ThyssenKrupp Industries India ILLUMINATION CALCULATION

Project Name: (4 X 600 MW) O.P.JINDAL TPP, TAMNAR, CHHATTISGARH Client Name: JINDAL POWER LIMITED
Project No: 3M0041
Doc.No: 7402-E-1792
Revision: 0

Quantity & Type Of Fixtures Required

Industrial Industrial Decorative


Trough type Trough type Mirror Optics
70W MH 250W MH 250W MH
Lumen 150W MH Fluorescent Fluorescent Fluorescent
Sr.N Length Height Area Room Average Lux Well Glass Flood Light Street Light
Area Description Width (M) COU Output of MF MediumBay Light Light Tube Light
o. (M) (M) (sq.m) Index Level (BJDWI 70 (BJFL 250 (BGEST 250
Fixture (BJMBI 150 MH) (1x36W) (2x36W) (4x14W)
MH) MH) MH)
(BJIE 136 (BJIE 236 (BTMRA 414
WEB 1) WEB 2) V2)

CONVEYOR GALLERIES
1 Conv 101A/B (Tunnel portion) 125 7.4 3.5 925 2.0 0.42 5300 0.55 100 76 ---- ---- ---- ---- ----
2 Conv 101A/B (Gallery portion) 84 7 3.15 588 2.1 0.42 5300 0.55 100 48 ---- ---- ---- ---- ----
3 Conv 101A/B (Stone picking portion) 12 9 3.15 108 1.6 0.42 5300 0.55 100 9 ---- ---- ---- ---- ----
4 Conv 102A/B 170 7 3.15 1190 2.1 0.43 5300 0.55 100 95 ---- ---- ---- ---- ----
5 Conv 103A/B 90 7 3.15 630 2.1 0.42 5300 0.55 100 51 ---- ---- ---- ---- ----

Transfer Points & OTHER AREAS

6 TP-32A

EL+18.200 11 8.8 4.5 96.8 1.1 0.61 13300 0.55 100 ---- 2 ---- ---- ---- ----

EL+22.700 11 8.8 5.4 96.8 0.9 0.54 13300 0.55 100 ---- 2 ---- ---- ---- ----

Take-up ---- ---- ---- ---- ---- ---- ---- ---- ---- 10 ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 4 ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ---- ---- ---- ---- 10 ---- ---- ---- ----

7 Crusher House

EL-0.200 20 14.5 5.8 290 1.4 0.61 13300 0.55 100 ---- 6 ---- ---- ---- ----

EL+7.300 20 14.5 5.9 290 1.5 0.63 13300 0.55 100 ---- 6 ----

EL+ 14.050 20 14.5 5.7 290 1.1 0.63 13300 0.55 100 ---- 6 ---- ---- ---- ----

EL+21.900 20 14.5 7.9 290 1.1 0.59 13300 0.55 100 ---- 7 ----

Take-up ---- ---- ---- ---- ---- ---- ---- ---- ---- 10 ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 4 ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ---- ---- ---- ---- 30 ---- ---- ---- ----

8 Pent house

EL-0.200 9 6 6 54 0.6 0.54 13300 0.55 100 ---- 1 ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 2 ---- ---- ----

Page 1 of 42
Industrial Industrial Decorative
Trough type Trough type Mirror Optics
70W MH 250W MH 250W MH
Lumen 150W MH Fluorescent Fluorescent Fluorescent
Sr.N Length Height Area Room Average Lux Well Glass Flood Light Street Light
Area Description Width (M) COU Output of MF MediumBay Light Light Tube Light
o. (M) (M) (sq.m) Index Level (BJDWI 70 (BJFL 250 (BGEST 250
Fixture (BJMBI 150 MH) (1x36W) (2x36W) (4x14W)
MH) MH) MH)
(BJIE 136 (BJIE 236 (BTMRA 414
WEB 1) WEB 2) V2)

9 Dumper Unloading Hopper (Shed)

EL+/-0.000 35 10 10 350 0.8 0.54 13300 0.55 100 ---- 9 ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 6 ---- ---- ----

10 Dumper Unloading Hopper (Under ground)


EL-9.350 20 2.2 3.3 44 0.6 0.2 5300 0.55 100 8 ---- ---- ---- ---- ----

EL-9.350 20 5 3.3 100 1.2 0.33 5300 0.55 100 10 ---- ---- ---- ---- ----

EL-9.350 22.5 2.2 3.3 49.5 0.6 0.2 5300 0.55 100 8 ---- ---- ---- ---- ----

EL-9.350 22.5 5 3.3 112.5 1.2 0.33 5300 0.55 100 12 ---- ---- ---- ---- ----

EL-14.500 27 5 3.3 135 1.3 0.37 5300 0.55 100 13 ---- ---- ---- ---- ----

EL-14.500 27 2.5 3.3 67.5 0.7 0.25 5300 0.55 100 9 ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ---- ---- ---- ---- 5 1 ---- ---- ---- ----

