Example 

Design a ribbed mat foundation for the column loads shown in Fig. 
below.
• Column size 40X40cm, ultimate soil bearing capacity = 100kPa,
• Use C25, fyk =300MPa
Y

350kN 770kN 840kN 420kN

4m

630kN
490kN 1120kN 1260kN

4m

350kN 770kN 840kN 420kN


X

4m 4m 4m
Solution 
• Location of center of gravity of loads
Location of center of gravity of loads

ΣP = 2*(350+770+840+420)+490+1120+1260+630 =8260kN
8260⎯X  = (770+1120+770)*4 +(840+1260+840)*8   
+(420+630+420)*12
⎯X
X= 6.27m
6 27
ex =6.27‐6.0 =0.27m

⎯Y = 4m
ey =0
• Actual contact pressure

∑P 6e 8260 6 * 0.27
σ max = (1 + x ) = (1 + ) = 97.66kPa..0 K !
BL L 8 *12 12
∑P 6e 8260 6 * 0.27
σ min = (1 − x ) = (1 − ) = 74.43kPa..0 K !
BL L 8 *12 12

• Design of Slab
• Thickness of slab from deflection requirement
⎛ f yk ⎞ Le
d ≥ ⎜⎜ 0.4 + 0.6 ⎟⎟
⎝ 400 ⎠ β a
• Where      f
Where fyk = characteristic  strength of reinforcement (MPa) 
characteristic strength of reinforcement (MPa)
le = effective span; and, for two‐ way slabs,  the 
p
shorter span
βa = constant (Table 5.1, EBCS‐2)
300 4000
d = ( 0 .4 + 0 .6 * )* = 85 mm
400 40
D = 85 + 50 + 6 = 141 mm
Take D = 145 mm
• Load analysis and moment calculations

• Span AB 4 5 6

• Dead load ,
gd =1m *0.145*25 1 2 3
• Live load , 
qd = 1m*(82.17+74.43)/2 
1m*(82 17+74 43)/2 A B C D

Pd = 1.3 
1.3 *ggd +1.6
+1.6*q
qd
74.43 82.17
89.92 97.66
• Panels 1 and 4
• Moment calculations
Moment calculations
Mxf = αxf *Pd * Lx2
Myf = ααyf *Pd * Ly2

Where
Mxf and Md Myf = field (span) moments per unit width in the x and y 
fi ld ( ) i id h i h d
directions
αxf and αyf = coefficients as  a functions of  Ly/Lx and support 
coefficients as a functions of Ly/Lx and support
condition
Lx =is the shorter span of the panel
Ly = is the longer span of the panel
Lx

Ly
• The  negative moment coefficients are taken as 4/3 times the 
positive moment coefficients for the same directions
positive moment coefficients for the same directions

Mxf

Mys Myf

Mxs

• Division of slab into Middle and Edge Strips
Ly
Edge strrip
Edge strip

Edge strip Lx/8


Middle 3/4Lx
Lx Middle strip
strip
Edge strip Lx/8
Ly/8 3/4Ly
Ly/8
• Balanced moment
– When
When differences of the negative moments on either sides of the 
differences of the negative moments on either sides of the
supports greater than 20%, distribute the differences to both sides 
according to their stiffness. But if the differences of the two sides  less 
than 20% take the average.g

•Thickness of slab from flexural requirement
M max
d≥ , b = 1m
0.32 * b * f cd

• Loads on supporting  Beams
•The design loads on beams supporting solid slabs spanning in two
•The design loads on beams supporting solid slabs spanning in two 
directions at right angles supporting uniformly distributed loads 
may be assessed from the following equations
Vx = β vx ( g d + qd ) Lx
V y = β vy ( g d + qd ) Ly
• The assumed distribution of the load on a supporting beam is 
shown in Fig. below
0.75L

• Dead load of supporting slab
• gd = 1.3 ( D * B *25),   