Sunteți pe pagina 1din 8

612 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO.

2, MARCH/APRIL 2010

Design of a High-Speed Motor Bus Transfer System


Murty V. V. S. Yalla, Fellow, IEEE

Abstract—This paper addresses the design of a high-speed mo-


tor bus transfer system for power-generating plants and industrial
facilities where motor loads require comprehensive source transfer
strategies during transfer of the load from one source to another.
Motor bus transfer schemes are needed not only to maintain
process continuity but also to transfer sources in such a manner
to prevent damage to the motors and connected loads. The motor
bus frequency and voltage decay rapidly upon disconnection from
the main source. This paper proposes a digital signal processing
algorithm that can measure the magnitude and phase angle of the
decaying bus voltage accurately while measuring the auxiliary-
source voltage magnitude and phase angle at rated frequency.
This paper details an algorithm to predict the phase coincidence
between the motor bus voltage and the auxiliary-source voltage.
The algorithm uses delta frequency, the rate of change of delta
frequency, and breaker closing time to predict the phase coinci- Fig. 1. Typical one-line diagram of a two-breaker motor bus transfer scheme.
dence. This paper also details the implementation of the motor bus
transfer scheme that includes fast, in-phase, and residual transfer phase-angle difference during source transfer, one can use
methods. The results of some real-time transfer cases are also ANSI/IEEE Standard C50.41-2000 [5], which states that the
included.
V/Hz across the open breaker must be less than 1.33 PU in order
Index Terms—Fast bus transfer, in-phase transfer, motor bus to prevent motor damage. The larger the phase-angle difference,
transfer, residual voltage transfer. the larger the V/Hz.
Electromechanical or static sync-check relays do not operate
I. I NTRODUCTION fast enough for motor bus transfer applications. If these relays
are used, the auxiliary-source breaker may close at a large
M OTOR BUS transfer schemes have been used in electric
power plants and industrial facilities for a number of
years to transfer a load bus that mainly comprises induction
phase angle due to the slow dropout of the sync-check relay,
or it may fail to close due to the slow pickup of the sync-
motors or a combination of induction and synchronous motors check relay. It is important to very quickly measure the voltage
from a main source to an auxiliary source [1]–[4]. Fig. 1 magnitude and phase angle for proper operation of the transfer
shows a typical one-line diagram of a two-breaker motor bus scheme. It is also important to measure the voltage magnitude
transfer scheme. The transfer from a main source to an auxiliary and phase angle of the motor bus voltage accurately over a
source takes place during a fault on the main source, scheduled wide frequency range as the bus frequency can be much lower
maintenance, or emergency conditions. The transfer may be than the frequency of the auxiliary source due to deceleration
initiated manually or automatically by a protective relay. of the motors. Another complication to the problem is that
During the bus transfer, there can be a substantial initial the measurement algorithm has to handle one signal (auxiliary
phase-angle difference between the motor bus voltage and the source) at rated frequency while handling the other signal (bus
auxiliary-source voltage (across the open breaker). There are voltage) at a decaying frequency.
several reasons for this phase-angle difference, including the The following sections of this paper describe the following:
following: the effect of a fault on the main source, system a general description of bus transfer methods, digital signal
separation between the two sources, supply source transformer processing algorithms that can measure the magnitude and
phase shifts, and phase shift as a result of the disconnection of phase angle of the decaying bus voltage accurately, and details
the motor from the main source. To determine the acceptable of an algorithm to predict the phase coincidence between the
motor bus voltage and the auxiliary-source voltage. The imple-
mentation of the motor bus transfer scheme that includes fast,
Paper 2008-PSPC-227, presented at the 2009 IEEE/IAS Industrial and in-phase, and residual transfer methods, along with some real-
Commercial Power Systems Technical Conference, Calgary, AB, Canada, time transfer cases, is also presented.
May 3–7, and approved for publication in the IEEE T RANSACTIONS ON
I NDUSTRY A PPLICATIONS by the Power Systems Protection Committee of
the IEEE Industry Applications Society. Manuscript submitted for review
February 1, 2009, and released for publication July 14, 2009. First published II. B US T RANSFER M ETHODS
February 5, 2010; current version published March 19, 2010.
The author is with Beckwith Electric Company, Inc., Largo, FL 33773-3724 The following methods of bus transfer are used to transfer a
USA (e-mail: myalla@beckwithelectric.com). motor bus from a main source to an auxiliary source and vice
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
versa:
Digital Object Identifier 10.1109/TIA.2010.2041097 1) residual voltage transfer;

0093-9994/$26.00 © 2010 IEEE


YALLA: DESIGN OF A HIGH-SPEED MOTOR BUS TRANSFER SYSTEM 613

Fig. 2. Graphical representation of bus transfer methods. Fig. 3. Sampling of a 60-Hz voltage waveform at 1.92-kHz sampling rate.

