2.

1)
R = 30ohm
L = 50mH
VL= 415V
f = 50Hz
Inductive Resistance XL = 2 pi f L
2 𝑥 𝑝𝑖𝑥50 𝑥 50 𝑥 10−3

15.708 ohm

Phase Impedance = Zp

𝑍𝑃 = ට𝑅 2 + 𝑋𝐿2

𝑍_𝑃 = 33.86 ohm

a) System Phase Voltage 𝑉𝑃 = 𝑉𝐿 /ξ3

𝑉𝑃 = 415/ξ3 𝑣
V_P = 239.6 v
V_P = 240v

b) Phase Current
𝑉𝑝
𝐼𝑝 =
𝑍𝑝
240
𝐼𝑝 =
33.86
𝐼𝑝 = 7.09𝐴

c) Line Current IL = IP
IL = 7.09A

d) Three Phase should provide same current with same power factor in that condition. The neutral
current is zero.
e) Total Power dispatched
ξ3x VL x IL cos ∅
𝑅 30
cos ∅ = 𝑍𝑃 = 33.86 = 0 . 886
𝑃

P = ξ3x VL x IL cos ∅

P = ξ3x 415 x 7.09 x .886 = 4515.32w =


4.51Kw
2.2)

ZAB = 50 ohm
ZBC = R + jwL w = 2*pi*f

ȁ𝑧ȁ = ඥ𝑅 2 + (𝑤𝐿)2

ȁ𝑧ȁ = ඥ202 + (2𝑥𝑝𝑖𝑥50𝑥25𝑥10−3 )2

|z| = 21.487

|z| =21.49

ZAB = 50 ohm
1
𝑍𝐴𝐶 = 𝑅 + 𝑗
𝑤𝑐
1
𝑍𝐴𝐶 =𝑅+𝑗
𝑗𝑤𝑐

1 1
𝑍𝐴𝐶 = ඨ𝑅 2 + = ඨ900 +
(𝑤𝑐)2 (2𝑥𝑝𝑖𝑥50𝑥100𝑥10−6 )2

𝑍𝐴𝐶 = 43.74ohm
Compare the resistance between terminal 1 & 2
P + Q = ZBC in parallel with ZAB + ZAC
𝑍𝐵𝐶 (𝑍𝐴𝐵+𝑍𝐴𝐶)
𝑃+𝑄 = 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶
-------------(A)

Resistance between terminal 2 & 3


𝑍𝐴𝐶 (𝑍𝐵𝐶+𝑍𝐴𝐵)
Q + R= 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶
-------------(B)

Resistance between terminal 1 & 3


𝑍𝐴𝐵 (𝑍𝐵𝐶+𝑍𝐴𝐶)
𝑃+𝑅 = 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶
-------------(C)

By Comparing A, B, C equations
𝑍𝐵𝐶 𝑥 𝑍𝐴𝐵 𝑍𝐵𝐶 𝑥 𝑍𝐴𝐶 𝑍𝐴𝐵 𝑥 𝑍𝐴𝐶
P = 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶 Q = 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶 R = 𝑍𝐴𝐵+𝑍𝐴𝐶+𝑍𝐵𝐶
21.49 𝑥 50
P = 50+21.49+43.74

P = 9.325 ohm
21.49 𝑥 43.74
Q = 50+21.49+43.74

Q = 8.157 ohm
43.74 𝑥 50
R = 50+21.49+43.74

R = 18.979 ohm
2.3)

ohmic impendences
Transformer A --B Primary; (33 𝑥 103 )2
8 𝑥 106
x j 0.2

27.225j

Secondary
(11 𝑥 103 )2
x j 0.2
8 𝑥 106

3.025j
Transformer B--C Primary
(11 𝑥 103 )2
x j 0.1
1 𝑥 106

12.1j
Secondary;
(400)2
1 𝑥 106
x j 0.1

0.016j
Load;
ȁ𝑣ȁ2 (400)2
< 𝜃 = < cos−1 0.85
ȁ𝑆ȁ 0.5 𝑥 106
0.32 < 31.788𝑜

Impedance bases (11kv as the voltage base & 8MVA as the systemwide MVA base)

(11 𝑥 103 )2
𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐵; = 15.125 𝑜ℎ𝑚
8 𝑥 106
(400)2
𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐶; = 0.02 𝑜ℎ𝑚
8 𝑥 106
Per unit impendences on new bases
3.025𝑗
Transformer A --B; 15.125 = 0.2j per unit
12.1 𝑗
Transformer B--C; 15.125 = 0.8j per unit
0.32
Load; 0.02 < 31.788 = 16 < 31.788
33𝑘𝑣
𝑉𝑅 = = 1 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡
33𝑘𝑣
16 < 31.788 + 1𝑗
𝑉𝑠 = 1.0 𝑥
16 < 31.788
𝑉𝑆 = 1.033 + 0.0533i

1.35 < 2.95 per unit


The Sending end voltage base is
33 𝑥1000
𝑉𝑠,𝑏𝑎𝑠𝑒 = 11 𝑥 1000
𝑥 11 𝑥 1000 =33kv

∴ 𝑡ℎ𝑒 𝑟𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝑒𝑛𝑑 𝑣𝑜𝑡𝑎𝑔𝑒 𝑖𝑠


𝑉𝑠 = 33 𝑥 103 𝑥1.033 < 2.95
𝑉𝑠 = 34.089𝑘𝑣 < 2.95
𝑉𝑆 = 1.033 + 0.0533i

1.35 < 2.95 per unit