Sunteți pe pagina 1din 14

Energy 170 (2019) 185e198

Contents lists available at ScienceDirect

Energy
journal homepage: www.elsevier.com/locate/energy

Analysis of an improved economizer system for active control of the


coal-fired boiler flue gas temperature
Pengcheng Xiao, Yanping Zhang*, Yuanjing Wang, Jizhou Wang
School of Energy and Power Engineering, Huazhong Uni. of Sci. and Tech., Wuhan, 430074, China

a r t i c l e i n f o a b s t r a c t

Article history: The use of a low pressure economizer (LPE) is an effective way to recover waste heat from the exhaust
Received 11 September 2018 flue gas in thermal power plants. In this paper, an improved bypass staged economizer scheme is pre-
Received in revised form sented for China's 600-MW ultra-supercritical power units. The simulation models of the bypass staged
28 November 2018
economizer and traditional LPE were established based on a 600-MW unit. The simulation results
Accepted 19 December 2018
showed that when the presented economizer system was adopted, the temperature of the exhaust flue
Available online 19 December 2018
gas was reduced to near the flue gas acid dew point, thereby greatly improving the energy-saving effects.
Compared with the traditional LPE system, the improved economizer system can reduce standard coal
Keywords:
Bypass staged economizer system
consumption rate by an additional 1.1 g/kWh. The bypass ratio under different loads could be adjusted to
Waste heat recovery achieve the best energy-saving effect. The optimum bypass ratio was analyzed under different loads. The
Off-design condition results showed that the improved economizer system had a better energy-saving effect by actively
Coal-fired power plant controlling the exhaust flue gas temperature.
© 2018 Elsevier Ltd. All rights reserved.

1. Introduction meeting the requirements of China's national environmental pro-


tection regulations. It is more desirable to decrease the exhaust flue
In China, coal consumption accounts for 62% of the total energy gas temperature and make full use of waste heat of the exhaust flue
consumption, with coal being mainly used as a boiler fuel. To the gas.
best of our knowledge, boiler exhaust heat loss accounts for the The utilization of waste heat of flue gas in thermal power plants
largest proportion of total heat loss [1]. High exhaust gas temper- can effectively increase the efficiency of power generation. There
atures will affect the economic operation of the boiler. In the actual are numerous methods to recover the flue gas waste heat. The
long-term operation of coal-fired power plants (CFPPs), the degree organic Rankine cycle system can use the low grade heat from the
of pollution of the heating surface increases with the boiler running exhaust gas to produce high grade energy and improve the unit
time, so that the exhaust gas temperature of the long-term oper- efficiency. The use of the organic Rankine cycle has been analyzed
ation boiler is higher than the design temperature of 10e30  C. As by many researchers [3e5]. Heat pump heat recovery technology is
shown in Ref. [2], when the exhaust gas temperature of a 400 t/h mainly aimed at gas boilers with high water vapor content in
ultra-high pressure boiler increases 10e15  C, the exhaust heat loss exhaust flue gas. The heat pump is used to recover heat of
will increase 1%, and standard coal consumption rate will increase condensation to heat feedwater in regenerative system [6e10].
2e3 g/kWh. Moreover, a method has been developed to extract the latent heat
Currently, the emissions requirements for air pollutants in CFPPs of water vapor from the flue gas to recover the waste heat [11e14].
are increasingly strict. Some CFPPs have begun to use lower tem- There is also system for waste heat recovery integrated with an
perature electrostatic precipitator (ESP) technology, which requires SeCO2 cycle for CFPPs [15].
that the inlet flue gas temperature of the ESP be lower than the acid Compared to the waste heat recovery methods mentioned
dew point temperature. The lower temperature ESP technology can above, the LPE is the most widely used to recover waste heat from
not only capture sulfur trioxide but also reduce PM2.5 emissions to the exhaust flue gas to heat the feedwater. The LPE is usually
installed at the end of the flue and similar to the high pressure
economizer in structure. The water side of the LPE is connected to
the low pressure feedwater heater (FWH) of the regenerative sys-
* Corresponding author.
tem to allow a part of the extraction steam to be saved and continue
E-mail address: zyp2817@hust.edu.cn (Y. Zhang).

https://doi.org/10.1016/j.energy.2018.12.147
0360-5442/© 2018 Elsevier Ltd. All rights reserved.
186 P. Xiao et al. / Energy 170 (2019) 185e198