2) in-phase transfer;
3) fast transfer.

A. Residual Voltage Transfer


The majority of bus transfer schemes in use today are of
the residual voltage type [1]–[3]. In this type of transfer, the
auxiliary loads are transferred once the motor residual voltage
reaches a low value to prevent motor damage. Typically, resid-
ual voltage transfers are done at 25%–30% of the rated voltage,
irrespective of the phase angle of the motor bus. As the residual
transfer is slow, process interruption is likely to take place.
Fig. 4. Sampling of a 55-Hz voltage waveform at 1.92-kHz sampling rate.
Also, in the majority of cases, motors cannot be reaccelerated
simultaneously following such a transfer as their speeds have
fallen so low that inrush currents approach motor locked-rotor The following are the two types of transfer schemes.
values, and stalling would occur due to depressed voltage. In 1) Sequential transfer: In sequential transfer, a “b” or early
some cases, critical drives are restarted in blocks so that full “b” contact of the main-source breaker is used to initiate
plant operations may not be reestablished for some time. closing of the auxiliary-source breaker. This approach
It is important to measure the voltage magnitude accurately provides increased security because the bus has been
during a very low bus frequency (as low as 4 Hz) as the bus disconnected from the main source prior to the auxiliary-
frequency can reach a very low value during residual transfer. source breaker closing. A bus dead time of 5–7 cycles is
normally encountered with this type of transfer.
2) Simultaneous transfer: In simultaneous transfer, both the
B. In-Phase Transfer
trip of the main breaker and the close of the auxiliary-
In the in-phase transfer scheme, the auxiliary-source breaker source breaker are initiated at the same time. This type of
is closed when the phase angle of the bus voltage is in-phase transfer has the shortest dead time of 1–2 cycles.
with the phase angle of the auxiliary-source voltage. To achieve Failure of the main source breaker to open will result in
this, a phase-angle measuring relay, which can predict the in- paralleling the two sources and, if out of phase, will result in
phase condition in advance of auxiliary-source breaker closing equipment damage. This type of transfer may not be possible
time, is required. In-phase transfer minimizes the resultant when the main source is lost due to a close-in electrical fault
V/Hz difference between the bus voltage and the auxiliary- or abnormal condition that causes the phase angle to move
source voltage. This is in contrast to the residual voltage trans- instantaneously. Also, a breaker failure scheme is required for
fer, which can allow closure even at 180◦ . In-phase transfer can simultaneous transfer so that if the main source breaker fails to
be used successfully on systems that exhibit a slow-to-moderate open during a transfer, then the auxiliary-source breaker will be
rate of change in phase angle. tripped to avoid paralleling both sources.
The aforementioned three methods are shown graphically
in Fig. 2. The following three windows are shown: fast, in-
C. Fast Transfer
phase, and residual. The scale for phase angle (solid line) is
In the fast-transfer scheme, the transfer is attempted as fast shown on the far left of the graph, and the scale for bus voltage
as possible, minimizing the time that the loads are discon- magnitude (dashed line) is shown on the far right of the graph.
nected from either source. The fast-transfer method requires A fast transfer is attempted during the first few cycles after
a very high speed sync-check relay (subcycle phase-angle the source breaker is tripped. If a fast-transfer attempt is not
measurement). successful due to large initial phase angle, then the transfer
614 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010

