Documente Academic
Documente Profesional
Documente Cultură
Gravity Separation
EDS-2004/GS-1
The first half of this session discusses gravity separation of fluids. The second half
discusses mist elimination and coalescing.
Surge Drums
EDS-2004/GS-2
Surge drums are vessels whose only function is to provide residence time. This
capability may also be provided in equipment that has other duties. The concept of
residence time is covered in this presentation because one important function of a
separator is the provision of residence times.
Surge Volume
EDS-2004/GS-3
EDS-2004/GS-4
The required residence time in a reactor is related to the desired chemical reactions
and the necessary time for them to come to completion.
The required residence time in a surge drum may be related to variations in flow
rate or to the time required to recognize an incident and take the appropriate action,
for example, stop or start a pump.
Examples of Uses
Surge capacity also provides temperature stability when the incoming stream
temperature has short term variations. The variations are eliminated by mixing with
the larger volume of uniform temperature material in the drum.
Surge Drum Orientation
Vertical
– Most economical orientation considering
vessel cost
– Level reacts more quickly to changes in flow
than in a horizontal vessel
Horizontal
– Greater liquid surface area results in less
change in liquid level during flow variations
EDS-2004/GS-6
Vertical surge drums take up a smaller amount of plot space than their horizontal
counterparts. The quick reaction to changes in flow allows rapid detection of flow
variations. Horizontal surge drums react much more slowly but provide a much
more constant liquid head and, possibly, flow rate to downstream pumps or other
equipment.
Vertical surge drums require skirts or legs for support; horizontal surge drums
require saddles for their support.
Surge/Storage Sizing Example
EDS-2004/GS-7
L/D is typically 3, but may be as low as 2 or as high as 4. This L/D ratio results in
an economical vessel cost to volume ratio.
For this example, we will use a residence time of 30 minutes. We will cover other
residence times later in the presentation.
Residence times are normally based upon a 50-75% full drum. The value to use is
based upon experience with the process and potential for and consequences of the
liquid level exceeding this point.
Surge/Storage Sizing Example
EDS-2004/GS-8
EDS-2004/GS-9
Other forms of separation using thermal or chemical means or molecular sieves (for
example, adsorption, fractionation) are not part of this presentation.
Separation
EDS-2004/GS-10
The above statements are part of the dictionary definition of separation. In the
refining environment, we are mostly concerned with separating vapors from liquids
and separating immiscible (see slide 13) liquids with different densities.
Reasons for Separation
EDS-2004/GS-11
In Crude Unit Desalters, salt laden water is removed from the crude oil.
EDS-2004/GS-12
Miscible fluids, such as alcohol and water, cannot be separated by gravity, nor can
fluids having similar or equal densities. Miscible fluids may separate under the
influence of heat, chemical reactions, filtering, etc.
Separation is not perfect. There will be some of the heavy fluid in the light fluid
and some light fluid in the heavy fluid. The degree of separation and cost of
separation are directly proportional.
Immiscible
EDS-2004/GS-13
Immiscible fluids can be mixed together, but they will not stay mixed unless some
form of emulsion is created during mixing. The fluids will separate on their own
under the influence of gravity.
• Suspension - Solid particles are mixed with, but undissolved, in a fluid (or
solid)
Momentum
Gravity Settling
Coalescing
EDS-2004/GS-14
Wire mesh coalescing blankets are used to help separate light and heavy liquids by
combining very small heavy liquid droplets into large droplets, which can then be
separated from the light liquid by gravity.
Momentum Separation
EDS-2004/GS-15
In two-phase flow through an elbow, the heavier phase will flow toward the outside
of the elbow, and the lighter phase will flow toward the inside of the elbow.
Gravity Separation
EDS-2004/GS-16
The dense phase sinks through the light phase, and the light phase floats up through
the dense phase. “Rise” means the lighter fluid is displaced by the falling heavier
fluid.
1.26 D
EDS-2004/GS-17
Smaller drops combine into larger drops due to random collisions. In the example
shown, the combined drop is 25% bigger and has twice the mass of the two
individual drops and, therefore, settles better.
Coalescing Separation
EDS-2004/GS-18
Gravity separation alone can be used if we have unlimited time and vessel size;
coalescing reduces both.
Other factors that affect combination or fusion of droplets include surface tension
and electrical attraction.
Separator Zones
EDS-2004/GS-19
The major part of the vessel provides the secondary (gravity) separation.
Coalescing blankets and mesh blankets coalesce small drops into larger ones. They
are generally located at the vapor outlet to remove liquid droplets from the exiting
vapor. They may also be immersed in the liquid to aid in liquid/liquid separation.
A drop leg or “boot” may be used to separate the light liquid phase from the dense
liquid phase (frequently water).
Horizontal and Vertical Separators
EDS-2004/GS-20
In both vessels:
EDS-2004/GS-21
In vertical vessels, keeping the velocity of the continuous phase less than the
terminal velocity of the dispersed phase means that the dispersed phase moves in the
opposite direction from the continuous phase, allowing separation. If the continuous
phase velocity exceeds the terminal velocity, both phases will go the same direction,
though at different speeds, and exit through the same nozzle unseparated.