11 Pump House
EL-0.200 6 6 5 36 0.6 0.3 13300 0.6 250 ---- 4 ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 4 ---- ---- ----

12 LT Switchgear & VFD Bldg. near CH


Swgr Room EL -0.2M 21 5.5 4.3 115.5 1.0 0.48 6500 0.65 250 ---- ---- ---- ---- 14

Swgr Room EL -0.2M 3 5.5 4.3 16.5 0.5 0.48 6500 0.65 250 ---- ---- ---- ---- 2

Control Room EL -0.2M 12 4 4.3 48 0.7 0.5 6500 0.75 400 ---- ---- ---- ---- 8

Office Room EL -0.2M 5 3.5 4.3 17.5 0.5 0.5 6500 0.75 400 ---- ---- ---- ---- 3

UPS Battery Room EL +/-0.0M 4 4 4.3 16 0.5 0.36 6500 0.65 200 ---- ---- ---- ----

UAF Room 8 5.3 4.3 42 0.66 0.42 6500 0.65 200 ---- ---- 6

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 6

Entrance

13 HT Switchgear Bldg. near TP-32A


Swgr Room EL -0.2M 22 9 4.3 198 1.5 0.48 6500 0.65 250 ---- ---- ---- ---- 24

Swgr Room EL -0.2M 5 4 4.3 20 0.5 0.48 6500 0.65 250 ---- ---- ---- ---- 2

Control Room EL -0.2M 12 4 4.3 48 0.7 0.5 6500 0.75 400 ---- ---- ---- ---- 8

220V DC Battery Room EL -0.2M 7.5 4.1 5 30.75 0.5 0.28 6500 0.65 200 ---- ---- ---- ----

HT Tfr. Yard Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 6

UAF Room 7.9 4.6 4.9 0.59 0.4 6500 ---- ---- 5

Peripheral Light ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 10

Entrance ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

Page 2 of 42
Industrial Industrial Decorative
Trough type Trough type Mirror Optics
70W MH 250W MH 250W MH
Lumen 150W MH Fluorescent Fluorescent Fluorescent
Sr.N Length Height Area Room Average Lux Well Glass Flood Light Street Light
Area Description Width (M) COU Output of MF MediumBay Light Light Tube Light
o. (M) (M) (sq.m) Index Level (BJDWI 70 (BJFL 250 (BGEST 250
Fixture (BJMBI 150 MH) (1x36W) (2x36W) (4x14W)
MH) MH) MH)
(BJIE 136 (BJIE 236 (BTMRA 414
WEB 1) WEB 2) V2)

TOTAL 404 45 20 22 0 54 19

Page 3 of 42
Industrial Industrial Decorative
Trough type Trough type Mirror Optics
70W MH 250W MH 250W MH
Lumen 150W MH Fluorescent Fluorescent Fluorescent
Sr.N Length Height Area Room Average Lux Well Glass Flood Light Street Light
Area Description Width (M) COU Output of MF MediumBay Light Light Tube Light
o. (M) (M) (sq.m) Index Level (BJDWI 70 (BJFL 250 (BGEST 250
Fixture (BJMBI 150 MH) (1x36W) (2x36W) (4x14W)
MH) MH) MH)
(BJIE 136 (BJIE 236 (BTMRA 414
WEB 1) WEB 2) V2)

AC Lighting Load for MLDB in


LT SwGr & VFD Bldg. near Crusher
House
Qty of Lighting Fixtures 166 5 4 16 0 32 8
Consumed kW 14.94 0.875 1.12 4.48 0 2.56 0.64
AC Lighting Load in kVA 30
Provision for Client's Lighting Load in
kVA 0
Total AC Lighting Load in kVA 30 32 with 10% margin
Total AC Emergency Lighting Load in kW 3.3

Qty. of MLDBs in PMCC Room 0

AC Lighting Load for MLDB in


HT SwGr Bldg. near TP-32A
Qty of Lighting Fixtures 52 9 10 16 0 24 19
Consumed kW 4.68 1.575 2.8 4.48 0 1.92 1.52
AC Lighting Load in kVA 21
Provision for Client's Lighting Load in
kVA 0
Total AC Lighting Load in kVA 21 23 with 10% margin
Total AC Emergency Lighting Load in kW 3.3

Qty. of MLDBs in PMCC Room 0

Page 4 of 42
Totally
Enclosed
Corrosion 100W GLS 100W GLS
Proof Bulk Head (DC Distribution of
Fluorescent (DC Emergency Lighting Remarks
Tube Light Emergency Light fixture) fixtures
(2x36W) (BJI Light fixture) (BJDR 100)
236 PC WEB
2))

---- 4 LT SwGr Bldg.

