RELAY COORDINATION
SEZ 11KV BUS FAULT
FAULT LEVEL 111.5856525 MVA
FAULT CURRENT 5856.899667 A
11 KV FEEDER (SEZ)
CTR 125 6
3 O/L 90%
TL 0.05
CURVE 3
TIME 0.15
FAULT CURRENT ( Fault Current/CT RATIO) 46.8551973 A
TRIPPING TIME 0.087386348 SECS
11 KV SEZ FEEDER
CTR 1000 4
3 O/L 40%
1 TL 0.14
CURVE 3
TIME 0.42
FAULT CURRENT ( Fault Current/CT RATIO) 5.85689967 A
TRIPPING TIME 0.360327035 SECS
11 KV SEZ FEEDER AT MRS DIVISION
CTR 1000 4
3 O/L 40%
TL 0.22
CURVE 3
TIME 0.66
FAULT CURRENT ( Fault Current/CT RATIO) 5.85689967 A
TRIPPING TIME 0.566228198 SECS
11 KV LV
CTR 1500
3 O/L 21%
TL 0.37
2 CURVE 3
TIME 1.11
FAULT CURRENT ( Fault Current/CT RATIO) 3.90459978 A
TRIPPING TIME 0.874458327 SECS
2
2
14.6422
SION 1.5
INST
14.6422 0.5
0
0 1000 2000 3000
18.5933
INST
O/L
BREAKER CT RATIO
3.9046 %
11KV FEEDER 125 90%
11KV SEZ 1000 40%
11KV SEZ AT MRS
1000 40%
DIVISION
11KV LV 1500 21%
110KV HV &
150 100%
INCOMER
FAULT AT 11KV BUS
0.22 0.66 4
0.27 0.81 6