RELAY COORDINATION
SEZ 11KV BUS FAULT
FAULT LEVEL 111.5856525 MVA
FAULT CURRENT 5856.899667 A

11 KV FEEDER (SEZ)
CTR 125 6
3 O/L 90%
TL 0.05
CURVE 3
TIME 0.15
FAULT CURRENT ( Fault Current/CT RATIO) 46.8551973 A
TRIPPING TIME 0.087386348 SECS
11 KV SEZ FEEDER
CTR 1000 4
3 O/L 40%
1 TL 0.14
CURVE 3
TIME 0.42
FAULT CURRENT ( Fault Current/CT RATIO) 5.85689967 A
TRIPPING TIME 0.360327035 SECS
11 KV SEZ FEEDER AT MRS DIVISION
CTR 1000 4
3 O/L 40%
TL 0.22
CURVE 3
TIME 0.66
FAULT CURRENT ( Fault Current/CT RATIO) 5.85689967 A
TRIPPING TIME 0.566228198 SECS
11 KV LV
CTR 1500
3 O/L 21%
TL 0.37
2 CURVE 3
TIME 1.11
FAULT CURRENT ( Fault Current/CT RATIO) 3.90459978 A
TRIPPING TIME 0.874458327 SECS
2

110KV HV & INCOMER


CTR 150 6
3 O/L 100%
TL 0.27
CURVE 3
TIME 0.81
11 KV THROUGH FAULT CURRENT 585.6899667 A
3 FAULT CURRENT 3.90459978 A
TRIPPING TIME 1.369222688 SECS
FAULT AT 11KV
INST
11 KV FEEDER ( SEZ TR
CURRENT
Incomers)
20% 1171.3799335 0.1474135906
40% 2342.7598669999 0.11375915
52.0613 60% 2928.4498337499 0.1059707251
80% 4685.5197339999 0.0926151605

100% 5856.8996674999 0.087386348


INST
2.5

2
14.6422

SION 1.5
INST

14.6422 0.5

0
0 1000 2000 3000

18.5933
INST

O/L
BREAKER CT RATIO
3.9046 %
11KV FEEDER 125 90%
11KV SEZ 1000 40%
11KV SEZ AT MRS
1000 40%
DIVISION
11KV LV 1500 21%

110KV HV &
150 100%
INCOMER
FAULT AT 11KV BUS

11KV SEZ # AT 110KV HV &


11KV SEZ 11KV LV
MRS DIVISION INCOMER
0.9000556967 1.4143732377 1.9460463856
0.5471116654 0.8597469028 1.2737870817
0.485786243 0.7633783819 1.1463067029
0.3930016585 0.6175740348 0.9467377153 1.6374668183

0.360327035 0.5662281978 0.8744583268 1.3692226878

3000 4000 5000 6000 7000


O/L
TL TIME INST
0.05 0.15 6
0.14 0.42 4

0.22 0.66 4

0.37 1.11 Disable

0.27 0.81 6