Kidde ECS Fire Suppression System

Component Description
Effective: June 2014
Cylinder and Valve Assembly, 350 lb. (158.7 kg)
Capacity K-90-2050 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant
• See Kidde Manual 06-236225-001 for USCG Approval

VALVE OUTLET
ORDERING INFORMATION

30°
Part Number Description

90-100350-001 STD

90-100351-001 w/LLI
PLAN VIEW
MATERIALS
SAFETY CAP CYLINDER VALVE
• Valve Body: Brass
LIQUID LEVEL
INDICATOR (LLI)
• Cylinder: Steel, Painted Red
LIFTING
LUGS
COMPATIBILITY
CYLINDER
For Use
Series
With
58.36" 53.14"
CYLINDER
NAMEPLATE
Kidde ECS HFC-227ea X

16.00" DIA

Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. Cylinders manufactured prior to May 2014 have only
1 boss. The safety burst disk and other port are on
the valve.
3. See K-90-2070 for additional information.

This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other
FENWAL, INC. assumes no responsibility for the product’s suitability for trademarks are the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder and Valve Assembly, 350 lb. (158.7 kg)
Capacity K-90-2050 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant
• See Kidde Manual 06-236225-001 for USCG Approval

VALVE OUTLET
ORDERING INFORMATION

30°
Part Number Description

90-100350-001 STD

90-100351-001 w/LLI
PLAN VIEW
MATERIALS
SAFETY CAP CYLINDER VALVE
• Valve Body: Brass
LIQUID LEVEL
INDICATOR (LLI)
• Cylinder: Steel, Painted Red
LIFTING
LUGS
COMPATIBILITY
CYLINDER
For Use
Series
With
58.36" 53.14"
CYLINDER
NAMEPLATE
Kidde ECS HFC-227ea X

16.00" DIA

Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. Cylinders manufactured prior to May 2014 have only
1 boss. The safety burst disk and other port are on
the valve.
3. See K-90-2070 for additional information.

This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other
FENWAL, INC. assumes no responsibility for the product’s suitability for trademarks are the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder and Valve Assembly, 600 lb. (272.1 kg)
Capacity K-90-2060 Rev BA

FEATURES
• See Kidde USCG Approved Manual 06-236225-001 for USCG Approval
• RoHS Compliant

ORDERING INFORMATION
VALVE OUTLET
Part Number Description
30°
90-100600-001 STD

90-100601-001 w/LLI

MATERIALS
PLAN VIEW • Valve Body: Brass
• Cylinder: Steel, Painted Red
SAFETY CAP CYLINDER VALVE

COMPATIBILITY
LIQUID LEVEL INDICATOR
LIFTING LUGS
For Use
Series
With

CYLINDER Kidde ECS HFC-227ea X

56.72" 50.51"
CYLINDER
NAMEPLATE

22.00" DIA

Notes:
1. The safety cap must be installed on the valve outlet
at all times, except when the cylinders are con-
nected to the system piping, or being filled. The
safety cap must not be removed from its chain.
2. See K-90-2070 for additional information.

This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other
FENWAL, INC. assumes no responsibility for the product’s suitability for trademarks are the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
600 lb. Agent Cylinder
P/Ns 90-100600-100 and 90-100601-100 K-90-9043

FEATURES
• 3-Inch Discharge Valve • FM Approved
• Optional Liquid Level Indicator • UL Listed
• Optional Low-Pressure Switch (P/N 06-118263-001) • TC Approved
• RoHS Compliant

DESCRIPTION
Kidde ECS System 600 lb. Agent Cylinders store sup-
pression agent super-pressurized with dry nitrogen to
360 psig at 70°F (2.48 Mpa at 21°C). The cylinders are
painted red and are equipped with a 3-inch pressure dif-
ferential valve, pressure gauge, optional liquid level indi-
cator and optional low-pressure switch assembly. The
safety burst disc is also located on the cylinder shoulder.
OPERATION
The agent storage container discharges when the actua-
tion assembly operates, causing the pressure differential
valve to open. All of the Kidde actuators may be used to
actuate the 600 lb. cylinder. The only exception is the
48650001, which is not compatible with this cylinder
valve.
INSTALLATION
The container is installed in a vertical position with the
valve assembly pointing up. Interconnection to discharge
piping is 3-inch NPT. Interconnection can be via a 3-inch
flex hose (P/N 06-118225-001) or via a suitably pressure
rated groove style fitting.
The container is secured in place by a mounting bracket
(P/N 294651), which must be fixed to a solid wall or strut
assembly. After the container is securely mounted it is
connected to discharge piping per the directions in the
design manual. QUARTERLY INSPECTION
An optional cylinder supervisory pressure switch (P/N 06- 1. Check the pressure gauges of each agent storage
118263-001) can be installed on the cylinder valve in the container. If the pressure gauge indicates a loss in
field if required. This cylinder supervisory pressure switch pressure of 10% or more, then it shall be recharged
has a 1/8-inch NPT connection, which is used on the 3- or replaced. Pressure varies with temperature, and
inch valve only. this must be taken into account when checking the
pressure gauge. In the range of 55°F to 85°F (13°C
ORDERING INFORMATION
to 29°C) the change is approximately 3 psi per
The part number for ordering the 600 lb. agent cylinder
degree F.
without liquid level indicator is 90-100600-100. The part
number for ordering the 600 lb.agent cylinder with liquid 2. Check all components, including supporting hard-
level indicator is 90-100601-100. ware, and tighten, repair or replace as required.
3. Replace any component if at all in doubt of its ability
MAINTENANCE to perform properly.
According to NFPA standards the following inspection
and/or maintenance procedure must be scheduled as
listed below and performed upon the occurrence of any
event which might affect the reliability of the system.

1
SEMI-ANNUAL INSPECTION DIMENSIONS
Qualified personnel are to determine the amount of agent
in all containers. The optional liquid level indicator may
be used to measure agent supply and compare it to the
original net weight which is marked on the container
label. If the measured net weight is less than 95% of the
original charged weight the container should be
recharged or replaced.
Inspect all piping, fittings and nozzles for looseness, dirt
or other damage. All outlet piping must be clean and free VALVE ORIENTATION
PLAN VIEW
of dirt, chips, fillings and other foreign material that may
cause the system to become inoperative or ineffective at
the time of discharge.
SPECIFICATIONS

Part 90-100600-100 90-100600-100


58” 50.5”
Number 90-100601-100 90-100601-100 (1478 mm) (1282 mm)

Fill range 258-600 Fill range 117-272 SAFETY BURST


DISC ASSEMBLY
(lb.) (kg)

Height (in.) 58 Height (mm) 1478

Diameter 22 Diameter 559


(in.) (mm)

Internal vol- 8.68 Internal vol- 0.246


ume (cu. ft.) ume (cu m)

Empty 362 Empty 164


22”
weight (lb.) weight (kg) (559 mm)

Temperature 32ºF to 130ºF Temperature 0ºC to 54ºC


range range
ACCESSORIES
Safety relief 800 to 975 psig Safety relief 5.5 to 6.7 Mpa
burst range burst range Description Part Number
Construction DOT 4BW-500 Construction OT 4BW-500 3-inch Stainless steel flexible 06-118225-001
specification specification
hose

3-inch Swing check valve 06-118058-001

Cylinder bracket 294651

Cylinder supervisory pres- 06-118263-001


sure switch

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL,
Inc.

2 Kidde Fire Systems


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
K-90-9043 Rev BA ©2014 Kidde-Fenwal, Inc. www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
900 lb. Agent Cylinder
P/Ns 90-100900-001 and 90-100901-001 K-90-9044

FEATURES
• Large Capacity Agent Cylinder • FM Approved
• 3-Inch Discharge Valve • UL Listed
• Optional Liquid Level Indicator • TC Approved
• Optional Low-Level Switch (P/N 06-118263-001) • RoHS Compliant

DESCRIPTION
Kidde ECS System 900 lb. Agent Cylinders store sup-
pression agent super-pressurized with dry nitrogen to
360 PSIG at 70°F (2.48 Mpa at 21°C). The cylinders are
painted red and are equipped with a 3-inch pressure dif-
ferential valve, pressure gauge, optional liquid level indi-
cator and optional low-pressure switch assembly. The
safety burst disc is also located on the cylinder shoulder.
OPERATION
The agent storage container discharges when the actua-
tion assembly operates, causing the pressure differential
valve to open. All of the Kidde actuators may be used to
actuate the 900 lb. cylinder. The only exception is the
48650001, which is not compatible with this cylinder
valve.
INSTALLATION
The container is installed in a vertical position with the
valve assembly pointing up. Interconnection to discharge
piping is 3-inch NPT. Interconnection can be via a 3-inch
flex hose (P/N 06-118225-001) or via a suitably pressure
rated groove style fitting.
The container is secured in place by a mounting bracket
(P/N 236125), which must be fixed to a solid wall or strut
assembly. After the container is securely mounted, it is
connected to discharge piping per the directions in the
Design, Installation, Operation and Maintenance Manual
(P/N 06-236115-001).
An optional cylinder supervisory pressure switch (P/N 06-
118263-001) can be installed on the cylinder valve in the
field if required. This cylinder supervisory pressure switch
has a 1/8-inch NPT connection, which is used on the 3-
inch valve only.
ORDERING INFORMATION
The part number for ordering the 900 lb. agent cylinder
without the liquid level indicator is 90-100900-001. The
part number for ordering the 900 lb. agent cylinder with
liquid level indicator is 90-100901-001.