to perform work in the steam turbine. In terms of thermodynamics, and case study 2 should be higher than the low temperature acid
the first law and the second law were used to evaluate the effi- dew point to prevent corrosion of the heat transfer surfaces.
ciencies of the LPE installed in a CFPP. The thermal equilibrium The baseline case is the original design system for comparison,
efficiencies and the second law efficiencies increased, whereas the as shown in Fig. 2. The schematic thermal system of Case study 1 is
first law efficiency decreased after applying the LPE [16]. Different shown in Fig. 3. The extracted steam for heating the feedwater in
connections of the LPE with the steam turbine recovery heat system FWH No. 6 is replaced by the heat recovered by the LPE. The LPE
have been discussed [17e19]. Analysis results show that very little inlet of the feedwater is connected with the outlet of FWH NO.7 and
increase in the back pressure of the steam turbine occurs when a the LPE outlet of feedwater is connected with the inlet of FWH
proper LPE is installed, i.e., there are few negative impacts on the NO.5. The LPE is installed between the air preheater and the ESP.
operation of the boiler thermal system. Moreover, the recovered The schematic thermal system of Case study 2 is shown in Fig. 4.
heat from heating the high temperature feedwater has a better The flue separation system is built at the downstream of the high
energy saving effect than heating the low temperature feedwater. pressure economizer. The flue is divided into a main flue and a
There are many in-service units that have been retrofitted with the bypass flue by adding separate flue baffles and a control valve. A
traditional LPE in China, such as the Yudong power plant [20] and part of the high temperature flue gas from the outlet of the high
the Shangdu power plant [21]. However, the traditional LPE has a temperature economizer is bypassed. First, the bypassed flue gas is
defect in terms of the larger heat transfer temperature difference, used to heat the feedwater from the outlet of the feedwater pump
which leads to not making full use of waste heat. Therefore, it is in the first-stage bypass economizer. The heated feedwater is led to
shown that greater benefits resulted from installing the two stages the outlet of FWH NO. 2. The cooled flue gas is led to the second-
air preheater system proposed in Ref. [22]. A lignite-fired power stage bypass economizer to heat the condensate from the outlet
plant was transformed by adding an additional high pressure of FWH NO. 6. The heated condensate is led to the outlet of FWH
economizer to increase the unit gross efficiency [23]. A bypass flue NO. 5. The main flue gas is cooled by the air preheater and then
scheme that can effectively recover waste heat was constructively mixed with the bypassed flue gas. A new device named pre-air
proposed in the 1000-MWe lignite-fired power plant Nieder- preheater is set up in the position after the flue gas mixture to
aussem Unit K [24]. The exhaust flue gas is cooled from approxi- heat the air and cool the flue gas to ensure the exhaust flue gas
mately 160  Ce100  C. Based on this scheme, different plant temperature and air temperature are appropriate. The mixed flue
configurations and the relevant cost analyses were simulated by gas passes through the pre-air preheater and finally leads to the
Aspen Plus under low temperature exhaust flue gas [25,26]. ESP. The air passes through the pre-air preheater to the main air
However, most relevant studies have focused on the energy- preheater and eventually to the boiler furnace. This approach can
saving effects through structural improvement and the analysis of not only make full use of boiler exhaust heat to reduce exhaust flue
thermodynamics. Only a few studies have shown the operational gas temperature but also reduce the heat rate of the steam turbine
strategy of a reliable scheme. For example, when the heat transfer system.
area of the LPE is fixed, the exhaust gas temperature cannot be
controlled because of the fluctuations in the flue gas temperature 3. Model approach
caused by long-term operation, which may cause low temperature
corrosion. 3.1. Model of the prototype unit
In this paper, an efficient flue gas waste heat recovery system is
proposed. The simulation model was built to analyze the perfor- To study the thermal economic performance of the bypass
mance of the presented heat recovery system and the traditional staged economizer system, a simulation model of a 600-MW pro-
LPE system. The optimum bypass ratio was analyzed under totype unit is established by MATLAB/Simulink (version 7.0.1) in
different loads. The results showed that the improved economizer this paper. The thermal system model of the CFPP is constructed
system had a better energy-saving effect by actively controlling the according to the structure shown in Fig. 1. The whole plant model
exhaust flue gas temperature. consists of three main modules, namely, the boiler, the steam tur-
bine and the regenerative system. First, the parameters of the main
2. Design of improved economizer system steam and reheat steam are simulated from the boiler and input to
the steam turbine model. The steam turbine model simulates the
The boiler discussed in this paper is China's most widely used pressure and enthalpy of each extraction port and input to the
600-MW supercritical once-through boiler, which produces regenerative system, and the boiler simulation results are corrected
531.4 kg/s of superheated steam at 25.4 MPa and 571  C and 440 kg/ by calculating the exhaust parameters of the high pressure cylinder.
s of reheated steam at 3.83 MPa and 569  C in BMCR working The regenerative system simulates the extraction steam flow to
condition. The coal used is bituminous with 62.83% carbon, 3.62% feedback to the steam turbine model and the feedwater parameters
hydrogen, 9.94% oxygen, 0.70% nitrogen, and 0.41% sulfur, and the to feedback to the boiler model. The main working parameters of
lower heating value (LHV) is 22760 kJ/kg. The boiler efficiency is the whole unit can be simulated by inputting the wind, coal
estimated as 93.55% (LHV basis). Fig. 1 shows a diagram of the parameter and steam flow from the boiler side. The prototype unit
power plant system structure. There are three high pressure FWHs, simulation model is shown in Fig. 5.
one deaerator and four low pressure FWHs. The overall perfor- The simulation model of the supercritical once-through p type
mances of the unit are included in Table 1, and the details of the boiler is divided into spiral water wall, vertical water wall, partition
steam parameters are showed in Table 2. screen superheater, high temperature reheater, the finishing su-
In this study, an improved bypass staged economizer system is perheater, low temperature reheater hot forging, coated tube, low
proposed to recover the waste heat of the exhaust flue gas. To temperature reheater cold section, economizer, and air preheater,
facilitate the comparison and analysis, the calculation and analysis as shown in Fig. 6. The model building methods in these sub-
of the original design system and the traditional LPE system are modules are similar. According to the structure of the boiler and
conducted at the same time. Table 3 shows the descriptions of the the thermodynamic process, the boiler is divided into several
three case studies. The minimum exhaust flue gas temperature is coupling horizontal layers, and the simultaneous equations are
restricted by the dew point of SOx to prevent low temperature acid used to represent the inner horizontal layer of the thermodynamic
corrosion. The exhaust flue gas temperature design of case study 1 process. Parameter changes exist in the vertical direction, and
P. Xiao et al. / Energy 170 (2019) 185e198 187

Prh
P0

HP IP P5 LP LP

Pc
Boiler
P2 P1 P3 P4
P6 P7
P8
Condenser

Tc

DEA

1FWH 2FWH 3FWH 5FWH 6FWH 7FWH 8FWH

Fig. 1. The schematic diagram of a 600-MW generation unit.