Terminal Velocity
EDS-2004/GS-22
Note that the terminal velocity is relative to the continuous phase, not as would be
seen by an outside observer. This is a very important concept to understand.
Terminal velocity applies to a bubble rising in a liquid (for example, a bubble rising
in a carbonated beverage).
Terminal velocity also applies to a drop falling through a lighter phase fluid (rain is
an example).
At terminal velocity, gravity, buoyancy, and friction effects balance and there is no
further acceleration of the particle.
Continuous Phase
EDS-2004/GS-23
EDS-2004/GS-24
A fluid may be a dispersed phase in one section of a separation vessel and the same
fluid may be the continuous phase in another section of the same vessel.
Gravity Settling Laws
Particle Settling in a Fluid
Fd + Fb Fd = Drag
Fb = Buoyant Force
Fg = Gravitational Force
F = Resultant Force
a = Particle Acceleration
Fg u = Particle Velocity
du
F = Fg − Fd − Fb = ma = m
dt
EDS-2004/GS-25
At terminal velocity, all of the forces are balanced. Gravity pulls down and
buoyancy pushes up. Drag tries to keep the particle or drop where it is.
The equation is equally valid for rising bubble (though Fd is down in that case) as
for falling droplets.
For a particle to fall (rise), ut must exceed the upward (downward) continuous phase
velocity. Normally, especially in horizontal vessels, the continuous phase is
virtually motionless in the direction of settling (droplets) or rising (bubbles). This is
why horizontal gravity separators are preferred. Drop legs are different, acting as
mini-vertical separators.
Gravity Settling Laws
Particle Settling in a Fluid
At Steady State:
du
=0
dt
So Fg = Fd + Fb
EDS-2004/GS-26
mg
Where: Fg =
gc
mρ g
Fb =
ρp g c
CDu t2ρA p
Fd =
2g c
πDp2
Ap =
4
1
m = πρp Dp3
6
EDS-2004/GS-27
As the size of a spherical particle increases, the gravity and buoyancy forces
increase in proportion to the mass, a function of Dp3. The drag force, however,
increases more slowly, as a function of Dp2. As a result, large particles pass through
a different density fluid more quickly than small particles, enhancing separation.
Gravity Settling Laws
Particle Moving in a Fluid
m = Mass of particle
g = Gravitational acceleration
gc = Gravitation constant
ρ = Density of continuous fluid
ρp = Density of particle
Ap = Projected area of particle
Dp = Diameter of particle
CD = Drag coefficient (based upon velocity
relative to continuous phase)
µ = Viscosity of continuous fluid
ut = Terminal velocity
EDS-2004/GS-28
Gravity Settling Laws
Particle Settling in a Fluid
4 D p g( ρ p − ρ )
0 .5
For Heavy Droplet -
ut = Light Continuous Phase
3CD ρ For Light Droplet -
Heavy Continuous Phase,
use ρ − ρp
EDS-2004/GS-29
Just as in universities and textbooks, proof of the formula derivation is left to the
student.
Clearly, larger particle diameter and larger density difference increase the terminal
velocity and higher drag (viscosity) decreases the terminal velocity.
Gravity Settling Laws
Particle Moving in a Fluid
Limitations
– Spherical particle
– Stagnant fluid
– No interaction with other particles
– No wall effects
EDS-2004/GS-30
100,000
10,000
1,000
100
Spheres
10
Disks
Cylinders
1.0
0.1
0.0001 0.001 0.01 0.1 1.0 10 100 1,000 10,000 100,000 1,000,000
EDS-R02-3446
EDS-2004/GS-31
Note that drag decreases in turbulent flow (high Reynolds numbers). The
turbulence breaks up the boundary layer, reducing drag.
Newton’s Equation
gDp (ρp − ρ )
0.5
And: u t = 1.75
ρ
EDS-2004/GS-32
We are concerned with the flat part of the curve where the drag coefficient is 0.44.
The droplet size (>1000 microns) is so large that it can cause excessive turbulence.
This equation is occasionally applied to liquid from vapor separation, but not often,
because the particle size is larger than designed for in practice.
Newton’s Equation
(continued)
100,000
10,000
1,000
100
SPHERES
10
DISKS
CYLINDERS
1.0
0.1
0.0001 0.001 0.01 0.1 1.0 10 100 1,000 10,000 100,000 1,000,000
SD-R03-01a
EDS-2004/GS-33
The flat section is the Newtonian Region (ignore magnetic attraction, electrical
attraction, etc.).
4Dp g(ρ L − ρ V )
0.5 0.5 0.5
4(1.75)(32.2) ρL − ρV
ut = =
3C Dρ V 3(1)(304.8) ρV
0.5
ρ − ρV
= 0.496 L
ρV EDS-2004/GS-34
This drag coefficient is frequently used for separation in the Newtonian region,
where the assumption of a spherical particle is questionable.