1
MAINTENANCE DIMENSIONS
According to NFPA standards, the following inspection
and/or maintenance procedure must be scheduled as
listed below and performed upon the occurrence of any
event which might affect the reliability of the system.

QUARTERLY INSPECTION
1. Check the pressure gauges of each agent storage
container. If the pressure gauge indicates a loss in VALVE ORIENTATION
PLAN VIEW
pressure of 10% or more, then it shall be recharged
or replaced. Pressure varies with temperature, and
this must be taken into account when checking the
pressure gauge. In the range of 55°F to 85°F (13°C
70”
to 29°C) the change is approximately 3 PSI per (1789 mm)
degree F (0.2 bar per degree C).
2. Check all components, including supporting hard- 62”
(1566 mm)
ware, and tighten, repair or replace as required.
3. Replace any component if at all in doubt of its ability
to perform properly. SAFETY BURST
DISC ASSEMBLY
SEMI-ANNUAL INSPECTION
Qualified personnel should determine the amount of
agent in all containers. The optional liquid level indicator
may be used to measure agent supply and compare it to
the original net weight which is marked on the container
label. If the measured net weight is less than 95% of the
original charged weight the container should be
recharged or replaced. 24”
(610 mm)
Inspect all piping, fittings and nozzles for looseness, dirt
or other damage. All outlet piping must be clean and free
of dirt, chips, fillings and other foreign material that may ACCESSORIES
cause the system to become inoperative or ineffective at
the time of discharge.
SPECIFICATIONS Part Number Description
90-100900-001
06-118225-001 3-inch stainless steel flexible hose
Part Number 90-100901-001
imperial metric 06-118058-001 3-inch swing check valve
Fill range 390-900 lb. 178-408 kg 06-236125-001 Cylinder bracket
Height 70 in. 1789 mm
06-118263-001 Cylinder supervisory pressure switc
Diameter 24 in. 610 mm
Internal Volume 13.0 cu. ft. 0.368 cu. m
COMPATIBILITY
Empty Weight 505 lb. 229 kg
Temperature 32oF to 130oF 0oC to 54oC For Use
Range Series
With
Safety Relief
Burst Range 800 to 975 PSIG 5.5 to 6.7 Mpa Kidde ECS HFC-227ea X
Construction Speci- DOT 4BW-500 DOT 4BW-50
fication

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL,
Inc

2 Kidde Fire Systems


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
K-90-9044 Rev BA ©2014 Kidde-Fenwal, Inc. www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder Data K-90-2070

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant

MODULAR SYSTEMS CYLINDER DATA

Empty Gross Weight


Fill Range With Height Diameter Volume
Part Number Weight
LLI
lb. kg lb. kg Min. Fill Max. Fill in. cm. in. cm. ft.3 m3
90-100010-001 6 to 10 3 to 5 25 11 31 14 35 16 No 17.3 44 7.07 18 0.167 0.0047
90-100020-001 11 to 20 5 to 9 31 14 42 19 51 23 No 24.97 64 7.07 18 0.286 0.0081
90-100040-001 23 to 40 10 to 18 38 17 61 27 78 35 No 26.76 64 9 23 0.572 0.0162
90-100070-001 41 to 70 19 to 32 52 24 94 43 123 56 No 38.83 99 9 23 1 0.0283
90-100121-001 71 to 125 32 to 57 98 45 169 77 223 101 Yes 35.93 92 12.75 33 1.788 0.0506
90-100125-001 71 to 125 32 to 57 98 45 169 77 223 101 No 35.93 92 12.75 33 1.788 0.0506
90-100200-001 126 to 200 56 to 91 139 63 265 120 339 154 No 50.35 128 13.6 35 2.859 0.081
90-100201-001 126 to 200 57 to 91 141 64 267 121 341 155 Yes 50.35 128 13.6 35 2.859 0.081
90-100200-101 126 to 200 57 to 91 133 60 259 118 333 151 No 52.75 134 12.75 33 2.859 0.081
90-100201-101 126 to 200 57 to 91 133 60 259 118 333 151 Yes 52.75 134 12.75 33 2.859 0.081
90-100350-001 201 to 350 91 to 159 201 91 406 182 555 250 No 58.36 149 16 41 5 0.1416
90-100351-001 201 to 350 91 to 159 203 92 408 183 557 251 Yes 58.36 159 16 41 5 0.1416
90-100600-001 351 to 500 159 to 227 335 152 686 312 835 380 No 56.72 145 22 56 8.572 0.2427
90-100601-001 351 to 500 159 to 227 337 153 688 313 837 380 Yes 56.72 145 22 56 8.572 0.2427

Note: Modular balanced systems have a fill density range of 40 lb./cu.ft. to 58.3 lb./cu.ft.

1
ENGINEERED SYSTEMS CYLINDER DATA

Empty
Fill Range Gross Weight With Height Diameter Volume
Part Number Weight
LLI
lb. kg lb. kg Min. Fill Max. Fill in. cm. in. cm. ft.3 m3
90-100010-001 5 to 10 3 to 5 25 11 30 14 35 16 No 17.3 44 7.07 18 0.167 0.0047
90-100020-001 9 to 20 4 to 9 31 14 40 18 51 23 No 24.97 64 7.07 18 0.286 0.0081
90-100040-001 17 to 40 8 to 18 38 17 55 25 78 35 No 26.76 68 9 23 0.572 0.0162
90-100070-001 30 to 70 14 to 32 52 24 82 38 123 56 No 38.83 99 9 23 1 0.0283
90-100121-001 54 to 125 25 to 57 98 45 152 69 223 101 Yes 35.93 92 12.75 33 1.788 0.0506
90-100125-001 54 to 125 25 to 57 98 45 152 69 223 101 No 35.93 92 12.75 33 1.788 0.0506
90-100200-001 86 to 200 39 to 91 139 63 225 102 341 154 No 50.35 128 13.6 35 2.859 0.081
90-100201-001 86 to 200 39 to 91 141 64 227 103 343 155 Yes 50.35 128 13.6 35 2.859 0.081
90-100200-101 86 to 200 39 to 91 133 60 219 100 333 151 No 52.75 134 12.75 33 2.859 0.081
90-100201-101 86 to 200 39 to 91 133 60 219 100 333 151 Yes 52.75 134 12.75 33 2.859 0.081
90-100350-001 150 to 350 68 to 159 201 91 351 159 555 250 No 58.36 149 16 41 5 0.1416
90-100351-001 150 to 350 68 to 159 203 92 341 160 557 251 Yes 58.36 149 16 41 5 0.1416
90-100600-001 258 to 600 114 to 272 335 152 593 270 935 425 No 56.72 145 22 56 8.572 0.2427
90-100601-001 258 to 600 114 to 272 337 153 595 270 937 426 Yes 56.72 145 22 56 8.572 0.2427
90-100600-100 258 to 600 117 to 272 362 165 620 281 962 437 No 58 147 22 56 8.68 0.246
90-100601-100 258 to 600 117 to 272 362 165 620 281 962 437 Yes 58 147 22 56 8.68 0.246
90-100900-001 390 to 900 178 to 408 505 230 895 407 1405 639 No 70 178 24 61 13 0.368
90-100901-001 390 to 900 178 to 408 505 230 895 407 1405 639 Yes 70 178 24 61 13 0.368

Note: Engineered systems have a fill density range of 30 lb./cu.ft. to 70 lb./cu.ft.

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL,
Inc.

