Sunteți pe pagina 1din 6

COLUMN

ABSTRACT
This article discusses verification of the
ability of a transformer to survive short
circuit. Fault current leads to large

Transformer
axial and radial forces on windings,
which have to be managed by proper
structural design. Test experience,
showing a failure rate of 20-25 % of
well-prepared transformers, suggests
that the highest degree of reliability
with respect to short-circuit withstand
verification is ensured through full-
scale testing in accordance with the
Short-circuit withstand capability
international standards. The prime
failure mode is winding deformation, of power transformers – Part I
but many other deficiencies, which
would not be discovered in a design
review, have also been observed. Introduction Power transformers are especially sensitive
to short-circuit events, as will be made clear
The power transformer is the most vital in the following. The effects of short-circuit
KEYWORDS substation component since its unavailabil­ currents in transmission and distribution
ity creates a major problem, given the high networks for electric energy are tremendous,
transformer, short circuit, testing, certi- costs and the long time involved in repair or both for the equipment and for the stability
fication, reliability replacement. of the networks. Since short circuits are not

78 TRANSFORMERS MAGAZINE | Volume 4, Issue 2


René SMEETS

Aerial view of KEMA Laboratories of DNV GL in the Netherlands, with a short-circuit tested transformer (on the barge in the foreground)

lifecycle
rare events (as a rule of thumb, one short dynamic forces on the windings that cause interaction of the current with the leakage
circuit per 100 km overhead line per year mechanical stresses in the radial as well magnetic field between the windings, in
[1]), short-circuit withstand capability is as axial direction. They result from the radial and axial direction.
regarded as one of the main characteristics
of the equipment installed. The capability
to withstand a short circuit is recognized
as a major and an essential requirement of Full-scale testing of over 300 transformers
power transformers. Failure to withstand it of 25 MVA and above, with rated voltages
results in damage to the internal (and even
external) parts, and can lead, in short or up to 765 kV, shows that around a quarter
longer term, to loss of service. fails to pass the standardized short-circuit
Short-circuit current leads to electro- withstand tests
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 79
COLUMN

Figure 1. Diagram showing the origin of radial forces (left), and the possible result: buckling of the inner winding (right)

lead to immediate damage or long-term is­


Fault current leads to large electro-dynamic sues because of insulation damage, obstruc­
forces on windings and other parts, which have tion of oil flow, material weakness or loose
to be managed by proper structural design parts. Damage and even break of bushings
due to the mechanical shock has been ob­
served as well.

Radial and axial forces may have the observed to result in spiralling and/or The control of the forces and stresses ex­
following effect on the winding: tilting of turns. Through the deformation erted by the short-circuit currents inside the
of turns, the oil flow may become transformer must be an integral part of the
ŸŸ The radial forces (see Fig.1) tend to obstructed, leading to the formation of design process and quality verification [3].
compress the turns in the inner (normally hot spots.
the lower voltage) winding and to expand With an increase of the short-circuit power
the turns in the outer winding (higher Apart from winding deformation, a variety during the years, the most severe short-cir­
voltage). When the mechanical design of deformation of internal, but also of exter­ cuit currents will appear when the transform­
of the supports is not adequate, radial nal parts has been observed in testing [2]. er is aged. Also these short-circuit currents
stresses may lead to forced buckling of Permanent deformation of windings may have to be withstood without impairing the
the inner winding, which is frequently
observed.
Short circuits are not rare events - as a rule of
ŸŸ The axial forces (see Fig. 2) act in the axial
direction with a pulsating compression thumb one short circuit happens per 100 km
force. Axial and radial forces have been overhead line per year

Figure 2. Diagram showing the origin of axial forces (left), and the possible result: tilting of the conductors (right)

80 TRANSFORMERS MAGAZINE | Volume 4, Issue 2


Table 1. Failure rates of transformers in the CIGRE 2015 study
69 ≤ kV < 100 100 ≤ kV < 200 200 ≤ kV < 300 300 ≤ kV < 500 500 ≤ kV < 700 kV ≥ 700 all