Table 1 vertical direction. According to this structure and mathematical


The overall performance of the unit on THA condition. equations [27,28], the boiler system is modeled successfully.
Main steam kg/s 465.3 The steam turbine adopts single reheat structure consisting of a
Reheat steam kg/s 389.0
high pressure cylinder, a medium pressure cylinder and two low
Flue gas mass flow rate kg/s 615.6 pressure cylinders. The input parameters of the steam turbine
Coal input rate kg/s 59.8 system model are steam pressure, temperature and flow, and then,
Lower heating value of coal kJ/kg 22760 the system is simulated using the following sub-modules in turn:
Gross electrical output MWe 607.3
the control valve, the governing stage, the grade group 1, the grade
Total auxiliary power MWe 30.4
Net electrical output MWe 576.9 group 2, the boiler reheater, the grade group 3, the grade group 4,
Gross efficiency % 44.64 the connected pipe and the grade group 5 to 9. The parameters of
steam extraction of the steam turbine can be simulated. The
regenerative system mainly includes the following sub-modules:
parameter changes in every horizontal layer can be ignored. The feedwater heater model, deaerator model, condenser model, pipe
thermodynamic process in one layer is simplified by means of the model and pump model. Among them, the small steam turbine
lumped-parameter method, and the thermal parameters of the model is the same as the turbine pressure stage model modeling
boiler are lumped in the horizontal direction and coupled in the process. The mathematical modeling process of each system of
steam turbine was described in detail in Ref. [29], and the system

Table 2
Details of the steam performance.

Items NO.1 FWH NO.2 FWH NO.3 FWH Deaerator NO.5 FWH NO.6 FWH NO.7 FWH NO.8 FWH

Extracted steam pressure (MPa) 5.977 4.047 1.829 0.951 0.392 0.119 0.059 0.019
Extracted steam enthalpy (kJ/kg) 3054.8 2970.1 3376.2 3189.1 2974.9 2733.8 2621.1 2493.7
Extracted steam flow rate (kg/s) 28.95 40.50 16.91 21.91 22.92 11.29 15.17 9.87
Outlet feedwater temperature ( C) 275 249.2 206.4 180.8 138.2 100.3 81.21 54.81
Drain temperature ( C) 254.8 211.9 186.4 0 105.9 86.87 60.19 42.52

Table 3
Descriptions of the case studies.

Cases Descriptions

Baseline The designed power plant system without waste heat recovery
Case study The power plant system with traditional LPE with one-stage LPE to heat the feedwater
1
Case study The power plant system with a bypass staged economizer system and with a control valve to divide the flue, the first-stage LPE to heat the feedwater, the
2 second-stage LPE to heat the condensate, and the pre-air preheater to preheat the air
188 P. Xiao et al. / Energy 170 (2019) 185e198

Flue gas
Economizer

FWH FWH FWH FWH FWH FWH FWH


NO. 1 NO. 2 NO. 3 Deaerator NO. 5 NO. 6 NO. 7 NO. 8
$LU

Flue gas
Pump

Air preheater
$LU

Flue gas

ESP

Fig. 2. Schematic of the thermal system of the baseline case.


Flue gas

Economizer

FWH FWH FWH FWH FWH FWH FWH


NO. 1 NO. 2 NO. 3 Deaerator NO. 5 NO. 6 NO. 7 NO. 8
$LU

Flue gas

Pump

Air preheater
Flue gas
$LU

LPE
Flue gas

ESP

Fig. 3. Schematic of the thermal system of case study 1.

diagram of each subsystem of steam turbine system established in further calculate the operating characteristics of the bypass staged
MATLAB/Simulink is given in Fig. 5. economizer system and calculate the energy-saving effect, a suit-
The boiler system and the steam turbine system simulation able unit simulation computing platform is established.
model are coupled and connected to establish the simulation
model of the coal-fired unit; the model intuitively reflects the
3.2. Unit model with bypass staged LPE systems
operating characteristics of the coal-fired unit and accurately sim-
ulates the operating parameters of equipment. According to the
An economizer model is developed to investigate the perfor-
design data of a 600-MW supercritical unit, the calculation results
mance of different LPE systems under all conditions by the water-
of the model are verified. The model calculation results have high
wall heat exchange surface mathematical method [27]. Case
accuracy compared with the design data. Among the data points
studies 1 and 2 can be modeled based on the prototype unit model
used to verify the calculation, the data points with error less than
built above. The bypass staged economizer system simulation
3% accounted for 97% of all data points, as shown in Table 4. To
model of case study 2 is introduced in Fig. 7. The import parameters
P. Xiao et al. / Energy 170 (2019) 185e198 189

Flue gas
Economizer
FWH FWH FWH FWH FWH FWH FWH
NO. 1 NO. 2 NO. 3 Deaerator NO. 5 NO. 6 NO. 7 NO. 8

Flue gas Pump


$LU

First-stage
economizer
Air preheater
Second-stage
economizer
$LU

Control
valve
Pre-air preheater
Flue gas
$LU

ESP

Fig. 4. Schematic thermal system of case study 2.

