Documente Academic
Documente Profesional
Documente Cultură
1.1.1 Protection coordination shall be designed to achieve sensitivity, speed, selectivity and
reliability to isolate faults from the rest of the healthy system and minimize the plant
loss due to the faults under all foreseen system operation condition.
earth fault protection of solidly earthed systems: and definite time schemes for
earth fault protection of resistance earthed systems.
When set as recommend, the protection schemes achieve discrimination and provide
satisfactory clearance times of phase and earth faults within the range of fault
currents available in the system
2.1.1 Fault clearance time shall be estimated as relay time plus switching device opening time.
Average opening times of circuit breakers have been taken as:
2.1.2 The grading time comprises of the following component times as recommended in Ref.
11:
tS (Safety margin in ms 30 ms 30 ms
Total grading time 230 ms 170 ms
Hence the minimum grading interval between inverse time and definite time relays
shall be at 0.25 s.
FORMT9-P REV-B (MUM)
2.1.3 The operating time of a fuse is a function of both the pre-arcing and arcing time of the
fusing element, which follows the I2t law. To achieve proper co-ordination between
two fuses in series, it is necessary to ensure that the to I 2t taken by the smaller fuse is
not greater than the pre-arcing I2t value of the larger fuse. It has been established by
tests that satisfactory grading between the two fuses will generally be achieved if the
current rating ratio between them is greater than two ( Ref. 10).
The minimum grading interval t” between inverse time relays and fuses shall be set in
accordance with the formula ( Ref.10);
When grading inverse time relays with fuses, it should be ensured that the relay backs
up the fuse and not vice versa, since it is very difficult to maintain correct
discrimination at high values of fault current because of the fast operation of the fuse.
The relay characteristic best suited for co-ordination with fuses is normally that of the
extremely inverse relay, which follows a similar I2t characteristic. For satisfactory co-
ordination between the relay and the fuse, the primary current setting of the relay
should be approximately three times the current rating of the fuse ( Ref.10).
2.1.4 Switchboards have short time current withstand rating of 1 second. No short circuit
protection settings are therefore allowed to exceed Is.
2.1.5 Protection discrimination and operational sensitivity shall be established for the maximum
and minimum three phase fault current as shown in the Power System Study Report.
The minimum three phase fault currents are generally based upon the least number of
generators and a transformer outage, and excludes the short-circuit current
contribution from motors.
Where the fault is electrically close to a generator or motors, the three phase fault
current value will follow the a.c. decrement curve. Generally, when remote from
generators or motors, the three-phase fault current shall be based on the initial
symmetrical current (Ik”).
2.1.6 Based on the transformer data sheets furnished by the manufacturers, the transformer
inrush current shall be considered as follows:
33/6.9 kV and 33/11.5 kV transformers: 8 times full load current for 0.2s.
b) The 6.6 kV switchgear and the 415V PCCs are provided with ‘Reverse Interlock’
between the outgoing feeders and the incomers. The contacts of the
overcurrent protection provided on the outgoing feeders are used to block the
operation of the high set overcurrent protection provided on the incomers. This
allows the high-set overcurrent protection on the incomers to be set with time
grading of 50 ms to provide fast busbar protection. The high-set overcurrent on
the incomers and the instantaneous overcurrent on the outgoing feeders are set
for the same pick up level at minimum150% of transformer rated current.
c) The 6.6 kV switchgear and the 415V PCCs are provided with ‘Reverse Interlock’
between the bus coupler and the incomers. The contacts of the IDMT
overcurrent and earth fault protections provided on the bus coupler are used to
block the operation of IDMT overcurrent and earth fault protection provided on
the incomers. This allows the IDMT overcurrent and earth fault protection on the
incomers to be set with the same time delay as that on the bus coupler.
e) Short circuit protection of the transformer should ensure that a through fault short
circuit current based upon the transformer impedance is cleared within 2
seconds ( Ref. 13)
2.1.8 The 33 kV and 415V systems are solidly earthed. Discrimination shall be provided for
earth fault protection between incomer and outgoing feeders.
2.1.9 The 6.6 kV system is resistance earthed with the earth fault current limited to 250A.
Discrimination shall be provided for earth fault protection between incomer and
outgoing feeders.
FORMT9-P REV-B (MUM)
Under voltage protection shall be set to distinguish between normal transient under
voltage occurring due to the motor starting or load additions, and the severe under
voltage associated with system fault conditions. Transient voltage dips to 80% of
nominal voltage will be regarded as normal and values below 80% as abnormal.