2 Kidde Fire Systems


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
K-90-2070 Rev BA ©2014 Kidde-Fenwal, Inc. www.kiddefiresystems.com
Kidde ADS
675-lb. Cylinder and Valve Assembly with A UTC Fire & Security Company
Nitrogen Driver Assemblies
P/N: 90-10067X-001 Effective: August 2011
K-90-112

FEATURES
• Designed for “Drop-In” Replacement for Halon • 347 lb. to 675 lb. Fill Capacity
Retrofit Applications • Optional Liquid Level Indicator
• Well Suited for Complicated Pipe Networks and • UL Listed
Large Area Coverage with Minimal Room for • FM Approved
Cylinder Storage
• 3-inch Valve Outlet

DESCRIPTION
Kidde Fire Systems FM-200® ADS Series Engineered
Fire Suppression Systems are Listed by the Underwriters
Laboratory, Inc. (UL) and tested by Factory Mutual (FM).
These systems are designed for total flooding in accor-
dance with NFPA 2001, Standard on Clean Agent Extin-
guishing Systems. These systems have been tested to
UL 2166, Standard for Safety; Standard for Halocarbon
Clean Agent Extinguishing System Units, and other
parameters established jointly by UL and FM.
The ADS uses a unique method for propelling the FM-
200 agent from the storage cylinder, through the piping
system and out of the discharge nozzles. Nitrogen gas
pressure from two separate storage cylinders is intro-
duced into the vapor space of the FM-200 cylinder at a
controlled rate. This nitrogen pressure acts to propel the
liquid FM-200 agent through the pipe at a higher flow
rate. It can also propel the FM-200 agent farther through
the pipe network allowing for the placement of storage
cylinders remotely from the protected hazard.
The FM-200 ADS Series is extremely well-suited to appli-
cations involving remote agent storage and situations
which limit the maximum pipe size to be used. The ADS
is capable of using smaller pipe sizes to discharge large
quantities of FM-200.
This system can be successfully applied to many existing
Halon 1301 system pipe networks, providing easy retrofit
of these systems to a new agent with long-term availabil-
ity.
OPERATION
When a control head actuates the two nitrogen cylinder OPERATING RANGE LIMITATIONS:
discharge valves, the nitrogen pressure actuates the • The operating temperature range for all components
agent cylinder discharge valve and pressurizes the cylin- used in the FM-200 ADS Series is 32°F to 130°F
der. FM-200 liquid agent is then propelled by its own (0°C to 54°C).
vapor pressure and the nitrogen pressure through the • The agent cylinder operating temperature must be
discharge valve and into the system pipe network. The between 60°F to 80°F (16°C to 27°C) when protect-
FM-200 liquid agent travels through the system pipe net- ing two or more separate hazards.
work at a high flow rate.
K

3
20.0 SIDE VIEW 7
8 5

34.0

FRONT VIEW
9
4

4070
A 675 lb. cu. in. H
1. ASSY - CYL. AND VALVE ADS ASSY
I 2. ASSY - CYL. AND VALVE NITROGEN DRIVER
B 1 3. HOSE - FLEXIBLE DISCHARGE
J 4. STRAP - FM 200 CYLINDER
5. ASSY - DISCHARGE HEAD
C 6. ASSY - ACTUATION
7. FITTING - ORIFICE
1.0 2 8. HOSE - HIGH PRESSURE
D 9. STRAP NITROGEN DRIVER CYLINDERS

F
E G
Figure 1. Nitrogen and Agent Cylinders

Table 1. Nitrogen and Agent Cylinder Dimensions, Imperial

Cylinder
A B C D E F G H I J K
Part Number

90-10067X-001 61.00 47.40 37.00 18.00 22.00 22.00 10.55 58.00 63.22 65.25 10.55

Note: The "X" within the part numbers denotes whether a liquid level indicator is ordered with the cylinder.
A one (1) is used if a LLI is needed, a five (5) is used if one is not.

Table 2. Nitrogen and Agent Cylinder Dimensions, Metric

Cylinder
A B C D E F G H I J K
Part Number

90-10067X-001 1549 1204 940 457 559 559 268 1473 1606 1657 268

Note: The "X" within the part numbers denotes whether a liquid level indicator is ordered with the cylinder.
A one (1) is used if a LLI is needed, a five (5) is used if one is not.

-2-
INSTALLATION MAINTENANCE
The FM-200 ADS Series installation is based on the According to NFPA standards, the following inspection
requirements of NFPA 2001, Standard on Clean Agent and/or maintenance procedure must be scheduled as
Extinguishing Systems, Current Edition. listed below and performed upon the occurrence of any
event, which might affect the reliability of the system.
ASSEMBLY:
Both the nitrogen drivers and agent storage cylinders are QUARTERLY:
to be installed in the vertical position only. The nitrogen 1. Check the weight of each agent storage container
driver is located to the immediate right apart from the and the pressure of the nitrogen drivers.
agent cylinder (see Figure 1). The nitrogen driver cylinder • Nitrogen driver if the pressure is less than 1800
is connected to the agent cylinder by using the nitrogen PSI (124 bar) at 70°F (21°C)
transfer components (two 1-in. nitrogen transfer hoses
Note: Pressure changes with temperature.
[P/N 06-118207-003] and a 3/4-in. NPT transfer fitting,
see Figure 2). The 3/4-in. transfer fitting connects into the •The containers should be removed and carefully
orifice fitting. The orifice fitting is a custom fitting that is inspected by certified personnel.
designed to regulate the nitrogen pressure flow required • The containers should then be reconditioned,
for the specific system. The orifice fitting then connects recharged or replaced.
into the nitrogen injector assembly to diffuse the nitrogen 2. Check all components supporting hardware and
in a horizontal pattern. tighten, repair or replace as required.
ACTUATION: 3. Visually check all components for evidence of physi-
The control head is attached to the master nitrogen driver cal wear and tear and take whatever action is
by means of electric, cable, lever, or pneumatic devices. required. Replace any component that looks like it
The actuating of the second nitrogen driver and agent may be damaged or worn.
cylinder is done upon transfer of nitrogen from the master SEMI-ANNUAL:
driver cylinder using the actuation assembly kit (P/N 06- The following checks/tests should be conducted by quali-
129985-001). fied personnel:
Assembly includes: 1. Determine the weight of FM-200 in each agent cylin-
• Nitrogen Transfer Fitting der by the procedure indicated in the Design, Instal-
lation, Operation and Maintenance (DIOM) Manual
• 1/8-in. Flex Loop
(P/N 90-FM200M-030).
• 1/8-in. Flare Fitting
2. Functional tests of required system devices (refer-
• 1/8-in. Branch Tee ence the DIOM manual).
• 1/8-in. Schrader Fitting and Cap
3. All outlet piping must be cleaned and free of dirt,
• Pressure Operated Control Head chips and other foreign material that may become
• 3/4-in. Nipple (Hex) hazardous projectiles or cause the system to
become inoperative or ineffective at the time of dis-
5
charge.

Table 3. Nitrogen Transfer Components Descriptions

Item
3 6 7 Qty. Part Number Description
No.

1 1 06-236260-001 Nitrogen Transfer "Y" Fitting

2 1 878737 Pressure Operated Control Head


2
3 2 06-118191-001 Fitting Flared 1/8" x 1/4"
4
1 4 1 06-118193-001 3/16" Flexible Actuation Hose

5 1 06-118192-001 1/8" Branch Tee

6 1 263303 1/8" Schrader Valve


8
3 7 1 263304 1/8" Schrader Valve Cap

8 1 06-118330-001 3/4" Nipple

Figure 2. Nitrogen Transfer Components

-3-
SPECIFICATIONS

Agent Storage Container Nitrogen Driver


90-10067X-001 90-104070-001
Element
Imperial Metric Imperial Metric

Fill Range (w/o LLI) 347 to 675 lb. 158 to 306 kg Factory Filled to 1800 PSIG Factory Filled to127 bar

Fill Range (w/ LLI) 347 to 675 lb. 158 to 306 kg — —

Height 58.5 in. 149.0 cm 62.00 in. 157.0 cm

Diameter 22.0 in. 56.0 cm 10.50 in. 26.70 cm

Internal Volume 8.68 cu. ft. 0.25 cu. m 4070 cu. in. 0.0667 cu. m

Empty Weight 362.0 lb. 164.0 kg 184.0 lb. 83.5 kg

Temperature Range 32°F to 130°F 0°C to 54°C 32°F to 130°F 0°C to 54°C

RECONDITIONING ORDERING INFORMATION


After a system has been discharged, it is recom-
mended that the local authorized Kidde Distributor be
contacted to recondition the system. Please refer- Part Number Description
ence the DIOM manual (P/N 90-FM200M-030) for
the appropriate reconditioning kit. 90-10067X-001* Agent Storage Cylinder

