SOP (Standard Operation Procedures)

MPS (Main Pumping Station)


1

10

11

Sludge Thickner & Anarobic Daigester


1

2
3

10

11

SBR C-Tech Basin


1

5
6

10

Teriary Treatment Plant


1

9
10

Laboratory
1

9
10
11
SOP (Standard Operation Procedures)
MPS (Main Pumping Station)
Coarse Screen should be operate regularly.

MPS Pump Should be working regularly as 06 W/ 02 S/B

Daily cleaning of Manual Coarse Screen and cleaning of all floating debris.

Submersible mixer should operate regularly.

Pumps should be operate & change by regular interval.

Daily Checking of all pumps gland & greasing condition and observe any obsessional so

Fine Screen should be operate by sump level and regular clean all coming debris

Grit Classifier Will regularly operate and grit should be clean periodically

Inlet flow record should be maintained hourly .

Primary Clarifier launder and scum box should clean by daily.

Primary sludge should be withdrawal regular as require & observe sludge concentration
laboratory chemist it should be more then 3-5 %.

Sludge Thickner & Anarobic Daigester


PST Sludge Should be more then 3-5 % and it should be regulary feed to sludge thickne

Daily Cleaning of Floting material and Scum from Sludge thickner Surface Its Scum Box
regularly.
Underflow sludge of Sludge Thickner should be more then 5-8 % and its pH should be 7

Feed sludge to the Anarobic Daigester TS % is 5-8 % and VSS % 60-70 %.

Anarobic Daigester Alkalinity Should be more then 2000 & VFA should be less then 40

VFA and Alkalinity retio should be 1:4.

Sludge feeding , Daigester recirculation pump and Gas Compressor Should be operate
schedule.

Sludge withdrawl (bleedoff) should be done regulary as per givven schedule.

underflow sludge of anarobic Daigester TS % is not more then 10-15 %.

Regulary monitor of sludge overflow Rate it should be regulary overflowing during slud
the Anarobic daigester.

Regularly monitor of Gas and sludge pipeline it should not leakage during operation.

SBR C-Tech Basin


All SBR should be operate as per design perameter. Tank level should not more then 4.5

Regulary monitor of level sensor, Water sensor and Decanter sensoer it should be work

Air Blower should be operate as per design perameter minimum 4 Air blower should be
feeling & Aeration mode.( 3 soft starter 01 VFD for DO management)

SBR MLSS Value should not more then 3000-3500 mg/ltr. And is DO should be more the

SBR Cycle should be operate 244 minute / batch.120 min (Feeling) 61 min (Settling) 63
Outlet Water of SBR tank should be crystal in color and odorless suspended partical sho
neglageble.

Chloring Gas should be dose 5.00 ppm in outlet of secondary water by 24 hrs .

Secondry water Permeter is as follows: - pH-7.0-7.5 , BOD > 20mg/l COD >100 mg/l & T

DO meter of all SBR tank should be working condition.

Excess sludge of SBR tank should be waste regulary to maintane MLSS .

Teriary Treatment Plant


Both pumps are shoud be in working Condition. 1 W 1 S/B. it should be operate by 24 h

Chemical Dosing at inlet of TTP should be dose by regulary.all dosing pump are in work
1W and 1S/B.
Fecl3 dose 20 mg/ltr with 10 % of solution strength Lime dose 50 mg/l with 10 % of sol
and Poly Electrolyte 5 mg/l with .25 % of solution strength.

Clariflocculator should be in working codition With all agitator.

RGF medial should be back wash 02 time in a day.

05 ppm Chlorine Gas should be dose reguarly in TTP chlorine content tank.

Under flow sludge of Clariflocculator should not more then 1 %. And it should be regula
the Clariflocculator.

Dairty backwash sump should be empty at the end of the backwash procedure.

Overhead tank should be full of water at the end of the back wash procedure.
All pumps Oil level, glands Grease should be check daily.

Laboratory
Daily Analysis of Following perameter;- .

Raw Sewage :-pH, TSS COD BOD Temp

Primary Outlet: pH, BOD COD TSS TS% VSS%

SBR Tank :- DO, MLSS, MLVSS, SV30,SVI .

Secondary Outlet:- pH, DO, BOD, COD, TSS.

Tertiary Outlet:- pH, DO, BOD, COD, TSS.

Primary under flow sludge: pH, TS% VSS%

Sludge Thickner under flow sludge: pH, TS% VSS%

Anarobic Sludge Daigester: pH , alkalinity ,VFA , temp. TS% ,VSS%


All analysis record and logsheet should be maintaine daily