0.93 % 0.44 % 0.55 % 0.75 % 0.54 % 0.37 % 0.57 %

transformer. A large-scale study showed


that aged transformers are more prone to
The failure rate of converter transformers sup-
short-circuit winding deformation because plying DC links is significantly higher than that
of diminishing winding fastening strength,
which is caused by insulation shrinkage and
of conventional station transformers
pieces of insulating material disappearing or
becoming displaced [4].
to observe that their failure rate is sign­ against the manufacturer’s design rules for
Power transformer ificantly higher than that of conventional short-circuit strength.
station transformers, between 1.6-5.4 %
in-service failure
depending on their size, compared to the These rules shall be based on a “solid expe­
A number of international studies, all con­ rate of 0.6 % of AC transformers. rimental basis”, a number of short-circuit
ducted between1974 and 2005, report a fail­ withstand tests of actual transformers or the
ure rate in the range of 0.4-3 %. Short-circuit withstand outcome of tests performed on representa­
tive transformer models combined with any
assessment
In 2015, a new extensive survey, covering indirect supportive evidence based on long
the period of 1996-2010, of 964 major trans­ Basically, two methods are applied to assess duration and trouble-free operation of a
former failures during 167.459 transform­ short-circuit withstand capability of power number of transformers in the field.
er years from 56 utilities in 21 countries transformers: design review and testing.
was reported by CIGRE WG A2.37 [5]. Limitations of the design
This s­tudy reports an overall failure rate of Assessment by design review review approach
0.57 % (“one major failure per 200 trans­
formers in a year”). In Table 1 a breakdown One of the methods for purchasers to assess CIGRE studies show that calculation meth­
is given in terms of voltage class. the short-circuit current withstand capabil­ ods are an indispensable tool in the design
ity of transformers is to conduct a design phase of electrical equipment and that
More detailed analyses on failed subcompo­ review. CIGRE has issued guidelines on this m­odern, multi-physics finite-element 3D si­
nent, failure mode and failure cause reveals method [10] that are implemented in the mulation tools can predict internal stresses.
the following: international standard IEC 60076-5, annex However, they cannot be applied for equip­
A [11]. This annex is an informative docu­ ment performance verification [12]. This
ŸŸ Ageing and external short-circuit are the ment giving guidelines only, and it is not a also applies to power transformers.
largest known failure causes (12.3 % and standard by itself.
11.6 %, respectively). For a number of reasons listed below, the
ŸŸ Windings are the most common failure In the design evaluation of a transformer, value of design review is limited, and gener­
location (40 %), followed by tap-changer two alternative approaches can be adopted: ally insufficient to be used as a replacement
(27 %) and HV bushing (14 %). for short-circuit withstand verification by
ŸŸ Mechanical failures account for over 20 a. Comparison with a short-circuit laboratory testing. The main limitations are
% of all failures, the second largest after tested reference transformer as follows:
dielectric failures (36 %).
ŸŸ The failure rate of GSU units is in all This method describes a comparison with a ŸŸ Simulation tools are a simplification of
voltage classes higher than that of reference transformer that passed short-cir­ the reality [13]. The most obvious sim­
substation transformers. cuit tests successfully, on the condition that: plifications are disregard of the influence
- the design under review can be considered of the other phases; and consideration of
EPRI (USA) maintains the IDB database [6] similar to the reference transformer; the windings as rigid and circular sym­
that began to be populated in 2006. By now - it is designed using the same calculation metrical.
it has collected data on more than 20.000 methods and withstand criteria; ŸŸ The list of reviewed sub-components is
U.S. power transformers. One result that - it is manufactured according to the same not complete. It should ensure that all
clearly stands out is that “inadequate short QA/QC practices; necessary aspects are considered. Cal­
circuit strength” is by far the largest cause of - the margins for short-circuit strength of culations related to lead supports and
failure, with 20 % of the total of 654 clearly both designs overlap. connections to bushings are not reques­
identified failures. ted.
b. Checking against manufacturer’s ŸŸ The design review approach is static
Converter transformers supplying DC links design rules for short-circuit strength w­hereas the phenomena are dynamic. As
are of a special design. Their reliability (in the dynamic behaviour of the windings
LCC based DC projects) has been addressed In this method, evaluation is conducted by during a short circuit is not mentioned
in several publications [7, 8, 9]. It is striking checking the force and stress parameters in design review, no aspects of inter-

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 81
Installation work carried out on one of the ten laboratory’s step-up transformers

Multi-physics simulation tools can predict in- their short-circuit power and can cover the
ternal stresses, but they cannot be applied for vast majority of power transformer ratings.

the verification of equipment performance There is very limited information on direct