Stokes’ Equation
For: N Re < 2
D P ρµ t
Where: N Re =
µ
24
Then: CD =
N Re
And:
ut =
(ρ P − ρ)gDP2
18µ
EDS-2004/GS-35
10,000
1,000
100
SPHERES
10
DISKS
CYLINDERS
1.0
0.1
0.0001 0.001 0.01 0.1 1.0 10 100 1,000 10,000 100,000 1,000,000
Dpρut
Particle Reynolds Number, NRe = µ Newton CD = 0.44
500<NRe<200,000
SD-R05-03
EDS-2004/GS-36
D p ρu t
Where: N Re =
µ
18.5
Then: CD =
N 0Re.6
0.153g 0 .71D1p.14 ( ρ p − ρ)
0 . 71
And: ut =
ρ 0 . 29 µ 0 .43
EDS-2004/GS-37
The intermediate segment of the curve yields a complicated formula where drop
diameter and density are the major contributors.
10,000
1,000
100
SPHERES
10
DISKS
CYLINDERS
1.0
0.1
0.0001 0.001 0.01 0.1 1.0 10 100 1,000 10,000 100,000 1,000,000
To determine ut, we need to find CD, which requires the particle Reynolds Number
(NRe). However, we need to know ut to find NRe. This is not the problem it appears
to be because we do not need the exact Reynolds Number; we only need to know
which of three regions it falls into - Newton, Intermediate, or Stokes. From case-to-
case, ut will vary by a factor of only 5 or 6, while Dp can vary by a factor of 100 or
more. Therefore, Dp has a much greater effect on NRe and the “region” to use. In
reality, certain types of separation (e.g., liquid from vapor) are considered to be in a
constant, specific, “region” (see Slide #41).
Close Fluid Densities
EDS-2004/GS-39
In Case A, the density difference is much greater and, therefore, the terminal
velocity is much greater for separating water from air than for separating water from
hydrocarbon.
Gravity Setting
Laws and
Particle
Characteristics
SD-R01-09
EDS-2004/GS-40
Stokes Law
– Vapor separation from a continuous liquid phase
– Dispersed liquid separation from a continuous
liquid phase
Intermediate Law
– Liquid separation from a continuous vapor phase
EDS-2004/GS-41
Liquid from vapor separation is based upon a rather large particle size. This is
because there is usually a mist eliminator (e.g., mesh blanket) to remove smaller
particles via coalescence.
The applicable separation law to use for each type of separation is based upon the
typical size of particles targeted for separation.
Selection of the Dispersed
Particle Size to be Separated
EDS-2004/GS-42
EDS-2004/GS-43
These default drop diameters are used unless we know something specific for a
particular system. This is almost never the case.
Horizontal Separator Sizing Example
Problem
Design a Reactor Product Separator for
a Naphtha Hydrotreating Process Unit.
EDS-2004/GS-44
EDS-2004/GS-45
When sizing a vessel, use actual sets of conditions, not the worst of each piece of
data (Q, ρ, etc.). Combining the worst data will yield a conservative, but oversized,
uneconomically, sized vessel.
Flow Schematic
SD-R01-10
EDS-2004/GS-46
Select L/D
EDS-2004/GS-47
The vessel length is a key component of many of the design formulas used in
horizontal separation vessel sizing. In the example problem, an L/D of 3 is built
into the formulas. Use of a different L/D will result in a different constant in many
of the formulas.
Horizontal Vessel Sizing Example
Sizing Steps (continued)
EDS-2004/GS-48
We will do several calculations and pick whichever gives us the largest vessel
diameter.
Liquid Coalescing Blanket
EDS-2004/GS-49
The coalescing blanket will be oriented vertically and cover the full cross section of
the vessel. The blanket is intended to coalesce small droplets into larger ones for
improved settling efficiency.
SD-R02-12
EDS-2004/GS-50
EDS-2004/GS-51
The high and low liquid levels determine the range of the level transmitter. High
and low level alarms are frequently provided.
Horizontal Vessel Sizing Example
EDS-2004/GS-52
UOP typically uses an L over D ratio of 3. See the comments on slide 47.
The normal liquid level (NLL) is usually placed at the centerline in horizontal
vessels.
Horizontal Vessel Sizing Example
0.36 ft 3 60 s
VL = Q L t = (10 min ) = 216 ft
3
s min
EDS-2004/GS-53
0.36 ft 3
= total liquid flow = 0.35 (hydrocarb on) + 0.01 (water)
sec
Horizontal Vessel Sizing Example
πD 2L 3πD 3
VV = =
4 4
( )
1 1
4V 3 4 432 ft
3 3
D= V =
3π 3π
D = 5.7 feet
EDS-2004/GS-54
The head volumes could be included in the total volume calculation but are not
because they add unnecessary complication to the calculation. The head volumes
are small compared to the cylindrical section and will have a small effect upon the
required vessel diameter.
