Sunteți pe pagina 1din 23

q7?

frq frqqqf,v etfrwar


#f,, AIRPORTS AUTHORITY OF INDIA
6rdcrd6 frtfld @. d an odraq
Office of Executive Diredor Enoa.lER)

+i. ('(r3flgl5$-freraz f:ntz \'6.&.{.2 rg frdiq. , 09.ro.2or9

r+-ffir trfrfqr

fusrq, - Eq-dtrerd Stm- wrqq srfrrd El+crd fuge fi il6tr6r trfitqr


s-+fird d,3rnrrr-3rerrr il6-dr& ffit;-d gfffi grr rnrrr rarf
Bl+qrfr frsa fi
ftig-a fuHtdi .Fr rrTarr fl+qr qr 16r t 3ilr gqfrq €m rd6 rr.fd qr qr+t rand'
E|+qra fuF.fr fi sara fuEtqrt or 5iar:nouo wt

aqaRrd gerr fi ft(',srqt rarf El+qra frgff 6r d-o-trfi frRtyar:rt ol scs


(+sdr) ERrurfud €frF + fr-qr-Ftract 6rql +qR fo-qr rrqr tr

,dqtr-trd ?16-#6r ffi{-d 3{ffi


srrq-srrdr w rfi-+ro ffiFr.Ft afraaq t
s$aw z Soeeqf; z t'+ffi ard-di fi 3{rrrr w frft{qrt +l srerflfl z riqifua
tn-t E6-i tt fa frft{cit of rEvrra }
frq qsfr tidffi h rqra Fnrr onql f
1ft ur q+,, $tt gcrr fi frv ggra, qE 6f$ d, d qu-+r g-fd{ 316&
jgmeeterchq@aai.aerotR gti6{Areftt 6t ;frfug d arqr Br go-tn tt

q$ rcs tqt;rart fr aqt fi +nq srt l+-qr urqr tl


rie'a-a, qcilqtl

,$wtHkl,il?
sg-in a-6r qdcr6 ({S-Ggd),furr

fuf,{ur
Ffra-d {fr fi rgun
t ffiq frqqqffiq ettrTwr

)dL- AIRPORTS AUTHORITY OF INDIA


adqtdo ftdva ifr t{ sn odtdq
Office of Executive Diredor Enaa,(ER)

No. AAI/Engg. (E)/ERIFDN19 Dtd.: 09.10.2019

TECHNICAL SPECI FICATIONS

Subject: - Systematic lmprovement Technical Specifications of Fire Alarm


Detection System
-

At present, different specifications of Fire Alarm Detection System are being followed
by different TS Authorities and hence it was essential to have common specifications of
Fire Alarm Detection System at all Airports.

For systematic improvement, technical specifications of Fire Alarm Detection System


have been framed by deliberation of the committee constituted by Member (Plg.).

Concerned TS Authority may update / modify the specifications based on latest lS /


CPWD / NBC Standards including latest technology time to time.

These specifications may be brought to the notice of all concerned for compliance.
Error or omissions, and suggestions for improvement, if any, may kindly be brought to
the notice to undersigned at e-mail id jgmeelerchq@aai.aero.

This is issued with approval of Member (Plg.)

Encl: As above

&rw#kil/n
JGM (Engg. -Elect)-ER, CHQ

Distribution
As per attached list
I tmdq frqtqrdq stfuTwr

)dk- AIRPORTS AUTHORITY OF INDIA


ddqqon*oz@Eq@
Office of Executive Director Enoo.(ER)

Distribution List

L. EAto Chairman, AAI,CHQ


2. Member (Finance),AAl, CHQ
3. Member (Ops.), AAl, CHQ
4. Member (Plg.), AAl, CHQ
5. Member (HR), Ml, CHQ
6. Member (ANS), AAl, CHQ
7. Chief Vigilance Officer, AAl, CHQ
8. Executive Director (Engg), AAl, NR/ WR/ ER/SR/NER, CHQ
9. Executive Director (Land Management), AAl, CHQ
10. Executive Director (PMQA) AAl, CHQ,
11. Regional Executive Director, AAl, NR/ WR/ ER/SR/NER
1.2. Executive Director (CNS-Plg.), AAl, CHQ
13. Executive Director (CNS-OM), AAl, CHQ
14. Executive Director (ATM) l/ll/lll, AAl, CHQ
15. Executive Director (Plg.)AAl, CHQ
16. Executive Director (Ops.) AAI,CHQ
17. Executive Director (kid)AAI,CHQ
18. Executive Director(Avn. Safety),AAl,CHQ
19. Executive Director(Arch.),AAl, CHQ
20. Executive Director(Admin),AAl,CHQ
21. Executive Director(Finance), AAI CHQ
22. Executive Director(Commercial),AAl CHQ
23. Executive Director(lT), AAl, CHQ
24. Executive Director(Airport System), AAl, CHQ
25. Executive Director(Security), AAl, CHQ
26. Executive Director(Tech.),AA|,CHQ
27. Executive Director(Cargo),AAl, CHQ
28. Principal (C.A.T.C), Allahabad
29. Director (l.A.A), AAl, Rangpuri
30. Airport Director, AAl, Kolkata/Chennai/Trivandrum Airports
31. GM (Vigilance)AAl, CHQ
32. GM (C&C)AAr, CHQ
33. GM (BDC),AA|,CHQ
34. GM Engg (project) AAl, Kolkata Project/ Chennai Project
35. GM Engg, AAl, NR/ WR/ ER/SR/NER, CHQ
36. GM Engg (Project)/project in-charge, AAl, Goa/PortBlair/Lucknow/Agartala Airport
37. GM Engg (C), AAl, NR/ WR/ ER/SR/NER, RHQ.
38. GM Engg (Electrical), AAl, NR/WR/ ER/ SR/NER, CHQ
39. GM Engg (C), AAl, NR, Operational Office, Rangpuri
40. GM (lT), Safdarjung Airport- pls. Upload Technical lnstruction/ Technical Circular on AAI
Website
41. MIS (Civil)& MIS (Ele.)AAI,CHQ
Addressable Fire Detection & Alarm System

_____________________________________________________________________________

ADDRESSABLE FIRE
DETECTION & ALARM SYSTEM

1/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________

ADDRESSABLE FIRE DETECTION & ALARM SYSTEM

1.0 GENERAL DESCRIPTION AND SCOPE OF WORK

1.1 This section covers the requirement of intelligent analog addressable fire alarm
system as per specification laid down below and as per description of item given
under the schedule of quantities.