evidence of failures in service after short-
circuit withstand evaluation. From a sur­
winding (dynamic) oil flow or tank stress formance of a design review. No uniform vey conducted by CIGRE SC12 (covering
calculations are considered. and generally accepted validation proce­ 121,460 transformer years in the period of
ŸŸ Design review does not cover material dure for the design calculations is estab­ 1993-1997), 15 failures attributed to short
and production deficiencies. Natural va­ lished. Statement letters provided are in circuit were identified. In 5 cases (33 %) de­
riations in properties of material, quality general unique to the inspecting body. sign reviews were performed, whereas none
assurance, workmen’s skills etc., cannot On the other hand, a short-circuit tested of the failed units (or similar designs) was
be taken into account fully, nor can any transformer is certified by an accredited short-circuit tested [5].
design review reveal deficiencies resul­ test laboratory which covers everything.
ting from this. The certificates (see an example in Fig.
ŸŸ Many failures occur in other than the 3) provided by accredited test labora­ References
“design reviewed” sub-components. tories operating under the umbrella of [1] CIGRE WG 13.08, Life Management
Complicated ‘secondary’ physical pheno­ the “Short-circuit Testing Liaison” (STL) of Circuit Breakers, CIGRE Technical
mena like shock waves in oil, shocks and are uniform in style and acknowledged Brochure 165, August 2000
vibrations (leading to untimely falling-off every­where without any restriction. [2] G. Bertagnolli, Power Transformers
of Buchholz relays or damage to ancil­lary & Short Circuits. Evaluation of short-
equipment – bushings, tap-changers, etc.) Design evaluation was partly introduced circuit performance of power transform­
are normally not considered at all in cal­ as an alternative to short-circuit testing be­ ers, Book printed on behalf of ABB Ltd.
culation methods. cause of testing limitations in the past. In Transformers, Switzerland, 2014
ŸŸ There is no quality control on the per­ due time, test laboratories have increased [3] CIGRE WG 12.19, The Short-Circuit

82 TRANSFORMERS MAGAZINE | Volume 4, Issue 2


Figure 3. The test certificates provided by STL test laboratories are uniform in style and
acknowledged worldwide

617, HVDC LCC Converter Transform­ [12] B. Verhoeven, R.P.P. Smeets, Secure
ers Converter Transformer Failure Sur- Verification of T&D Equipment needs
vey Results From 2003 To 2012, 2015 Laboratory Testing, Position paper
[10] CIGRE WG 12.22, Guidelines for KEMA Laboratories, www.dnvgl.com/
Consulting Design Reviews for Trans- energy/publications/download/KEMA_
formers 100 MVA and 123 kV and Laboratories_Position_Paper.html, 2015
above, CIGRE Technical Brochure 204, [13] K. Spoorenberg, The relevance of in-
August 2002 sulation supports in large power trans-
[11] IEC standard 60076-5, Power Trans- formers for short-circuit withstand, on
Performance of Power Transformers, formers - Part 5, Ability to withstand behalf of Royal SMIT, Transformer User’s
CIGRE Technical Brochure 209, August short-circuit, 2006 Meeting, 2016
2002
[4] T. Kobayashi, Y. Shirasaka, Y. Ebisawa,
H. Murakami, Expected Life and Main-
tenance Strategy for Transformers, CIG­ Author
RE 6th Southern Africa Regional Conf., Dr. René Peter Paul Smeets is Service Area Leader with
paper P102, 2009 KEMA Laboratories of DNV GL, Arnhem, the Netherlands.
[5] CIGRE WGA2.37, Transformer Re- He re­ceived his M.Sc. degree in physics (cum laude) from the
liability Survey, CIGRE Technical Bro­ Eindhoven University of Technology, the Netherlands, and a
chure 642, December 2015 Ph.D. degree following research work on switchgear. Until 1995,
[6] B. Desai and M. Lebow, Needed: ASAP he was an assistant professor at Eindhoven University. During
1991 he worked with Toshiba Corporation in Japan on the
Approach, Power and Energy Magazine,
development of switchgear. He joined KEMA in 1995. In 2001
IEEE, vol.8, no.6, pp. 53-60, November
he was appointed part-time professor at Eindhoven University in the field of high-
2010
power testing. He has received six international awards. In 2013 he became adjunct
[7] CIGRE Joint TaskForce B4.04/A2-
professor at Xi’an Jiaotong University, China. Dr. Smeets is convener and member
1, Technical Brochure 240, Analysis of
of working groups and study/advisory/turorial committees of CIGRE in the field of
HVDC Thyristor Converter Transform­
emerging high-voltage equipment. He is convener of two maintenance teams of IEC
er Performance, 2004
on high-voltage switchgear. He has published and edited three books and authored
[8] CIGRE WG A2/B4.28, Technical Bro­
over 250 international papers on testing and switching in power systems. In 2008 he
chure 406, HVDC Converter Transform­
was elected Fellow of IEEE and since 2008 he has been the chairman of the “Current
ers. Design Review, Test Procedures,
Zero Club”, a scientific study committee on current interruption. All over the world,
Ageing Evaluation and Reliability in
he has conducted many international workshops and trainings on high-voltage
Service, 2010 equipment, including technology, application, requirements, testing and certification.
[9] CIGRE WG B4.04, Technical Bro­chure

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 83

S-ar putea să vă placă și