of the model are the flue gas temperature at the outlet of the high water vapor will condense on the wall, resulting in the low tem-
pressure economizer, the flue gas flow rate, the condensate inlet perature acid corrosion.
temperature and the feedwater inlet temperature. The heat transfer The following equations given by “Boiler Unit Thermal Calcu-
area under rated load can be calculated by assuming the heat lation Standard Method” of the former Soviet Union is widely used
transfer end difference. When the share of the bypass flue gas is to calculate the flue gas dew point:
given, the temperature increase in the condensate and feedwater,
the heat of the flue gas being cooled and the temperature of the flue pffiffiffiffiffi
b  3 Sn
gas before entering the pre-air preheater can be calculated. tsld ¼ tld þ (1)
1:05ah A
n
The simulation model of the baseline case is the prototype unit,
as shown in Fig. 5. The traditional LPE is connected with the pro-
totype unit model between the ESP and the air preheater in the tld ¼ 1:2102 þ 8:4064gh  0:4749g2h þ 0:01042g3h (2)
simulation model of case study 1. The detailed simulation model of
scheme 1 is omitted here. The unit simulation model of case study 2
is shown in Fig. 8; a part of exhaust flue gas is sent to the bypass Sn ¼ 4187Sar =Qnet (3)
economizers to heat the condensate and the feedwater. The heated
feedwater and condensate are returned to the regenerative system.
Therefore, the heat consumption of the steam turbine system and An ¼ 4187Aar =Qnet (4)
the standard coal consumption rate of the entire unit will be
reduced. The model of the steam turbine system also must increase where t sld is the flue gas acid dew point, tld is the water vapor dew
the input of heat at the corresponding location. point in the flue gas calculated by Eq. (2). b is a constant associated
with the excess air ratio aT , aT < 1.25, b ¼ 121; aT > 1.25,
and b ¼ 129. Sn is the converted share of the flue sulfur; Sar is the
4. Model of performance share of the sulfur in the as received flue. An is the converted share
of the flue ash. Aar is the share of the ash in the as received flue. Qnet
4.1. Acid dew point is the LHV of as received flue. ah is the fly ash content of the flue ash,
generally taken as 0.9 in China. gh is the share of water vapor in the
To avoid corrosion caused by a low temperature heating surface flue gas.
to ensure boiler operation safety and improve boiler efficiency, low Eq. (1) showed that the flue gas acid dew point t sld is mainly
temperature acid corrosion is one of the important factors that related to the water vapor dew point t ld . t ld varies with the share of
must be considered when reducing the exhaust gas temperature. water vapor in flue gas under different loads. The flue gas acid dew
When the temperature of the wall surface is lower than the acid point of the boiler discussed in this paper under different loads is
dew point, the sulfuric acid vapor produced by sulfur trioxide and calculated, as shown in Table 5.
190 P. Xiao et al. / Energy 170 (2019) 185e198

D_MS, P_MS, T_MS The flow, pressure and temp of the main steam T_DW The temp of the primary desuperheating water
P_RS, T_RS The pressure and temp of the reheated steam D_PA, T_PA The flow and temp of the primary air
D_FW, P_FW, T_FW The flow, pressure and temp of the feed water D_SA, T_SA The flow and temp of the secondary air
The flow of the primary and secondary The flow and temp of the outlet flue gas of
D_PDW, D_SDW D_FG_Eco T_FG_Eco
desuperheating water economizer

Fig. 5. The prototype unit simulation model.

4.2. The heat rate and standard coal consumption rate 4.3. The bypass ratio

Because the accurate model of the whole unit mentioned above The bypass flue gas flow is controlled by the flue baffle. The
can be used, relevant accurate data can be extracted directly from bypass ratio is actually a mathematical description of the opening
the model when the economizer model is connected to the steam degree of the flue baffle. The bypass ratio is the proportion of the
turbine model and the regenerative system model. Coal, wind, and flue gas flow entering the bypass flue to the outlet flue gas flow of
water-related input parameters can be calculated when the load the high temperature economizer and can be calculated by Eq. (7):
and coal quality are entered. After the calculation of the boiler
model, the parameters of the pressure, temperature and flow of the Fby
R¼ (7)
main steam and reheated steam can be calculated. When the Ft
output parameters of the boiler are used as the input parameters of
the steam turbine system model, the power generation and the where R is the bypass ratio; Fby is the bypassed flue gas flow; Ft is
enthalpy of the inlet reheated steam can be calculated. the outlet flue gas flow of the high temperature economizer.
The heat rate and standard coal consumption rate can be
calculated by Eq. (5) and Eq. (6): 5. Results and discussion

Q0    .
5.1. Performance analysis of THA condition
q¼ ¼ D0 h0  hfw þ Drh ðhrh  h1 Þ Pe (5)
Pe
The performance parameters of three cases are simulated at the
Bcp BQnet turbine heat-rate acceptance (THA) condition with electric power
bcp ¼ ¼ (6) output at 600 MW. The temperature parameters of the baseline
Pe 29270Pe
case can be extracted in the prototype unit model. In case study 1,
where q is the heat rate; Q0 is the heat consumption; Pe is the unit the outlet temperature of the high pressure economizer is 347.4  C.
power; D0 and Drh are the main steam flow and the reheat steam The air is heated from 25 to 313.3  C. The flue gas side temperature
flow, respectively; h0 and hfw represent the enthalpy of the main of the air preheater will drop to 135.8  C. The feedwater from the
steam and the enthalpy of the boiler feedwater, respectively. hrh outlet of the FWH NO. 7 is heated by the exhaust flue gas then sent
and h1 represent the enthalpy of the reheat steam and the enthalpy to the outlet of FWH NO. 6. The flue gas temperature will drop to
of the high pressure cylinder outlet, respectively. 95.4  C.
P. Xiao et al. / Energy 170 (2019) 185e198 191

Low
temper-
Division High ature
Final
panel tenper- reheater Coated
super-
Flue gas parameters super- ature (high pipes
heater
(flow temperature heater reheater temperat
component) ure HP Cylinder Exhaust
section)

Low temper-
Vertical ature
water wall Steam parameters reheater
(flow temperature (low
model pressure)
Reheat temperature )
steam FWH NO. 1 Outlet
Super-
heated
steam
Spiral water
wall model
Economizer

Coal parameters
(consumption
Gas
ingredient content)

Air
preheater
Air parameters
(flow temperature)
Air Feedwater parameters
(flow temperature
pressure)

Fig. 6. The boiler system model.