Fig. 5. Measurement error of the delta angle with a fixed-window DFT


algorithm.
Fig. 6. Measurement error of the delta angle with the adaptive window DFT
algorithm.
scheme will wait and try for an in-phase transfer. The in-phase
transfer scheme will try to send a close signal to the auxiliary- The rms value of the voltage signal (Vrms ) is calculated using
source breaker in advance so that the phase-angle difference voltage samples as follows [7]:
between the bus voltage and the auxiliary-source voltage when 

the breaker closes is close to zero. If an in-phase transfer is 1  m

not possible, then the transfer scheme will wait for the residual Vrms =  vk2 Δt (1)
T
k=1
transfer. Some schemes also utilize fixed-time transfer, which
is basically a residual voltage transfer, but no measurement of where vk is the sampled value of the voltage signal at sample
voltage is performed as the time delay will be such that the number “ k,” T is the time period of the voltage signal, and m is
voltage is assumed to have reached a safe level. the total number of samples in one cycle of the voltage signal.
Time period T can be calculated using the following:
   
III. D IGITAL S IGNAL P ROCESSING A LGORITHMS v1 vm
T= Δt + Δt + (m −1)Δt (2)
v1 − v 0 vm+1 − vm
A. Voltage Magnitude Calculation
When the main source is disconnected from the motor bus, where v0 and v1 are the voltage samples on the negative and
the frequency of the motor bus voltage will decay rapidly from positive sides of a positive-going zero-crossing, respectively;
the nominal value. Application of a Discrete Fourier Transform vm and vm+1 are the voltage samples on the negative and
(DFT) algorithm to calculate the magnitude and phase angle positive sides of a next successive positive-going zero-crossing,
will introduce large errors at abnormal frequencies. respectively; and Δt is the sampling interval.
A frequency-tracking technique was applied in the past to The frequency (f ) of the motor bus voltage is calculated
reduce measurement errors, where the sampling frequency is from time T as
adjusted continuously so that the number of samples per fun-
damental frequency cycle of the signal is kept constant [6]. f = 1/T. (3)
However, for bus transfer application, the frequency of the
auxiliary-source voltage is kept constant near its nominal value B. Voltage Phase-Angle Calculation
(60 or 50 Hz),whereas the frequency of the bus voltage is
varying. If the sampling frequency is changed to track the bus The phase angle of the voltage can be calculated using a DFT
frequency, then the auxiliary-voltage phase-angle and magni- algorithm. A recursive form of the DFT algorithm is used here
tude calculations suffer from inaccuracies. to reduce the number of computations.
To eliminate the inaccuracies during off-nominal frequen- The real (V R) and imaginary (V I) components of the fun-
cies, the voltage magnitude is calculated using a rms algorithm damental frequency voltage phasor are given by the following:
in the time domain [7] instead of a DFT algorithm. Voltage 2 2πk
V Rk = V Rk−1 + (vk − vk−N ) cos (4)
signals are also prefiltered to remove any noise that can cause N N
measurement errors. This method provides a very accurate 2 2πk
V Ik = V Ik−1 + (vk − vk−N ) sin (5)
measurement of voltage magnitude down to 4 Hz. This is N N
particularly important for a residual voltage transfer where the where vk is the sampled value of the voltage signal at the kth
frequency can reach very low values. If the voltage measure- sample, N is the number of samples in a fundamental frequency
ment algorithm is not accurate down to this low frequency, the cycle, and v−1 , v−2 , . . . , v−N , V R−1 , and V I−1 are set to zero.
bus transfer can take place at a much higher residual voltage The phase angle is given by
than the undervoltage setpoint, which can cause motor damage.  
The voltage magnitude calculation is performed 16 times per VI
θ = tan−1 . (6)
cycle. VR
YALLA: DESIGN OF A HIGH-SPEED MOTOR BUS TRANSFER SYSTEM 615

Fig. 7. Hardware block diagram of a digital MBTS.