Phase Separation in Horizontal Vessels
Horizontal Vessels D Inside diameter, ft
DDL O.D. of drop leg, in
Vessel dimensions based on vapor/liquid/liquid separation with drop leg. ADL Area of drop leg, ft2
L L Tangent length, ft
LDL Length of drop leg, ft
0.5D L-D 0.5D
VCV Velocity of continuous vaper phase, ft/s
Max. Minimum Max. VDV Velocity of dispersed vaper phase, ft/s
VTL Velocity of total liquid phase, ft/s
VCV VDL Velocity of dispersed liquid phase, ft/s
VDL
VDLL Velocity of dispersed light liquid phase, ft/s
VDV D
VDHL Velocity of dispersed heavy liquid phase, ft/s
VTL VHL Velocity of continuous heavy liquid phase, ft/s
VDHL X Diameter fraction of the continuous phase under study
L
VDLL Y - 1 (inlet and outlet 0.5D from ends)
D
coalescing LDL VHL 0.5D
mesh blanket Z Fraction of cross-section area corresponding to X
DDL Max.
(optional) T Time, minutes
0.5D ρL Liquid density, lb/ft3
ρV Vapor density, lb/ft3
QCV Vapor flow rate, ft3/sec
Diameter for gravity setting liquid from vapor phase
µ Vapor viscosity, lb/ft•sec
V
µ Liquid viscosity, lb•ft/s
L
DPV Vapor particle diameter, ft (in the absence of
specific process data ,use 0.00057 ft.)
DPL Liquid in thevapor particle diameter (feet) (0.00082 ft.)
DPH Heavy liquid particle diameter (feet) (0.00041 ft.)
QL Total liquid flow rate, gpm
QCHL Heavy liquid flow rate, gpm
SD-R03-13
EDS-2004/GS-55
The dimensions to the inlet and outlet nozzles are to the side of the nozzle furthest
from the heads, giving the least length available for gravity separation. As shown,
the nozzles are at their maximum permitted distance (½D) from the head.
Horizontal Separator Liquid Levels
EDS-2004/GS-56
In all cases, review the maximum and minimum liquid levels per the next slide.
Horizontal Separator Liquid Levels
(continued)
EDS-2004/GS-57
Use of a minimum vapor (or conversely, liquid) space of 25% of the diameter (20%
of the cross sectional area) keeps an adequate interface surface for separation and
keeps the continuous phase velocity in the small volume from becoming too large.
A minimum liquid level also guards against cavitation of any pumps taking suction
from the vessel. If either the liquid or the vapor space becomes too small, the
resultant high velocity will tend to re-entrain the other, already separated, phase at
the interface between the phases
Phase Separation in Horizontal Vessels
Continuous (Liquid)
VDV =
2
gD PV (ρ L − ρ V )
18µ L
Dispersed (Vapor)
EDS-2004/GS-58
EDS-2004/GS-59
Phase Separation in Horizontal Vessels
(continued)
QL QL
VTL =
(
Z 0.785D 2
)(7.48)(60) =
352.3ZD2
Where: - QL is the liquid flow rate, gpm
- Z is the fraction of cross-sectional area
corresponding to X
- 0.785D2 is the total cross-sectional area
- (7.48)(60) converts from ft3/s to gpm
EDS-2004/GS-60
VTL is the velocity of the total liquid phase from the inlet to the hydrocarbon outlet.
7.48 = gal/ft3
352.3 = constant dependent upon the units as given above (gpm)
Phase Separation in Horizontal Vessels
(continued)
YD
T=
VTL
EDS-2004/GS-61
L
Y= − 1 is based upon the inlet and outlet nozzles being as far from the
D heads (0.5D each) as permitted; it is conservative.
The portion of the vessel length available for separation is the distance between the
inlet and outlet nozzles. It is expressed as a function of the diameter, with Y being
the number of vessel diameters in this length.
YD = L − (0.5D + 0.5D )
YD = L − D
L
Y= −1
D
Phase Separation in Horizontal Vessels
(continued)
XDQL gYDD2PV (ρ L − ρ V )
=
352.3ZD2 18µ L
EDS-2004/GS-62
The worst case is for the bubble to rise from the lowest point in the vessel to the
surface just as the hydrocarbon liquid is withdrawn from the vessel.
– Solve for D
0.5 0.5
18X Q Lµ L
D= 2
352.3ZY gDPV (ρ L − ρ V )
EDS-2004/GS-63
Solve for D:
Y = 2 based upon Y =
L with L
−1 =3
D D
(Nozzles as far from the tangent lines as possible)
Phase Separation in Horizontal Vessels
(continued)
EDS-2004/GS-64
If we use the minimum hydrocarbon level, the vapor bubbles have the least distance
to rise, but the liquid velocity is at its maximum.
For a design where, at the minimum liquid level, a rising bubble reaches the surface
at the moment it reaches the outlet, at the maximum liquid level, the same bubble
will reach the surface only ¾ of the way to the outlet. The bubble must rise three
times as far (0.75φ vs. 0.25φ) taking three times as long (the terminal velocity, ut, is
the same in both cases). However, it takes four times as long to travel from the inlet
to the outlet. The velocity is ¼ as great because the flowing area is four times as
great (0.8ATOTAL vs. 0.2ATOTAL). After three times as long (when the bubble
reaches the surface), it is only ¾ of the way to the outlet.
