from level 3. The DNP3.0 communication uses the Ethernet ports at the rear side of
this device. The Ethernet ports are optional: electrical or optical.
Please see the DNP3.0 protocol standard for the details about the transport functions.
Date: 2011-08-05
8 Communication
Master 0x17 - - -
Slave 0x81 0x34 0x02 0x07
1) Supported qualifiers
The protection operation signals, alarm signals and binary input state change signals are
transported respectively according to the variation sequence in above table.
Object 2, SOE
If the master qualifier is “0x07”, the slave responsive qualifier is “0x27”; and if the master
qualifier is “0x01”, “0x06”or “0x08”, the slave responsive qualifier is “0x28”.
Date: 2011-08-05
8 Communication
The measurement values are transported firstly, and then the relay measurement values are
transported.
The master adopts the “Object 60”for the Class 0 data request and the variation is “0x01”.
The slave responds with the above mentioned “Object 1”, “Object 30”and “Object 40”(see
“Supported objects and variations” in the Section “Communication”->“DNP3.0 Interface”
->“Application Layer Functions”->“Supported Reading Functions”for the details.).
The master adopts the “Object 60”for the Class 1 data request and the variation is “0x02”.
The slave responds with the above mentioned “Object 2” (see “Supported objects and
variations” in the Section “Communication”->“DNP3.0 Interface” ->“Application Layer
Functions”->“Supported Reading Functions”).
The master adopts the “Object 60”for the multiple object request and the variation is “0x01”,
“0x02”, “0x03”and “0x04”.
The slave responds with the above mentioned “Object 1”, “Object 2”, “Object 30”and “Object
40” (see “Supported objects and variations” in the Section “Communication”->“DNP3.0
Interface”->“Application Layer Functions”->“Supported Reading Functions”).
The function code 0x03 and 0x04 are supported in this device. The function code 0x03 is for the
remote control with selection; and the function code 0x04 is for the remote control with execution.
The selection operation must be executed before the execution operation, and the single point
control object can be supported to this device.
Date: 2011-08-05
8 Communication
Date: 2011-08-05
8 Communication
Date: 2011-08-05
9 Installation
9 Installation
9.1 General
The equipment must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
DANGER: Strictly follow the company and country safety regulations. Working in a high
voltage environment requires serious approach to avoid human injuries and damage to
equipment.
DANGER: Do not touch circuitry during operation. Potentially lethal voltages and
during normal operation. Hazardous voltages and currents are present that may be lethal.
Operation may be disrupted and device and measuring circuitry may be damaged.
DANGER: Always connect the device to ground, regardless of the operating conditions.
This also applies to special occasions such as bench testing, demonstrations and off-site
configuration. Operating the device without proper grounding may damage both terminal
and measuring circuitry, and may cause injuries in case of an accident.
DANGER: Never open the front or back cover from a powered equipment or from a
device connected to powered circuitry. Potentially lethal voltages and currents are
present.
WARNING: The modules of this equipment may only be inserted in the designated slots.
Date: 2011-08-05
9 Installation
WARNING: Only insert or withdraw the other boards while the power supply is switched
off.
Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, discharge yourself by touching station ground (the cubicle)
beforehand.
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The ambient temperature and humidity required
for storage please refer to 2.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this device is mounted in cubicles).
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
Date: 2011-08-05
9 Installation
1) The location should not be exposed to excessive air pollution (dust, aggressive substances).
2) Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normall y mounted vertically
(visibility of markings).
WARNING: Excessively high temperature can appreciably reduce the operating life of
this device.
4 .0 0
20
6.80
465.00
482.60
Figure 9.6-1 Dimensions of the PCS-9705 and the cut-out in the cubicle (unit: mm)
Date: 2011-08-05
9 Installation
Note! It is necessary to leave enough space top and bottom of the cut-out in the cubicle
All the modules must be plugged into the proper slots of this device respectively. The safety
instructions must be abided by when installing the boards, see Section “9.2 Safety Instructions”.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Note! All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non -corroding.
Note! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of
it forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 9.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Date: 2011-08-05
9 Installation
Note! For metallic connections please observe the voltage difference of both materials
The cubicle ground rail must be effectively connected to the station ground rail by a grounding
strip (braided copper).
There are some ground terminals on some connectors of this device, and the sign is “GND”. All
the ground terminals are connected in the cabinet of this device. So, the ground terminal on the
rear panel (see in the following figure) is the only ground terminal of this device.