Table 4
Value of operating parameters.

Parameter (THA condition) Design value Simulation value Relative error (%)

Main steam P_MS (MPa) 25.4 25.22 0.71


T_MS ( C) 571 570.6 0.4a
Reheat steam P_RS (MPa) 3.83 3.79 1.04
T_RS ( C) 569 568.3 0.7a
Power Generator power (MW) 600238 602010 0.30
No. 1 FWH P1 (MPa) 5.977 6.111 2.24
h1 (kJ/kg) 3054.8 3056 0.04
D1 (kg/s) 28.95 28.76 0.66
No. 2 FWH P2 (MPa) 4.047 4.237 4.69
h2 (kJ/kg) 2970.1 2977 0.23
D2 (kg/s) 40.50 40.37 0.32
No. 3 FWH P3 (MPa) 1.829 1.833 0.22
h3 (kJ/kg) 3376.2 3374 0.07
D3 (kg/s) 16.91 17.05 0.83
DEA P4 (MPa) 0.9513 0.9593 0.84
h4 (kJ/kg) 3189.1 3188 0.03
D4 (kg/s) 21.91 21.84 0.32
No. 5 FWH P5 (MPa) 0.3915 0.3967 1.33
h5 (kJ/kg) 2974.9 2978 0.10
D5 (kg/s) 22.92 22.90 0.09
No. 6 FWH P6 (MPa) 0.1189 0.1221 2.69
h6 (kJ/kg) 2733.8 2738 0.15
D6 (kg/s) 11.29 11.30 0.09
No. 7 FWH P7 (MPa) 0.05871 0.05953 1.40
h7 (kJ/kg) 2621.1 2623 0.07
D7 (kg/s) 15.17 15.30 0.86
No. 8 FWH P8 (MPa) 0.01874 0.01915 2.19
h8 (kJ/kg) 2493.7 2540 1.86
D8 (kg/s) 9.87 9.91 0.41
a
Absolute error.
192 P. Xiao et al. / Energy 170 (2019) 185e198

Flue gas flow Flue gas flow Flue gas flow Air temperature

Flue gas temperature Flue gas temperature Air flow


Pre-Air
Air flow Air preheater Flue gas temperature Mixture
Air flow preheater Exhaust flue gas flow

Air Temperature Air temperature Air temperature Exhaust flue gas temperature

Bypass ratio

Bypass flue gas flow Flue gas flow Flue gas flow

Flue gas temperature Flue gas temperature

First-stage Feedwater flow Second-stage Flue gas temperature


Feedwater pump flow
economizer economizer
Feedwater pump temperature Feedwater temperature

Feedwater temperature Feedwater temperature

Fig. 7. The simulation model of the bypass staged economizer system.

Low
Divisio High temper-
Final ature
n panel tenper- Coated
super- reheater
Flue gas parameters super- ature (high pipes
heater
(flow temperature heater reheater temperatur
HP Cylinder Exhaust
component) e section)

Low temper-
ature
Vertical water reheater
Steam parameters
wall model (low
(flow temperature
Reheat pressure) temperature )
FWH NO.1 Outlet
steam
Super-
heated
Spiral water steam
wall model
Economizer
Mixture

Gas Pre-air
preheater

Air
preheater

Heated air from


pre-air preheater Bypass Condensate
Condensate
staged
economizer
Feedwater
Steam turbine system Feedwater

Fig. 8. The unit simulation model of the bypass staged economizer system.
P. Xiao et al. / Energy 170 (2019) 185e198 193

