Table of Contents

1. INTRODUCTION .................................................................................................................................3

2. SCOPE AND PURPOSE OF STUDY....................................................................................................3

3. BASIS AND ASSUMPTIONS ...........................................................................................................3

4. OBJECTIVE OF RELAY CO-ORDINATION .........................................................................................4

5. RECOMMENDATIONS / OBSERVATIONS .........................................................................................5

6. EXCLUSION........................................................................................................................................5

7. ANNEXURES.......................................................................................................................................5
1. INTRODUCTION

This report depicts the result of Protection, Relay Settings & Co-ordination Study for 250 TPD
Caustic Expansion Plant – GRCD- Ganjam.

2. SCOPE AND PURPOSE OF STUDY


This document provides coordinated time and current settings of the relays for Over Current
(OC) and Earth Fault (EF) protection. The settings proposed in this document are obtained
from the protection coordination study done in STAR module of Electrical Transient Analyser
Program (ETAP), version 12.6.0.
Presently, the power supply to GRCD-Ganjam Plant is received at 132kV level at incoming
terminals of 31.25MVA (132/ 11kV) Schnieder make transformer (Single Bay system).
M/s GRCD is in the process of installing one more 31.25MVA (132/11kV) EMCO make
transformer in parallel with Schnieder make transformer.
The protective relay settings for the existing Feeder are adopted considering parallel operation
(later) of the main incoming transformers at 11kV level.

Settings for following feeders are not included in the present protection study. Same shall be
separately issued after receipt of available data is available from GRCD.
a. Protective relay settings for 420kW HT motor Feeder for Cl2 Liquefaction
- Motor characteristic/ performance curves and parameters are not available.
b. Protective relay settings for 250kW LT motor feeder for Cl2 Compressor
- Motor characteristic/ performance curves and parameters are not available.

3. BASIS AND ASSUMPTIONS

The following documents / information form the basis of this study:-


3.1 The complete power system is designed for maximum earth fault current of 1000A based on
NGR rating of EMCO transformer. It is not possible to provide sensible earth fault setting to suit
400Amp rated NGR (Schneider Make transformer NGR). Since additional hardware needs to
be installed in all existing outgoing feeders, which is difficult and expensive, it is strongly
recommended to replace the currently installed 400Amp NGR with the original 1000 Amp
rated NGR. Hence, the adopted earth fault settings are based on 1000 Amp earth fault current
to have proper coordination with the existing system.

3.2 The settings are done as per available information from GRCD, due to non-availability of
information related to type / model no. of relays to be used for new switchgears (11kV
expansion and New 415V MCC), report is prepared with standard type of relays available in
the ETAP library, GRCD to validate the same for new switchgears.

3.3 Relay models are available in the standard library of ETAP and the same are used for plotting
the TCC curves, wherever existing relay model numbers are not available in ETAP closest
possible relay model is used in calculation.

3.4 The protection functions which do not need coordination are not included in the coordination
study. These relays are shown separately in the setting chart.
3.5 The studies are carried out on the based on the following:
 Key Single Line diagram (Doc Id: 0192-ELT-00-FA-0001)
 Loading details of existing PMCC- received from GRCD email dtd. 24.09.16
 Protection functions as defined by the Single Line Diagrams
 Relay coordination report of existing 150TPD plant
 OPTCL study report for max SC level and max E/F current
3.6 Guidelines for protective relay coordination outlined in IEC, IEEE Buff book (IEEE Std.242,
Recommended Practice for Protection and Coordination of Industrial and Commercial Power
Systems) and IEEE Red book (IEEE Std. 141, Recommended Practice for Electric Power
Distribution for Industrial Plants) and general engineering practices are largely followed.

4. OBJECTIVE OF RELAY CO-ORDINATION

The basis for relay co-ordination is as follows:

a) Sensitivity of relay during a fault, so as to rapidly isolate the faulted section of the power
system with no or minimum damage to equipment.

b) Discrimination between relays and selective tripping, thereby providing minimum


disruption and continuity of supply in the un-faulted section.

c) Settings of relays are provided such that spurious tripping of feeders are avoided.

d) Fault clearing times are less than the withstand time of the equipment.

e) These settings are based on our experience in the chloro - alkali plants. These settings
are adopted considering the minimum earth fault current available in the system.

f) In case of any non-co-ordinated tripping, the tripping shall be analysed and the setting
shall be reviewed for further modification if required.

While the best efforts are made to meet the above objective, with the limitation on data
available for Relays, Earth fault current and CT ratios, the protection grading for feeder 14F2
in PMCC-121 ACB with SR18G releases (used to fed New MCC -122) could not achieved.

With the proposed settings the sending end and receiving end ACBs shall trip simultaneously
in case of any fault downstream to receiving end ACB. However this no adverse effect on the
power system since the ACBs are in series and in same Substation.

The releases have inherent limitation to coordinate with the downstream relay. To achieve
proper coordination it is recommended to replace the existing release at feeder 14F2 in
PMCC-121 by seprate protection relay and associated CT.
5. RECOMMENDATIONS / OBSERVATIONS

5.1 It is recommended to operate 132/11kV (EMCO & Schneider make) transformers in


parallel only after implementing the following :-
a. Full busbar differential protection with feeder rearrangement is recommended.
Since the same is little difficult to implement, atleast partial differential protection
scheme shall be provided.

b. REF & standby ground fault protection shall be provided for both the transformers
(132/11kV).

c. Directional overcurrent as well as directional earth fault relays with dual


polarisation (i.e both current & voltage) shall be provided in both incoming feeders
at 11kV kiosk (existing incomers are not designed for parallel operation).

d. Difference in impedence values of the transformer shall be matched as close as


possible in order to have proper load sharing and to avoid circulating currents
within the transformer windings.

5.2 Schnieder make transformer NGR (400Amps) shall be replaced with 1000Amp rated
NGR, similar to EMCO make transformer NGR, failing which earth fault relays may not
operate during earth faults.

5.3 Replacement of existing release (SR18G) at feeder 14F2 in PMCC-121 by separate


protection relay and associated CT.

6. EXCLUSION

Protection Relay settings for the new Transformer to be operated in parallel with new
transformer.

7. ANNEXURES

Various star views are created to study the whole system in parts to have proper settings in relay
coordination. Following are the star views attached.
ANNEXURE-1:
Annexure 1.1: Star View >>MCC-122 to TR-112
Annexure 1.2: Star View >>SW12 to UPSTREAM
Annexure 1.3: Star View >>11kV INDOOR SWGR
Annexure 1.4: Star View >> 11kV OUTDOOR KIOSK
Annexure 1.5: Star View >> SW12 to OPTCL PARALLEL

The final relay setting shall be as per the following annexure.