---- 3 LT SwGr Bldg.

---- 0 LT SwGr Bldg.

---- 6 HT SwGr Bldg.

---- 3 HT SwGr Bldg.

---- 2 HT SwGr Bldg.

---- 2 HT SwGr Bldg.

---- HT SwGr Bldg.

---- HT SwGr Bldg.

---- 12 HT SwGr Bldg.

---- 2 LT SwGr Bldg.

2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

2 LT SwGr Bldg.

---- LT SwGr Bldg.

---- LT SwGr Bldg.

---- 34 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- LT SwGr Bldg.

Page 5 of 42
Totally
Enclosed
Corrosion 100W GLS 100W GLS
Proof Bulk Head (DC Distribution of
Fluorescent (DC Emergency Lighting Remarks
Tube Light Emergency Light fixture) fixtures
(2x36W) (BJI Light fixture) (BJDR 100)
236 PC WEB
2))

---- 2 LT SwGr Bldg.

---- LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- 6 LT SwGr Bldg.

---- 2 LT SwGr Bldg.

---- LT SwGr Bldg.

3 LT SwGr Bldg.

LT SwGr Bldg.

3 15 LT SwGr Bldg.

15 LT SwGr Bldg.

2 LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

2 LT SwGr Bldg.

3 HT SwGr Bldg.

HT SwGr Bldg.

3 15 HT SwGr Bldg.

6 HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

---- 2 HT SwGr Bldg.

Page 6 of 42
Totally
Enclosed
Corrosion 100W GLS 100W GLS
Proof Bulk Head (DC Distribution of
Fluorescent (DC Emergency Lighting Remarks
Tube Light Emergency Light fixture) fixtures
(2x36W) (BJI Light fixture) (BJDR 100)
236 PC WEB
2))

8 114 45

Page 7 of 42
Totally
Enclosed
Corrosion 100W GLS 100W GLS
Proof Bulk Head (DC Distribution of
Fluorescent (DC Emergency Lighting Remarks
Tube Light Emergency Light fixture) fixtures
(2x36W) (BJI Light fixture) (BJDR 100)
236 PC WEB
2))

6 33
0.48 3.3

8 33
0.64 3.3

Page 8 of 42
Document No.: 7402-E-1085 Page 1 of 3
Reference: Drg. No. 3M0020 H25 000 01

TYPICAL CALCULATIONS FOR TRANSFER POINT (TP-25)


(Transfer Point TP - 25 at EL -0.200)

Transfer Point Floor Length (L) = 8.5 Meters

Transfer Point Floor Width (W) = 7.6 Meters

Mounting Height (H) = 5.70 Meters

Room Index = LXW


(L + W) x H

= 8.5 x 7.6
(8.5 + 7.6) x 5.7

= 0.7

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %

Type of Lighting Fixture Selected: 150W MH Medium Bay

Co-efficient of Utilisation (COU) = 0.55

Maintenance Factor = 0.55

Average Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 13300 Lux

Number of Lighting Fixtures Required = Lux Level X Area


Lumen O/P X MF X COU

= 100 x (8.5 x 7.6)


13300 x 0.55 x 0.55

= 2

= 2 Nos.
Document No.: 7402-E-1085 Page 2 of 3
Reference: Drg. No. 3M0020 H25 000 01

TYPICAL CALCULATIONS FOR TRANSFER POINT (TP-25)


(Transfer Point TP - 25 at EL +5.800)

Transfer Point Floor Length (L) = 8.5 Meters

Transfer Point Floor Width (W) = 7.6 Meters

Mounting Height (H) = 4.7 Meters

Room Index = LXW


(L + W) x H

= 8.5 x 7.6
(8.5 + 7.6) x 4.7

= 0.85

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %

Type of Lighting Fixture Selected: 150W MH Medium Bay

Co-efficient of Utilisation (C.O.U) = 0.58

Maintenance Factor = 0.55

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 13300 Lux

Number of Lighting Fixtures Required = Lux Level X Area


Lumen O/P X MF X COU

= 100 x (8.5 x 7.6)


13300 x 0.55 x 0.58

= 3

= 3 Nos.
Document No.: 7402-E-1085 Page 3 of 3
Reference: Drg. No. 3M0020 H25 000 01