Motors shall be tripped on abnormal under voltage in order to protect the motor from
the transient torques that occur when the voltage is depressed and restored in rapid
succession.
The undervoltage setting shall also be selected to ensure that the motor does not stall
due to load torque requirement exceeding the motor pullout torque while operating at
reduced voltages.
Voltage : 75% of nominal voltage ( set below the minimum normal voltage limit of
80%)
Time: 0.8s (set above the operating time of the incomer/outgoing feeder overcurrent
and earth fault protections, thus preventing nuisance tripping of the motor feeders
under temporary undervoltage conditions due to fault elsewhere in the electrical
system). Overcurrent and undervoltage protection should be checked for
coordination.
For non-motor feeders, the intention will be to trip only when a complete failure of the
system has occurred. Hence, no undervoltage tripping is provided for these feeders.
3.3.0 Incomers
The undervoltage protection for the switchboard incomers is related to the operation
of the switchboard auto-change over scheme. Refer to Section 5.3.11 below for
details of setting the under voltage protections for incomers.
ACO schemes are provided for 6.6 kV and 415V systems. This enables automatic
closing of the bus coupler circuit breaker on loss of normal supply to any of the bus
sections. The following conditions shall be fulfilled before the ACO scheme issues
closing command to the bus coupler Circuit Breaker:
All outgoing motor feeders connected to the de-energised bus are tripped on
undervoltage. This will prevent simultaneous restarting of these motors on
FORMT9-P REV-B (MUM)
ACO schemes shall be blocked by high set over current and earth fault protection
when there is a bus fault. In addition, the overcurrent protection on the HV side of the
incomer transformer shall be graded with the incomer overcurrent protection to ensure
that the upstream relay does not clear a switchboard bus fault before the incomer
protection operates and inhibits the ACO scheme.
Undervoltage protection for the bus section shall be set at 20% nominal voltage
with no time delay to indicate “dead bus” conditions, permitting operation of the
ACO scheme.
The total operation time of the ACO scheme at 6.6 kV switchboards shall be
0.9s (Incomer under voltage protection time delay) + 0.6S (Incomer CB opening
time) + 0.06S (Bus coupler CB closing time) = 1.02s.
The ACO scheme for the 415V Switchboards shall be time-delayed to take
place only if the operation of the ACO scheme at the upstream 6.6 kV
switchboards has not occurred.
Undervoltage protection for the incomer feeder shall be set at 75% of the
nominal voltage with 1.2s time delay (graded with the time delay settings of the
upstream 6.6 kV switchboard ACO switchboard scheme).
Undervoltage protection for the incomer feeder shall be set at 20% of the
nominal voltage with no time delay to indicate “dead bus” conditions, permitting
operation of the ACO scheme.
FORMT9-P REV-B (MUM)
The total operation time of the ACO scheme at 415V switchboards shall be 1.2s
(Incomer undervoltage protection time delay) + 0.05s (Incomer CB opening
time) +0.05s (Bus coupler CB closing time) = 1.3s.
The check synchronizing function is provided for 6.6 kV switchgear and 415V PCC as
part of the individual incomer and bus coupler protection relays. The check
synchronizing function permits closing of the associated circuit breaker under the
following conditions:
For incomer/bus coupler circuit breakers, the closing of the circuit breaker is
permitted if voltages on both sides of the circuit breaker are within the limits of
synchronization.
Closing of incomer circuit breaker is permitted in case the incomer voltage is
‘Live’ (i.e. greater than 80%) and the associated bus section voltage is “Dead”
(less than 20%).
Closing of bus section circuit breaker is permitted in case one bus section
voltage is ‘Live’ (i.e. greater than 80% and the other bus section voltage is
‘Dead’ (less than 20%).
The following settings are selected in the voltage and synchro-check functions:
Dead –Bus /Live-Line (to permit manual Live-Bus/Dead-Line (to permit ACO
closing of CB operation when incomer is operation or manual closing of CB when
‘Live’ and associated bus is ‘Dead’ Bus-A is ‘Live’ and Bus-B is ‘Dead’
in Ref. 14, which for utilization category AC-3 (squirrel case induction motors started
DOL) is minimum 8 times rated operational current.
(a) Highset instantaneous overcurrent for reverse interlocking scheme shall be set at
150% of transformer rated current with definite time delay of 50 ms as stated in
Section 5.3.7(b).