ANNEXURE-2: Relay Setting Chart
AmpsX100PMCC-122
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K 1K TR-112_I/C_CB

PMCC-121BUSBI/CRelay-P Cable231-
500 ABBSPAJ140C(SPCJ4D29)C 500 3/C300
TRatio4500:5
IEC-NormalInverse ±
TR-112I/Crelay
300 Pickup=1.03(0.5- 300 I>
2.5xCTSec)TimeDial=0.31
3x=1.95s,5x=1.33s,8x=1.02sInst=4.
03(0.5-40xCTSec)TimeDelay=0.68s

100 PMCC-121BC-1Relay-P TR-112I/Crelay-P


3.15MVA
ABBSPAJ140C(SPCJ4D29)C 100 TR-112
TRatio4500:5 OC1
IEC-NormalInverse AREVAP121C
Pickup=0.94(0.5- c) TRatio200:1 Relay
±

2.5xCTSeTimeDial=0.23 I>TR-112SBEF
50 IEC-StandardInverse 50
3x=1.45s,5x=0.984s,8x=0Inst=3.758s Pickup=1.1(0.1-
.66(0.5- 25xCTSec)TimeDial=0.3
30 40xCTSec)TimeDelay=0.48s 3x=1.89s,5x=1.28s,8x=0.989sInst=10 30
.79(0.5-40xCTSec)TimeDelay=0.1s
Bu sDuct-TR-112
Lightingtrafofuse
L&THN(Size2)O 14F2RELEASE
10 ther0.415kV250 1250AwithSR18GRelease
±

10 I>PMCC-121BUSBI/CRel ay
OverloadPickup=1
Instantaneous=12at0.06
PMCC-122I/CRelay-
5 POC1 5
Seconds

AREVAP121CT S
Ratio1250:1 ∆0.487s ec
PMC C-121_BUSB_I/C_CB
3 IEC- 3
ExtremelyInversePickup=1(0.) o
1-25xCTSecTimeDial=1.05
3x=10.5s,5x=3.5s,8x=1Inst=1.33sc
∆0.265s n I>PMCC-121BC-1Relay

0.49(0.5- ) ds PMCC-121_B/C-1_CB.
40xCTSeTimeDelay=0.2s
1 TR-112 1 PMCC-121BUSB
PMCC -121BUSA ±

22K001DN_Fuse
L&THN(Size3)O
.5 ther0.415kV500 .5

.3 .3 PMCC-121_O/C_CB_RELEA SE

Lighti ngtrafofuse

TR-112 Cable15840
.1 Inrush .1 -3/C2

.05 .05
15000A,0.06s ± I>
PMCC-122I /CRelay
.03 TR-112I/Crelay-3P.03

22_I/
PMCC-1 C_CB
44272A,0.0102s
14F2RELEASE6
5kA@0.415kV PMCC -122
.01.01.51351030501003005001K3K5K10K

AmpsX100PMCC-122
22K001D _Fuse outgoing<32A
ETAPStar12.6.0C
N

1.MCC-122toTR-112 ±

R 22K001DNRelay
±
I> motor_CBCT
Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
tion:GanjamOrissa SN:THYS- Cable21
4-3/C240
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Phase

22K001DN2
50kW
AmpsX10PMCC-121BUSA(Nom.kV=0.415,PlotRef.kV=0.415)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K 1K TR-112_I/C_CB

TR-112SBEFRelay Cable2350
500 ABBICM2 0 1-3/C300
CTRatio2000:1In
TR-112I/Crelay
±

300 verse 300 I>


Pickup=0.6(0.2-0.8Sec-
5A)TimeDial=0.4
3x=2.48s,5x=1.69s,8x=1.32s

100 outgoing<32A PMCC-121BUSBI/CRelay-G 100 3.15MVA


TR-112
L&THF ABBSPAJ140C(SPCJ4D29)C
Other0.415kV3 TRatio4500:5
2 IEC-ExtremelyInverse ±

Pickup=0.17(0.1- I>TR-112SBEF Relay


50 0.8xCTSec)TimeDial=0.25
50
3x=2.5s,5x=0.833s,8x=0.317sInst=0.
98(0.1-10xCTSec)
30 30
TimeDelay=0.48sLi
ghtingtrafofuse
Bu sDuct-TR-112
L&THN(Size2) PMCC-121BC-1Relay-
GOther0.415kV
ABBSPAJ140C(SPCJ4D29)25
±
0 CTRatio4500:5 ay
10 10 I>PMCC-121BUSBI/CRel
IEC-ExtremelyInverse
Pickup=0.17(0.1-
0.8xCTSec)TimeDial=0.25
3x=2.5s,5x=0.833s,8x=0.317sInst=0.
Seconds

5 5
97(0.1-10xCTSec)
TimeDelay=0.48s
S
PMC C-121_BUSB_I/C_CB
3 3
ec
o
n I>PMCC-121BC-1Relay
24000A,0.888s3 ds PMCC-121_B/C-1_CB.
45A,0.734s
1 1 PMCC-121BUSB
PMCC -121BUSA ±

.5 .5

PMCC-121_O/C_CB_RELEA SE
.3 .3
Lighti ngtrafofuse
PMCC-122I/CRelay-
GOC1
AREVAP121 14F2ReleaseEarth Cable15840
CTRatio1250:1 -3/C2
.1 IEC-ExtremelyInverse 1250AwithSR18GRelease
.1Pickup=0.08(0.002-1xCTSec)
DTcurve
TimeDial=0.1 Pickupvalue=0.4*In=500Amp
± I>
.05 3x=1s,5x=0.333s,8x=0.127s TimeDelay=0.3 PMCC-122I /CRelay
.05Inst=0.276(0.002-1xCTSec)
TimeDelay=0.2s
.03 .03
22_I/
PMCC-1 C_CB

PMCC -122
.01.01.51351030501003005001K3K5K10K

AmpsX10PMCC-121BUSA(Nom.kV=0.415,PlotRef.kV=0.415) 22K001D _Fuse outgoing<32A


ETAPStar12.6.0C N

1.MCC-122toTR-112 ±

22K001DNRelay
R

±
I> motor_CBCT
Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
Cable21
tion:GanjamOrissa SN:THYS- 4-3/C240
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Ground