Once the voltage phasors of the bus (V Rbus + jV Ibus ) and cycle. That is, the measurement window is increased in integral
the auxiliary-source (V Raux + jV Iaux ) voltage are calculated, steps of 32, 33, 34, 35, 36, 37, and 38 samples as the frequency
the delta phase angle (Δθ) between the bus and the auxiliary- is decreasing from 60 to 50 Hz. A total of seven recursive
source voltage can be calculated using the following: DFT calculations are implemented—one for each of the sample
  window lengths—in parallel, and the appropriate phasors are
V Ibus V Raux − V Rbus V Iaux selected based on the measured frequency.
Δθ = arctan . (7)
V Rbus V Raux + V Ibus V Iaux The time window in samples for the bus voltage will increase
as the bus frequency is decaying. That means that the bus
As described earlier, the frequency of the bus voltage decays voltage and the auxiliary-source voltage may use different
rapidly, and the phase angle calculated from the DFT algorithm rotating references to obtain phasors. This introduces an error
suffers from errors at off-nominal frequencies. In order to in the delta phase angle, which can be calculated as follows:
reduce these errors, an adaptive time window DFT algorithm
is proposed here. 2π(Maux − Mbus )
The phase-angle measurements are obtained 16 times per Δθerror (i) = i (8)
Mbus · Maux
cycle, and a high-speed sync check is also performed 16 times
per cycle.
where Maux and Mbus are the time windows in samples of
Adaptive time window DFT algorithm: Fig. 3 shows the
the auxiliary-source and bus voltages, respectively, and index
sampling of a 60 Hz voltage signal at 1.92 kHz (32 × 60). Also,
“i” represents the sample number.
Fig. 4 shows the sampling of 55 Hz voltage signal at 1.92 kHz
The corrected delta phase angle (Δθc ) between the bus and
(32 × 60). As shown, when the frequency deviates from the
the auxiliary-source voltage can be calculated using auxiliary-
nominal value, the number of samples in one cycle window is
source and bus voltage phasors—as given by (7), along with the
increased from 32 (for a 60 Hz signal) to 35 (for a 55 Hz signal).
compensation for delta phase-angle error—as given by (8), as
Therefore, taking only 32 samples for a 55 Hz signal does not
follows:
include a full cycle of the waveform. Hence, the magnitude and
phase angle calculated using DFT from this partial waveform
suffer from inaccuracies. Δθc = Δθ + Δθerror . (9)
Fig. 5 shows the delta phase-angle measurement error with
a standard DFT (window fixed at 32 samples) for a delta Fig. 6 shows the delta phase-angle measurement error using
frequency of 0–10 Hz. These results are obtained using a fixed the adaptive time window DFT algorithm. Using this technique,
32-sample window for the bus voltage and the auxiliary-source the worst case measurement error for a delta-frequency range
voltage waveform. As shown in Fig. 5, the delta phase-angle of 0–10 Hz is less than 1◦ . Also, the noise level of the phase-
error increases from 0 ◦ to 5.25◦ as the bus frequency is decayed angle measurement is considerably reduced, which makes
from 60 to 50 Hz. the delta-frequency and double-delta-frequency calculation,
Several discrete frequency steps are used by increasing the which is required for zero phase-coincidence prediction, more
time window from 32 samples per cycle to 38 samples per accurate.
616 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010

Fig. 8. Live in-phase transfer event at a power-generating plant.

C. Delta-Frequency Calculation D. Zero-Phase Coincidence Prediction


The delta frequency between the bus and auxiliary-source The phase angle at the instant of breaker closing (ΔθP ) can
voltages is calculated using the rate of change of the delta phase be predicted using the estimated delta frequency Δfe , the rate
angle as follows: of change of delta frequency, and the breaker closing time (TB )
1 (Δθ − Δθ ) as follows:
Δf = (10)
2π T    
where Δθ is the delta phase angle at the previous measure- 1 Δfave
ΔθP = Δθ + 2π Δfe + d · (TB ) · TB . (12)
ment and T is the time interval in seconds between the two 2 dt
measurements.
The delta frequency is averaged over a period of Tave to filter When the motor bus is disconnected from the main source,
the noise in the measurements. Assuming that the rate of change the frequency of the motor bus decays rapidly. The phase angle
of delta frequency (d(Δfave )/dt) is constant, the average delta calculated with only delta frequency and breaker closing time
frequency Δfave is at the middle of the Tave window. The will not be accurate as the delta frequency is varying with
delta frequency (Δfe ) can be estimated using Δfave , Tave , and time. The use of the rate of change of delta frequency in the
d(Δfave )/dt as follows: prediction of phase angle at the instant of breaker closing in
Tave d(Δfave ) (12) will greatly reduce these errors as the delta frequency is
Δfe = Δfave + . (11)
2 dt not constant during this period.
YALLA: DESIGN OF A HIGH-SPEED MOTOR BUS TRANSFER SYSTEM 617

Fig. 9. Live simultaneous fast-transfer event at a power-generating plant.