(b) The incomer IDMT overcurrent and definite time earth fault protection settings
shall be kept same as the settings for the bus coupler protection as explained
in Section 5.3.7(c) above. These protections shall coordinate with the over
current and the earth fault protection of the outgoing feeders, to provide backup
protection to the outgoing feeders.
(c) It shall be ensured that the over current protection does not operate during the
starting of the largest connected motor with the maximum possible standing
load.
(d) The earth fault protection shall be definite-time type, set at 180A and graded with
the outgoing feeders to provide backup protection to the outgoing feeders.
(e) Standby earth fault protection shall be definite-time type, set at 200A and graded
with the incomer earth fault protection shall trip the circuit breakers on both 33
kV and 6.6 kV sides of the transformer.
(a) The bus coupler IDMT overcurrent and definite time earth fault protection shall
coordinate with the over current and the earth fault protections of the outgoing
feeders, to provide backup protection to the outgoing feeders.
(b) It shall be ensured that the overcurrent protection does not operate during the
starting of the largest connector motor.
(c) The instantaneous overcurrent protection on the bus coupler shall be blocked
from use.
In certain units, a satellite substation is fed from a main substation through a tie
feeder.
(a) IDMT overcurrent and definite-time earth fault protection is provided for the Tie
feeders. If required, high-set definite-time overcurrent shall be used to
supplement the IDMT overcurrent protection, while ensuring proper
coordination with all downstream protections. This protection shall be graded
with the outgoing feeders of the satellite station.
FORMT9-P REV-B (MUM)
(b) Wherever the tie feeder from Main Substation feeds a 6.6 kV Switchboard with
ACO facility, the overcurrent and earth fault protection at the main substation
end of the tie feeder shall be graded with the protection at the satellite
substation end.
(c) The IDMT overcurrent pickup shall also be used in the reverse interlocking
scheme to block the high set instantaneous overcurrent protection on the
incomer as described in Section 5.3.7(b).
(a) Overcurrent pickup setting shall be set to pick up at 125% FLC for use in the
reverse interlocking scheme (Refer to Section 5.3.7 (b) for details).
(b) Short circuit protection shall be set at 1.25 times of the maximum possible locked-
rotor current with a time delay of 0.1 seconds to avoid nuisance tripping during
motor start.
(c) Thermal overload protection shall be set at 100% FLC and shall be coordinated
with motor locked-rotor time, starting characteristics and thermal withstand
curves.
(d) IDMT negative phase sequence protection shall be set as per the I 22t value
indicated by the motor manufacturer. In case this is not available I 22t= 20 as
indicated in IEC 60034 shall be used as the basis for the relay setting.
For motors with run-up time not exceeding the ‘hot’ locked rotor withstand time,
both Prolonged Start protection and Locked Rotor protection are provided
through inverse-time overcurrent characteristic. The current settling shall be
250% FLC and time setting shall not exceed the ‘hot’ locked rotor withstand
time or the maximum allowable run-up time (whichever is lower). Unless
specified by vendor, the motor run-up plus 15% margin shall be used.
For motors with run-up time exceeding the ‘hot’ locked rotor withstand time, the
prolonged Start protection is provided through inverse-time overcurrent
characteristic. The current settling shall be 250% FLC and time setting shall not
exceed the maximum allowable run-up time. Unless specified by the vendor,
the motor run-up-time plus 15% margin shall be used. The locked Rotor
protection is provided through a separate definite-time overcurrent
characteristic. The current setting shall be 250% FLC and time setting shall
generally not exceed 85% of the ‘hot’ locked rotor withstand time. The
operation of the locked Rotor protection is inhibited once the motor starting
condition is verified (through speed-switch contacts wired to one of the digital
inputs of the motor protection relay).
FORMT9-P REV-B (MUM)
(f) Sensitive earth fault protection is energised by 50/1A CBCT. The earth fault
protection shall be set at 2% (1A) with time delay of 0.1s. For motors with long
feeder cables, a reasonable upper margin of 1.5 – 2 times charging current
shall be taken into consideration.
(g) Other motor protection settings shall be set in accordance with recommendation
by motor manufacturer.
The protection shall be instantaneous and the pick up value shall be arrived at
by considering the conditions listed below. The higher of the two current
values, thus arrived, shall be set as pick up.