1.2 The work described in this specification consists of all labour, materials, equipment
and services necessary and required to complete, test and commission the fire
detection and alarm system. Any material not specifically mentioned in this
specification but required for proper performance and operation shall be provided
and installed for a complete and operational system, by the contractor without any
extra cost to AAI.

1.3 The contractor shall furnish, and install complete and ready for intended use and
operation, an intelligent, addressable fire detection and alarm system including Fire
alarm panel(s), initiating devices (manual call stations, addressable multi sensor
detectors, beam detectors etc.) indicating devices (sounders, bells, visual warning
signals etc.) and supervisory devices, annunciators, wiring apparatus and
accessories.

1.4 The installation and locations of equipment and devices in the building shall be
governed by the relevant codes / standards with due regard to actual site
conditions, manufacturers' recommendations, ambient factors affecting the
equipment and other operations in the vicinity. If any deviation from the
specifications is necessary, approval shall be obtained from AAI before work is
started thereon.

1.5 Materials and equipment supplied shall be new, standard; current models of the
manufacturer and shall be suitable for this system. Where two or more pieces of
equipment performing the same function are required, they shall be exact duplicates
produced by the same manufacturer.

1.6 All materials, devices, and equipment shall be compatible with the circuits or
systems in which they are utilized.

1.7 Provision shall be made for interfacing Fire System Panel(s) through BMS / PA.
The panel shall be capable of inter-connected with BMS and shall have open code
architecture / open protocol.

2.0 In addition to SITC of Fire detection and alarm system, the following work shall
also be deemed to have included in the scope of work to be executed by the bidder
within his quoted amount.
i) It includes obtaining approvals from Chief Fire Officer / Fire Department
concerned and all other statutory authorities for complete scope of work as per
the prevailing rules & regulations etc.
ii) The Fire Detection and Alarm System of the building shall be integrated
with respective to the zoning of PA system so that, in case of fire, the PA
system shall automatically come in announcement mode of that
particular zone and play pre-recorded evacuation messages from PA
system.

2/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
iii) Providing repeater panel at Main Fire Station Control Room and
interconnecting the same with main FACP installed in the building.
3.0 REQUIREMENTS

a. This installation shall be made in accordance with the specifications i/c local
codes and local fire authorities having jurisdiction over this project.

b. Fire Detection & Alarm System Installation work shall be carried out in
accordance with Indian Standard Code of Practice for Electrical Wiring
Installation IS: 732 - 1989, IS: 2274-1963 and IS 2189-2008 with upto date
amendment. The control cable used shall be of Fire Retardant, Low
Smoke, Halogen Free type.
c. It shall also be in conformity with the current Indian Electricity rules and
regulations and requirements of the Local Fire Authority. Proposed Intelligent
Addressable Fire Detection & Alarm system in general shall be carried out as
per following Specifications-
d. Reference Standards
All equipment and installation shall be installed in compliance with the following
codes and listing with update amendments:
LOCAL CODES
CPWD – General Specifications for Electrical Work – Part VI : Fire Alarm
and Detection System - 2018
 National Building Code- 2016 : Fire and Life safety
IS: 2175 : Specification for Heat Sensitive Fire Detectors for Use
In Automatic Fire Alarm System
IS : 2189 : Selection, installation and Maintenance of automatic
fire· detection and alarm system code of practice
IS: 11360 : Specification for smoke detectors for use in automatic
electrical fire alarm system
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) - USA:
 NFPA 71 & 72 : National Fire Alarm Code
 UL 464 : Audible Signaling Appliances
 UL 38 : Manually Actuated Signaling Boxes
BRITISH STANDARD (BS EN54) – EUROPE:
 BS 5839 : Fire alarm system Design
Wherever these specifications calls for a higher standard of material and or
workmanship than those required by any of the above mentioned regulations and
specification then the specification here under shall take precedence over the said
regulations and standards.

e. Test at Site

i) All commissioning tests at site will be in line with NFPA / EN (Latest).


ii) Following test shall be conducted: -
- Loop Checking.
- Checking of multi sensor detectors etc. by simulation/functional test
by Aerosol Spray or as recommended by the manufacturer.

3/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
- Functional tests for fire alarm panel.
- The Mock trial of the complete Fire Detection and Alarm system.

f. Tests Certificates

Tests certificates will be furnished for all Fire alarm system devices by the
manufacturer.

4. SHOP DRAWINGS

On the basis of GFC drawings issued by the department along with soft copy (CD /
Pen Drive), the Contractor shall submit three (3) sets of Shop drawings containing
the following within 30 days of issue of GFC drawings for approval of Engineer –In –
charge.

i. Block Diagram showing all detectors and devices area wise, their
connectivity to the panel including wire description.

ii. Point-to-point wiring diagrams showing the points of connection and


terminals used for all electrical field connections in each system, all
equipment or systems which are supervised and controlled by the fire alarm
system. Diagrams shall show all connections from field devices to the
control panel initiating modules, output modules, switches, relays and
terminals. Diagrams shall show interconnection of all devices, modules,
output modules, switches, relays and terminals.

iii. The Contractor shall submit specific catalogue for each of the item specified
in SOQ for approval from AAI before procurement.

5. POWER SUPPLY

a. The control panel shall drive from 230 Volts main power supply. In case of
failure of main power supply, the panel shall be automatically switched over
to standby power supply i.e. battery. The standby battery as secondary
supply shall be such that when charged by associated battery charging
equipment it can operate independently for a period of 24 hours normal
working and then be capable of operating the system for 30 minutes during
an emergency / fault conditions. Batteries shall be of Lead Acid type sealed
Maintenance free / Li-ion.

b. In addition to the batteries, an automatic battery charger suitable for


operation on the auxiliary power available in the plant as specified above.
The capacity of the charger shall be such that the same can charge the
battery (within 12 hrs) while supplying the rated load of the fire detection
system. Facilities shall be provided to limit the voltage supplied to fire
detection and alarm system to their rated values during the time of charging.
The charger shall normally supply the battery trickle charging current and the
DC load of the fire detection and alarm system. In case the AC supply on the
input side of the charger fails the necessary power for the complete fire
detection and alarm system shall be supplied by the battery.

c. Visible and audible annunciation for troubles or failure in the power supply
system like "charger Failure", "Battery Low Voltage", etc. shall be provided.

d. Battery fault indication/annunciation shall be included in the panel.