Table 5 When the inlet flue gas temperature changes significantly in


The flue gas acid dew point under different loads. case study 1 and case study 2, to ensure that the economizer
Load (MW) 660 600 550 500 450 feedwater outlet temperature matches the temperature of the
Flue gas acid dew point ( C) 79.21 79.26 78.55 77.94 77.35
corresponding FWH at the regenerative system, the inlet feedwater
flow should be controlled. In case study 2, when controlling water
flow changes in variable load conditions, the bypass ratio and the
flow of the second-stage feedwater is fixed. The first-stage feed-
When case study 2 is adopted, the following assumptions are
water flow varies with the load, making it easier to control and
made. The share of bypass gas is designed to be 15% preliminarily.
adjust, as shown in Fig. 11.
Because the flow of flue gas into the air preheater is reduced by 15%,
The performance parameters change significantly when the
the outlet temperature of the air drops from 313.3  C to 266.1  C,
load changes in different cases. As shown in Fig. 12, coal con-
and the outlet temperature of the flue gas drops to 112  C; this
sumption is set to be constant; because of the reduced steam
situation will ensure proper boiler operation. To ensure the air
extraction in the regenerative system, power generation will in-
preheater outlet air temperature, a pre-air preheater can be
crease. The higher the load, the more extra power will be gener-
installed to increase the air inlet temperature of the air preheater to
ated. The average extra power generation in case study 2 under
69.7  C downstream of the flue gas mixing point. The ratio of
different loads is 5292.9 kW, which is more than that of case study
feedwater drawn out of the feedwater pump outlet pipe is 5.1%; this
1 at 2431.7 kW. The heat rate and standard coal consumption rate
feedwater is sent to the first-stage bypass economizer and then
for each load condition can be calculated using Eq. (8) and Eq. (9), as
heated from 175.4  C to 249.1  C before finally being led to the
shown in Fig. 13 and Fig. 14. The heat rate and standard coal con-
outlet of the FWH NO. 2. The mixing point can be selected on the
sumption rate decrease as the load increases. The average heat rate
boiler side to reduce the pipeline investment and part of the
of case study 2 under different loads is 57 kJ/kWh lower than that of
pipeline pressure loss. The ratio of condensate drawn out of outlet
case study 1. The average standard coal consumption rate of case
of FWH NO. 6 was 13.4%; this condensate was sent to the second-
study 2 under different loads is 1.1 g/kWh lower than that of case
stage bypass economizer and heated from 96.8 to 138.2  C before
study 1. The reduction in the heat rate and standard coal con-
finally being led to the outlet of FWH NO. 5.
sumption rate does not change much as the load changes. In Fig. 15,
The energy-saving indicators of the three cases are compared in
the waste heat recovery systems are beneficial to the unit, enabling
Table 6 and Fig. 9. When the scheme of the bypass staged econo-
the unit to gross efficiency as the load increases. The average gross
mizer is adopted, the temperature of the flue gas entering the ESP
efficiency of case study 2 under different loads is 0.2% higher than
can be reduced to 95.6  C which is almost the same with the Case
that of case study 1. From the performance parameters, although
study 1 (95.4  C). But with lower Heat rate, case study 2 has lower
case study 1 has a certain energy-saving effect, case study 2 has a
standard coal consumption rate. Compared with the traditional LPE
better energy saving effect than case study 1 under different loads.
system, the new type economizer has better energy-saving effects,
and the standard coal consumption rate decreased significantly.
5.3. Bypass ratio optimization analysis

5.2. Performance analysis of the part load conditions In case study 2, the change in the bypass ratio will directly affect
the exhaust gas temperature. For example, the flow of bypassed
When the unit load changes, the outlet temperature of the air flue gas will change when the bypass ratio changes at the THA
preheater will also change significantly. In this situation, the energy working condition. To ensure that the economizer feedwater outlet
saving effect of these cases is a matter of concern. In Fig. 10, the temperature matches the temperature of the corresponding FWH
temperature of exhaust flue gas varies with the load. The design at the regenerative system, the flow of feedwater of two stage
temperatures of case study 1 and case study 2 are the same at the economizers should be correspondingly changed. The changes in
THA condition; thus, the exhaust temperature is similar between flow of two stage economizers in different bypass ratios are shown
case studies 1 and 2. However, in comparison to the baseline, the in Fig. 16. The second-stage feedwater flow is changed for main
exhaust temperature is greatly reduced by an average of 34.9  C. adjustment, while the first-stage feedwater flow is changed for
Notably, when the load is less than 600 MW, the exhaust temper- auxiliary adjustment.
ature is lower than the design temperature. The acid dew point is The exhaust flue gas temperatures of the unit under different
calculated according to Eq. (1) and Eq. (2) as 81.42  C with the load loads with different bypass ratios are shown in Fig. 17. Fig. 18 shows
changes. The exhaust temperature is 77.86  C at 450 MW, i.e., when the energy saving effects of case study 2 at different bypass ratios,
the load is lower than 450 MW, the heat recovery system faces the which are compared with the results of case study 1. The exhaust
risk of acid corrosion. Thus, the performance analyses only consider flue gas temperature is different when the load and bypass ratio
loads between 450 MW and 600 MW. change. The greater the bypass ratio is, the lower the exhaust

Table 6
Comparison of performance parameters in three cases.

Parameter Unit Baseline Case study 1 Case study 2

Unit power kW 601931 604978 607393


Coal consumption t/h 215.2 215.2 215.2

Inlet air temperature of air preheater C 25 25 69.7
Standard coal consumption rate g/kWh 278 276.6 275.5
Heat rate kJ/kWh 7495 7470.9 7438.8
Flue gas bypass ratio % 0 0 15

Exhaust flue gas temperature C 135.8 95.4 95.6
Boiler efficiency % 94.08 95.05 95.12
Reduction of the heat rate kJ/kWh 0 24.1 56.2
Reduction of the standard coal consumption rate g/kWh 0 1.4 2.5
194 P. Xiao et al. / Energy 170 (2019) 185e198

300 278 276.6 300


275.5
Baseline
Case study 1
250 250
Case study 2

Standard coal consumption rate(g/kWh)


200 200

Temperature( )
150 135.8 150

95.4 95.6
100 100

50 50

0 0
SCE consumption Exhaust flue gas temperature

Fig. 9. Comparison of the standard coal consumption rate and the exhaust flue gas temperature.

140

130

120
Temperature ( )

110

100

90
Baseline
80
Case study 1
70
Case study 2
60
400 450 500 550 600 650
Load (MW)

Fig. 10. Temperature of the exhaust flue gas under different loads in the three case studies.

55

50

45

40
Flow (kg/s)

35

30

25

20 First-stage
15 Second-stage
10
400 450 500 550 600 650
Load (MW)

Fig. 11. The inlet feedwater flow under different loads.


P. Xiao et al. / Energy 170 (2019) 185e198 195

6000
Case study 1
5500
Case study 2

Extra power generation (kW)


5000

4500

4000

3500

3000

2500

2000
440 460 480 500 520 540 560 580 600 620
Load (MW)

Fig. 12. Extra power generation under different loads.

7850
Baseline

7750 Case study 1

Case study 2
Heat rate (kJ/kWh)

7650

7550

7450

7350
400 450 500 550 600 650
Load (MW)

Fig. 13. Heat rate under different loads.