TYPICAL CALCULATIONS FOR TRANSFER POINT (TP-25)


(Transfer Point TP - 25 at EL +10.940)

Transfer Point Floor Length (L) = 8.5 Meters

Transfer Point Floor Width (W) = 7.6 Meters

Mounting Height (H) = 5.3 Meters

Room Index = LXW


(L + W) x H

= 8.5 x 7.6
(8.5 + 7.6) x 5.3

= 0.76

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %

Type of Lighting Fixture Selected: 150W MH Medium Bay

Co-efficient of Utilisation (C.O.U) = 0.56

Maintenance Factor = 0.55

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 13300 Lux

Number of Lighting Fixtures Required = Lux Level X Area


Lumen O/P X MF X COU

= 100 x (8.5 x 7.6)


13300 x 0.55 x 0.56

= 3

= 3 Nos.
Document No.: 7402-E-1085 Page 1 of 2
Reference: Drg. No. 3M0020 C29 000 01

TYP. CAL. FOR CONVEYOR 29 GALLERY

Conveyor Gallery Length (L) = 52.0 Meters

Conveyor Gallery Width (W) = 4.2 Meters

Mounting Height (H) = 2.7 Meters

Room Index = LXW


(L + W) x H

= 52 x 4.2
(52 + 4.2) x 2.7

= 1.44

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %

Type of Lighting Fixture Selected: 70W MH Well Glass

Co-efficient of Utilisation (COU) = 0.37

Maintenance Factor = 0.55

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Lux Level X Area


Lumen O/P X MF X COU

= 100 x (52 x 4.2)


(5300 x 0.55 x 0.38)

= 22

= 22 Nos.
Document No.: 7402-E-1085 Page 2 of 2
Reference: Drg. No. 3M0020 C14 000 01

TYP. CAL. FOR CONVEYOR 14A/B GALLERY

Conveyor Gallery Length (L) = 291.0 Meters

Conveyor Gallery Width (W) = 7.9 Meters

Mounting Height (H) = 3.15 Meters

Room Index = LXW


(L + W) x H

= 291 x 7.9
(291 + 7.9) x 3.15

= 2.44

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %

Type of Lighting Fixture Selected: 70W MH Well Glass

Co-efficient of Utilisation (C.O.U) = 0.46

Maintenance Factor = 0.55

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Lux Level X Area


Lumen O/P X MF X COU

= 100 x (291 x 7.9)


(5300 x 0.55 x 0.46)

= 172

= 172 Nos.
ThyssenKrupp Industries India
Project Name: 2 x 660 MW NCC Power project
Project No: 3M0043
Doc.No: 7402-E-1852
Revision: 0

Sr.N Length Height Area Room


Area Description Width (M) COU
o. (M) (M) (sq.m) Index

CONVEYOR GALLERIES
BCN E-1A/B ( Crusher to JNT-1E) 245 8.5 2.5 2082.5 3.3 0.54
1 BCN 1A/B ( Crusher to JNT-1) 134 8.5 2.5 1139 3.2 0.54
2 BCN 1A/B ( JNT-1 to JNT-2) 112 8.5 2.5 952 3.2 0.54
3 BCN 1A/B ( JNT-2 to JNT-3) 111.7 8.5 2.5 949.45 3.2 0.54
4 BCN 2A (up to JNT-6) 68 5 2.5 340 1.9 0.43
5 BCN 2B ( up to JNT-5) 68 5 2.5 340 1.9 0.43
6 BCN 2C ( up to JNT-4) 106 5 2.5 530 1.9 0.43
7 BCN 3A/B ( JNT-4 to NT-5) 111.7 7.7 2.5 860.09 2.9 0.5
8 BCN 3A/B ( JNT-5 to JNT-6) 112 7.7 2.5 862.4 2.9 0.5
9 BCN 3A/B ( JNT-6 to JNT-7) 484 7.7 2.5 3726.8 3.0 0.5
10 BCN 4A/B ( JNT-7 to JNT-8) 324 7.7 2.5 2494.8 3.0 0.5
11 BCN 4A/B ( JNT-8 to JNT-9) 265 7.7 2.5 2040.5 3.0 0.5
12 BCN 5A/B ( JNT-9 to JNT-10) 294 7.7 2.5 2263.8 3.0 0.5
BCN 6A/B ( JNT-10 to MCC room-3
13
onwards) 231 7.7 2.5 1778.7 3.0 0.5