4/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________

6.0 DESIGN REQUIREMENT


a) The system shall be provided with multiple loops and distributed as per GFC
drawing issued by the department on award of work. All devices shall be
connected directly to the loop with 2x1.5 sq. mm Armored copper FRLSZH
cable. The system shall be compatible to integrate with the PA / BMS system.
b) Addressable Multi-Sensor Detectors (smoke + heat), Addressable smoke
Detectors Addressable Heat Detectors, Addressable Beam Detectors
Addressable Manual Pull Station, Fault Isolators, Control Modules, Monitor
Module, Response Indicators, Addressable Hooters cum strobe etc.
c) The Panel shall have necessary Logic Software and Hardware built into it for
time delay starting of strobe.
d) Suitable racks shall be provided for housing control equipments etc.

7.0 SPECIFICATION
The design, supply, installation testing & commissioning of entire fire alarm
system shall conform to BS / NFPA 72. All devices including Main Fire Alarm
Panel shall be UL / EN listed.

7.1 ADDRESSABLE MAIN FIRE ALARM PANEL


a) The Fire Alarm Control Panel shall be Modular Microprocessor based
expandable fully intelligent Addressable Control Unit which shall control
all intelligent addressable detectors, manual call stations Control / Monitor
module etc. connected to it.
b) All Addressable Units shall be connected to the Panel through the Loop
Cards and shall be addressed through individualized numbers. The Panel
shall be able to obtain intelligent value for all detectors in the circuit through
a pulsed digitalized current data. The panel shall be able to analyze all
intelligent inputs from all addressable units and through its own software and
ambient level screening the panel shall be able to identify fire, possible fire
or fault conditions. The unit supervision shall be dynamic and continuous.
c) The Fire Alarm Panel itself shall have all loop cards in it. No isolated mother
board or transponder is allowed. Each loop shall be able to access a
minimum of 240 addressable detectors / devices (in any combination) per
loop.
d) The Panel shall also give adequate warning signal whenever there is Dust
Accumulation in Detectors, and upto the point of its replacement it should be
possible to change the level of ambient alarm calibration condition either by
the use of software programme operable by the Owner or by resetting the
detector.
e) Short circuiting, loose wiring or missing units shall also be reported at the
panel with pin point or segment-wise location. In such cases, the system
through the use of Fault Isolators shall be able to isolate that segment
between the two Fault Isolators.
f) The panel shall have a liquid crystal display type on it to indicate
immediately all conditions. In case of testing of the system from the panel,
the display shall be able to give readouts of intelligent value of all detectors
being tested. The panel shall also be able to carry out continuous self
monitoring when in normal condition.

5/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
g) Number of detectors / devices per loop should not be exceeding 90 percent
of the full capacity of each loop as per IS code.

The panel shall have either an in-built or external printer coupled to the panel which shall
log all events with time. The printer shall be suitable for printing panel’s event logs or
as per the configuration to print automatically any of the events such as Fire, Fault,
Alarm or Test, the unit address, time along with option for printing the Inputs, Outputs,
Disablements, Network Faults etc.

h) The panel shall also be able to discriminate between false alarms and fire
conditions, as well as priority selection of alarm address in case alarm activates in
two or more remotely located units simultaneously. In such cases, the manual call
box shall be reported first, group of sequentially laid detectors (in one room for
example) second and a detector with the greatest obscuration over a period of time
third.
i) Any time, the operator shall have following manual capacities at fire alarm panel
under password control:
 Operator privileges & ID number of upto four digits shall be assignable only by
the main operator or designated official.
 Action taken by operator shall be automatically printed on FAP printer with
operator initial, date and time.
j) The panel shall also be able to actuate switches automatically in case of fire
condition that of AHUs and power supply or other systems. The bidder will be
required to design and install the system in operation in coordination with the
associate contractor for air conditioning / other work. The bidder will not be allowed
to charge extra on this account, and such charges shall be included in his package.
k) The system shall be fail safe and adequate safe guards should be under taken that
in the event of a failure of a part of the system it shall not handicap the complete
system. The mother board shall be of modular construction.
l) The Bidder shall undertake the responsibility of the complete installation,
commissioning, user trials, training and maintenance of the system as required. The
software shall be such so as to be easily operated by the departmental Personnel,
is secured against Software errors, ability to be upgradable so as to incorporate
more detector units or replacement / changing of detector units, can incorporate
more features at a later date such as illumination control, security etc.
m) It shall be able to withstand temperature variations from 0 degree to 49 degree
Centigrade. The acceptable Relative Humidity (non condensing type) shall be upto
93%. The voltage rating shall be from as per OEM, though the voltage may be
changed depending upon the working voltages of a proprietary fire alarm panel.
n) The panel shall be totally enclosed dust and vermin proof type made of suitable
gauge dust inhibited sheet with finish. The panel shall be of completely solid state
design.
o) The logic circuitry shall be based on high noise immunity solid state hardware
employing modular construction. Logic cards shall be of epoxy fiber glass
construction.
p) The system shall meet the BS / NFPA 71 & 72 standards and shall be listed with UL
/ EN (Latest Versions).
q) Further, the system shall be expandable.