22K001DN2
50kW
AmpsX100SW-12indoor(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K RTR-OldI/CRelay-P
1K
OC1
500 AREVAP121
CTRatio1600:1 500
RTR-NewI/CRelay-P IEC-StandardInverse
OC1 Pickup=0.65(0.1-25xCTSec)
300AREVAP121
TimeDial=0.075
CTRatio1300:1
300
IEC-StandardInverse
3x=0.473s,5x=0.321s,8x=0.247s
Pickup=0.9(0.1-
Inst=4.04(0.5-
25xCTSec)TimeDial=0.075
40xCTSec)TimeDelay=0.1s
3x=0.473s,5x=0.321s,8x=0.247sInst=5.
Note:BlockingFeatureofrelayshallbeenabled.
71(0.5-40xCTSec)
100 TimeDelay=0.1s
Note:BlockingFeatureofrelayshallbeenabled.
100

50 50

30 30 SchneiderTrafo
SW-12I/CRelay- 31.25MVA
SW-11AI/Crelay-
POC1
POC1
AREVAP121CT
AREVAP121CT
Ratio2000:1
Ratio2000:1
IEC- ±

IEC-StandardInverse I>SW-11AI/CSB
StandardInversePickup= CTSec)
10 Pickup=0.89(0.1- 10
0.77(0.1-
25xCTSec)TimeDial=0.25
25xTimeDial=0.15 s,8x=0.495sSe Cable1
3x=1.58s,5x=1.07s,8x=0.824sInst=5. 18-1/C630
3x=0.945s,5x=0.642Inst c)
1(0.5-40xCTSec)
=4.13(0.5-
TimeDelay=0.7s ±

5 40xCTTimeDelay=0.3s 5 I>SW-11AI/Crelay
Seconds

11kVO/GtoSW12-P
OC1
S
3 AREVAP121CT
3
ec
Ratio2000:1
IEC-StandardInverse
on
Pickup=0.81(0.1- ds 11_I/C_CBSW-11A(KIOSK)
SW-
25xCTSec)TimeDial=0.2
3x=1.26s,5x=0.856s,8x=0.659sInst=4.
59(0.5-40xCTSec)
SW-11_O/C_CB
1 TimeDelay=0.5s 1
±

I>11kVO/GtoSW12

.5 20177A,0.3s .5
Cable4
18-1/C630.3
.3
±

I>SW-12I/CRelay

SchneiderTrafoI
nrush SchneiderTrafo SW-12_I/C_CB
SW-12indoor

.1 .1
RTR-OLD
RTR-NEW RTR-111_CB RTR-112_CB
Inrush
Inrush ±

.05 .05 I>CBCT_RECT_NEW

± ±

I>
.03 I>
.03 RTR-OldI/CRelay RTR-NewI/CRelay
SW-11AI/Crelay-3P
19.749MVA 22.454MVA
RTR-NEW
RTR-OldI/CRelay-3P SW-12I/CRelay-3P RTR-OLD

RTR-NewI/CRelay-3P
11kVO/GtoSW12-3P
.01.01.51351030501003005001K3K5K10K

AmpsX100SW-12indoor(Nom.kV=11,PlotRef.kV=11)
Lump112. Lump312.
ETAPStar12.6.0C
5MVA 5MVA

2.SW12toUPSTREAM

Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
tion:GanjamOrissa SN:THYS-
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Phase
AmpsSW-12indoor(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K
10K1K1K

500
500
SW-11AI/Crelay-G
OC1
300 AREVAP121
300
CTRatio2000:1
Inst=0.07(0.002-
1xCTSec)TimeDelay=0.7s

11kVO/GtoSW12-G
100 OC1 100
AREVAP121CT
Ratio2000:1
Inst=0.06(0.002-1xCTSec)
50 TimeDelay=0.5s 50

30 SW-12I/CRelay- 30 SchneiderTrafo
GOC1 31.25MVA
AREVAP121CT
Ratio2000:1
Inst=0.05(0.002-
1xCTSec)TimeDelay=0.3s ±

I>SW-11AI/CSB
10 10
RTR-OldI/CRelay- Cable1
SW-11AI/CSB 18-1/C630
GOC1
GECCDG11/21/31
5 AREVAP121CT S
Seconds

Ratio1600:1 CTRatio400:1 5 I>SW-11AI/Crelay

Inst=0.05(0.002- ShortTimeNormalInversePicku ec
1xCTSec)TimeDelay=0.1s
3 p=40(10-
40xCTSec)TimeDial=0.9 3 on
3x=2.27s,5x=1.62s,8x=1.3s ds
SW-11_I/C_CB
SW-11A(KIOSK)
1000A,1.45s
SW-11_O/C_CB
1 CBCT_RECT_NEW-P-50 ∆0.752s 1
OC1
ALSTOMP120 ±

CTRatio20:1 I>11kVO/GtoSW12
Inst=0.5(0.002-
.5 1xCTSec)TimeDelay=0.1s .5
Cable4
18-1/C630.3
.3
±

I>SW-12I/CRelay

SW-12indoor SW-12_I/C_CB

.1 .1

RTR-111_CB RTR-112_CB

.05 .05 I>CBCT_RECT_NEW

± ±

RTR-OldI/CRelay-G-LG I> I>


.03 .03
SW-11AI/Crelay-G-LG RTR-OldI/CRelay RTR-NewI/CRelay
11kVO/GtoSW12-G-
19.749MVA 22.454MVA
LGCBCT_RECT_NEW-LG RTR-NEW
RTR-OLD
SW-11AI/CSB-LG
SW-12I/CRelay-G-LG
.01 .01 Project:GRCD:NaOHExpansion_RelayCo
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
tion:GanjamOrissa
AmpsSW-12indoor(Nom.kV=11,PlotRef.kV=11) INDI2Contract:66-0192-700 Lump112.5MVA
ETAPStar12.6.0C

:
2.SW12toUPSTREAM
Lump312.5MVA
AmpsX10SW-12indoor(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K 1K

TR-112I/Crelay- SW-12I/CRelay-
POC1 POC1
500 500
AREVAP121C AREVAP121CT
TRatio200:1 Ratio2000:1
IEC- IEC-StandardInverse
300 Pickup=0.77(0.1- 300
StandardInversePickup CTSec)
=1.1(0.1- 25xCTSec)TimeDial=0.15
25xTimeDial=0.3 8x=0.989sT 3x=0.945s,5x=0.642s,8x=0.495sInst=4.
3x=1.89s,5x=1.28s,Inst Sec) 13(0.5-40xCTSec)
=10.79(0.5- TimeDelay=0.3s
40xCTimeDelay=0.1s