The same scenario holds for all intermediate liquid depths; therefore, the minimum
liquid depth governs.
Phase Separation in Horizontal Vessels
(continued)
– Then:
0.5
Q Lµ L
D = 0.18
gDPV (ρ L − ρ V )
2
0 .5
D = 0.18
(163)(0.000282)
(32.2 )(0.00057 ) (46.34 − 0.125 )
2
D=1.75 feet
for vapor from liquid separation
EDS-2004/GS-65
Use the lower liquid density (hydrocarbon) because this is, by far, the predominant fluid in
the liquid phase and use of the lower density is conservative, if anything. The vapor will
separate more quickly from a denser fluid.
The vessel diameter determined is the minimum that will achieve separation of the specified
size of particle. If the actual diameter used is larger, the distance the dispersed phase particle
must travel, i.e., the continuous phase depth (at 25% of the diameter), increases as a function
of the diameter. The horizontal fluid velocity decreases as a direct function of the flowing
area, which increases as a function of the square of the diameter.
For example, double the vessel diameter from φMIN to 2φMIN. The flowing area in the first
case = 0.2πφMIN2/4. In the second case, the flowing area = 0.2π (2φMIN)2/4 = 0.2π4φMIN2/4.
Therefore, the flowing area is four times as great, and the velocity ¼ as great; hence, it takes
four times as long to travel the same distance. Additionally, the travel distance is a function
of the diameter (e.g., L = 2D) and would double; therefore, a droplet would take 4 x 2 = 8
times as long to go from the vessel inlet to outlet. The liquid depth doubles; therefore, it
takes twice as long to rise through the liquid.
For an increased vessel diameter, the time to escape the continuous phase is a function of the
diameter change, while the time in the vessel is a function of the second (or third,
considering that the length is also a function of diameter) power of the diameter. Therefore,
the desired particle size will escape the continuous phase more easily for a larger diameter
vessel, or one where the L/D is greater than the L/D used in determining the minimum
diameter.
Phase Separation in Horizontal Vessels
(continued)
EDS-2004/GS-66
Phase Separation in Horizontal Vessels
(continued)
gD2PH (ρ HL − ρ LL )
VHL =
18µ LL
– and:
XD YD
T= =
VHL VTL
EDS-2004/GS-67
Phase Separation in Horizontal Vessels
(continued)
0.5 0.5
18 X Q Lµ LL
D= 2
352.3YZ gDPH (ρ HL − ρ LL )
EDS-2004/GS-68
Here, Y is not strictly the correct value to use. What should be used is the distance
from the inlet to the leading edge of the boot, as a function of D (this may be the
same as Y).
Phase Separation in Horizontal Vessels
(continued)
0.5
Q Lµ LL
D = 0.18
gD2PH (ρ HL − ρ LL )
0 .5
D = 0.18
(163)(0.000282)
(32.2 )(0.00041)2 (61.55 − 46.34 )
D = 4.2 ft
for liquid/liquid separation
EDS-2004/GS-69
Thus, we know that a larger vessel diameter is required to separate water from the
hydrocarbon liquid phase. The reason is that the densities are closer than for
vapor/liquid separation.
Phase Separation in Horizontal Vessels
(continued)
EDS-2004/GS-70
Calculate liquid separation from the vapor phase at the maximum liquid level. This
gives the minimum continuous phase (vapor) depth (0.25φ). This governs the
design for the same reasons the minimum liquid depth is used for separation from
the liquid (see Slide #64).
Separate the hydrocarbon liquid from the vapor; separating the water from the vapor
will not govern the design because water is denser than hydrocarbon.
Here, we use the more complicated formula applicable to the Intermediate Reynolds
number regime. This is because the target particle size is greater because a mist
eliminator is typically present at the vapor outlet to trap and coalesce smaller
particles. Gravity separation of these particles is not necessary.
Phase Separation in Horizontal Vessels
(continued)
XD YD
T= =
VDL VCV
XDVCV = YDVDL
QCV
VCV =
(
Z 0.785D 2 )
VDL =
0.153g 0.71D1PL
.14
(ρL − ρ V )0.71 (Intermediate Law )
ρ 0V.29µ 0V.43
EDS-2004/GS-71
Here, QCV is in units of ft3/sec, not gallons per minute, hence the different form of
the equation for VCV versus that for VTL (see Slide 60). The difference is the
conversion factor for changing GPM to ft3/sec.
Phase Separation in Horizontal Vessels
(continued)
YD 0.153g 0 .71D1PL.14 ( ρ L − ρ V )
0 . 71
XDQ CV
=
(
Z 0.785D 2 ) ρ 0V. 29 µ 0V.43
0 .5 0 .5
X Q CV ρ 0V. 29 µ 0V.43
D= 0 .71 1.14 0 . 71
0.785( 0.153) YZ g D PL ( ρ L − ρ V )
EDS-2004/GS-72
Solve for D.