6/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________

7.2 INTELLIGENT ADDRESSABLE MULTI SENSOR DETECTOR

a) The detector shall have both optical and thermal sensor and shall be capable of
working in combined mode (Optical + Thermal) or heat mode (only Thermal) or
smoke mode with inbuilt fault isolator / isolator base.
b) The combined modes of operation both the inputs from the optical and thermal
sensors are processed using special algorithms before an alarm decision are
made. If the presence of smoke is detected above a threshold value for a period of
time or if heat sensor temperatures rise above certain fixed temp or rate of rise,
than an alarm condition will be generated. In “heat only” mode only temperature
above certain fixed level will generate an alarm conditions.
c) The microprocessor design shall be capable of selecting the appropriate sensitivity
levels based on the environment type it is in (office, kitchen etc.) and then have the
ability to automatically change the setting as the environment changes in order to
avoid nuisance alarm.
d) The multi sensor detector shall be a combination of smoke & heat and it can be
used as a smoke detector, as a heat detector or as a combined smoke/heat
detector upon demand and is programmed and set-up specifically for the
environmental conditions that it is part of. It should detect smoldering and open
fires at an initial stage by being able to detect and evaluate the characteristics of
fire and smoke (Tyndall or relevant applicable principle) as well as heat (NTC
sensor / thermistor principle). The sensitivity of the detector can be adjusted, if
required as per site conditions.
e) The multi sensor detector shall activate on receiving smoke particles in the 0.5 to
10 micro meter range or as manufactured specified. The detector shall be
completely solid state with LED indication.
f) The detector shall be able to sense incipient fire by detecting the presence of
visible and invisible products of combustion. The detector shall be suitable for low
voltage two wire supply as per OEM. The sensitivity of the detector shall not vary
with change in ambient temperature, humidity, pressure and voltage variation.
g) Neither its performance shall be affected by air current upto 10 mtr. per second.
The detector shall be suitably protected against dust accumulation / ingress and it
shall be free from maintenance and functional test at intervals. All detectors shall
be identical in construction design and characteristic to facilitate easy replacement.
The detector housing shall be damage resistant made of polycarbonate or
proprietary self extinguishing material.
h) The coverage per detector shall be as listed with UL / EN. This coverage area will
reduce depending upon structural configurations or partitions etc. The sensitivity of
detector shall be set adjusted by the supplier to suit the site requirement.
i) The multi sensor detector shall be intelligent addressable detector with electronic
addressing or manually-set digital code and be able to give intelligent output to the
fire alarm panel regarding its condition.
j) The Base of the detector shall be interchangeable with other detectors and the
construction shall be of polycarbonate or any approved flame retardant material.
The enclosure shall at least meet IP 54 protection grade.
k) It shall be able to withstand temperature variations from 0 degree Centigrade to 50
degree Centigrade. Relative humidity (non condensing type) upto 93% shall not
hamper its performance. The voltage rating shall be from as per OEM, though the

7/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
voltage may be changed depending upon the working voltages of a proprietary Fire
Alarm Panel.
l) The Detector shall meet the requirements of UL / EN and be approved by UL / EN.
It shall be possible to test the detector’s working both from the Panel as well as
locally by means designed by the bidder.
7.3 ADDRESSABLE MANUAL CALL POINT
Manual Call Station shall be of Pull / Push down Resettable type units and inbuilt
fault isolator or isolator module, completely encased in a cast aluminium housing
or in 16 gauge MS / LEXAN / Polycarbonate, with provision for cable or conduit
coupling. The Manual call station shall have the word prescribed in clear bold
letters on facia window “In Case of Fire / Push In / Pull Down / as per OEM”. Its
casing shall be of red color:
The Manual Call Box Station shall be fully addressable with its own set code and
operated by digitized signals sent from the Panel. The Voltage range shall be as
per OEM. It shall have protection as per IP 54 for indoors & IP 65 enclosure for
outdoor applications. The operating temperature range shall be from 0 degree C
to 50 degree C. Relative Humidity (non condensing) range for performance
parameters shall be between 0 to 93%.
7.4 ADDRESSABLE HOOTER CUM STROBE
The wall mounted Hooters cum Strobe and inbuilt fault isolator or isolator module,
shall be suitable for indoor and outdoor application with adjustable sound level of
90 db to 120 db at 1M distance. Strobe shall be of red colour. It shall flash at 1Hz
over the strobe’s entire operating voltage. The Hooters cum Strobe shall be
addressable and loop powered.
7.5 ADDRESSABLE DUCT SMOKE DETECTOR
The smoke detector housing shall accommodate an intelligent photoelectric
detector, of that provides continuous intelligent monitoring and alarm verification
from the panel. The Duct Casting Units shall be directly installed in the air
conditioning ducts (Return air) for detecting any hazardous quantity of products of
combustion being carried through the ducts.
The complete unit shall consist of a housing to accommodate Photo Electric
Detector with plug - in facility and sampling tubes, one for air inlet and other as the
air outlet. The Inlet tube shall extend into and across the duct width (from 0.5
meter to 3.0 meter), the outlet tube shall be of fixed length of 7.5 cm length.
When the AHU blower fan operates, a continuous cross sectional sampling of air
from the duct shall flow through the housing containing the Detector. The outlet
tube shall return the sampled air into the duct.
The housing shall be mounted outside the duct; the probe tubes shall be inserted
through the duct by cutting precision sized holes into the duct and sealed with
rubber gaskets.
7.6 ADDRESSABLE NETWORK REPEATER PANEL
The Network Repeater Panel shall be provided to display all system intelligent
points (Devices). It shall be capable of displaying all information for all points
(devices) on the network.
Network repeater panel shall have with minimum 320-character LCD (minimum)
touch screen coloured LCD display / HMI Display with touch sensor. It shall be
possible to silence alarms, evacuate and reset.
7.7 ADDRESSABLE MOTORISED AUTO ALIGN BEAM DETECTOR

8/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
a) Addressable motorised auto align type linear optical beam smoke beam detector
having control panel at low height designed to operate as components of fire alarm
systems. It should be the combination of transmitter/receiver units that can be
connected to a detector loop.
b) The Infra-Red transmitter generates a beam of light towards a high efficiency
reflector. The reflector returns the beam to the receiver where an analysis of the
received signal is made. The change in the strength of the received signal is used to
determine the alarm condition.
c) The sensitivity of the detector can be set to between 25% and 60% obscuration,
providing application flexibility to suit the environment in which the detector will be
installed. In addition to four fixed value alarm thresholds, there are two variable
thresholds that automatically compensate for changes in the environment which
could otherwise result in unwanted alarms while remaining within a known
sensitivity range.
d) The detector incorporates automatic drift compensation, whereby the detector will
adjust its detection thresholds in line with any long term signal reduction of the
beam caused by contamination of the optical surfaces.
e) Different alert for Fault and Fire condition.
f) The detector can be adjusted up to 10 degrees vertically and horizontally for
alignment. Where greater angular adjustment is required, the multi-mount
accessory will be provided.
g) The detectors have a range of 9 m to 50m, extending to 100m with a long-range
reflector kit.
a. Tested and approved to FM / LPCB / UL / BS / VdS
b. Voltage Range As per OEM
c. Temperature Range (Nominal Range) 0 deg C to (+) 50 deg C
d. Humidity (Nominal Range) 10 to 93% RH (non-condensing)
7.8 MODULES