90-104070-001** Nitrogen Driver with Standard


Gauge

90-104070-101** Nitrogen Driver with Switch-In


Gauge

*Note: X denotes liquid level indicator. Use a 1 in place of


the X to order cylinder with LLI or a 5 to order a
cylinder without an LLI.
Example: 90-100675-001 (no LLI)

**Note: Two are required for each 675 lb. agent cylinder

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or ques- A UTC Fire & Security Company
tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
K-90-112 Rev AD © 2010 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder Mounting Straps K-90-8130 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant

CYL. O.D. A B C D E F
CYL.
PART NO.
SIZE
in. mm in. mm in. mm in. mm in. mm in. mm in. mm

WK-283945-000 10, 20 7.07 1.80 6.48 165 9.62 244 8.62 219 1.00 25 2.78 71 .437 11.1

WK-283934-000 40, 70 9.00 229 8.16 207 11.69 297 10.69 272 1.00 25 3.50 89 .437 11.1

292971 200 13.60 345 13.09 332 17.06 433 15.44 392 1.75 44 6.06 154 .625 15.9
pre-3/98

06-235317-001 125, 200 12.75 324 12.93 329 16.18 411 14.56 370 1.75 44 5.59 142 .625 15.9

WK-281866-000 350 16.00 406 15.5 394 19.5 495 17.88 454 1.75 44 6.06 154 .625 15.9

WK-294651-000 600 22.00 559 21.56 548 25.75 654 24.12 613 1.75 44 10.25 260 .625 15.9

06-236125-001 900 24.00 610 23.75 603 27.75 705 26.00 660 1.75 44 12.13 308 .625 15.9

MATERIALS
• Steel, Painted Black SAE 1020

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder Valve K-90-2080 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant
• See Kidde Manual 06-236225-001 for USCG Approval

P/N: 90-1X0000-000 TECHNICAL DATA


• Working Pressure: 360 to 609 PSIG
CAP • Proof Pressure: 1000 PSIG
• Burst Pressure: 2000 PSIG
• Temperature Range: 1ºF to 130ºF

BODY
Equivalent Length
SLAVE CYLINDER
ACTUATION PORT
1/8" NPT 1-1/2” 16.7’ of 1-1/4”
A
SAFETY 2” 28.0’ of 2”
DISC
PRESSURE 2-1/2” 3.5’ of 2-1/2”
GAGE

MATERIALS
B
• Valve Body: Brass
SAFETY CHAIN ACTUATION PORT
• Piston: Brass
CONTROL HEAD
VENT HOLE
CONNECTION
• Finish: Natural
• Seat: Rubber
DISCHARGE PISTON
OUTLET PORT COMPATIBILITY
SUPERVISORY For Use
PRESSURE Series
SAFETY SWITCH With
CAP CONNECTION
SEAT
Kidde ECS HFC-227ea X

C Kidde ECS Advanced Delivery FM-200® X

Part Number Valve Size A B C D E F

90-140000-000 1 1/2” 7.63” 4.83” 5.22” 754-900 PSI 242461 9.9 lb.

90-150000-000 2” 8.80” 5.32” 6.28” 798-972 PSI 264925 15 lb.

90-160000-000 2 1/2” 10.04” 6.30” 6.61” 798-972 PSI 264929 24 lb.

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
180 Degree Pendant Nozzle K-81-9150 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed & FMRC Approved Systems
• RoHS Compliant

P/N: 90-19401X-XXX

METAL STAMP X-XXX (DASH NO.)


IN .093 .031 HIGH CHARACTERS
ON ANY FLAT

C
A

60°

KIDDE
30°

Pipe Size A B C D

1/2" (12.20 mm) 1.25" (31.75 mm) 1.250" (31.75 mm) 1.687" (42.84 mm) 2.000" (50.80 mm)
3/4" (19.05 mm) 1.50" (38.10 mm) 1.375" (34.92 mm) 1.950" (48.89 mm) 2.296" (58.31 mm)
1" (25.40 mm) 1.75" (44.45 mm) 1.562" (39.67 mm) 2.218" (56.33 mm) 2.671" (67.84 mm)
1¼"(31.75 mm) 2.25" (57.15 mm) 1.750" (44.45 mm) 2.656" (67.46 mm) 3.250" (82.55 mm)
1½" (38.10 mm) 2.50" (63.50 mm) 1.950" (48.89 mm) 2.950" (74.93 mm) 3.625" (92.07 mm)
2" (50.80 mm) 3.00" (76.2 mm) 1.968" (49.98 mm) 2.875" (73.02 mm) 3.656" (92.86 mm)

Note: A selection of orifices are available for each nozzle


size. Consult your Kidde Design and Installation
Manual for details.

COMPATIBILITY

Series For Use With

Kidde ECS HFC-227ea X

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are


This literature is provided for informational purposes only. KIDDE- the property of their respective owners.
FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: October 2014
360 Degree Pendant Nozzle K-90-2140 Rev BA

FEATURES
• For Use with UL, ULC and FM Approved Systems • RoHS Compliant
• See Kidde Manual 06-236225-001 for USCG Approval

P/N: 90-19402X-XXX

IN .093 .031 HIGH


CHARACTERS ON ANY FLAT
A

KI
C

Pipe Size A B C D

1/2” (12.20 mm) 1.250” (31.75mm) 1.468” (37.28mm) 1.937” (49.19mm) 1.250” (31.75mm)

3/4” (19.05 mm) 1.500” (38.10 mm) 1.578” (40.08 mm) 2.125” (53.97 mm) 1.500” (38.10 mm)

1” (25.40 mm) 1.750” (44.45 mm) 1.718” (43.63 mm) 2.375” (60.32 mm) 1.750” (44.45 mm)

1-1/4” (31.75 mm) 2.250” (57.15 mm) 1.950” (49.53 mm) 2.750” (69.85 mm) 2.250” (57.15 mm)

1-1/2” (38.10 mm) 2.250” (63.50 mm) 2.000” (50.80 mm) 2.937” (74.59 mm) 2.250” (63.50 mm)

2” (50.80 mm) 3.000” (76.20 mm) 2.062” (52.37 mm) 3.125” (79.37 mm) 3.000” (76.20 mm)

Note: A selection of orifices are available for each nozzle size. Consult your Kidde design and installation manual for
details.

COMPATIBILITY

Series For Use With

Kidde ECS HFC-227ea X

This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other
FENWAL, INC. assumes no responsibility for the product’s suitability for trademarks are the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Electric Control Head K-90-8010 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems

P/N: WK-890181-000

Ordering Information

Part Number Control Head

Voltage Current

WK-890181-000 24 VDC 2.0A

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde Fire Systems
Component Description
Lever Operated Control Head
Effective: November 2015
P/N: WK-870652-000
K-85-6005 Rev AA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant

MATERIALS
• Lever: Stainless Steel
• Body: Brass

COMPATIBILITY

For Use
Series
With

Kidde ECS with HFC-227ea Agent X

Kidde ADS with FM-200™ Agent X

Kidde ECS with 3M™ Novec™ 1230 Fire Protection Fluid X

Kidde ADS with 3M Novec 1230 Fire Protection Fluid X

Kidde FE-13™ Engineered Suppression System X

Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are


This literature is provided for informational purposes only. KIDDE- the property of their respective owners.
FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2015 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Main and Reserve Nameplates K-90-9010 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant
• See Kidde® Manual 06-236225-001 for USCG Approval

P/N: WK-3103XX-000

P/N: WK-310330-000

P/N: WK-310340-000

MATERIALS
• Aluminum with Red Painted Letters

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

1. IDENTIFICATION

Product Name FM-200® (Fire Extinguishing Agent with Expellant)


Other Names Heptafluoropropane, HFC-227ea
Recommended use of the chemical and
restrictions on use
Identified uses Fire Extinguishing Agent
Restrictions on use Consult applicable fire protection codes
Company Identification Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721
USA
Customer Information Number (508) 881-2000
Emergency Telephone Number
Chemtrec Number (800) 424-9300
(703) 527-3887 (International)
Issue Date October 1, 2015
Supersedes Date April 10, 2015

Safety Data Sheet prepared in accordance with OSHA’s Hazard Communication Standard (29 CFR 1910.1200) and the Globally
Harmonized System of Classification and Labelling of Chemicals (GHS)

2. HAZARD IDENTIFICATION

Hazard Classification
Gas under pressure – liquefied gas
Simple Asphyxiant

Label Elements
Hazard Symbols

Signal Word: Warning

Hazard Statements
Contents under pressure; may explode if heated.
May displace oxygen and cause rapid suffocation.