Phase Separation in Horizontal Vessels
(continued)
0 .5
QCV ρ 0V.29µ 0V.43
D = 2.28
g DPL (ρ L − ρ V )0.71
0.71 1.14
QCV = 1.54 ft 3 s
ρ V = 0.125 lb ft 3 ρ L = 46.34 lb ft 3
D=0.68 feet
EDS-2004/GS-74
The calculated diameter is low due to the high density difference and large particle
(droplet) diameter.
Phase Separation in Horizontal Vessels
(continued)
Diameter Requirements
– Residence time 5.7 feet
– Vapor from liquid 1.75 feet
– Liquid from liquid 4.2 feet
– Liquid from vapor 0.68 feet
EDS-2004/GS-75
Phase Separation in Horizontal Vessels
(continued)
D = 6 feet
L = 3D = 18 feet
EDS-2004/GS-76
Take the governing calculated diameter (5.7 feet), round up to 6 feet, and determine
length based on 3 x D = 3 x 6 = 18 feet. Overall vessel dimensions (diameter and
tangent length) are rounded up to the next multiple of 6 inches (English units) or
100mm (metric units).
Using the selected vessel diameter, the “actual” particle size gravity separated in
each of the preceding cases (vapor from liquid, liquid from liquid, liquid from
vapor) and the actual residence time provided could be determined. All will be
better, perhaps greatly so, than the values used for design.
If a demisting (mesh) blanket is used at the vapor outlet, check the vessel geometry
to insure that the blanket is entirely above the high liquid level. There must also be
sufficient space between the high liquid level and the underside of the blanket for
vapor flow (vapor can enter the blanket only from the underside). The clearance
should normally be a minimum of one fourth the largest dimension of the blanket.
Phase Separation in Horizontal Vessels
(continued)
EDS-2004/GS-77
When the liquid level is low, the velocity through the mesh blanket may be too
high, but this is rarely the case. Check.
As noted on Slide 60, the 352.3 value is dependent upon the units used. Here, QL is
in GPM and is converted to ft3/sec.
At this point, a decision is necessary. At the lowest liquid level, the velocity
through the liquid coalescing blanket exceeds the target value (3 ft/min). One
option is to increase the vessel size to lower the velocity to less than 3 ft/min. The
other is to accept the consequences of the high velocity when the liquid level is at its
lowest. A little deeper liquid will result in a lower, acceptable, velocity. At the NLL
(half full), Z = 0.5 and the velocity = 3.9 x 0.2/0.5 = 1.56 ft/min, well below the
larger of 3 ft/min.
Phase Separation in Horizontal Vessels
(continued)
163
0.05 =
( )
352.3(0.2 ) D2
1
163 2 1
D= = (46.3 ) 2
(352.3)(0.2 )(0.05 )
We need to increase the vessel diameter to 6.8 feet, per this velocity criteria, so the
new vessel diameter is 7 feet.
Horizontal Vessel Sizing Example
(continued)
Drop Leg (Boot) Sizing Steps
EDS-2004/GS-79
Calculate the boot diameter assuming the standard length of 3.5 feet. This length is
nearly always adequate to provide the required residence time with a boot diameter
below ½ the vessel diameter (see following slide). Long boots result in interference
with equipment and piping below the vessel and require the vessel elevation to be
increased to provide the needed net positive suction head (NPSH) on the water
pumps taking suction from the boot.
Horizontal Vessel Sizing Example
(continued)
Drop Leg (Boot) Sizing Steps
EDS-2004/GS-80
The drop leg diameter must be less than ½ of the vessel diameter or special,
expensive reinforcement of the vessel/drop leg attachment will be required.
In rare cases, we may have to reduce the drop leg diameter at the expense of
separation efficiency.
Drop leg diameters are usually selected based on standard pipe sizes.
If the drop leg diameter is greater than ½ the vessel diameter, reduce to less than ½
the vessel diameter and increase the drop leg, or boot, length. This is the normal
solution and will provide for the required residence time and solve the “problem”
when residence time governs the diameter and the new diameter is still greater than
needed for separation efficiency. If, at the new diameter, the continuous phase
velocity exceeds the terminal velocity, the separation of the desired particle size will
not occur. In that case, either use the boot size required for the desired separation
and design a special boot/vessel convection or back-figure the size of particle that
will be separated and determine if it is acceptable.
Horizontal Vessel Sizing Example
(continued)
SD-R01-14
EDS-2004/GS-81
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
EDS-2004/GS-82
Because of the greater difference in densities, vapor separates out of the water phase
more easily than hydrocarbon liquid separates from the water so vapor separation
rarely, if ever, governs.
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
VDLL =
2
gD PL (ρ HL − ρ LL )
18µ HL
Velocity of the continuous heavy liquid phase
(water) is the volumetric flow rate divided
by the cross-sectional area of the drop leg
Q CHL Q CHL
VCHL = = 2
A DL 0.785D DL
EDS-2004/GS-83
In this case, the flows are vertical with the heavy water phase flowing down and the
light hydrocarbon liquid phase flowing up. The larger the drop leg, the better the
separation because the downward heavy phase moves more slowly.