290
Baseline
Standard coal consumption rate (g/kWh)

288
Case study 1
286 Case study 2

284

282

280

278

276

274
400 450 500 550 600 650
Load (MW)

Fig. 14. Standard coal consumption rate under different loads.


196 P. Xiao et al. / Energy 170 (2019) 185e198

45

44.5

Unit gross efficiency (%)


44

43.5

43
Baseline
42.5 Case study 1

Case study 2
42
400 450 500 550 600 650
Load (MW)

Fig. 15. Unit gross efficiency under different loads.

90
First Stage
80
Second Stage
70

60
Flow (kg/s)

50

40

30

20

10
10 15 20 25 30 35 40 45
Bypass ratio (%)

Fig. 16. The flow of two stage economizers in different bypass ratios.

95
550MW

500MW
90
600MW
Temperature ( )

450MW

85

80

75
5 10 15 20 25 30 35 40 45
Bypass ratio (%)

Fig. 17. The exhaust flue gas temperature of case study 2 at different bypass ratios.
P. Xiao et al. / Energy 170 (2019) 185e198 197

Standard coal consumption rate reduction


2.5

2
(g/kWh)

1.5

1 600MW
550MW
0.5 500MW
450MW
0
5 10 15 20 25 30 35 40 45
Bypass ratio (%)

Fig. 18. The energy saving effects of case study 2 at different bypass ratios.

temperature. Therefore, flue gas temperature control can be ach- bypass ratio. This ratio can ensure not only that the temperature of
ieved by adjusting the bypass ratio. Taking into account the flue gas flue gas at inlet of the lower temperature ESP is 80  C but also that
acid dew point limit, the exhaust gas temperature must be operations are safe. The higher the unit load, the greater the pro-
controlled at above 80  C. The maximum bypass ratio can be read portion of flue gas that can be used to heat the feedwater and
from Figs. 17 and 18. The bypass ratio should be controlled below condensate and the lower the standard coal consumption rate.
42% when the load is 600 MW. The corresponding maximum en- Therefore, the performance of case study 2 is better than case study 1.
ergy saving effect is approximately 2.5 g/kWh. If the bypass ratio is
greater than 42%, then the temperature of the flue gas at the inlet of
the ESP will be below the acid dew point (80  C). When the load is 6. Conclusions
550 MW, the bypass ratio should be controlled below 31%. The
corresponding maximum energy saving effect is approximately An improved economizer system for China's typical 600-MW
2.3 g/kWh. When the load is 500 MW, the bypass ratio should be ultra-supercritical power units is proposed that can effectively
controlled below 19%. The corresponding maximum energy saving recover the waste heat and increase the unit efficiency. The scheme
effect is approximately 1.8 g/kWh. When the load is 450 MW, the can be used not only for the transformation of the economizer
bypass ratio should be controlled below 13%. The corresponding system of the existing unit in China but also for the design of the
maximum energy saving effect is approximately 1.4 g/kWh. new unit. The following conclusions are drawn from this study:
The optimal bypass flue gas ratio and the best coal saving effects
for different loads are shown in Fig. 19. The unit can adjust the (1) At the THA condition, in comparison with the baseline, the
separate flue baffles according to different loads to achieve the best bypass staged economizer can reduce the standard coal
consumption rate by 2.5 g/kWh at the optimal bypass ratio.

45 3

40
2.5
Standard coal consumption rate

35
reduction(g/KWh)
Bypass ratio (%)

30
2
25

20 1.5

15
Optimal bypass ratio 1
10
Optimal SCE consumption reduction
5 0.5
400 450 500 550 600 650
Load (MW)

Fig. 19. Optimal bypass ratio and best coal saving effects for different loads.
198 P. Xiao et al. / Energy 170 (2019) 185e198

Because of the cascade utilization of the exhaust flue gas Chinese].