Transfer Points & OTHER AREAS

14 JNT-1
EL+0.00 12.5 11.8 4.2 147.5 1.4 0.37

EL+0.00 (B-C portion) 7.3 3.5 4.2 25.55 0.6 0.29

EL+4.2 12.5 11.8 5.6 147.5 1.1 0.33


EL+9.8 12.5 11.8 4.2 147.5 1.4 0.37

EL+19.2 12.5 11.8 5.2 147.5 1.2 0.33

Take-up ---- ---- ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ----

JNT-2

EL+0.00 12.5 11.8 4.2 147.5 1.4 0.37

EL+0.00 (B-C portion) 7.3 3.5 4.2 25.55 0.6 0.29

EL+4.2 12.5 11.8 5.6 147.5 1.1 0.33

EL+9.8 12.5 11.8 4.2 147.5 1.4 0.37

EL+19.2 12.5 11.8 5.2 147.5 1.2 0.33

Take-up ---- ---- ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ----

JNT-3

EL+0.00 16 11.7 4 187.2 1.7 0.43

EL+9.30 16 11.7 5.3 187.2 1.3 0.37

EL+14.5 16 11.7 5.2 187.2 1.3 0.37

EL+20.7 16 11.7 6.2 187.2 1.1 0.27

Take-up ---- ---- ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ----

JNT-4

EL+0.00 12 8.5 4.5 102 1.1 0.33

EL+9.30 12 8.5 3.4 102 1.5 0.37

EL+14.5 12 8.5 5.3 102 0.9 0.37

EL+20.7 12 8.5 6.2 102 0.80252 0.24

Take-up ---- ---- ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ----

JNT-5
EL+0.00 10 9 8.5 90 0.6 0.48
EL+8.5 12.5 9 6 112.5 0.87209 0.24
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

JNT-6
EL+0.00 10 9 8.5 90 0.6 0.48
EL+8.5 12.5 9 6 112.5 0.87209 0.24
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

JNT-7
EL+0.00 12 10 5.4 120 1.0 0.29
EL+0.00 (B-C) 3.5 10 9.4 35 0.3 0.48
EL+5.4 12 10 5 120 1.1 0.33
EL+9.4 16 11.7 6 187.2 1.1 0.33
EL+9.4 (B-C) 3.5 10 3.9 35 0.7 0.29
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

JNT-8
EL+0.00 13 10 7.5 130 0.8 0.24
EL+7.5 13 10 5.5 130 1.0 0.29
EL+13.0 10 10 3.5 100 1.4 0.37
EL+16.25 13 10 3 130 1.9 0.43
EL+20.5 13 10 6.5 130 0.9 0.24
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

JNT-9
EL+0.00 12 10.5 7.5 126 0.7 0.48
EL+7.5 12 10.5 4.7 126 1.2 0.33
EL+12.2 12 10.5 3.5 126 1.6 0.43
EL+15.7 12 10.5 7 126 0.8 0.53
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

JNT-10
EL+0.00 12 10.5 39 126 0.1 0.48
EL+39.00 12 10.5 4.2 126 1.3 0.33
EL+43.20 12 10.5 6 126 0.9 0.43
EL+49.20 12 10.5 3.5 126 1.6 0.53
EL+52.70 3.8
EL+56.50 6.7
Take-up ---- ---- ---- ---- ---- ----
Peripheral Light ---- ---- ---- ---- ---- ----
Stair Case Light ---- ---- ---- ---- ---- ----