12 times the transformer full load current (to account for the inrush current)
1.5 times the through fault current reflected on the 6.6 kV side, for a fault on
the LV side of the transformer
The protection will act as a backup to the protection provided on the L.V side
Incomer. It will also act as the primary protection for the circuit between the
transformer 6.6 kV terminals and the LV incomer breaker. It shall be set to
1.1 times the transformer FLC and coordinated with the protection setting
characteristics provided on the LV side incomer.
The IDMT overcurrent pickup shall also be used in the reverse interlocking
scheme ( Refer to Section 5.3.7 (b) for details).
(a) Highset instantaneous overcurrent for reverse interlocking shall be set at 150% of
transformer rated current with definite time delay of 50ms as stated in Section
5.4.7(b).
(b) The incomer IDMT overcurrent and earth fault protection settings shall be kept
same as the settings for the bus coupler protection as explained in Section
5.3.7(c). These protections shall coordinate with the over current and the earth
fault protection of the outgoing feeders, to provide backup protection to the
outgoing feeders.
(c) It shall be ensured that the over current protection does not operate during the
starting of the largest connected motor with the maeimum possible standing
load.
(d) The earth fault protection shall be IDMT type, set at 20% and graded with the
incomer earth fault protection. This protection shall trip the circuit breakers on
both 6.6 kV and 415V sides of the transformer.
(a) The buscoupler IDMT overcurrent and earth fault protection shall coordinate with
the over current and the earth fault protection of the outgoing feeders, to
provide backup protection to the outgoing feeders.
(b) It shall be ensured that the overcurrent protection does not operate during the
starting of the largest connected motor.
(c) The instantaneous overcurrent protection on the buscoupler shall be blocked form
use.
The IDMT protection shall be coordinated with the largest downstream fuse. To
have a proper coordination with the fuse, an extremely inverse characteristic
shall be adopted. The two characteristics combine to give a very effective
protection.
(b) Since the PMCC is provided with ACO scheme, the overcurrent and earth fault
protection for the tie feeder at the PCC end shall be graded with the protection
at the PMCC incomer.
(c) The IDMT overcurrent pickup shall also be used in the reverse interlocking
scheme to block the high set instantaneous overcurrent protection on the
FORMT9-P REV-B (MUM)
In the case of fused contactor feeders, any fault currents in excess of the
contactor’s breaking capability are cleared by the fuse (Refer to section 5.3.13
for details).
Overload protection shall set at 100% of FLC and shall be coordinated with
motor locked-rotor time, starting characteristics and thermal withstand curves.
(c) Negative phase sequence with IDMT protection shall be set as per the I22t value
indicated by the motor manufacturer. In case this is not available I 22t=20 as
indicated in IEC 60034 shall be used as the basis for the relay setting.
(e) Where required (e.g. motors for fin fan coolers), under current protection shall
be provided set at 40% of FLC with time delay of 10s.
(a) Highset instantaneous overcurrent for reverse interlocking shall be set at 150% of
transformer rated current with definite time delay of 50 ms as stated in Section
5.3.7(b).
(b) The incomer IDMT overcurrent and earth fault protection settings shall be kept
same as the settings for the bus coupler protection as explained in Section
5.3.7(c) above. These protections shall coordinate with the over current and
the earth fault protection on the outgoing feeders, to provide backup protection
to the outgoing feeders.
(c) It shall be ensured that the over current protection does not operate during the
starting of the largest motor with the maximum possible standing load.
(d) The earth fault protection shall be IDMT type, set at 20% and graded with the
outgoing feeder to provide backup protection to the outgoing feeders.
(e) As stated in Section 5.4.8(b), an attempt shall be made to grade the incomer
IDMT overcurrent and earth fault protection with the protection on the upstream
PCC feeder.
These protections shall coordinate with the over current and the earth fault
protection on outgoing feeders, to provide back up protection to the outgoing
feeders.
Earth fault protection shall be definite-time type, set at 10% of maximum earth fault
current (25A) with time delay of 0.1s.
The protection settings shall be similar to the philosophy described in Section 5.4.4.
However, the following shall be taken into account while deciding the protection
settings.
(a) The undervoltage protection setting for 11 kV induction motor shall be coordinated
with the minimum possible voltage that can occur at the 11 kV switchgear
terminals during satisfactory motor starting.
(c) The tripping delay for undervoltage protection of synchronous motors shall be
coordinated with the out-of-step protection.
(d) Motor generator sets shall be provided with neutral overvoltage protection, in the
form of an over voltage relay connected to the Neutral Grounding Transformer
terminals. This protection shall be set at 10% with time delay of 0.1s.
FORMT9-P REV-B (MUM)