100 100
RTR-NewI/CRelay-
PFIC7thRelay.- POC1
POC1 AREVAP121CT
50 AREVAP121C Ratio1300:1 50
TRatio400:1 IEC-StandardInverse
IEC-StandardInverse Pickup=0.9(0.1-
Pickup=0.85(0.1- 25xCTSec)TimeDial=0.075
30 30
25xCTSec)TimeDial=0.05 3x=0.473s,5x=0.321s,8x=0.247sInst=5.
3x=0.315s,5x=0.214s,8x=0.165sInst=6. 71(0.5-40xCTSec)
56(0.5-40xCTSec) TimeDelay=0.1s
TimeDelay=0.1s

RTR-OldI/CRelay-
10 PFIC11th-BRelay- POC1 10
POC1 AREVAP121CT
AREVAP121C Ratio1600:1
TRatio700:1 IEC-StandardInverse
5 IEC-StandardInverse Pickup=0.65(0.1- 5
Seconds

Pickup=0.75(0.1- 25xCTSec)TimeDial=0.075
3x=0.473s,5x=0.321s,8x=0.247sInst=4.
S
25xCTSec)TimeDial=0.05
3 3x=0.315s,5x=0.214s,8x=0.165sInst=5. 04(0.5-40xCTSec)
3
ec
TimeDelay=0.1s
82(0.5-40xCTSec)
TimeDelay=0.1s
on
ds

1 PFIC5thRelay- 1
POC1
AREVAP121C
TRatio700:1
.5 IEC- .5
StandardInversePicku xCTSec)
p=0.85(0.1-
.3 25TimeDial=0.05 4s,8x=0.165sTS .3
3x=0.315s,5x=0.21Inst ec)
=6.55(0.5- ±

I> SW-12I/CRelay
40xCTimeDelay=0.1s

.1 .1

SW-
12_I/C_CB .05 .05SW-12indoor

.03 .03

SW -12I/CRelay-3P RTR-111_CB TR-112_I/C_CB


RTR-112_CB PFIC3rdCB2 23U001N-
TR-112I/Crelay-3PPFIC7thRelay.-3P RTR-
M01_CB CBCT_RECT_NEW PFIC3rdCB PFIC11thCB
Cable23
OldI/CRelay-3PPFIC11th-BRelay-3P
±
±

I> 1-3/C300 R±

RTR-NewI/CRelay-3PPFIC5thRelay-3P
.01 .01.51351030501003005001K3K5K10K I> ± ± ± 23U001N-M01_Relay
I> I>
± RTR-
AmpsX10SW-12indoor(Nom.kV=11,PlotRef.kV=11) OldI/CRelay
RTR-NewI/CRelay TR-112I/Crelay I> ±

ETAPStar12.6.0C I>
±

Cable11PFIC5thRelayI> 1-3/C185
PFIC7thRelay.PFIC11th-BRelay
3.11kVINDOORSWGR

Project:GRCD:NaOHExpansion_RelayCo
PFICBANK-5th
Date:12.07.16Loca 6.5Mvar PFICBANK-7th 23U001N-
PFICBANK-11th-B
tion:GanjamOrissa SN:THYS- 3.5Mvar 420kW
M016Mvar
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Phase
AmpsX10SW-12indoor(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K SW-12I/CRelay- 1K
GOC1
AREVAP121CT
500 Ratio2000:1 500
Inst=0.05(0.002-
1xCTSec)TimeDelay=0.3s
300 RTR-OldI/CRelay- 300
GOC1
AREVAP121CT
Ratio1600:1
Inst=0.05(0.002-
1xCTSec)TimeDelay=0.1s
100 CBCT_RECT_NEW-P- 100
50OC1
ALSTOMP120
CTRatio20:1
50 Inst=0.5(0.002- 50
1xCTSec)TimeDelay=0.1s

30 TR-112I/Crelay-G 30
OC1
AREVAP121C
TRatio200:1
Inst=0.1(0.002-
PFIC5thRelay-G10 1xCTSec)TimeDelay=0.1s
OC1 10
AREVAP121C
TRatio700:1
Inst=0.05(0.002-1xCTSec)5
TimeDelay=0.1s
5
Seconds

PFIC11th-BRelay-G S
OC1
3 AREVAP121 3
ec
CTRatio700:1
Inst=0.05(0.002-
on
1xCTSec)TimeDelay=0.1s ds
PFIC7thRelay.-G1
OC1
AREVAP121C 1
TRatio400:1
Inst=0.05(0.002-1xCTSec)
.5 TimeDelay=0.1s
.5

.3 .3
±

I> SW-12I/CRelay

.1 .1

SW-
12_I/C_CB .05 .05SW-12indoor

.03 .03
PFIC5thRelay-G-LG
RTR-111_CB TR-112_I/C_CB
SW-12I/CRelay-G-LGRTR- RTR-112_CB PFIC3rdCB2 23U001N-
M01_CB CBCT_RECT_NEW PFIC3rdCB PFIC11thCB
OldI/CRelay-G-LG ±
Cable23 ±

CBCT_RECT_NEW-LG I> 1-3/C300 R±

.01 .01 I> ± ±


±
23U001N-M01_Relay
I> I>
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K ± RTR-
OldI/CRelay
TR-112I/Crelay I>
AmpsX10SW-12indoor(Nom.kV=11,PlotRef.kV=11) RTR-NewI/CRelay
±

I>
ETAPStar12.6.0C Cable11PFIC5thRelayI> 1-3/C185
PFIC7thRelay.PFIC11th-BRelay

3.11kVINDOORSWGR

PFICBANK-5th
Project:GRCD:NaOHExpansion_RelayCo PFICBANK-7th 23U001N-
6.5Mvar PFICBANK-11th-B
Date:12.07.16Loca 3.5Mvar M016Mvar
420kW
tion:GanjamOrissa SN:THYS-
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Ground
AmpsX10SW-11A(KIOSK)(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
1K 1K

500 500
SW-11AI/Crelay-
POC1
300 300
AREVAP121CT
Ratio2000:1
IEC-StandardInverse
Pickup=0.89(0.1-
25xCTSec)TimeDial=0.25
3x=1.58s,5x=1.07s,8x=0.824sInst=5.
1(0.5-40xCTSec)
100 100
TimeDelay=0.7s