15
Crusher House

EL+0.00 24.5 23.6 5.5 578.2 2.7 0.5

EL+5.5 24.5 23.6 4.5 578.2 2.4 0.47

EL+ 10.0 24.5 23.6 5.0 578.2 1.9 0.37

EL+15.0 24.5 23.6 6.3 578.2 1.9 0.36

EL+21.3 24.5 23.6 4.3 578.2 2.8 0.59

EL+25.6 24.5 23.6 10.6 578.2 1.1 0.56

EL+25.6 24.5 23.6 6 578.2 2.0 0.36

Take-up ---- ---- ---- ---- ---- ----

Peripheral Light ---- ---- ---- ---- ---- ----

Stair Case Light ---- ---- ---- ---- ---- ----

16 CHP control / MCC room-1


EL+0.00 40 20 5 800 2.7 0.68

Control Room EL +5.0M 12 4 4.3 48 0.7 0.5

Peripheral Light ---- ---- ---- ---- ---- ----

17 MCC room-2 / comp. room


EL+/-0.000 53 14.7 5 779.1 2.3 0.66
Control Room EL +5.0M 12 4 4.3 48 0.7 0.5

Peripheral Light ---- ---- ---- ---- ---- ----

18 MCC room-3
EL+/-0.000 53 14.7 5 779.1 2.3 0.66

Control Room EL +5.0M 12 4 4.3 48 0.7 0.5

Peripheral Light ---- ---- ---- ---- ---- ----

19 Pump House
EL-0.200 6 6 5 36 0.6 0.3

Peripheral Light ---- ---- ---- ---- ---- ----

20 LT Switchgear & VFD Bldg. near CH


Swgr Room EL -0.2M 21 5.5 4.3 115.5 1.0 0.48

Swgr Room EL -0.2M 3 5.5 4.3 16.5 0.5 0.48

Control Room EL -0.2M 12 4 4.3 48 0.7 0.5

Office Room EL -0.2M 5 3.5 4.3 17.5 0.5 0.5

UPS Battery Room EL +/-0.0M 4 4 4.3 16 0.5 0.36

UAF Room 8 5.3 4.3 42 0.66 0.42

Peripheral Light ---- ---- ---- ---- ---- ----

Entrance

21 HT Switchgear Bldg. near TP-32A


Swgr Room EL -0.2M 22 9 4.3 198 1.5 0.48

Swgr Room EL -0.2M 5 4 4.3 20 0.5 0.48

Control Room EL -0.2M 12 4 4.3 48 0.7 0.5

220V DC Battery Room EL -0.2M 7.5 4.1 5 30.75 0.5 0.28

HT Tfr. Yard Light ---- ---- ---- ---- ---- ----

UAF Room 7.9 4.6 4.9 0.59 0.4

Peripheral Light ---- ---- ---- ---- ---- ----

Entrance ---- ---- ---- ---- ---- ----

TOTAL

AC Lighting Load for MLDB in


LT SwGr & VFD Bldg. near Crusher
House
Qty of Lighting Fixtures
Consumed kW
AC Lighting Load in kVA
Provision for Client's Lighting Load in
kVA
Total AC Lighting Load in kVA

Total AC Emergency Lighting Load in kW

Qty. of MLDBs in PMCC Room

AC Lighting Load for MLDB in


HT SwGr Bldg. near TP-32A
Qty of Lighting Fixtures
Consumed kW
AC Lighting Load in kVA
Provision for Client's Lighting Load in
kVA
Total AC Lighting Load in kVA

Total AC Emergency Lighting Load in kW

Qty. of MLDBs in PMCC Room


ILLUMINATION CALCULATION
Client Name: NCC Power Project Lt

Quantity & Type Of Fixtu

70W MH 250W MH
Lumen 150W MH
Average Lux Well Glass 150W MH HighBay Flood Light
Output of MF MediumBay
Level (BJDWI 70 (BJHBI 150 MH) (BJFL 250
Fixture (BJMBI 150 MH)
MH) MH)

5300 0.50 100 146

5300 0.50 100 80 ---- ----

5300 0.50 100 67 ---- ----

5300 0.50 100 66 ---- ----

5300 0.50 100 30

5300 0.50 100 30

5300 0.50 100 47

5300 0.50 100 65 ---- ----

5300 0.50 100 65 ---- ----

5300 0.50 100 281

5300 0.50 100 188

5300 0.50 100 154

5300 0.50 100 171

5300 0.50 100 134

5300 0.5 100 15 ----

5300 0.5 100 3

5300 0.5 100 17 ----


5300 0.5 100 15

5300 0.5 100 17

---- ---- ---- 10 ----

---- ---- ---- ---- 4

---- ---- ---- 10 ----

5300 0.5 100 15

5300 0.5 100 3

5300 0.5 100 17

5300 0.5 100 15

5300 0.5 100 17

---- ---- ---- 10

---- ---- ---- ----

---- ---- ---- 10

5300 0.5 100 16

5300 0.5 100 19

5300 0.5 100 19

13300 0.5 100 - 10

---- ---- ---- 10

---- ---- ---- ----

---- ---- ---- 10

5300 0.5 100 12

5300 0.5 100 10

5300 0.5 100 10

13300 0.5 100 - 6

---- ---- ---- 10

---- ---- ---- ----

---- ---- ---- 10


13300 0.5 100 - 3
13300 0.5 100 - 7
---- ---- ---- 10
---- ---- ---- ----
---- ---- ---- 10

13300 0.5 100 - 3


13300 0.5 100 - 7
---- ---- ---- 10
---- ---- ---- ----
---- ---- ---- 10

5300 0.5 100 16


13300 0.5 100 - 1
5300 0.5 100 14
5300 0.5 100 21
5300 0.5 100 5
---- ---- ---- 10
---- ---- ---- ----
---- ---- ---- 10

