3 All protection trip to 86 relay Digital Output For Trip & Annuciation
4
Over current trip (Directional + Digital Output For Trip & Annuciation
Non - directional)
5
Earth fault trip (Directional + Digital Output For Trip & Annuciation
Non - directional)
6 U/F & O/F Trip Digital Output For Trip & Annuciation
7
Breaker Close Command from Digital Output
Relay
8
Breaker OFF Command from Digital Output
Relay
Annunication + Adjacent
9 Feeder Protection Relay Fail Digital Output
relay input
10 Close Permissive from Relay Digital Output
SIGNAL LIST FOR RELAYS FOR 11kV INCOMER FEEDER
A) List of Digitial Inputs:
SL. No Signal Description Type of Signal Remarks
1 Breaker ON / OFF Digital Input
2 Breaker Trip Digital Input
3 86 Optd. Digital Input
4 TC -1 Healthy Digital Input
5 TC -2 Healthy Digital Input
6 Bus PT Supply Fail Digital Input
7 EMPB Optd. Digital Input
8 Breaker Spring Charged Digital Input
Local Remote Swicth in Local Digital Input
9 Mode
Local Remote Swicth in Remote Digital Input
10 Mode
11 DC Supply Healthy Digital Input
12 Feeder Isolator - 1 ON/OFF Digital Input
13 Bus Isolator ON/OFF Digital Input
14 Adjacent feeder -2 relay fail Digital Input
15 Spare Digital Input
16 Spare Digital Input
TC Healthy for
Indication & TC
1 TCH -1 Healthy Digital Output -Unhealthy for
annunciation
7
Breaker Close Command from Digital Output
Relay
8
Breaker OFF Command from Digital Output
Relay
Annunication +
9 Feeder Protection Relay Fail Digital Output Adjacent relay
input
10 Close Permissive from Relay Digital Output
SIGNAL LIST FOR RELAYS FOR 33kV TRAFO FEEDER
A) List of Digitial Inputs:
SL. No Signal Description Type of Signal Remarks
1 Breaker ON / OFF Digital Input
2 Breaker Trip Digital Input
3 86 Optd. Digital Input
4 TC -1 Healthy Digital Input
5 TC -2 Healthy Digital Input
6 EMPB Optd. Digital Input
7 Breaker Spring Charged Digital Input
Local Remote Swicth in Local Digital Input
8 Mode
Local Remote Swicth in Remote Digital Input
9 Mode
10 Feeder Isolator - 1 ON/OFF Digital Input
11 Adjacent feeder -2 relay fail Digital Input
Transformer Trouble Aux. Relay - Digital Input
12 1
Transformer Trouble Aux. Relay - Digital Input
13 2
Transformer Trouble Aux. Relay - Digital Input
14 3
Transformer Trouble Aux. Relay - Digital Input
15 4
Transformer Trouble Aux. Relay - Digital Input
16 5
Transformer Trouble Aux. Relay - Digital Input
17 6
4
Over current trip (Directional + Digital Output For Trip & Annuciation
Non - directional)
5
Earth fault trip (Directional + Digital Output For Trip & Annuciation
Non - directional)
6 U/F & O/F Trip Digital Output For Trip & Annuciation
7
Breaker Close Command from Digital Output
Relay
8
Breaker OFF Command from Digital Output
Relay
Annunication + Adjacent
9 Feeder Protection Relay Fail Digital Output relay input
10 Close Permissive from Relay Digital Output
TC Healthy for
Indication & TC
1 TCH -1 Healthy Digital Output -Unhealthy for
annunciation
For Trip &
2 TCH -2 Healthy Digital Output Annuciation
For Trip &
3 All protection trip to 86 relay Digital Output Annuciation
For Trip &
4 Over current trip Digital Output Annuciation
For Trip &
5 Earth fault trip Digital Output Annuciation
For Trip &
6 U/F & O/F Trip Digital Output Annuciation
7
Breaker Close Command from Digital Output
Relay
8
Breaker OFF Command from Digital Output
Relay
Annunication +
9 Feeder Protection Relay Fail Digital Output Adjacent relay
input
10 Close Permissive from Relay Digital Output