11kVO/GtoSW 12-
POC1
50 50
AREVAP121CT
Ratio2000:1
IEC-StandardInverse
30 30
Pickup=0.81(0.1-
25xCTSec)TimeDial=0.2
3x=1.26s,5x=0.856s,8x=0.659sInst=4.
59(0.5-40xCTSec)
TimeDelay=0.5s
PFIC11th-Arelay-
POC1
10 10
AREVA
P121
CTRatio200:1IEC-
VeryInverse
5 Pickup=0.95(0.1- CTSec) 5
Seconds

25xTimeDial=0.1 S ±

3x=0.675s,5x=0.338sInst ,8x=0.193sSe
ec I> SW-11AI/Crelay3
3 =7.55(0.5- c)
40xCTTimeDelay=0.1s
on
ds

PFIC3rdRelay.-
1 POC1 1
AREVAP121C
TRatio200:1
IEC-VeryInverse

.5
Pickup=0.63(0.1-
.5
SW-11_I/C_CB
25xCTSec)TimeDial=0.1
3x=0.675s,5x=0.338s,8x=0.193sInst=4.
86(0.5-40xCTSec)
.3 TimeDelay=0.1s .3
SW-11A(KIOSK)

PFICBANK-2_CB SW-11_O/C_CB
.1 .1
PFICBANK-1_CB

±
±

.05 .05 I> ±


I>
I>
PFIC3rdRelay.
.03
.03 PFIC11th-Arelay 11kVO/GtoSW12
PFIC11th-Arelay-3P
SW-11AI/Crelay-3P
PFIC3rdRelay.-3P
11kVO/GtoSW 12-3P PFICBANK-3rd
PFICBANK-11th-
.01 .01 1.5Mvar A2.5Mvar
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
AmpsX10SW-11A(KIOSK)(Nom.kV=11,PlotRef.kV=11)
ETAPStar12.6.0C

4.11kVOUTDOORKIOSK

Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
tion:GanjamOrissa SN:THYS-
INDI2Contract:66-0192-700 Rev:BaseEngineer:
Fault:Phase
AmpsX10SW-11A(KIOSK)(Nom.kV=11,PlotRef.kV=11)
.5 1 3 5 10 30 50 100 300500 1K 3K 5K
10K1K1K

500 500

300 300

PFIC11th-Arelay-
GOC1
100 100
AREVA
P121
CTRatio200:1S
horttimeDefinit
50 eTime 50
Pickup=0.1(0.002-
1xCTSec)TimeDial=0.1
30 30
PFIC3rdRelay.-
GOC1
AREVAP121C
TRatio200:1
Inst=0.1(0.002-
1xCTSec)TimeDelay=0.1s
10 10

SW-11AI/Crelay-
GOC1
AREVAP121CT
5 5
Seconds

Ratio2000:1
S ±

Inst=0.07(0.002-
I> SW-11AI/Crelay3
3
1xCTSec)TimeDelay=0.7s ec
11kVO/GtoSW 12- on
GOC1
ds
AREVAP121CT
Ratio2000:1
Inst=0.06(0.002-1xCTSec)
TimeDelay=0.5s 1
1

.5 .5
SW-11_I/C_CB
.3 .3

SW-11A(KIOSK)

PFICBANK-2_CB SW-11_O/C_CB
.1 .1
PFICBANK-1_CB

±
±

.05 .05 I> ±


I>
PFIC3rdRelay..03 I>
.03
PFIC11th-Arelay 11kVO/GtoSW12
11kVO/GtoSW 12-G-LG
PFICBANK-3rd
SW-11AI/Crelay-G-LG
PFICBANK-11th-
.01 .01 1.5Mvar A2.5Mvar
.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K
AmpsX10SW-11A(KIOSK)(Nom.kV=11,PlotRef.kV=11)
ETAPStar12.6.0C

4.11kVOUTDOORKIOSK

Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
tion:GanjamOrissa SN:THYS-
INDI2Contract:66-0192-700 Rev:BaseEngineer:
Fault:Ground
1109.6MVAsc
AmpsX100SW-12indoor(Nom.kV=11,PlotRef.kV=11) IncomingLineFromOPTCL

.5 1 3 5 10 30 50 100 300500 1K 3K 5K 10K


1K 1K
TR-1_I/C_CB

500 SW -12I/CRelay- 500


POC1
AREVAP121CT
300 Ratio2000:1 300
IEC-StandardInverse
Pickup=0.77(0.1-
25xCTSec)TimeDial=0.15 Bus12
3x=0.945s,5x=0.642s,8x=0.495sInst=4.
13(0.5-40xCTSec) SchniederTrafoICRelay-
TimeDelay=0.3s POC1 TR-1_I/C_CB2 TR-
100 AREVAP122C 1_I/C_CB3 100
TRatio200:1
IEC-StandardInverse
±

RTR-OldI/CRelay- R SchniederTrafoICRelay ±

Pickup=0.89(0.1- R Emco_ICRelay
POC1
50 25xCTSec)TimeDial=0.3 50
AREVAP121CT 3x=1.89s,5x=1.28s,8x=0.989sInst=5.
Ratio1600:1 SchneiderTrafo
44(0.5-40xCTSec)
IEC- 31.25MVA EMCOTrafo
TimeDelay=0.1s
30 StandardInversePickup=0.TSec) 30 31.25MVA
65(0.1- SW -11AI/Crelay-
25xCTimeDial=0.075 8x=0.247sec POC1
3x=0.473s,5x=0.321s,Inst=) AREVAP121CT
I> SW-11AI/CSB
±

4.04(0.5- Ratio2000:1
40xCTSTimeDelay=0.1s IEC-StandardInverse
Pickup=0.89(0.1-
10 10
RTR-NewI/CRelay- 25xCTSec)TimeDial=0.25
3x=1.58s,5x=1.07s,8x=0.824sInst=5. Cable1
POC1 18-1/C630
Cable3
1(0.5-40xCTSec) SW11BCRelay 18-1/C630
AREVAP121CT TimeDelay=0.7s
Ratio1300:1 5 I>
5 ±

S
Seconds

IEC-StandardInverse 11kVO/GtoSW 12- I> SW-11AI/Crelay ±

I> SW-11BICRelay
Pickup=0.9(0.1-
25xCTSec)TimeDial=0.075
POC1
3 ec
3 AREVAP121CT CB4
3x=0.473s,5x=0.321s,8x=0.247sInst=5.
71(0.5-40xCTSec) Ratio2000:1 o ±