Date: 2011-08-05
9 Installation
The grounding strips must therefore be of (preferably tinned) braided copper and not round
copper conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
CT Circuits:
Heavy-duty terminal block, M4 threaded terminal ends for wire cross sections from 2.5 to 4.0 mm.
Welding terminals for wire cross sections should br from 1.5 to 2.5 mm2. Those devices are
Date: 2011-08-05
9 Installation
supplied with sufficient M4 screws for making connections to the rear mounted terminal blocks
using ring terminals, with a recommended maximum of two ring terminals per terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
Optical Fiber communication is an option, and should be ordered as such along with the required
mechanical modules. The equipment can have an optional 100 Mbps Ethernet port. It is
recommended that OF port should use permanent connection in substation environment. 100
Mbit OF port adopts SC connector and it is compatible with 850nm multi-mode optical fiber cable.
Specific care should be taken with the bend radius of the fibers, and the use of optical shunts is
not recommended as these can degrade the transmission path over time.
Non-observance of the following measure can result in death, personal injury or substantial
property damage.
RJ-45 Port:
It can be connected to 100Base-TX Ethernet switch with shield Ethernet Cable. Ethernet network
with RJ-45 connections has to stay inside a cubicle. The RJ-45 connector when seen face on, flat
side on bottom, side tab on top, then pin 1 is on the left and pin 8 on the right.
Since IRIG-B using RS485 serial communication interface, a termination 120 ohm resistor has to
be connected at each extremity of the busbar.
Date: 2011-08-05
9 Installation
There must be no more than two wires connected to each terminal, this ensures that a “Daisy
Chain”or “straight line”configuration is use.
Date: 2011-08-05
10 Commissioning
10 Commissioning
10.1 General
This device is set in normal working mode when it is sent to the users, it can operate normally
when energized. If any question is found, please contact the vendors.
Note! Before carrying out any work on the equipment, the user should be familiar with the
contents of the safety and technical data sections and the ratings on the equipment’
s
rating label.
WARNING: Hazardous voltages are present in this electrical equipment during operation.
Non-observance of the safety rules can result in severe personal injury or property
damage.
WARNING: Only qualified personnel shall work on and around this equipment after
becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the technical data (2) must not be exceeded at all, not even during
testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.
DANGER: Current transformer secondary circuits must have been short-circuited before
Date: 2011-08-05
10 Commissioning
WARNING: Primary test may only be carried out by qualified personnel, who are familiar
with the commissioning of protection system, the operation of the plant and safety rules
and regulations (switching, earthing, etc.)
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
Note! Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
With the front cover in place all keys are accessible. All menu cells can be read. LED indicators
and alarms can be reset. Configuration settings can be changed, or fault and event records
cleared. However, menu cells will require the appropriate password to be entered before changes
can be made.
Before turning on the power supply voltage, the following items must be checked:
Does the external (and measured) power supply voltage of the station agree with the nominal
Date: 2011-08-05
10 Commissioning
Are the current and voltage transformer (if used) connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly isolated.
Once all checks have been made, the power supply voltage may be turned on.
After the voltage has been applied, this device starts up. The LED indicator labeled “HEALTHY”
will light up. After approximately 20s, this device is ready for operation.
After settings have been made, the following checks should be carried out before any
interlockings or isolation is cancelled:
The following sections describe the checks to be performed to answer these questions and
ensure than this device is fully operation in its application.
This test verifies that the accuracy of voltage measurement is within the acceptance tolerance.
The measurement accuracy of this device is ±2%. However, an additional allowance must be
made since the accuracy of the test equipment has to be considered.
This test verifies that the accuracy of current measurement is within the acceptance tolerance.
The measurement accuracy of this device is ±2%. However, an additional allowance must be
made since the accuracy of the test equipment has to be considered.
This test verifies that the accuracy of transducer input (if applicable) measurement is within the
acceptance tolerance. The measurement accuracy of this device is ±1% of full scan. However, an
additional allowance must be made since the accuracy of the test equipment has to be
considered.
Date: 2011-08-05
10 Commissioning
After parameter setting and clock setting, switch off the auxiliary power of this device and start up
it again. Here, the clock should run correctly; no reports and records should be lost; no SOE
should be missent to SCADA and none of the binary output contact is closed by mistaken.
The control point— Local or Remote— is selected by means of special purpose binary signal input
[BI_Rmt/Loc]. Please refer to the Section “Operation Theory”->“Binary Input” for detailed
description.
Date: 2011-08-05
10 Commissioning
The switch apparatus to be controlled is selected and executed by pressing the keys on the
device front panel.