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
0.5 0.5
18 QCHLµ HL
D DL = 12 × 2
.785(7.48 )(60 ) gDPL (ρ HL − ρ LL )
EDS-2004/GS-84
Solve for the drop leg diameter when the terminal velocity and water velocity are equal.
The constants in the above equation are based upon Q in gallons/minute, converting it to ft3/sec.
Setting the continuous phase and terminal velocities equal gives the largest continuous phase
velocity, hence the smallest diameter boot in which the desired separation will occur.
To illustrate why the heavy phase velocity must be less than the light phase terminal velocity,
consider continuous and dispersed phase droplets that begin together. Assume the continuous phase
moves down at 10 feet/second, and the dispersed phase terminal velocity is 8 feet/second, meaning it
rises relative to the continuous phase at 8 feet/second. After one second, the continuous phase has
moved down 10 feet, and the dispersed phased has moved up 8 feet relative to the continuous
phase. It still dropped 2 feet, however, and will eventually be carried out the same outlet as the
continuous phase, hence no separation. If the terminal velocity were 12 feet/second, then the
dispersed phase moves up and out of the boot. This would happen for a larger particle size than the
particle with the 8 feet/second terminal velocity. In the example, particles with a terminal velocity
greater than 10 feet/second will separate. Another solution is to increase the drop leg diameter to
slow the continuous phase. Terminal velocities are not affected by the drop leg diameter.
Another illustration is an airplane flying into the wind. If the plane flies at 150 mph into a 200 mph
wind, it is moving at 150 mph relative to the wind and remains airborne. However, its speed relative
to the ground is 50 mph backwards! It will never reach its destination.
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
0.5
QCHLµ HL
D DL = 2.71
gDPL (ρ HL − ρ LL )
2
0 .5
D DL = 2.71
(5)(0.000342)
(32.2)(0.00041)2 (61.55 − 46.34 )
EDS-2004/GS-85
Thus, we need a minimum 12.4 inch diameter drop leg for good separation of the
specified particle (droplet) size, density, and viscosity.
Use of a larger diameter drop leg means a slower continuous phase velocity and
better separation. The terminal velocity of the specified particle size will exceed the
continuous phase velocity by more. Smaller particles will separate because their
terminal velocity will then exceed the continuous phase velocity.
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
πD 2DL L
VDL = QCHL t =
4
5 gal ft 3 3.5πD 2DL
(10 min ) =
7.48 gal
min 4
D 2DL = 2.43
In this case, residence time governs and the necessary drop leg diameter increases to
18.7 inches.
Horizontal Vessel Sizing Example
(continued)
Vessel Drop Leg (Boot)
EDS-2004/GS-87
Round up 18.7 inches to 20 inches OD. It may be necessary to increase two pipe
sizes to provide the necessary ID, considering the wall thickness needed (for
pressure, etc.). For example, if the required ID were 19.7 inches, a 20 inch OD pipe
would not be adequate. 22 inches might work, but flanges are not readily available
for this size (therefore, the pipe may also be hard to get), meaning we might need to
increase three pipe sizes to 24 inches.
The drop leg is usually considered expendable and is flanged for easy replacement.
If replacement is difficult (all welded construction), an internal lining is sometimes
added to increase usable life. See the next slide for lining and flanging criteria.
Vessel Drop Leg (Boot)
EDS-2004/GS-88
Vessel Drop Leg (Boot)
(continued)
EDS-2004/GS-89
Placing the outlet on the side allows the bottom of the boot to act as a trap for solids.
For this to work, the continuous phase velocity in the boot and out the outlet must
be low enough that the particles are not carried out with it.
Reactor Products Separator
Inlet Vapor Outlet
21"-0"
Tangent Tangent
Line Line
1'-1" 2'-4" MR MR 1'-8" 1'-5" 8"
AI AH AU BL BK BB BO
Inlet Distributor
C Vortex Breaker C
2'-4"
20” OD
BO
3'-6" 6"
6" BN
12" Thick Mesh Blanket 9"
Tangent Line
Vortex Breaker
Hydrocarbon
BW Outlet
4'-4" 4'-4"
15'-7"
Water
PROVIDE 1/8" THICK E 316L WELD OVERLAY ON THE Outlet
BOTTOM HALF OF THE VESSEL. 316L OVERLAY IS CORROSION ALLOWANCE
NOZZLES IN LINED SECTION
SHALL BE LINED AND FACED.
SD-R03-15
EDS-2004/GS-90
The result of our vessel design calculations is a diameter of 7 feet and a tangent length of 21 feet.
The 4'4" dimension from the mesh blanket to the center of the dropleg is ½ the vessel diameter (the
minimum acceptable distance from the mesh blanket to the outlet, i.e., the leading edge of the
dropleg) plus ½ the drop leg diameter ½(7'0") + ½(20") = 3'6" + 10" = 4'4".