TimeDelay=0.1s IEC-StandardInverse
Pickup=0.81(0.1-
n SW-11_I/C_CB SW-11B_I/C_CB
SchneiderTrafo 25xCTSec)TimeDial=0.2 ds SW-11A(KIOSK) SW-11B(KIOSK)
3x=1.26s,5x=0.856s,8x=0.659sInst=4.
59(0.5-40xCTSec)
1 SW-11_O/C_CB
1 TimeDelay=0.5s

I> 11kVO/GtoSW12 .5
.5

Cable4
.3 .3 18-1/C630

I> SW-12I/CRelay

SW-12indoor SW-
RTR-
.1 12_I/C_CB.1
OLDInrus
h
RTR- SchneiderTrafoI RTR-111_CB RTR-112_CB
NEW.05 Inrush nrush
.05 ±

I>CBCT_RECT_NEW

± ±

.03 .03 I> I>

SW -11AI/Crelay-3P RTR-OldI/CRelay RTR-NewI/CRelay

RTR-OldI/CRelay-3P 19.749MVA 22.454MVA


SW -12I/CRelay-3P RTR-NEW
RTR-OLD
RTR-NewI/CRelay-3P
11kVO/GtoSW 12-3P
.01.01.51351030501003005001K3K5K10K

AmpsX100SW-12indoor(Nom.kV=11,PlotRef.kV=11)
ETAPStar12.6.0C
Lump112.5 Lump312.5
MVA MVA
5.SW12toOPTCLPARALLEL

Project:GRCD:NaOHExpansion_RelayCo
Date:12.07.16Loca
tion:GanjamOrissa SN:THYS-
INDI2Contract:66-0192-700
Rev:BaseEngineer
: Fault:Phase
1109.6MVAsc
AmpsX10SW-12indoor(Nom.kV=11,PlotRef.kV=11) IncomingLineFromOPTCL

.5 1 3 5 10 30 50 100 300500 1K 3K 5K
10K1K1K
TR-1_I/C_CB

500 500

SW -11AI/CSB-LG(Min)
300 300

Bus12
SchniederTrafoICRelay-
GOC1
TR- TR-1_I/C_CB3
AREVAP122C
100 TRatio200:1 1_I/C_CB2 100
IEC-StandardInverse ±

Pickup=0.12(0.002- R SchniederTrafoICRelay ±

1xCTSec)TimeDial=0.35 R Emco_ICRelay

50 3x=2.21s,5x=1.5s,8x=1.15s 50
SchneiderTrafo
SW -11AI/CSB
31.25MVA EMCOTrafo
30 GECCDG11/21/31
30 31.25MVA
CTRatio400:1
ShortTimeNormalInversePicku
p=40(10-
40xCTSec)TimeDial=0.9 ±

I> SW-11AI/CSB
3x=2.27s,5x=1.62s,8x=1.3s

10 SW -11AI/Crelay- 10
GOC1
Cable1 Cable3
AREVAP121CT 18-1/C630
SW11BCRelay 18-1/C630
Ratio2000:1
5 Inst=0.07(0.002-
5 I>
1xCTSec)TimeDelay=0.7s
Seconds

S
±

I> SW-11AI/Crelay ±

I> SW-11BICRelay

3 RTR-OldI/CRelay- 3
ec
CB4
GOC1 o ±

AREVAP121CT
Ratio1600:1
n SW-11B_I/C_CB
SW-11_I/C_CB
Inst=0.05(0.002- ds SW-11A(KIOSK) SW-11B(KIOSK)
1xCTSec)TimeDelay=0.1s
1 1 SW-11_O/C_CB

I> 11kVO/GtoSW12

.5 11kVO/GtoSW 12- .5
GOC1
AREVAP121 Cable4
.3 CTRatio2000:1 .3 18-1/C630
Inst=0.06(0.002-
1xCTSec)TimeDelay=0.5s ±

I> SW-12I/CRelay

SW -12I/CRelay-
GOC1 SW-12_I/C_CB
SW-
.1
12indoor.1
AREVAP
121CTRatio2000
:1 RTR-111_CB RTR-112_CB
Inst=0.05(0.002-
1xCTSec)TimeDelay=0.3s
.05 .05 ±

I>CBCT_RECT_NEW
CBCT_RECT_NEW-P-50
ALSTOM
OC1
± ±

.03 CBCT_RECT_NEW-LG I>


P120 I>

RTR-OldI/CRelay RTR-NewI/CRelay
.03
11kVO/GtoSW 12-G-LG 19.749MVA 22.454MVA
TimeDelay=0.1s RTR-NEW
Inst=0.5(0.002-1xCTSec) RTR-OLD
SW -11AI/Crelay-G-LG RTR-OldI/CRelay-G-LG
CTRatio20:1 SW -12I/CRelay-G-LG
SW -11AI/CSB-LG
.01.01.51351030501003005001K3K5K10K
RelaySettings Pageno-1Of17

RelaySettingChartforGRCD-NaOHPlantatGanjam,Orissa

Relayposition-
132kVOutgoingtoSchniederTrafoRelaymodel-
MicomP122(AREVA)
CTRatio-200/1

Low-set3-phasenondirectionalovercurrentprotection,stageI>/51

Description Range Step Valuetobeset Remarks

Settingrangeofpick-upcurrent'I>' 0.1to25xIn 0.01 0.89


IECStandardI
DelayType
nverse
Timemultipliersetting'k' 0.025to1.5 0.001 0.3

Highset3-phasenon-directionalovercurrentprotection,stageI>>/50-1

Description Range Step Valuetobeset Remarks

Settingrangeofpick-upcurrent'I>>' 0.5to40xIn 0.01 5.44

DelayType DT

Operatetimedelay(DMT)'t>>' 0to150s 0.0025 0.1

Low-setnondirectionalearth-faultprotection,stageIo>/51N

Description Range Step Valuetobeset Remarks

Settingrangeofpick-upcurrent'Io>' 0.02to1xIn 0.001 0.12


IECStandardI
DelayType
nverse
Operatetimedelay't>'(DMT) 0.025to1.5sec 0.001 0.1

High-setnondirectionalearth-faultprotection,stageIo>>/50N

Description Range Step Valuetobeset Remarks

Settingrangeofpick-upcurrent'Io>>' 0.1to10xIn 0.001 - Tobedisabled

DelayType - Tobedisabled

Operatetimedelay't>'(DMT) 0.05to300sec 0.001 - Tobedisabled

Relayposition-
132kVOutgoingtoSchniederTrafoRelaymodel-
VAGM22(Alstom)
CTRatio-200/1