7.8.1 MONITOR MODULE (FOR INPUT TO FIRE ALARM PANEL)


The Input Device and inbuilt fault isolator or isolator module shall provide an
addressable input for N.O. or N.C. contact devices such as manual water flow
switches, pressure switches, etc. The input device shall provide a supervised
initiating circuit.
An open-circuit fault shall be annunciated at the Fire Alarm panel (Subsequent
alarm shall be reported.) The device shall contain an LED which blinks upon being
scanned by the Fire Alarm panel. Upon determination of an alarm condition, the
LED shall be latched on. The operating voltage shall be in the range of 15 to 32
VDC, Maximum current draw 5.0 mA (LED on).
7.8.2 CONTROL MODULE (FOR OUTPUT FROM FIRE ALARM PANEL)
The control module and inbuilt fault isolator or isolator module shall provide an
addressable output for a separately powered alarm indicating circuit or for a
control relay. The control module shall provide a supervised indicating circuit
where indicated on the plans. An open circuit fault shall be annunciated at the
Fire Alarm panel.
The Output Device shall provide a control relay where indicated on the plans. The
relay contacts shall be SPDT rated at one amps / as per OEM, 24 V DC. The

9/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
device module shall contain an LED which blinks upon being scanned by the Fire
Alarm panel. Upon activation of the device, the LED shall be latched on.
8.0 Fire Cable
Multi core Copper conductor cable shall be PVC insulated, FRLSZH type
conforming to BIS specification.

9.0 TESTING
9.1 RANDOM SAMPLE TESTING:
About 5% of all fire alarm components shall be subjected to random testing by
connecting to the panels. All smoke detectors shall be tested as given above and
later cleaned with a vacuum cleaner. Hooters shall also be tested through direct
24V supply for 10 minutes.
9.2 TESTING OF EARTHING SYSTEM:
The earth continuity conductor including metallic parts of the equipments shall be
tested for earth to electrical continuity. All tests shall be carried out as per IS 3043
and resistance of complete installation shall not be more than one ohm.
9.3 TESTING AT SITE:
Following testing shall be conducted: -
a. Loop Checking
b. Checking of smoke detectors, Heat detectors etc. by simulation.
c. Functional tests for fire alarm panel.
d. The Mock trial of the complete Fire Detection and Alarm system.

10.0 COMMISSIONING AND ACCEPTANCE TESTS


The commissioning and acceptance tests shall be apart from the standard or
routine tests prescribed and normally conducted by the manufacturer / Design-
Build Contractor and will be irrespective of the fact whether the same are covered
by such tests or not. All commissioning tests at site will be in line with NFPA 71
and 72.
a. Each sounder circuit shall be energized separately and the sound level reading
taken to check for conformity with the minimum standards.
b. Mains failure performance.
c. Battery disconnection test.
d. Open circuit of each sounder circuit to be tested.
e. Short circuit of each sounder circuit to be tested.

The results of the above tests either by fault warning or fire alarm shall be
recorded in the log books which will be signed both by the Contractor and the
AAI’s Representative.
11. ASPIRATING SMOKE DETECTION SYSTEM
11.1.1 Scope of Work
Note: System shall be designed for high ceiling areas of Terminal Building and
critical areas i.e. ATC, Server / Equipments rooms etc.
This specification covers the requirements of design, supply of materials,
installation, testing and commissioning of Aspirating Smoke Detection System.
The system shall include all equipment’s, appliances and labour necessary to
install the system, complete with highly sensitive Smoke Detectors with aspirators

10/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
connected to network of sampling pipes.
11.1.2 The Bidder shall also make provision in the Aspirating Smoke Detectors to give
trip alarm to trip AHU and to shut fire dampers in the event of fire through the
relay contacts.

11.2 Codes and standards


The entire installation shall be installed to comply one or more of the following
codes and standards:
NFPA Standards-75 / 76 / 72
British Standards, BS 12839 part: 1

11.3 Approvals
All the equipments shall be designed, tested, approved or listed by:
LPCB (Loss Prevention Certification Board), UK /
FM (Factory Mutual), US /
UL (Underwriters Laboratories Inc.), US /
ULC (Underwriters Laboratories Canada) / Canada VDS (Verband der
Sachversicherer e.V), Germany

11.4 Design Requirements


11.4.1 System shall be designed and validated by OEM or its authorized System
Integrator and shall submit the detailed flow modeling calculation report from UL /
EN listed software tools for design validation of system.
11.4.2 The System shall consist of a highly sensitive smoke detector, aspirator, and filter.
11.4.3 It shall have a display featuring LCD / LEDs and Reset / Isolate button. The
system shall be configured by a programmer that is either integral to the system,
portable or PC based.
11.4.4 The system shall allow programming of:
a) Multiple Smoke Threshold Alarm Levels.
b) Time Delays.
c) Faults including airflow, detector, power, filter block and network as well as an
indication of the urgency of the fault.
d) Configurable 4 relay outputs for remote indication of alarm and fault Conditions.
11.4.5 It shall consist of an air sampling pipe network to transport air to the detection
system, supported by calculations from a FM approved computer- based design
modeling tool. Maximum transport time shall not exceed 90 seconds.
11.4.5 Optional equipment may include intelligent remote displays and/or a high level
interface with the building fire alarm system and a dedicated System Management
graphics package.

11.4.6 Performance Requirements


a) Shall provide very early smoke detection and provide multiple output levels
corresponding to Alert, Action, Fire 1 & 2. These levels shall be programmable
and shall be able to set sensitivities ranging from 0.0015– 20% obscuration /
meter.
b) Shall report any fault on the unit by using configurable fault output relays or via
the graphics Software.
c) Shall monitor for filter contamination automatically.
d) Shall incorporate a flow sensor in each pipe and provide staged airflow faults.
e) Shall have a clean air supply to maintain chamber clean all the time.