13300 0.5 100 - 8


5300 0.5 100 17
5300 0.5 100 10
5300 0.5 100 11
13300 0.5 100 - 8
---- ---- ---- 10
---- ---- ---- ----
---- ---- ---- 14

13300 0.5 100 - 4


5300 0.5 100 14
5300 0.5 100 11
13300 0.5 100 - 4
---- ---- ---- 10
---- ---- ---- ----
---- ---- ---- 12

13300 0.5 100 - 4


5300 0.5 100 14
5300 0.5 100 11
13300 0.5 100 - 4

---- ---- ---- 10


---- ---- ---- ----
---- ---- ---- 12

5300 0.5 100 44 ----

5300 0.5 100 46

5300 0.5 100 59 ----

13300 0.5 100 - 24

5300 0.5 100 37

13300 0.5 100 - 16

13300 0.5 100 - 24

---- ---- ---- ----

---- ---- ---- 4

---- ---- ---- 46 ----

6500 0.5 250 ---- ---- ----

6500 0.5 500

---- ---- ---- ---- 2

6500 0.5 250 ---- ---- ----


6500 0.5 500

---- ---- ---- ---- 6

6500 0.5 250 ---- ---- ----

6500 0.5 500

---- ---- ---- ---- 6

13300 0.6 250 ---- 4 ----

---- ---- ---- ---- 4

6500 0.65 250 ---- ---- ----

6500 0.65 250 ---- ---- ----

6500 0.75 400 ---- ---- ----

6500 0.75 400 ---- ---- ----

6500 0.65 200 ---- ---- ----

6500 0.65 200 ----

---- ---- ---- ---- ---- ----

6500 0.65 250 ---- ---- ----

6500 0.65 250 ---- ---- ----

6500 0.75 400 ---- ---- ----

6500 0.65 200 ---- ---- ----

---- ---- ---- ---- ---- ----

6500 ----

---- ---- ---- ---- ---- ----

---- ---- ---- ---- ----

2183 114 26
182 0 4
16.38 0 1.12
30
0
30 33 with 10% margin
3.1
0

Err:502 Err:502 Err:502


Err:502 Err:502 Err:502
Err:502
0
Err:502 Err:502 with 10% margin
Err:502
Err:502
CC Power Project Ltd

Quantity & Type Of Fixtures Required

Totally
Industrial Industrial Decorative Enclosed
Trough type Trough type Mirror Optics Corrosion 100W GLS 100W GLS
250W MH
Fluorescent Fluorescent Fluorescent Proof Bulk Head (DC
Street Light
Light Light Tube Light Fluorescent (DC Emergency
(BGEST 250
(1x36W) (2x36W) (4x14W) Tube Light Emergency Light fixture)
MH)
(BJIE 136 (BJIE 236 (BTMRA 414 (2x36W) (BJI Light fixture) (BJDR 100)
WEB 1) WEB 2) V2) 236 PC WEB
2))

---- ---- ---- ---- 4

---- ---- ---- ---- 4

---- ---- ---- ---- 4

---- ---- ---- ---- 4

---- ---- ---- ---- 4

---- ---- ---- ---- 2

---- ---- ---- ---- 2


---- ---- ---- ----

---- ---- ---- ----

---- ---- ---- ---- 12


---- ---- ---- ---- 2

---- 2

---- ---- ---- ---- 2

---- 2

---- ---- ---- ----

---- ---- ---- ----

---- ---- ---- ---- 34

---- ---- 90 ---- ---- 2

15

---- ---- ---- ----

---- ---- 91 ---- ---- 2


15

---- ---- ---- ----

---- ---- 91 ---- ---- 2

15

---- ---- ---- ----

---- ---- ---- ---- 2

---- ---- ---- ----

---- 14 3

---- 2

---- 8 3 15

---- 3 15

---- 2

---- 6

---- 24 3

---- 2

---- 8 3 15

---- 6

---- 5

10

---- ---- ---- 2

22 0 371 19 8 101 45
16 0 32 8 6 31
4.48 0 2.56 0.64 0.48 3.1

th 10% margin

Err:502 Err:502 Err:502 Err:502 Err:502 Err:502


Err:502 Err:502 Err:502 Err:502 Err:502 Err:502

th 10% margin
Distribution of
Lighting Remarks
fixtures

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.
HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.
LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.
LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

LT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.