Precautionary Statements
Prevention
Do not enter confined space unless adequately ventilated.
In case of inadequate ventilation wear respiratory protection.

Revision Date: October 1, 2015 Page 1 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

2. HAZARD IDENTIFICATION

Response
None
Storage
Keep container tightly closed.
Protect from sunlight and store in well-ventilated place.
Disposal
None

Other Hazards
Direct contact with the cold gas or liquid can cause freezing of exposed tissues. Exposure to vapor at
high concentrations can cause cardiac sensitization and suffocation if air is displaced by vapors.

Specific Concentration Limits


The values listed below represent the percentages of ingredients of unknown toxicity.
Acute oral toxicity 0%
Acute dermal toxicity 0%
Acute inhalation toxicity 0%
Acute aquatic toxicity 0%

3. COMPOSITION/INFORMATION ON INGREDIENTS

Synonyms: Heptafluoropropane
This product is a substance.

Component CAS Number Concentration


1,1,1,2,3,3,3-Heptafluoropropane 431-89-0 >99.9%

Note: The expellant is nitrogen.

4. FIRST- AID MEASURES

Description of necessary first-aid measures


Eyes
Immediately flood the eye with plenty of water for at least 15 minutes, holding the eye open. Obtain
medical attention if soreness or redness persists.
Skin
Flush with water. Obtain medical attention if frostbite or blistering occurs or redness persists.
Ingestion
Ingestion is not considered a potential route of exposure.
Inhalation
Remove from exposure. If there is difficulty in breathing, give oxygen. Obtain medical attention
immediately.

Most important symptoms/effects, acute and delayed


Aside from the information found under Description of necessary first aid measures (above) and
Indication of immediate medical attention and special treatment needed, no additional symptoms and
effects are anticipated.

Revision Date: October 1, 2015 Page 2 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

4. FIRST- AID MEASURES

Indication of immediate medical attention and special treatment needed


Notes to Physicians
In case of frostbite, place the frostbitten part in warm water. If warm water is not available or impractical
to use, wrap the affected parts gently in blankets. DO NOT USE HOT WATER.
The use of epinephrine or similar compounds can increase susceptibility to heart irregularities caused by
excessive exposure to these types of compounds.

5. FIRE - FIGHTING MEASURES

Suitable Extinguishing Media


FM-200® is used as an extinguishing agent and therefore is not a problem when trying to control a blaze.
Use extinguishing agent appropriate to other materials involved. Keep containers and surroundings cool
with water spray as containers may rupture or burst in the heat of a fire.

Specific hazards arising from the chemical


Containers may explode in heat of fire.

Special Protective Actions for Fire-Fighters


Wear full protective clothing and self-contained breathing apparatus as appropriate for specific fire
conditions.

6. ACCIDENTAL RELEASE MEASURES

Personal precautions, protective equipment and emergency procedures


Wear full protective clothing and self-contained breathing apparatus. Remove leaking cylinder to a safe
place. Ventilate the area. Leaks inside confined spaces may cause suffocation as vapors may displace
air, and should not be entered without a self-contained breathing apparatus.

Environmental Precautions
Prevent the material from being released into the environment.

Methods and materials for containment and cleaning up


Material evaporates.

7. HANDLING AND STORAGE

Precautions for safe handling


Wear appropriate protective clothing. Prevent skin and eye contact.

Conditions for safe storage


Pressurized containers should be properly stored and secured to prevent falling or being knocked over.
Do not drag, slide or pressurized containers. Do not drop pressurized containers or permit them to strike
against each other. Never apply flame or localized heat directly to any part of the pressurized or plastic
container. Store pressurized and plastic containers away from high heat sources. Storage area should
be: - cool - dry - well ventilated - under cover - out of direct sunlight

Revision Date: October 1, 2015 Page 3 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

8. EXPOSURE CONTROLS/PERSONAL PROTECTION

Control parameters
Exposure limits are listed below, if they exist.

1,1,1,2,3,3,3-Heptafluoropropane
None assigned.

Appropriate engineering controls


Use with adequate ventilation. There should be local procedures for the selection, training, inspection and
maintenance of this equipment. When used in large volumes or odor becomes apparent, use local exhaust
ventilation.

Individual protection measures


Respiratory Protection
Not normally required under conditions of use as a portable fire extinguisher. For other applications
creating oxygen deficient atmospheres, use a self contained breathing apparatus, as an air purifying
respirator will not provide protection.
Skin Protection
Wear rubber gloves. Avoid contact with skin.
Eye/Face Protection
Chemical goggles or safety glasses with side shields. Avoid contact with eyes.
Body Protection
Normal work wear.

9. PHYSICAL AND CHEMICAL PROPERTIES

Agent – FM-200®
Appearance
Physical State Liquefied gas under pressure
Color Colorless
Odor Slight ether like
Odor Threshold No data available
pH Neutral
Specific Gravity 1.46
Boiling Range/Point (°C/F) -16.4oC/3 oF
Melting Point (°C/F) -129.5oC/265 oF
Flash Point (PMCC) (°C/F) Not flammable
Vapor Pressure 540 hPa at -30 °C
29,360 hPa at 123 °C
Evaporation Rate (BuAc=1) Not applicable
Solubility in Water 0.23 g/l at 25oC
Vapor Density (Air = 1) 5.8
VOC (%) Not applicable
Partition coefficient (n- 2289
octanol/water)
Viscosity Not applicable
Auto-ignition Temperature No data available
Decomposition Temperature No data available

Revision Date: October 1, 2015 Page 4 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

9. PHYSICAL AND CHEMICAL PROPERTIES

Upper explosive limit Not explosive


Lower explosive limit Not explosive
Flammability (solid, gas) Not flammable
Expellant - Nitrogen
Appearance
Physical State Compressed gas
Color Colorless
Odor None
Odor Threshold No data available
pH Not applicable
Specific Gravity 0.075 lb/ft3 @70oF as vapor
Boiling Range/Point (°C/F) -196oC/-321 oF
Melting Point (°C/F) No data available
Flash Point (PMCC) (°C/F) Not flammable
Vapor Pressure 838 psig @70oF and 1 atmosphere(Carbon Dioxide)
Evaporation Rate (BuAc=1) No data available
Solubility in Water No data available
Vapor Density (Air = 1) Not applicable
VOC (g/l) None
VOC (%) None
Partition coefficient (n- No data available
octanol/water)
Viscosity Not applicable
Auto-ignition Temperature No data available
Decomposition Temperature No data available
Upper explosive limit Not explosive
Lower explosive limit Not explosive
Flammability (solid, gas) Not flammable

10. STABILITY AND REACTIVITY

Reactivity
Decomposes on heating. Containers may rupture or explode if exposed to heat.

Chemical Stability
Stable under normal conditions.

Possibility of hazardous reactions


Hazardous polymerization will not occur.

Conditions to Avoid
Heat - High temperatures - Exposure to direct sunlight

Incompatible Materials
Powdered metals (ex. aluminum, zinc, etc.) - strong oxidizing agents – strong reducing agents – strong
alkalis

Hazardous Decomposition Products


Oxides of carbon – hydrogen halides – fluorocarbons – carbonyl halides

Revision Date: October 1, 2015 Page 5 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

11. TOXICOLOGICAL INFORMATION

Acute Toxicity
FM-200®
4 hour LC50(rat) >788,698 ppm
Low Observed Adverse Effect Concentration (LOAEC)/dog : 105000 ppm
Cardiac sensitization
No Observed Adverse Effect Concentration (NOAEC)/dog : 90000 ppm
Nitrogen
Simple asphyxiant

Specific Target Organ Toxicity (STOT) – single exposure


Nitrogen: Exposure to nitrogen gas at high concentrations can cause suffocation by reducing oxygen
available for breathing. Breathing very high concentrations can cause dizziness

Specific Target Organ Toxicity (STOT) – repeat exposure


No relevant studies identified.

Serious Eye damage/Irritation


Not expected to cause eye irritation based on review of properties of the substance.

Skin Corrosion/Irritation
Not expected to cause skin irritation based on review of properties of the substance.

Respiratory or Skin Sensitization


FM-200®: Not expected to cause skin sensitization based on review of properties of the substance. Did
not cause respiratory sensitization in laboratory animals.