11.5 Materials and Equipment’s

11/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
11.5.1 Both Light Scattering and Particle Counting shall be utilized in the device as follows:
The detection Chamber shall be of the mass Light Scattering type and capable of
detecting a wide range of smoke particle types of varying size. A particle counting
method shall be employed for the purposes of

a) Preventing large particles from affecting the true smoke reading.


b) Monitoring contamination of the filter (dust & dirt etc.) to notify automatically
when maintenance is required.
11.5.2 The Detection Chamber shall incorporate a separate secondary clean air feed from
the filter; providing clean air barriers across critical detector optics to eliminate
internal detector contamination.
11.5.3 The detector shall not use adaptive algorithms to adjust the sensitivity from the set
values during commissioning. A learning tool shall be provided to ensure the best
selection of appropriate alarm thresholds during the commissioning process.

11.6 Detector Assembly


11.6.1 The Detector, Filter, Aspirator and Relay Outputs shall be housed in a mounting box
and shall be arranged in such a way that air is drawn continuously from the fire risk
area by the Aspirator and a sample passed through the Dual Stage Filter and then to
the detector.
11.6.2 The detector shall have an obscuration sensitivity range of 0.0015 – 20% obscuration
per meter.
11.6.3 The detector shall have four independent field programmable smoke alarm
thresholds across its sensitivity range
11.6.4 The Detector shall also incorporate facilities to transmit the following faults
a) Detector b) Airflow
c) Filter d) System
e) Zone f) Network
g) Power
h) Urgent and Minor faults. Minor faults shall be considered as servicing or
maintenance signals. Urgent fault shall indicate that the unit may not be able to
detect.
11.6.5 The detector shall have four pipe inlets which must contain a flow sensor.
Both Minor and Urgent flow faults shall be reported.
11.6.6 The filter must be a two-stage disposable filter cartridge. The first stage shall be
capable of filtering particles in excess of 20 microns from the air sample. The
second stage shall be ultra-fine, removing more than 99% of contaminant particles
of 0.3 microns or larger, to provide a clean air barrier around the detector’s optics to
prevent contamination and increase service life.
11.6.7 The aspirator shall be a purpose-designed rotary vane air pump. It shall be capable
of allowing / supporting for a single pipe run / multiple sampling pipe runs with a
transport time of less than 90 seconds.
11.6.8 The Assembly must contain relays for fire alarm and fault conditions.
The relays shall be software programmable (latching or non-latching). The relays
must be rated at 2 A at 30V DC. Remote relays shall be offered as an option and
either configured to replicate those on the detector or programmed differently.
11.6.9 The Assembly shall have built-in event and smoke logging. It shall store smoke
levels, alarm conditions, operator actions and faults. The date and time of each event
shall be recorded. Each detector (Zone) shall be capable of storing up to minimum
18,000 events.

11.7 Displays on the Detector Assembly

12/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
11.7.1 The detector shall have a LCD / LED / Bar graph display for the multiple alarm
threshold levels indicated and faults such as detector fault, airflow fault and
indication for Isolate and Reset.

11.8 Programmers
11.8.1 Programmer module may be located within the detector, or in remote mounting box.

11.8.2 Each Programmer at a minimum shall support the following features:


a) Programming of any device on the system.
b) Viewing of the status of any device in the system.
c) Adjustment of the alarm thresholds of a nominated detector.
d) Setting of Day/night, weekend and holiday sensitivity threshold settings.
e) Initiation of Auto Learn, to automatically configure the detectors alarms threshold
settings to suit the current environment.
f) Multi-level password control.
g) To Program latching or non-latching relay operation.
h) To Program energizing or de-energizing relays.
i) To Program high and low flow settings for airflow supervision.
j) To Program aspirator speed control.
k) To Program maintenance intervals.
l) Facilities for referencing with time dilution compensation.
m) Testing of relays assigned to a specific zone to aid commissioning.

11.9 Network
The devices in the smoke detection system shall be capable of communicating with
each other via twisted pair RS4812 cable. The network shall be able to support up to
2120 devices (detectors, displays units and programmers), of which at least 100
detectors can be supported.

The network shall be capable of being configured in a fault tolerant loop for both
short circuit and open circuit. Any communication faults shall be reported
unambiguously and shall be clearly attributable to an individual device or wire link
in the fault messages.

PC based configuration tools shall be available to configure and manage the network
of detectors.
Digital Communication Port shall comply with EIA RS4812 Protocol.

11.10 System Manager Graphic Software for Complete MONIOTIRING and Control of Very
Early Warning Smoke Detection System:

The software package shall centrally monitor and configure very early warning
smoke detection and fire protection systems in multiple local or remote locations.
The software package shall be compatible with smoke detection and fire protection
systems that are approved by global approvals bodies and meet all local codes,
standards and regulations.
The software shall consist of monitoring and configuration components:
The configuration component shall allow users to configure all detectors remotely by
using a connected PC.
The monitoring component shall allow users to monitor individual detectors, multiple
detectors connected via a HLI (High Level Interface) or multiple HLIs.

13/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
11.10.1 System Description
11.10.1.1 Access and Usability
The software shall support local and remote password-based access control:
Three local password-protected levels of software access: designer, user and
administrator.
Multiple user accounts with unique user-ID and password based access control.
Remote password-management of remote fire networks
The software shall have a user-friendly graphics user interface.
The software shall support cut and paste functionality for common tasks.
The software shall provide support for multiple languages including English
The software shall support translations of messages from one supported
language to another.
The software shall support disk space monitoring.

11.10.1.2 Monitoring Functionality


The software shall have the capacity to monitor multiple connections: The
software shall enable one or more workstations to monitor and configure
multiple detector systems in multiple buildings and multiple sites.
The software shall provide an event list that provides a single integrated view of
all events (faults / troubles and alarms) across multiple sites.
The software shall prioritize all events presented in the event list according to
logical precedence rules.
The software shall allow management of all events from the event list including
acknowledgement of events and resetting of devices.
The software shall allow colors to be assigned to different event types.
The software shall allow printing of event lists.

The software shall be able to provide an all-in-one monitoring solution:

Using standard RS232 ports (or Ethernet) on existing and future monitoring and
control systems, PCs using the software shall connect to and interpret status
change data transmitted from the ports and provide graphic annunciation,
control, history logging and reporting as specified herein.

Network systems that cannot interface to Network systems or systems requiring


the use of a “dry contact” or “voltage monitoring” interfaces to connect to
Network shall not be accepted.

The software shall be able to connect to multiple remote sites via IP- based LAN
or WAN using virtual serial port emulation.