Description Range Step Valuetobeset Remarks

Undervolatge(U/V) 0.04to0.08xUn 7steps 80% Sincealternatesourceisnota


vailable,trippingshallbeavoi
dedonUndervoltage
VTT11 NotAvailable - MaxPossible

Relayposition-
132kVOutgoingtoSchniederTrafoRelaymodel-
CDG11(Alstom)
CTRatio-400/1

Description tI>

I>
Range Step Valuetobeset Remarks

10-40% 5% 40

0.1-1 0.1 0.9


Code : GRCD-NaOH Page no - 2 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW11 11kV Outdoor Kiosk : Incomer


Relay model - MICOM P111 (AREVA)
CT Ratio - 2000/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.89


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.25

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 5.1

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.7

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.07

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.7

Relay position -132kV Outgoing to Schnieder Trafo


Relay model -TEB3 Easun Reyrolle
CT Ratio - 200/1

Description Range Step Value to be set Remarks

Since alternate source is


Undervolatge (U/V) 0.4 to 0.9 Un 0.1 0.8 Un
not available, tripping shall
be avoided on
U/V Time setting Not Availble Max Possible
Undervoltage
Code : GRCD-NaOH Page no - 3 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW11 11kV Outdoor Kiosk : Outgoing to 11kV Incomer


Relay model - MICOM P111 (AREVA)
CT Ratio - 2000/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.81


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.2

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 4.59

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.5

Very high set 3-phase non-directional overcurrent protection, stageI>>>/50-2

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>>' 1 to 40 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay(DMT) 't>>>' 0.0 to 200 s 0.01 - To be disabled

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.06

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.5


Code : GRCD-NaOH Page no - 4 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW11 11kV Outdoor Kiosk : Outgoing to 3rd Harmonic filter Bank
Relay model - MICOM P111 (AREVA)
CT Ratio - 200/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.63


IEC Very
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.1

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 4.86

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.1

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1

MIT 161 (Easun Reyrolle) Capacitor Neutral unbalance Protection

Description Range Step Value to be set Remarks

NCT (I0>) 0.5% to 25% 0.50% 25% of I0 To be finalised only after availibilty of
NCT (t0>) 0 to 60 sec 1 sec 3s OEM's data

Under Voltage Over Voltage Protection


Description % Voltage Time Delay Remarks

Under Voltage 80 0.5s Under voltage & Overvoltage protection shall be


provided for capacitor feeders in the
Over Voltage 115% 10s corresponding relay
Code : GRCD-NaOH Page no - 5 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW11 11kV Outdoor Kiosk : Outgoing to 5th Harmonic filter Bank
Relay model - MICOM P111 (AREVA)
CT Ratio - 200/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.95


IEC Very
Delay Type
inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.1

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 7.55

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.1

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1

MIT 161 (Easun Reyrolle) Capacitor Neutral unbalance Protection

Description Range Step Value to be set Remarks

NCT (I0>) 0.5% to 25% 0.50% 25% of I0 To be finalised only after availibilty of
NCT (t0>) 0 to 60 sec 1 sec 3s OEM's data

Under Voltage Over Voltage Protection


Description % Voltage Time Delay Remarks

Under Voltage 80 0.5s Under voltage & Overvoltage protection shall be


provided for capacitor feeders in the
Over Voltage 115% 10s corresponding relay
Code : GRCD-NaOH Page no - 6 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 Incomer


Relay model - MICOM P111 (AREVA)
CT Ratio - 2000/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.77


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.15

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 4.13

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.3

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.05

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.3

Relay position -SW-12 Incomer


Relay model -TEB3 Easun Reyrolle
CT Ratio - 200/1

Description Range Step Value to be set Remarks

Since alternate source is


Undervolatge (U/V) 0.4 to 0.9 Un 0.1 0.8 Un
not available, tripping shall
be avoided on
U/V Time setting Not Availble Max Possible
Undervoltage
Code : GRCD-NaOH Page no - 7 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to TR-111 & TR-112


Relay model - MICOM P111 (AREVA)
CT Ratio - 200/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 1.1


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.3

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 10.79

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.1

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1


Code : GRCD-NaOH Page no - 8 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to Rectifier (Old)


Relay model - MICOM P111 (AREVA)
CT Ratio - 1600/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.65


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.075

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 4.04

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.05

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1


Code : GRCD-NaOH Page no - 9 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to Rectifier (New)


Relay model - MICOM P111 (AREVA) Relay type is assumed
CT Ratio - 1300/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.9


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.075

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 5.71

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.1


Input hrough CBCT of ratio
Delay Type DT
20/1
Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1
Code : GRCD-NaOH Page no - 10 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to 5th Harmonic Filter Bank


Relay model - MICOM P111 (AREVA) Relay type is assumed
CT Ratio - 700/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.85


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.05

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 6.55

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.05

Delay Type DT

Operate time delay 't>' (DMT) 0.0 to 100 0.01 0.1

Relay Type Unknown

Description Range Step Value to be set Remarks

NCT (I0>) 25% of I0 To be finalised only after availibilty of


NCT (t0>) 3s OEM's data
Code : GRCD-NaOH Page no - 11 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to 7th Harmonic Filter Bank


Relay model - MICOM P111 (AREVA) Relay type is assumed
CT Ratio - 400/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.85


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.05

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 6.56

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.05

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1

Relay type is unknown

Description Range Step Value to be set Remarks

NCT (I0>) 0.5% to 25% 0.50% 25% of I0 To be finalised only after availibilty of
NCT (t0>) 0 to 60 sec 1 sec 3s OEM's data
Code : GRCD-NaOH Page no - 12 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position -SW-12 : Outgoing to 7th Harmonic Filter Bank


Relay model - MICOM P111 (AREVA) Relay type is assumed
CT Ratio - 700/1

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 4 x In 0.01 0.75


IEC Standard
Delay Type
Inverse
Time multiplier setting 'k' 0.02 to 1.5 0.01 0.05

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.1 to 40 x In 0.01 5.82

Delay Type DT

Operate time delay(DMT) 't>>' 0.02 to 1.5 0.01 0.1

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.01 to 2.0 x In 0.01 - To be disabled