Carcinogenicity
Not considered carcinogenic by NTP, IARC, and OSHA.

Germ Cell Mutagenicity


FM-200®: Animal testing and testing on bacterial or mammalian cell cultures did not show mutagenic
effects.

Reproductive Toxicity
FM-200®: Animal testing showed no reproductive toxicity. (Based on data obtained from similar
substances.) Animal testing showed no developmental toxicity.

Aspiration Hazard
Not an aspiration hazard.

Other
FM-200®: Cardiac sensitization threshold limit : 730190 mg/m3

12. ECOLOGICAL INFORMATION

Ecotoxicity
FM-200®
LC50 > 200 mg/l zebra fish 96h
EC50> 200 mg/l Water flea 48h

Revision Date: October 1, 2015 Page 6 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

12. ECOLOGICAL INFORMATION

Mobility in soil
No relevant studies identified.

Persistence/Degradability
Not readily biodegradable.

Bioaccumulative Potential
No relevant studies identified.

Other adverse effects


No relevant studies identified.

13. DISPOSAL CONSIDERATIONS

Disposal Methods
Dispose of container in accordance with all applicable local and national regulations. Do not cut
puncture or weld on or near to the container. If spilled, contents will vaporize to the atmosphere.

14. TRANSPORT INFORMATION

Safety Data Sheet information is intended to address a specific material and not various forms or states
of containment.

DOT CFR 172.101 Data Heptafluoropropane, 2.2, UN3296


UN Proper Shipping Name Heptafluoropropane
UN Class (2.2) Non-Flammable Gas
UN Number UN3296
UN Packaging Group Not applicable
Classification for AIR Consult current IATA Regulations prior to shipping by air.
Transportation (IATA)
Classification for Water Consult current IMDG Regulations prior to shipping by water.
Transport IMDG

This section is believed to be accurate at the time of preparation. It is not intended to be a complete
statement or summary of the applicable laws, rules, or hazardous material regulations, and is subject to
change. Users have the responsibility to confirm compliance with all laws, rules, and hazardous
material regulations in effect at the time of shipping.

15. REGULATORY INFORMATION

United States TSCA Inventory


All components of this product are in compliance with the inventory listing requirements of the US Toxic
Substance Control Act (TSCA) Chemical Substance Inventory.

Canada DSL Inventory


All ingredients in this product have been verified for inclusion on the Domestic Substance List (DSL).

SARA Title III Sect. 311/312 Categorization


Pressure Hazard

Revision Date: October 1, 2015 Page 7 of 8


SAFETY DATA SHEET
FM-200®
(Fire Extinguishing Agent with Expellant)

15. REGULATORY INFORMATION

SARA Title III Sect. 313


This product does not contain any chemicals listed in Section 313 at or above de minimis concentrations.

16. OTHER INFORMATION

NFPA Ratings
NFPA Code for Health - 1
NFPA Code for Flammability - 0
NFPA Code for Reactivity - 0
NFPA Code for Special Hazards – None
HMIS Ratings
HMIS Code for Health - 1
HMIS Code for Flammability - 0
HMIS Code for Physical Hazard - 0
HMIS Code for Personal Protection - See Section 8
*Chronic

Legend
ACGIH: American Conference of Governmental Industrial Hygienists
CAS: Chemical Abstracts Service
IARC: International Agency for Research on Cancer
N/A: Denotes no applicable information found or available
NTP: National Toxicology Program
OSHA: Occupational Safety and Health Administration
PEL: Permissible Exposure Limit
SDS: Safety Data Sheet
STEL: Short Term Exposure Limit
TLV: Threshold Limit Value

Information Source and References


This SDS is prepared by Hazard Communication Specialists based on information provided by internal
company references.

Revision Date:
Replaces: April 10, 2015
Changes made: Update to Section 14.

Prepared By: EnviroNet LLC.

FM-200 is a registered trademark of DuPont.

The information and recommendations presented in this SDS are based on sources believed to be
accurate. Kidde-Fenwal, Inc. assumes no liability for the accuracy or completeness of this information. It
is the user's responsibility to determine the suitability of the material for their particular purposes. In
particular, we make NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY,
EXPRESS OR IMPLIED, with respect to such information, and we assume no liability resulting from its
use. Users should ensure that any use or disposal of the material is in accordance with applicable
Federal, State, and local laws and regulations.

Revision Date: October 1, 2015 Page 8 of 8


Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
K-90-9030 Rev BA
Warning Nameplate (FM-200®)
FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant
• See Kidde® Manual 06-236225-001 for USCG Approval

P/N: 06-231865-739

10.000
0.063
0.340 9.360
0.340

WARNING
THIS AREA IS PROTECTED BY A
0.062
5.000
FM-200® EXTINGUISHING
4.360
SYSTEM. DO NOT ENTER WITHOUT
AUTHORIZATION DURING OR
AFTER DISCHARGE

0.281 .005 DIA. TYP. 4 HOLES

MATERIALS
• Aluminum Type 1100–H14, 0.032 ± 0.003 Thick. All Let-
ters to be 48 pt., Alternate Gothic #2, Etched 0.003 to
0.005 and Filled in With Red Chip Proof Enamel Color
No. 21105 per Fed. Stc. 595
• Finish: One Coat Clear Lacquer Both Sides

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
2/14/2017 GAQF.EX4674 ­ Clean­agent Extinguishing System Units

GAQF.EX4674
Clean­agent Extinguishing System Units
Page Bottom

Clean­agent Extinguishing System Units

See General Information for Clean­agent Extinguishing System Units

KIDDE­FENWAL INC EX4674
400 Main St
Ashland, MA 01721­2150 USA

PRE­ENGINEERED, Fenwal Modular Spherical, Pre­Engineered, Models 93­120250­001, 93­120251­001, 93­120253­001, 93­120351­001, 93­
120353­001, 93­110201­001, 93­110202­001, 93­110203­001, 93­110204­001, 96­110204­001, HFC­227ea Clean Agent Extinguishing System
Units, stored pressure type, having nominal charging capacities of 15, 30, 30, 30, 30, 44, 63, 101, 130 and 196 lbs., respectively. The units are
super­pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection
against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
Part No. 06­236117­001 dated October 2014.

Kidde ECS Series Pre­Engineered, Models 90­100010­001, 90­100011­001, 90­100020­001, 90­100021­001, 90­100040­001, 90­100041­001,
90­100070­001, 90­100071­001, 90­100121­001, 90­100125­001, 90­100200­101, 90­100201­101, 90­100201­001, 90­100200­001, 90­100350­
001, 90­100351­001, 90­100600­001, 90­100601­001 HFC­227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal
charging capacities of 10, 10, 20, 20, 40, 40, 70, 70, 125, 125, 200, 200, 200, 200, 350, 350, 500 and 500 lbs, respectively. The units are
super­pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection
against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
Part No. 06­236116­001 dated October 2014, and Manual Supplement for Placement Supervision Part No. 06­236116­002 dated November
2015.

Fenwal 9300 Modular Pre­Engineered, Models 93­100010­001, 93­100011­001, 93­100020­001, 93­100021­001, 93­100040­001, 93­100041­001,
93­100070­001, 93­100071­001, 93­100121­001, 93­100125­001, 93­100200­101, 93­100201­101, 93­100201­001, 93­100200­001, 93­100350­
001, 93­100351­001, 93­100600­001, 93­100601­001 HFC­227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal
charging capacities of 10, 10, 20, 20, 40, 40, 70, 70, 125, 125, 200, 200, 200, 200, 350, 350, 500 and 500 lbs, respectively. The units are
super­pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection
against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
Part No. 06­236088­001 dated October 2014, and Manual Supplement for Placement Supervision Part No. 06­236088­002 dated January 2016.

Kidde FE­13 Modular Pre­Engineered, Models 96­100065­001, 96­100112­001, HFC­23 Clean Agent Extinguishing System Units, stored pressure
type, having nominal charging capacities of 65, 112 lb of HFC­23 Clean Agent, respectively. The units have operating temperatures of ­40 F to
130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring
within an enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's
installation manual P/N 96­FE13MA­000 dated October 2002.