IV. I MPLEMENTATION OF THE B US T RANSFER S YSTEM interface. The relay is powered by a switching power
supply.
The hardware implementation of a digital motor bus transfer
Some of the main features implemented in the MBTS are as
system (MBTS) is shown in Fig. 7. The MBTS has analog
follows:
inputs for single- or three-phase voltages for measuring main-
1) automatic and manual transfer modes with fast, in-phase,
source, auxiliary-source, and bus voltages; main- and auxiliary-
and residual transfer;
source currents; contact inputs for breaker status, transfer
2) manual hot parallel transfer (make before break);
initiate, trip/close coil monitoring, and block transfer; and 3) sequential and simultaneous transfer modes;
contact outputs for breaker trip/close, load shedding, and other 4) transfer initiate from external contacts or internally using
alarm conditions. The MBTS also has several communications bus undervoltage;
ports (RS-232, RS-485, and Ethernet) to communicate with a 5) load shedding using bus undervoltage, under frequency
personal computer or SCADA system. The analog hardware and rate of change of frequency;
consists of an analog data acquisition system that includes 6) trip/close coil monitoring and breaker failure detection;
signal scaling, isolation, filtering (anti-aliasing), analog multi- 7) auto trip feature in case both breakers are in close
plexing, and analog-to-digital conversion. The digital subsys- condition;
tem consists of a microprocessor, Flash memory for program 8) bus VT fuse loss detection;
storage, random access memory for temporary storage of 9) adaptive breaker closing-time measurement;
information, and electrically erasable programmable memory 10) event recorder with transfer event logs and sequence of
for storage of setpoints. It also has front-panel light-emitting events;
diodes for target indication and a local human–machine 11) oscillography recording of bus transfer events.
618 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 46, NO. 2, MARCH/APRIL 2010

Fig. 10. Live in-phase transfer event at a chemical plant.

V. L IVE B US T RANSFER E VENTS


the advantage of using the rate of change of delta frequency in
This section details three cases of live bus transfer events. predicting the phase coincidence.
Fig. 8 shows an oscillograph of a live transfer event at a Fig. 9 shows an oscillograph of a live transfer event at a
power-generating plant. The transfer was initiated manually and power-generating plant. The transfer was initiated by a gen-
completed by the in-phase transfer method. The transfer initiate erator trip via a generator lockout relay and completed by a
signal started at 23.8◦ phase angle with a bus voltage of 121.6 V. simultaneous mode of the fast-transfer method.
The breaker opening time is 2.4 cycles, and the breaker closing The initiated signal started at −0.4◦ phase angle with a bus
time is 3 cycles. The auxiliary-source breaker was closed at voltage of 121.7 V. The breaker opening time is 1.0 cycle,
2◦ with a bus frequency at 53.12 Hz and a bus voltage at and the breaker closing time is 3.27 cycles. The breaker was
79 V. The open transition (bus interrupting) time is 13.3 cycles. closed at −15.2◦ with a bus frequency at 59.45 Hz and a bus
For this example, if the rate of change of delta frequency is not voltage at 100.7 V. The open transition (bus interrupting) time is
used in the calculation of phase coincidence in (12), then the 2.27 cycles.
breaker closing would have been delayed by 12◦ and the phase Fig. 10 shows an oscillograph of a live transfer event that was
angle at closing would be 14◦ instead of 2◦ . This clearly shows initiated by an undervoltage relay due to a trip of the upstream
YALLA: DESIGN OF A HIGH-SPEED MOTOR BUS TRANSFER SYSTEM 619

breaker. The transfer was completed by the in-phase transfer [4] R. D. Pettigrew, “Motor bus transfer—Report prepared by the motor bus
method. The initiated signal started at 178.5◦ phase angle with transfer Working Group of the Power System Relaying Committee,” IEEE
Trans. Power Del., vol. 8, no. 4, pp. 1747–1758, Oct. 1993.
a bus voltage of 96.3 V. The breaker opening time is 2.5 cycles, [5] American National Standard for Polyphase Induction Motors for Power
and the breaker closing time is 2.9 cycles. The bus-tie breaker Generating Stations, ANSI C50.41-2000, 2000.
was closed at −1.7◦ with a bus frequency at 55.22 Hz and a bus [6] G. Benmouyal, “An adaptive sampling-interval generator for digital relay-
ing,” IEEE Trans. Power Del., vol. 4, no. 3, pp. 1602–1609, Jul. 1, 1989.
voltage at 95.6 V. The open transition (bus interrupting) time is [7] M. V. V. S. Yalla, “Design and implementation of a digital volts per hertz
4.4 cycles. All of the transfers were successful, and there was protective relay for generators and transformers,” presented at the CIGRE
no process interruption. SC34 Colloq., Johannesburg, South Africa, Oct. 1997, Paper 109.