The software shall communicate with one or more Network-compliant detectors


via a high level interface (HLI) natively using the Network protocol without the
necessity for using protocol translation or other communications equipment.

The software shall be able to monitor up to 2120 devices. The software shall be
compatible with 4 alarm levels:

Alert (Alarm Level 1) – may be used to activate a visual and audible alarm in the
fire risk area.

Action (Alarm Level 2) – may be used to activate the electrical/electronic


equipment shutdown relay and activate visual and audible alarms in the Security
Office or other appropriate location.

14/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
Fire 1 (Alarm Level 3) – may be used to activate an alarm condition in the Fire
Alarm Control Panel to call the Fire Brigade and activate all warning systems.

Fire 2 (Alarm Level 4) – may be used to activate a suppression system and/or


other suitable countermeasures (e.g. evacuation action or shutdown of systems).

The software shall allow importation of .wav files for event notification.

The software shall have a text-to-speech option to allow natural language


annunciation of all faults and alarms:

The text-to-speech component of the software shall use Nuance’s Real Speak
speech engine.
The text-to-speech functionality shall be available in a number of different
languages.

The software shall support sophisticated floor plan development and


management functionality:

The software shall enable floor plan drawings to be used in the software to
graphically notify users where a smoke event is occurring in their monitored
system.

The software shall allow development of multiple levels of interconnected floor


plans.

The software shall allow importation of AutoCAD, jpg, bmp and other common
image files

The software shall include software to allow designers to create and manipulate
CAD images for incorporation in meaningful context- sensitive multi-level floor
plans the software shall allow for multiple device smoke trending on a single
graph. The software shall support printing on a printer such as a line printer that
supports Unicode.

The software shall support sophisticated event log management functionality:


Event logs from all networked detectors shall be able to be retrieved and viewed.
Event logs for each monitored site and / or combined event logs for multiple
sites.
Event logs shall be able to be archived and sorted
Total event integration, consolidation and archiving across multiple networks shall
be provided. All system, network and device events shall be stored in an ODBC-
compliant database.
A remote notification facility shall enable the use of email (or SMS) to provide
immediate and up-to-date information the system’s operational status
irrespective of location.
The software shall enable presentation of unique customized corporate response
procedures upon occurrence of specific events in defined parts of the facility

11.10.1.3 Configuration Functionality


The software shall allow configuration of all models of detectors: Full remote
programming of all detector functions.
Saving of detector configurations for safe storage.

15/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
The software shall allow creation of off-line configurations for all such detectors
and allow a merge and compare of off-line configuration with on-line
configurations.

11.10.1.4 Performance Requirements


The software shall operate on either Windows 2000 Professional or Windows
XP Professional.

The software shall function on the following minimum PC specifications:


Processor – Pentium. Minimum configuration: P4 2.8 GHz 1MB cache RAM – 2
GB
Hard Disk – 1 by 80 GB system Disk; 2 by 80 GB if connected to Raid Storage
Display – Preferred: Dual Monitor AGP Card with 2126 MB memory. Minimum:
Single Monitor 128 MB memory.

11.11 Sampling Pipe (UL / LPCB listed pipes)


11.11.1 The sampling pipe shall be smooth bore with outer dia. of 25 mm. and inner
diameter of 21mm.
11.11.2 The pipe material should be suitable for the environment in which it is installed,
or should be the material as required by the specifying body.
11.11.3 All joints in the sampling pipe must be air tight and made by using solvent
cement, except at entry to the detector.
11.11.4 The pipe shall be identified as Aspirating Smoke Detector Pipe along its entire
length at regular intervals not exceeding the manufacturer’s recommendation or
that of local codes and standards.
11.11.5 All pipes should be supported at not less than 1.12 m at centres, or that of the
local codes or standards.
11.11.6 The far end of each trunk or branch pipe shall be fitted an end cap and drilled
with a hole appropriately sized to achieve the performance as specified and as
calculated by the system design.

11.12 Sampling Holes


11.12.1 Sampling Holes of 2mm, or otherwise appropriately sized holes, shall not be
separated by more than the maximum distance allowable for conventional
detectors as specified in the local codes & standards. Intervals may vary
according to calculations.
11.12.2 Each sampling point shall be identified in accordance with Codes or Standards.
11.12.3 Consideration shall be given to the manufacturer’s recommendations and
standards in relation to the number of Sampling Points and the distance of the
Sampling Points from the ceiling and roof structure and forced ventilation
systems.

11.13 Installation
11.13.1 The Contractor shall install the system in accordance with the manufacturer’s
recommendation.
11.13.2 Where false ceilings are available, the sampling pipe shall be installed above
the ceiling and Capillary Sampling Points shall be installed on the ceiling and
connected by means of a capillary tube.
11.13.3 The minimum internal diameter of the Capillary tube shall be 12mm, the
maximum length of the capillary tube shall be 2m unless the manufacturer in
consultation with the engineer have specified otherwise.
11.13.4 The Capillary tube shall terminate at a ceiling Sampling Point specifically

16/17
Addressable Fire Detection & Alarm System

_____________________________________________________________________________
approved by AAI. The performance characteristics of the sampling points shall be
taken into account during the system design.
11.13.5 Air Sampling Piping network shall be laid as per the approved pipe layout. Pipe
work calculations shall be submitted with the proposed pipe layout design for
approval.

11.14 Testing
11.14.1 Commissioning Test
11.14.1.1 Commissioning of the entire installation shall be done in presence of AAI
representative.
11.14.1.2 All necessary instrumentation, equipment, materials and labour shall be
provided by the Contractor.
11.14.1.3 The Contractor shall record all tests and system calibrations and a copy of these
results shall be retained on site in the system Log Book.

11.14.2 Functional Test


11.14.2.1 Introduce Smoke into the Detector Assembly to provide a basic functional test.
11.14.2.2 Introduce smoke to the least favorable Sampling Point in each Sampling Pipe.
Transport time is not to exceed 90 Secs.