[3] Dai Y, Wang J, Gao L. Parametric optimization and comparative study of
energy, the energy-saving effect of the bypass staged econ-
organic Rankine cycle (ORC) for low grade waste heat recovery. Energy
omizer is better than that of the traditional LPE. This tech- Convers Manag 2009;50(3):576e82.
nology can reduce standard coal consumption rate by an [4] Liu BT, Chien KH, Wang CC. Effect of working fluids on organic Rankine cycle
additional 1.1 g/kWh compared to that of the traditional LPE. for waste heat recovery. Energy 2004;29(8):1207e17.
[5] Łukowicz H, Kochaniewicz A. Analysis of the use of waste heat obtained from
(2) Different bypass ratios have different energy-saving effects, coal-fired units in Organic Rankine Cycles and for brown coal drying. Energy
which are controlled by adjusting the control valve for 2012;45(1):203e12.
different exhaust gas temperatures to achieve active control [6] Qu M, Abdelaziz O, Yin H. New configurations of a heat recovery absorption
heat pump integrated with a natural gas boiler for boiler efficiency
of the exhaust gas temperature. Therefore, a unit can achieve improvement. Energy Convers Manag 2014;87:175e84.
the best energy-saving state by adjusting the control valve to [7] Wei M, Yuan W, Song Z, Fu L, Zhang S. Simulation of a heat pump system for
ensure the bypass ratio is optimal under different load con- total heat recovery from flue gas. Appl Therm Eng 2015;86:326e32.
[8] Wei M, Zhao X, Fu L, Zhang S. Performance study and application of new coal-
ditions, thereby eliminating the problem of low air temper- fired boiler flue gas heat recovery system. Appl Energy 2017;188:121e9.
ature of the air preheater outlet in the bypass staged [9] Zhao H, Dai P, Cao S, Hao Q. Waste heat recovery system using coal-fired
economizer system. The flue gas temperature is low, but it is boiler flue gas to heat heating network return water. In: Li A, Zhu Y, Li Y,
editors. Lecture notes in electrical engineering; 2014. p. 567e75.
higher than the acid dew point, thereby enabling the ESP to
[10] Zhu K, Xia J, Xie X, Jiang Y. Total heat recovery of gas boiler by absorption heat
operate safely and efficiently. pump and direct-contact heat exchanger. Appl Therm Eng 2014;71(1):213e8.
[11] Manassaldi JI, Mussati SF, Scenna NJ. Optimal synthesis and design of heat
recovery steam generation (HRSG) via mathematical programming. Energy
Acknowledgments
2011;36(1):475e85.
[12] Wang D, Bao A, Kunc W, Liss W. Coal power plant flue gas waste heat and
This research was supported by the National Basic Research water recovery. Appl Energy 2012;91(1):341e8.
[13] Westerlund L, Hermansson R, Fagerstro € m J. Flue gas purification and heat
Program of China (Project No. 2015CB251504).
recovery: a biomass fired boiler supplied with an open absorption system.
Appl Energy 2012;96:444e50.
Nomenclature [14] Xiong Y, Niu Y, Wang X, Tan H. Pilot study on in-depth water saving and heat
recovery from tail flue gas in lignite-fired power plant. Energy Proc 2014;61:
2558e61.
tsld flue gas dew point,  C [15] Liu M, Zhang X, Ma Y, et al. Thermo-economic analyses on a new conceptual
tld water vapor dew point,  C system of waste heat recovery integrated with an S-CO2 cycle for coal-fired
aT excess air ratio power plants[J]. Energy Convers Manag 2018;161:243e53.
[16] Wang C, He B, Yan L, Pei X, Chen S. Thermodynamic analysis of a low-pressure
Sn converted share of the flue sulfur economizer based waste heat recovery system for a coal-fired power plant.
Sar share of the sulfur in the as-received flue Energy 2014;65:80e90.
An converted share of the flue ash [17] Wang C, He B, Sun S, Wu Y, Yan N, Yan L, et al. Application of a low pressure
economizer for waste heat recovery from the exhaust flue gas in a 600 MW
Aar share of the ash in the as-received flue
power plant. Energy 2012;48(1):196e202.
ah fly ash content of the flue ash [18] Xu G, Xu C, Yang Y, Fang Y, Li Y, Song X. A novel flue gas waste heat recovery
gh share of water vapor in the flue gas system for coal-fired ultra-supercritical power plants. Appl Therm Eng
2014;67(1e2):240e9.
h specific enthalpy, kJ/kg
[19] Yang Y, Xu C, Xu G, Han Y, Fang Y, Zhang D. A new conceptual cold-end design
q heat rate, kJ/kWh of boilers for coal-fired power plants with waste heat recovery. Energy
Q heat consumption, J/s Convers Manag 2015;89:137e46.
D working fluid flow, t/h [20] Jin C, Chen T, Xu J. Research on reform plan of low temperature economizer of
2315 MW unit. Henan Chem Ind 2013;Z3:15e9 [in Chinese].
Pe power, W [21] Liu Q. Thesis for the master degree retrofit of low temperature economizer for
Bcp coal consumption, t/h 2660MW unit in the third-stage project of Shangdu power plant. North
bcp standard coal consumption rate, g/kWh China Electric Power University; 2017 [in Chinese].
[22] Xu G, Huang S, Yang Y, Wu Y, Zhang K, Xu C. Techno-economic analysis and
Qnet minimum heat value, kJ/kg optimization of the heat recovery of utility boiler flue gas. Appl Energy
F bypass ratio 2013;112(SI):907e17.
Fby bypassed flue gas flow, kg/s [23] Han X, Liu M, Zhai M, Chong D, Yan J, Xiao F. Investigation on the off-design
performances of flue gas pre-dried lignite-fired power system integrated with
Ft total flue gas flow waste heat recovery at variable external working conditions. Energy 2015;90:
1743e58.
Abbreviations [24] Henderson C. Fossil fuel-fired power generation :case studies of recently
constructed coal- and gas-fired power plants. Paris: OECD/IEA; 2007.
LPE low-pressure economizer
[25] Espatolero S, Romeo LM, Cortes C. Efficiency improvement strategies for the
ESP electrostatic precipitator feedwater heaters network designing in supercritical coal-fired power plants.
CFPP coal-fired power plant Appl Therm Eng 2014;73(1):449e60.
[26] Espatolero S, Cortes C, Romeo LM. Optimization of boiler cold-end and inte-
FWH feedwater heater
gration with the steam cycle in supercritical units. Appl Energy 2010;87(5):
THA turbine heat rate acceptance 1651e60.
LHV lower heating value [27] Wang J, Zhang Y, Li Y, Huang S. A non-equal fragment model of a water-wall
in a supercritical boiler. J Energy Inst 2015;88(2):143e50.
[28] Qi L, Huang S, Zhang Y, Xu X, Li Y, Wang Y. A compartmental model for su-
References percritical coal-fired boiler systems. J Energy Resour ASME
2014;136(0216022).
[1] Annual report on the development of China's electric power industry. Beijing: [29] Zhang Y, Wang J, Yang S, Gao W. An all-condition simulation model of the
Electricity Council; 2017 [in Chinese]. steam turbine system for a 600MW generation unit. J Energy Inst 2016;91(2):
[2] Zeng X. Analysis and countermeasure on boiler exhaust gas superheating in 279e88.
cogeneration power plant. North China Electr Power 2004;03:44e6 [in

S-ar putea să vă placă și