ENGINEERED UNITS, Kidde ECS Series Engineered, Models 90­100010­001, 90­100020­001, 90­100040­001, 90­100070­001, 90­100121­001,
90­100125­001, 90­100200­001, 90100201­001, 90­100350­001, 90­100351­001, 90­100600­001, 90­100601­001, 90100600­100, 90­100601­
100, 90­100900­001, 90­100901­001, HFC­227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging
capacities of 10, 20, 40, 70, 125, 125, 200, 200, 350, 350, 600, 600, 600, 600, 900, 900 lb of HFC­227ea Clean Agent, respectively. The units
are super­pressurized to 360 psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against
Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 06­236115­001 dated October 2014, and Manual Supplement for Placement Supervision Part No. 06­236115­003 dated November 2015.
These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Fenwal 9300 Series Engineered, Models 93­100010­001, 93­100020­001, 93­100040­001, 93­100070­001, 93­100121­001, 93­100125­001, 93­
100200­001, 93­100201­001, 93­100350­001, 93­100351­001, 93­100600­001, 93­100601­001, 93­100600­100, 93­100601­100, 93­100900­
001, 93­100901­001, HFC­227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 10, 20,
40, 70, 125, 125, 200, 200, 350, 350, 600, 600, 600, 600, 900, 900 lb of HFC­227ea Clean Agent, respectively. The units are super­pressurized
to 360 psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning,
Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 06­236081­001 dated October 2014 and Manual Supplement for Placement Supervision P/N 06­236081­003 dated January 2016. These
installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies are available from the above Listee.

Fenwal Sphere and Bottom Discharge Engineered, Models 93­120250­001, 93­120251­001, 93­120253­001, 93­120351­001, 93­120353­001, 93­
110201­001, 93­110202­001, 93­110203­001, 93­110204­001, 93­192041­001, 93­192041­002, 93­193040­001, 93­192040­002, 93­192042­
001, 93­192042­002, HFC­227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 15, 30,
http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=GAQF.EX4674&ccnshorttitle=Clean­agent+Extinguishing+System+Units… 1/3
2/14/2017 GAQF.EX4674 ­ Clean­agent Extinguishing System Units
30, 30, 30, 44, 63, 101, 196, 350, 350, 560, 560, 850, 850 lb of HFC­227ea Clean Agent, respectively. The units are super­pressurized to 360
psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B
flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 06­235879­001 dated October 2014. These installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies
are available from the above Listee.

Kidde ADS Series Engineered, Models 90­100225­001, 90­100221­001, 90­100395­001, 90­100391­001, 90­100675­001, 90­100671­001, 90­
101010­001, 90­101011­001 , HFC­227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 225, 225, 395, 395,
675, 675, 1010, 1010 lb of HFC­227ea Clean Agent, respectively. The units have operating temperatures of 32 F to 130 F. The units are
designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 06­236068­001 dated October 2014, and Manual Supplement for Placement Supervision Part No. 06­236068­003 dated November 2015.
These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Fenwal Phoenix Series Engineered, Models 93­100225­001, 93­100221­001, 93­100395­001, 93­100391­001, 93­100675­001, 93­100671­001,
93­101010­001, 93­101011­001 HFC­227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 225, 225, 395, 395
lb of HFC­227ea Clean Agent, respectively. The units have operating temperatures of 32 F to 130 F. The units are designed for total flooding
protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

The description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 06­236069­001 dated October 2014, and Manual Supplement for Placement Supervision Part No. 06­236069­003 dated January 2016. These
Installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies are available from the above Listee.

Engineered Clean Agent Extinguishing System Units containing HFC­227ea, stored pressure type utilizing IS 7285 cylinders, having nominal
storage capacities of 34, 80, 120, and 140 L HFC­227ea. The units are super­pressurized with dry nitrogen to 360 psig (24.8 bar) at 70°F
(21°C) with operating temperatures of 0°F to 130°F (­18°C to 55°C). The units are designed for total flooding protection against Class A
surface burning, Class B flammable liquid and Class C fires occurring within an enclosure. A description of these extinguishing system units and
the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 06­237298­
001, revised August 2014, and Manual Supplement for Placement Supervision P/N 06­237298­002 dated January 2016. These installations
require the use of the Listee's Design and Flow Calculation Software, KID Version 4.00. Copies are available from the above Listee.

Kidde FE­13 Engineered, Models 96­100065­001, 96­100112­001, HFC­23 Clean Agent Extinguishing System Units, stored pressure type, having
nominal charging capacities of 65, 112 lb of HFC­23 Clean Agent, respectively. The units have operating temperatures of ­40 F to 130 F. The
units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an
enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation
manual P/N 96­FE13MA­002 dated October 2002, and Manual Supplement for Placement Supervision Part No. 06­236169­003 dated November
2015. These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Kidde Novec™ 1230™ Engineered Series, Models 45­100010­001, 45­100020­001, 45­100040­001, 45­100070­001, 45­100121­001, 45­100125­
001, 45­100200­001, 45­100201­001, 45­100350­001, 45­100351­001, 45­100600­001, 45­100601­001, 45­100900­001, 45­100901­001 Clean
Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 350, 350,
600, 600, 900, 900 lb of Novec™ 1230™ Clean Agent, respectively. The units are super­pressurized to 360 psig with operating temperatures of
0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires
occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation,
Operation and Maintenance Manual, P/N 45­N1230M­001, dated August 2005, Manual Supplement for Nitrogen Pilot Bracket P/N 06­236553­002,
dated January 2013, and Manual Supplement for Placement Supervision P/N 06­236553­004 dated November 2015. These installations require
the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* (reference the User's Manual for Kidde Novec 1230 Design and
Flow Calculation Software, P/N 45­N1230M­100, dated March 2006) or Version 4.0 (reference the User's Manual for Kidde Novec 1230 Design
and Flow Calculation Software, P/N 06­237379­001, dated July 2015). Copies are available from the above Listee.

Kidde Novec™ 1230™ Engineered Series (EU Compliant), Models 45­990010­001, 45­990020­001, 45­990040­001, 45­990070­001, 45­990121­
001, 45­990125­001, 45­990200­001, 45­990201­001, 45­990350­001, 45­990351­001, 45­990600­001, 45­990601­001, 45­990900­001, 45­
990901­001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10 (4.5), 20 (9.1), 40 (18.1),
70 (31.7), 125 (56.7), 125 (56.7), 200 (90.7), 200 (90.7), 350 (158.8), 350 (158.8), 600 (272.1), 600 (272.1), 900 (408.2), 900 (408.2) lb
(kg) of Novec™ 1230™ Clean Agent, respectively. The units are super­pressurized to 360 psig with operating temperatures of 0°F to 130°F. The
units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an
enclosure. A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design,
Installation, Operation and Maintenance Manual, P/N 45­N1230M­001 (alternate P/N 06­236553­001), dated August 2005, Manual Supplement
for Nitrogen Pilot Bracket P/N 06­236553­002, dated January 2013, and Manual Supplement for Placement Supervision P/N 06­236553­004
dated November 2015. These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* (reference the
User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 45­N1230M­100, dated March 2006). Copies are available from
the above Listee.

Fenwal Novec™ 1230™ Engineered Series, Models 44­100010­001, 44­100020­001, 44­100040­001, 44­100070­001, 44­100121­001, 44­
100125­001, 44­100200­001, 44­100201­001, 44­100350­001, 44­100351­001, 44­100600­001, 44­100601­001, 44­100900­001, 44­100901­001
Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 350,
350, 600, 600, 900, 900 lb of Novec™ 1230™ Clean Agent, respectively. The units are super­pressurized to 360 psig with operating
temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and
Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation,
Operation and Maintenance Manual, P/N 44­NV1230­001 (alternate P/N 06­236554­001), September 2014, Manual Supplement for Nitrogen
Pilot Bracket P/N 06­236554­003, dated January 2013, and Manual Supplement for Placement Supervision P/N 06­236554­004 dated December
2015. These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* (reference the User's Manual for
Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44­NV1230­100, February 2005). Copies are available from the above Listee.

Fenwal Novec™ 1230™ Sphere and Bottom Discharge Engineered Series, Models 44­120250­001, 44­120251­001, 44­110201­001, 44­110202­
001, 44­110203­001, 44­110204­001, 44­192041­001, 44­192041­002, 44­193040­001, 93­192040­002, 44­192042­001, 44­192042­002, Clean
Agent Extinguishing System Units, stored pressure type , having nominal charging capacities of 15, 30, 44, 63, 101, 196, 350, 350, 560, 560,

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=GAQF.EX4674&ccnshorttitle=Clean­agent+Extinguishing+System+Units… 2/3
2/14/2017 GAQF.EX4674 ­ Clean­agent Extinguishing System Units
850, 850 lb of Novec™ 1230™ Clean Agent, respectively. The units are super­pressurized to 360 psig with operating temperatures of 0°F to
130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring
within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation,
Operation and Maintenance Manual, P/N 44­NV1230­001 (alternate P/N 06­236554­001), September 2014, Manual Supplement for Nitrogen
Pilot Bracket P/N 06­236554­003, dated January 2013, and Manual Supplement for Placement Supervision Part No. 06­236554­004 dated
December 2015. These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* (reference User's
Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44­NV1230­100, February 2005). Copies are available from the
above Listee.