The switchgear units can be controlled via the communication interface (SCADA or Control
Center).
10.5.13 Final
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from this device in order to perform the wiring
verification tests, it should be ensured that all connections are replaced in accordance with the
relevant external connection or scheme diagram.
Ensure that all event records, fault records, and alarms have been cleared and LEDs has been
reset before leaving this device.
Date: 2011-08-05
10 Commissioning
Date: 2011-08-05
11 Maintenance
11 Maintenance
It is only allowed to plug or withdraw the board when the supply is reliably switched off. Never
allow the CT secondary circuit connected to this equipment to be opened while the primary
system is live when withdrawing an AI(AC) module. Never try to insert or withdraw this
device board when it is unnecessary.
Check weld spots on PCB to see whether they are well soldered without any rosin joint. All
dual inline components must be well plugged.
The terminals connected to external apparatus must match the design paper. Labels of the wiring
terminals and nameplates in the panel must be correct and clear.
Date: 2011-08-05
11 Maintenance
11.3.1 Alarms
The LED indicator labeled ALARM should first be checked to confirm if any alarm conditions
happen. If so, try to find the cause, eliminate it and clear the alarms to extinguish the LED by
resetting this device.
Replacing boards can reduce transport costs but requires clean, dry on site conditions and higher
skill from the person performing the repair. If an unauthorized service centre performs the repair,
the warranty will be invalidated.
Before any disconnection, check the labels correctly define the connectors and match with the
wishing description you have. Otherwise, note the wiring in order to prepare the new device
installation.
Disconnect the Ethernet RJ-45, optical fiber and IRIG-B/PPS links connected to the CPU
boards
Date: 2011-08-05
11 Maintenance
Note! The use of a magnetic bladed screwdriver is recommended to minimize the risk of
the screws being left in the terminal block or lost. Without exerting excessive force or
damaging the scheme wiring, pull the terminal blocks away from their internal
connectors. Remove the screw used to fasten this device to the panel, rack, etc. With
the larger diameter across heads, these screws are accessible when the access covers
are fitted and open.
Note! Withdraw this device from the panel or rack carefully and take care of its weight
because there are some heavy parts due to the internal CT/VT transformers.
To reinstall the repaired or new device, follow the above procedures in reverse. Ensure that each
terminal block is rel ocated in the correct position and the case correctly earthed, IRIG-B/PPS,
Ethernet or optical fiber connections are put back in place.
Once reinstallation is complete, this device should be commissioned again using the instruction in
10.
Primarily, the auxiliary power supply must be switched off. It is also strongly recommended that
the voltage and current transformer connections and trip circuit are isolated. After removing the
corresponding connector, screw off the two fixation screws on a desired board. By applying
outward pressure to the two fixation screws of the board, it can be pulled out from its slot. See in
the following figure.
Refit the new board and screw the two fixation screws.
Date: 2011-08-05
11 Maintenance
Note! From here on, the board pulled out is exposed and not protected against
electrostatic discharges, dust ingress, etc. Therefore, ESD precautions and clean
working conditions should be maintained at all times.
Note! Once this device has been reassembled after repair, it must be commissioned
again.
Note! All the parameter settings required for the application will need to be re-entered
Note! Do not forget to set the jumpers on the new board in the same position as the
replaced one.
11.5 Cleaning
Before cleaning the equipment ensure that all AC and DC supplies, current transformer and
voltage transformer connections are isolated to prevent any chance of an electric shock whilst
cleaning. Use a smooth cloth to clean the front panel. Do not use abrasive material or detergent
chemicals.
11.6 Storage
The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be -40°C to +70°C, but the temperature of 0°C to +40°C
is recommended for long-term storage.
Date: 2011-08-05
12 Decommissioning and Disposal
12.1 Decomissioning
12.1.1 Switching Off
To switch off this device, switch off the external miniature circuit breaker of the power supply.
DANGER: Before disconnecting the power supply cables that connected with the PWR
module of this device, make sure that the external miniature circuit breaker of the power
supply is switched off.
DANGER: Before disconnecting the cables that are used to connect analog input
module with the primary CTs and VTs, make sure that the circuit breaker for the primary
CTs and VT s is switched off.
12.1.3 Dismantling
The device rack may now be removed from the system cubicle, after which the cubicles may also
be removed.
DANGER: When the station is in operation, make sure that there is an adequate safety
12.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note! Strictly observe all local and national regulations when disposing of the device.
Date: 2011-08-05
12 Decommissioning and Disposal
Date: 2011-08-05
13 Manual Version History
Date: 2011-08-05