VI. C ONCLUSION
The design of a digital high-speed bus transfer system has
been presented in this paper. Digital signal processing algo-
rithms that calculate the magnitude and phase angle of a voltage
signal over a wide frequency range have been presented. Also
Murty V. V. S. Yalla (M’84–SM’92–F’06) received
presented is an algorithm to predict the phase coincidence the Diploma in electrical engineering from Andhra
between the motor bus voltage and the auxiliary-source voltage Polytechnic, Kakinada, India, in 1976, the B.S.
using delta frequency, the rate of change of delta frequency, and degree in electrical engineering from Jawaharlal
Nehru Technological University, Kakinada, India, in
breaker closing time, which results in a very accurate prediction 1981, the M.S. degree in electrical engineering from
of phase coincidence. The algorithm has also calculated the the Indian Institute of Technology, Kanpur, India, in
bus voltage magnitude very accurately down to 4 Hz, which is 1983, and the Ph.D. degree in electrical engineering
from the University of New Brunswick, Fredericton,
important for the residual transfer method. The data from some NB, Canada, in 1987.
real-time events have also been presented. With the present-day He has been with Beckwith Electric Company,
digital signal processing technology, high-speed MBTSs can Largo, FL, since 1989, where he is currently the President. From 1988 to
1989, he taught and conducted research on digital power system protection
be designed to safely transfer a motor bus from a main source at the Memorial University of Newfoundland, St. John’s, NL, Canada. He has
to an auxiliary source using fast, in-phase, or residual transfer published several research papers in international journals on digital protection.
method. He is the holder of five U.S. patents in the areas of digital controls and protective
relays.
Several hundred digital bus transfer schemes are installed and Dr. Yalla is the Convener of the IEC Technical Committee 95 Maintenance
successfully running at various power-generating plants and Team 4—Measuring Relays and Protection Equipment: Functional Standards.
industrial facilities around the world using the design presented He is also a member of CIGRÉ Working Groups B5.04 Modern Techniques for
Protecting and Monitoring Generating Plants and B5.05 Modern Techniques
in this paper. for Protecting, Controlling and Monitoring of Power Transformers. In 2006, he
was elected as a Fellow by the IEEE Fellow Committee for his contributions
in computer relays for power systems. He has been an active member of the
R EFERENCES IEEE Power System Relaying Committee (PSRC) for the past 18 years. He is
[1] T. A. Higgins, W. L. Snider, P. L. Young, and H. J. Holley, “Report on also a member of several working groups in PSRC and the Chairman of the
bus transfer: Part I—Assessment and application,” IEEE Trans. Energy working group that developed IEEE Standard C37.102-2006 “Guide for AC
Convers., vol. 5, no. 3, pp. 462–469, Sep. 1990. Generator Protection.” He coauthored an IEEE PES tutorial on “Protection
[2] T. A. Higgins, W. L. Snider, P. L. Young, and H. J. Holley, “Report on of Synchronous Generators.” He was the Chairman of the working group
bus transfer: Part II—Computer modeling for bus transfer studies,” IEEE that received the IEEE Power Engineering Society (PES) Working Group
Trans. Energy Convers., vol. 5, no. 3, pp. 470–476, Sep. 1990. Recognition Award for an outstanding technical report entitled “Application
[3] T. A. Higgins, W. L. Snider, P. L. Young, and H. J. Holley, “Report on bus of Peer-to-Peer Communications for Protective Relaying” at the IEEE PES
transfer: Part III—Full scale testing and evaluation,” IEEE Trans. Energy General Meeting held in Denver, CO, in June 2004. He also received the IEEE
Convers., vol. 5, no. 3, pp. 477–484, Sep. 1990. Florida Council Outstanding Engineer Award in 2005.

S-ar putea să vă placă și