________________________________

17/17
MODEL SOQ FOR FIRE ALARM & DETECTION SYSTEM ` `
Schedule of Quantity
Sl. No Description of Item Qty Unit Rate Amount Remark
1 Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Modular Microprocessor
based expandable intellegent Addressable Type Fire Alarm Control Panel of following loops, with
minimum 320 character graphics / LCD display with touch screen or other keypad and minimum 4000
events history log in the non volatile memory (EPROM) ,The panel should be equiped with loop capacity to
take minimum 240 intellegent addressable detectors/ devices (In any combination ) in one loop. Four
access levels, capable of taking Protocol Devices, Graphical Display, sufficient numbers of programmable
relay controls for controlling ventilation fan, fire pump room, monitoring of fire sprinkler and fire hydrant
pump, 230 volts, 50 Hz AC power supply, automatic battery charger, 24 volts sealed maintenance free lead
acid batteries sufficient for 2 hours normal working and then be capable of operating the system for 30
minutes during an emergency / fault conditions along with battery stand as required. The panel shall have
facility for seamless integration with PA system (For Giving triger Signal to Start pre-recorded Digital Voice
Evacuation from PA system in case of fire ). The panel shall be compatible for Building Management
System with open protocol BACNET / MODBUS etc. as per specification, complete as required.

1.1 __________ LOOPS Each

2 Supply, Installation, Testing & Commissioning of Graphic User Interface (GUI) / Operator work station Optional for
with PC having Intel Pentium I7 Processor including Serial ports (RS232) and USB ports and following Major
accessories etc. complete with software all as specified): Projects
a. 4 Gigabytes of RAM memory
b. 2 TB of hard disk space
c. DVD ROM
d. 21” LED colour monitor
e. Mouse with Mouse Pad
f. Standard Key Board
g. Latest Windows Operating System
h. Compatible Fire Alarm System Control Software
i. Laser Printer colour A4- 1 No
j. Software for Automatic Fire Detection and Alarm System
k. Software for Aspiration Based Smoke Detection System
l. UPS 800 VA or better
3 Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) Repeater Panel shall provide
pin point location of the fault or fire event and should Provide complete control of system at remote location. The
panel shall have a 320 character graphics / LCD display with touch screen or other keypad.

Page 1 of 3
4 Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable Each
multi criteria detector {Smoke + heat } with inbuilt fault isolator / isolator base and with unique optical
sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2
wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or
polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling
roof and concealed space and as per enclosed specifications ,complete as required. (Cost of plug in
common base shall deemed to be included in cost of detectors)

5 Supply, installation, testing and commissioning of UL / EN listed (Latest Version) intelligent Addressable Each
type Heat Detector (Fixed cum-rate of rise type) with inbuilt fault isolator / isolator base with max.
triggering temperature programable from 58 degree C to 69 degree C complete with all fixing accessories
like base, base box, self adhesive sticker indicating loop number and address etc. to be installed below /
above false ceiling, roof and concealed space, etc. interconnecting to loop cable, etc. as per specification
complete as required.

6 Supply, installation, testing and commissioning of UL / EN listed (latest version) Intelligent addressable Each
Control Module/ Relay Module (output module) with inbuilt fault isolator / isolator module for tripping
of AHU & Ventilation / pressurisation fans / hooter complete with termination etc. complete as required
and as per enclosed specifications.

7 Supply, installation, testing and commissioning of UL / EN listed (Latest Version) Response Indicators for Each
getting fire indications of detectors i/c mounting boxes installed above false ceiling area interconnecting to
loop cable etc. as per specification complete as required.

8 Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable Each
Manual call station (Resetable pull / push type) suitable for semi flush mounting, IP 54 for indoor use &
IP 65 for outdoor use with inbuilt fault isolator / isolator module with double gang outlet box, equipment
for key operated test-reset lock, electronic or rotary switches for address setting. Manual pull station shall
be connected with two wire to SLC loop of Fire Control Panel. Cover shall be made out of LEXAN (or poly
carbonate equivalent) with clear operating instruction and the word Fire appearing on the front complete
with connections etc. as required and as per enclosed specifications.

9 Supply, installation, testing and commissioning of UL / EN listed (latest version) loop powered Each
addressable Hooter-cum- strobe with inbuilt fault isolator / isolator module with adjustable sound
level in the range of min. 90 db to Max. 120 db at 1M distance complete with termination etc. as required
and as per enclosed specification.
10 Providing, installation, testing & commissioning of UL / EN listed (Latest Version) Monitor Module / input Each
module with inbuilt fault isolator / isolator module (for monitoring different electrical / mechanical device
etc) as per specifications.

Page 2 of 3
11 Supplying & laying of 2 x 1.5 sqmm FRLS armoured cable, 600 / 1000V rated with annealed Mtr
copper conductor as per applicable IS standared complete as required.
12 Supplying & drawing of 2 x 1.5 sqmm FRLS unarmoured cable, 600 / 1000V rated with annealed Mtr
copper conductor as per applicable IS standared complete in existing surface / recessed steel / PVC
conduit as required.
13 Supplying, Installing, Testing and Commissioning of UL / EN listed (Latest Version) Addressable Each Suitable
motorised auto align Beam detector with transmitter, receiver & control panel as per where height
specification,complete as required. more than 10
meter
ASPIRATING SMOKE DETECTION SYSTEM (ASDS)
14 Design, Supply, Installation, Testing and commissioning of Intellegent Addressable UL / EN listed (Latest Suitable for
Version) Following channel - LED / Laser Based Aspiration Detection Unit with area coverage with highrise area
sensitivity ranging from 0.0015 - 20% obs/m along with 8 Relay Outputs, 3 Stage Filtration with TCP / IP of Tr.
network Capability. as required. Bldg.and
The cost will include Power Supply Unit for above detector 230 V AC to 24 V DC 1.5 Amp with 24 hour critical area
battery backup in normal condition and 30 minutes in alarm condition etc. complete with as per i.e ATC,
specificationsas , complete as required. Server /
Equipment
room etc.
14.1 Four Channel with area coverage of 28000 sq. feet Lot
14.2 Single Channel with area coverage of 2000 sq. feet Lot
14.3 Supply, Installation, Testing and commissioning of Fire Retardant c-PVC PIPE (25 mm OD) including end Lot
cap complete in all respect as required. The air sampling holes on pipe should be clearly marked for
identifiacation.
Note: Actual pipe quantities shall be calculated by tenderer based on hydraulic calculation through UL / EN
listed approved software considering design parameter provided in tender, the bidder is received to submit
detail calculation & drawings for evaluation of the design and quantities requirement.

Page 3 of 3