Engineered Clean Agent Extinguishing System Units containing 3MTM NovecTM 1230 Fire Protection Fluid (FK­5­1­12), stored pressure type
utilizing IS 7285 cylinders, having nominal storage capacities of 34, 80, 120 and 140 L of NovecTM 1230 Fluid (FK­5­1­12). The units are super­
pressurized with dry nitrogen to 360 psig (24.8 bar) at 70°F (21°C) with operating temperatures of 0°F to 130°F (­18°C to 55°C). The units are
designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation,
Operation and Maintenance Manual, P/N 45­N1230M­600 (alternate P/N 06­237127­600), revised August 2013, and Manual Supplementfor
Placement Supervision P/N 06­237127­601 dated January 2016. These installations require the use of the Listee's Design and Flow Calculation
Software, Version 1.0.X* (reference User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44­NV1230­100, February
2005). Copies are available from the above Listee.

Kidde ADS Series Engineered, Models 45­500201­001, 45­500351­001, 45­500601­001, and 45­500901­001 clean agent extinguishing system
units, having nominal charging capacities of 200, 350, 600, and 900 lbs 3M™ Novec™ 1230 Fire Protection Fluid (FK 5­1­12), respectively. The
units are super­pressurized to 360 psig (25 bar) at 70°F (21°C) with operating temperatures of 32°F to 130°F (0°C to 54°C). The units are
designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's Installation Manual
Part No. 06­237256­001 dated July 2014, Manual Supplement for Placement Supervision Part No. 06­237256­005 dated November 2015. These
installations require the use of the Listee's flow calculation software ADS Version 4.0 (reference flow calculation manual Part No. 06­237256­
004 dated July 2014). Copies of the software and manuals may be obtained from the above Listee.

* Numeric version code, where X may be 0­9.

Last Updated on 2016­06­03

Questions? Print this page Terms of Use Page Top

© 2017 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=GAQF.EX4674&ccnshorttitle=Clean­agent+Extinguishing+System+Units… 3/3
Clean Agent Fire Extinguishing Systems
These systems contain electrically nonconducting, volatile, or gaseous fire extinguishing agents that don't leave a residue upon
evaporation (per NFPA 2001 paragraph 1-3.1). They are effective for total flooding protection against hazards involving liquid
flammable materials, electrical equipment, and ordinary solid combustibles in occupancy arrangements which produce only surface
burning. In general, these agents are not effective or appropriate for hazards which produce deep-seated burning or for those which
involve chemicals containing their own oxygen (such as cellulose nitrate), metal hydrides, or reactive metals (such as sodium,
magnesium or uranium).
Clean Agent systems are similar in many respects to Halon 1301 and carbon dioxide systems. Discharge of the agent by total flooding
or local application may create atmospheric hazards to personnel. Toxic thermal decomposition products can be minimized by fast fire
detection coupled with rapid agent discharge. Personnel should not remain in the area following system discharge. Table A-1-5.1.1 of
NFPA 2001 provides information on toxicological and physiological effects covered in this equipment classification. The No Observed
Adverse Effect Level (NOAEL) is the highest concentration at which no adverse physiological or toxicological effect has been
observed. The Lowest Observed Adverse Effect Level (LOAEL) is the lowest concentration at which an adverse physiological or
toxicological effect has been observed.
Systems can only be FM Approved under this classification if they use agents having a component Approval. The system Approvals
specifically reference the relevant agent Approval. Individual agent listings appear under the category Clean Extinguishing Agents.
Compatible FM Approvals controls must be used. (See AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER
FIRE PROTECTION EQUIPMENT under ELECTRICAL SIGNALING.)
Application of this equipment should be subject to the limitations specified and subject to FM Global's acceptance of plans prior to
installation. Required design concentrations vary from agent to agent and depending upon maximum design parameters, the
concentration may vary among system manufacturers. The design concentrations listed by the system manufacturers are generally
accepted in electrical/electronic hazards, i.e. computer, telecommunication areas, provided that Class A ordinary combustibles are
kept to a minimum, thereby minimizing the potential for a deep seated Class A fire.
System charging and recharging shall be done only by the manufacturer or a FM Approved representative.
The Clean Agent systems FM Approved under this classification have been addressed by NFPA 2001, Standard on Clean Agent
Extinguishing Systems, 1994 Edition and must be listed in the United States Environmental Protection Agency (EPA) Significant New
Alternatives Policy (SNAP) as an acceptable substitute to Halon 1301.
Jurisdictions outside the United States may not recognize NFPA and EPA sanction of certain clean agents. Local and national
governmental regulations should be consulted prior to agent selection.
*Alternative to Halon 1211 and Halon 1301.

Kidde Fire Systems® ECS Fire Suppression System with HFC-227ea Agent

System Designation: Kidde Fire Systems® ECS Fire Suppression System with
HFC-227ea Agent

System Type: Engineered, Unbalanced Systems Designed for Total Flooding


Applications

Agent Identification: HFC-227ea

Minimum and Maximum Agent Storage Temperatures: Balanced System: 32 to 130ºF (0 to 54ºC)
Unbalanced System: 60 to 80 ºF (16 to 27ºC)

Types of Nozzles Available: 180°, 360°

Minimum and Maximum Nozzle Heights: 1 to 16 feet (0.3 to 4.9 meters)

Maximum Area of Coverage for Nozzle Type: 180°: 44 x 40 ft. (13.3 x 12 m), 48.3 ft (14.7 m) maximum
discharge radius

360°: 44 x 40 ft. (13.3 x 12 m), 29.7 ft. (9.1 m) maximum


discharge radius

Minimum Design Concentrations for Hazard Class: Class A: 6.25%


Class B: 8.7% (and per table in DIOM)

Flow Calculation Software: Kidde Fire Systems® Clean Agent Flow Calculation Program,
Version 4.00

© 2007-2017 FM Approvals. All rights reserved. 1 of 3


Design, Installation, Operation, and Maintenance Manuals: Kidde Fire Systems® ECS Fire Suppression System with
HFC-227ea Agent: Design, Installation, Operation and
Maintenance Manual, P/N 06-236115-001, October 2014

Kidde Fire Systems® ECS Fire Suppression System Flow


Calculation Software User’s Guide for use with FM-200®
Agent, Applies to Software Version 4B, part number
06-236272-001, Rev. AD, March 2013

Supplement to Kidde Fire Systems® ECS Fire Suppression


System with HFC-227ea Agent: Design, Installation,
Operation, and Maintenance Manual Rev BA, 06-236115-001,
Placement Supervision 06-236115-003, Rev. AB, July 2016

Supplement to Kidde Fire Systems® ECS Fire Suppression


System with HFC-227ea Agent: Design, Installation,
Operation, and Maintenance Manual Rev BA, 06-236115-001,
Stainless Steel Nozzles 06-236115-004 Rev. AA May 2016

Limitations or Exceptions to Approval: As described in the system manuals

Approved Filling Stations: Kidde-Fenwal, Inc.


400 Main Street
Ashland, MA 01721

Healey Fire Protection, Inc.


134 Northpoint Dr.
Orion, MI 48359
United States

Control Fire Systems, Ltd


Building A
63 Advance Road
Toronto, Ontario M8Z 2S6
Canada

Onity Industrial,S.A. de C.V.


Prolongacion Galeana No. 52
Col. Miguel Hidalgo
Tlalnepantla, Edo De Mexico
CP 54060
Mexico

UTC Fire & Security Singapore Pte. Ltd.


28 Teban Gardens Crescent
Singapore 608926

Kidde Brasil Ltda


Rua Irecema Lucas 755
Distrito Industrial
13.280-00
Vinhedo SP
Brazil

Company Name: Kidde-Fenwal Inc


Company Address: 400 Main St, Ashland, Massachusetts 01721, USA
Company Website: http://www.kidde-fenwal.com
New/Updated Product Listing: No
Listing Country: United States of America
Agent Type: HFC-227
Certification Type: FM Approved

© 2007-2017 FM Approvals. All rights reserved. 2 of 3


© 2007-2017 FM Approvals. All rights reserved. 3 of 3