HT SwGr Bldg.
Document No.: 7402-E-1852 Page 1 of 7
Reference: Drg. No. 3M0043 H01 000 01 NCC drg. No. NPT10111-PE-V-GA-410100-005

TYPICAL CALCULATIONS FOR JNT-1


(At EL +0.000)

Floor Length (L) = 12.5 Meters

Floor Width (W) = 11.8 Meters

Mounting Height (H) = 4.20 Meters

Room Index = LXW


(L + W) x H

= 12.5 x 11.8
(12.5 + 11.8) x 4.2

= 1.4

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)
Co-efficient of Utilisation (COU) = 0.37

Maintenance Factor = 0.5

Average Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (12.5 x 11.8)


5300 x 0.5 x 0.37

= 15

= 15 Nos.
Document No.: 7402-E-1852 Page 2 of 7
Reference: Drg. No. 3M0043 H01 000 01 NCC drg. No. NPT10111-PE-V-GA-410100-005

TYPICAL CALCULATIONS FOR JNT-1


(At EL +4.20)

Floor Length (L) = 12.5 Meters

Floor Width (W) = 11.8 Meters

Mounting Height (H) = 5.60 Meters

Room Index = LXW


(L + W) x H

= 12.5 x 11.8
(12.5 + 11.8) x 5.6

= 1.1

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)
Co-efficient of Utilisation (COU) = 0.33

Maintenance Factor = 0.5

Average Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (12.5 x 11.8)


5300 x 0.5 x 0.33

= 17

= 17 Nos.
Document No.: 7402-E-1852 Page 3 of 7
Reference: Drg. No. 3M0043 H01 000 01 NCC drg. No. NPT10111-PE-V-GA-410100-005

TYPICAL CALCULATIONS FOR JNT-1


(At EL +9.80)

Floor Length (L) = 12.5 Meters

Floor Width (W) = 11.8 Meters

Mounting Height (H) = 4.20 Meters

Room Index = LXW


(L + W) x H

= 12.5 x 11.8
(12.5 + 11.8) x 4.2

= 1.4

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)
Co-efficient of Utilisation (COU) = 0.37

Maintenance Factor = 0.5

Average Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (12.5 x 11.8)


5300 x 0.5 x 0.37

= 15

= 15 Nos.
Document No.: 7402-E-1852 Page 4 of 7
Reference: Drg. No. 3M0043 H01 000 01 NCC drg. No. NPT10111-PE-V-GA-410100-005

TYPICAL CALCULATIONS FOR JNT-1


(At EL +19.20)

Floor Length (L) = 12.5 Meters

Floor Width (W) = 11.8 Meters

Mounting Height (H) = 5.20 Meters

Room Index = LXW


(L + W) x H

= 12.5 x 11.8
(12.5 + 11.8) x 5.2

= 1.2

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)
Co-efficient of Utilisation (COU) = 0.33

Maintenance Factor = 0.5

Average Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (12.5 x 11.8)


5300 x 0.5 x 0.33

= 17

= 17 Nos.
Document No.: 7402-E-1852 Page 5 of 7
Reference: Drg. No. 3M0043 C00 000 03 ( Preliminary)

TYP. CAL. FOR CONVEYOR GALLERY BCN-1A/B

Conveyor Gallery Length (L) = 134.0 Meters

Conveyor Gallery Width (W) = 8.5 Meters

Mounting Height (H) = 2.5 Meters

Room Index = LXW


(L + W) x H

= 134 x 8.5
(134 + 8.5) x 2.5

= 3.20

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well Glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)

Co-efficient of Utilisation (COU) = 0.54

Maintenance Factor = 0.50

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (134 x 8.5)


(5300 x 0.5 x 0.54)

= 80

= 80 Nos.
Document No.: 7402-E-1852 Page 6 of 7
Reference: Drg. No. 3M0043 C00 000 03 ( Preliminary)

TYP. CAL. FOR YARD CONVEYOR GALLERY- BCN 2A

Conveyor Gallery Length (L) = 68.0 Meters

Conveyor Gallery Width (W) = 5.0 Meters

Mounting Height (H) = 2.50 Meters

Room Index = LXW


(L + W) x H

= 68 x 5.0
(68 + 5.0) x 2.5

= 1.86

Reflection Factors
Ceiling = 50 %
Wall = 30 %
Floor = 10 %
For calculation purpose, bajaj
Type of Lighting Fixture Selected: 70W HPSV Well Glass make fittings are considered.
( BJVW / BJVWI 70W SON / E)

Co-efficient of Utilisation (C.O.U) = 0.43

Maintenance Factor = 0.50

Lux Level = 100 Lux

Lumen Output of Lighting Fixture = 5300 Lux

Number of Lighting Fixtures Required = Avg. Lux Level X Area


Lumen O/P of single fixture X MF X COU

= 100 x (68 x 5)
(5300 x 0.5 x 0.43)

= 30

= 30 Nos.