Delay Type - To be disabled

Operate time delay 't>' (DMT) 0.02 to 1.5 0.01 - To be disabled

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.05 to 2.0 x In 0.01 0.05

Delay Type DT

Operate time delay 't>' (DMT) 0.02 to 100 0.01 0.1

Relay type is unknown

Description Range Step Value to be set Remarks

NCT (I0>) 0.5% to 25% 0.50% 25% of I0 To be finalised only after availibilty of
NCT (t0>) 0 to 60 sec 1 sec 3s OEM's data
Code : GRCD-NaOH Page no - 13 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position - I/C-1 & I/C2 of PMCC-121 (Existing LV switchgear)


Relay model - SPAJ140C (SPCJ 4D29)
CT Ratio - 4500/5

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.5 to 2.5 x In 0.01 1.03


IEC Normal
Delay Type
Inverse
Time multiplier setting 'k' 0.05 to 300s 0.01 0.31

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.5 to 40 x In 0.1 4.03

Delay Type DT

Operate time delay(DMT) 't>>' 0.04 to 300s 0.01 0.68

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.1 to 0.8 x In 0.01 0.71


IEC Extremely
Delay Type
Inverse
Operate time delay 't>' (DMT) 0.05 to 300 sec 0.01 0.25

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.1 to 10 x In 0.01 0.98

Delay Type DT

Operate time delay 't>' (DMT) 0.05 to 300 sec 0.01 0.48

Relay position - I/C-1 & I/C2 of PMCC-121 (Existing LV switchgear)


Relay model - IRXM 64R REF (ABB)
1-10 Knob
Description in % 0.5 or 5% Remarks
Position
I 10% 5 2
Relay position - I/C-1 & I/C2 of PMCC-121 (Existing LV switchgear)
Relay model - ICM21np for 51G
CT Ratio - 2000/1

Description Range Step Value to be set Remarks

i> 0.2-0.8 7 step 0.6 In


t i> 10-100% 0.4
Relay position - I/C-1 & I/C2 of PMCC-121 (Existing LV switchgear)
Relay model - VHXm22A

Description Range Step Value to be set Remarks

U/V 0.4 to 0.8 Un 0.8 Un

U/V Time setting 0.5 to 5 s 0.5


Code : GRCD-NaOH Page no - 14 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position - B/C -1 of PMCC-121 (Existing LV switchgear)


Relay model - SPAJ140C (SPCJ 4D29)
CT Ratio-4500/5

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.5 to 2.5 x In 0.01 0.94


IEC Normal
Delay Type
Inverse
Time multiplier setting 'k' 0.05 to 300s 0.01 0.23

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.5 to 40 x In 0.1 3.66

Delay Type DT

Operate time delay(DMT) 't>>' 0.04 to 300s 0.01 0.48

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.1 to 0.8 x In 0.01 0.17


IEC Extremely
Delay Type
Inverse
Operate time delay 't>' (DMT) 0.05 to 300 sec 0.01 0.25

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.1 to 10 x In 0.97

Delay Type DT

Operate time delay 't>' (DMT) 0.05 to 300 sec 0.48

Relay position - B/C -1 of PMCC-121 (Existing LV switchgear)


Relay model - SKE-11 (AREVA)

Description Range Step Value to be set Remarks

% Diff V1-V2 0.04 Time 2s


Code : GRCD-NaOH Page no - 15 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position - B/C -2 of PMCC-121 (Existing LV switchgear)


Relay model - SPAJ140C (SPCJ 4D29)
CT Ratio -1250/5A

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.5 to 2.5 x In 0.01 2.5


IEC Normal
Delay Type
Inverse
Time multiplier setting 'k' 0.05 to 300s 0.01 1

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.5 to 40 x In 0.1 5

Delay Type DT

Operate time delay(DMT) 't>>' 0.04 to 300s 0.01 0.5

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.1 to 0.8 x In 0.01 0.1


IEC Extremely
Delay Type
Inverse
Operate time delay 't>' (DMT) 0.05 to 300 sec 0.01 0.05

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.1 to 10 x In 0.01 10

Delay Type DT

Operate time delay 't>' (DMT) 0.05 to 300 sec 0.01 0.05
Code : GRCD-NaOH Page no - 16 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position - Outgoing Releases from PMCC-121 to incomer of PMCC-122


Release model - L&T SR18G

Description Range Step Value to be set Remarks

0.5, 0.6, 0.65, 0.7,


Pick up current (Ir)=In x .. 0.75, 0.8, 0.85, 0.9, - 1
0.95, 1.0
2, 3, 4, 5, 6, 7, 8, 9,
Short circuit protection = In x .. - 10
10
20, 60, 100, 160,
Time delay 200, 260, 300, 400, - 600 ms
500, 600 ms
Instantaneous 6 & 12 In 12
0.2, 0.3, 0.4, 0.5,
Earth Fault pick-up current = In x .. - 0.4
0.6
100, 200, 300, 400
Earth Fault time delay - 300 ms
ms & OFF
Code : GRCD-NaOH Page no - 17 Of 17
Contract No. 66-0192
Relay Settings
Doc. no - 0192-ELT-00-ED-0001
Rev :00

Relay position - Incomer of PMCC-122 (New MCC)


Relay model - Micom P121 (AREVA) Relay type is assumed
CT Ratio - 1250/1 A

Low-set 3-phase non directional overcurrent protection, stage I>/51

Description Range Step Value to be set Remarks

Setting range of pick-up current 'I>' 0.1 to 25 x In 0.01 1


IEC Extremely
Delay Time
Inverse
Time multiplier setting 'k' 0.025 to 1.5s 0.001 1.05

High set 3-phase non-directional overcurrent protection, stageI>>/50-1

Description Range Step Value to be set Remarks

Setting range of pick-up current' I>>' 0.5 to 40 x In 0.01 10.49

Delay Time DT

Operate time delay(DMT) 't>>' 0 to 150s 0.0025 0.2

Low-set non directional earth-fault protection, stage Io>/51N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>' 0.02 to 1 x In 0.001 0.08


IEC Extremely
Delay Time
Inverse
Operate time delay 't>' (DMT) 0.025 to 1.5 sec 0.001 0.1

High-set non directional earth-fault protection, stage Io>>/50N

Description Range Step Value to be set Remarks

Setting range of pick-up current 'Io>>' 0.1 to 10 x In 0.001 0.276

Delay Time DT

Operate time delay 't>' (DMT) 0.05 to 300 sec 0.001 0.2