The dimension from the inlet to the boot is 15'7" - 10" (boot radius) - 3" (inlet nozzle radius) = 14'6".
The value used in the calculations was 2 x D = 2 x (7') = 14 feet. The value used is less than the
actual value…OK.
The 4'4" dimension from the tangent line to the center of the boot is found by allowing space for the
hydrocarbon outlet nozzle, the saddle, half of the boot diameter, flange and reinforcement clearances,
and clearance to the tangent line.
Generally, the inlet and outlet nozzles are placed as close to the tangent line as possible to maximize
the vessel length available for separation.
Since the vessel diameter was governed by the 3 feet/min (max) velocity through the coalescing
blanket criteria, it may be possible to shorten the vessel to 3 x the minimum diameter needed for
settling, e.g. 3 x 6 = 18 feet. Use of a shorter vessel than this would require recalculation of all of the
vessel dimensions because an L/D of 3 was incorporated into all of the separation calculations.
As sized, the vessel allows a longer than designed residence time and will also separate smaller
diameter particles than designed for (sometimes much smaller, e.g. actual φ = 7'0”, required diameter
for liquid from vapor = 0.68 feet). The actual potentially separated size particle could be back-
figured, although separation of very small particles will be affected by other factors such as
electromagnetic forces.
Horizontal Vessel Level Relationships
SD-R01-15a
EDS-2004/GS-91
The maximum liquid depth is 0.75 of the vessel diameter and the minimum liquid
depth is 0.25 of the diameter.
The high and low liquid levels are to be the same distance from the normal liquid
level. The smallest permitted distance (normal to high or low level) sets the total
range.
Horizontal Vessel Level Ranges
0.0625D below C
L 42 0.375D 5.5 10.9 16.4 21.9 27.4 32.9 38.3
At C
L 50 0.5D 6.0 12.0 18.0 24.0 30.0 36.0 42.0
0.0625D above C
L 58 0.375D 4.0 7.9 11.9 15.9 19.8 23.8 27.8
0.125D above C
L 66 0.25D 2.3 4.5 6.8 9.1 11.4 13.6 15.9
EDS-2004/GS-92
If the normal liquid level is 0.125D above the centerline (at 0.625φ), the high liquid level is
at its maximum, 0.75φ. The difference is 0.125φ. Set the low liquid level the same distance
from the NLL as the high level or 0.625D - 0.125D = 0.500φ. If the material in the vessel at
NLL = 5 minute residence time, the time to go from the high to low level is found from the
following volume ratio:
Use of the NLL at the centerline maximizes the range of high to low liquid levels, and the
fluid volume between those levels, hence the retention times between the high and low
levels. If the residence time at ½ full = 5 minutes, the time from the high level (0.75D) to
the low level (0.25D), which contains 0.60 of the vessel volume takes
EDS-2004/GS-93
Residence Time
(continued)
EDS-2004/GS-94
Experience is the best method of determining the proper residence time. The
recommendation of the process specialist and operations engineers are the best
sources.
Residence Time Guidelines
EDS-2004/GS-95
For a critical service vertical separator, if the liquid outlet line is blocked in, provide
two minutes of residence time after reaching the high liquid level. This allows time
for operator action. An example is a compressor suction drum upstream of a
compressor (locate near the compressor to minimize possible condensation between
the drum and the compressor).
Residence Time Guidelines
(continued)
EDS-2004/GS-96
Drop legs that are manually drained usually have 600 minutes or 10 hours of
residence time so they can be drained no more frequently than once per operator
shift. This is used for small liquid loadings.
Residence Time
Two Liquid Phases
EDS-2004/GS-97
If the densities are close together, separation is difficult. The same is true for a high
viscosity.
Horizontal Separator Nozzle Locations
0.25D + 4" + 0.5 Dia. of Manway + 6" (Minimum)
3'-6" Max. (For Tangent Length 10'-0" through 14'-6")
4'-0" Max. (For Tangent Length 14'-6" through 24'-6")
5'-0" Max. (For Tangent Length over 24'-6")
0.5 Dia. of Ventilation Flange +
0.5 Dia. of Process Outlet
0.5 D (1' min Flange + 3" 6" + 0.5 Dia. of Process Outlet
5' max) Flange (min), 0.5D (max)
L=3D
Ventilation
6” + 0.5Dia of inlet flange (min) Nozzle Process Outlet Nozzle
0.5D (max)
Manway
Saddle
Generally, the inlet and outlet nozzles are as close to the tangent lines as possible to
maximize the length available for gravity separation. The minimum dimension is
measured between the tangent line and the nearest point on the nozzle ID. The
maximum distance is measured between the tangent line and the furthest point on
the nozzle ID. This is conservatively used when sizing the vessel.
The 6" clearance from the inlet/outlet flanges allows for some straight flange on the
head and access for head/shell weld inspection and NDE.
UOP Manways and Auxiliary Nozzles
EDS-2004/GS-99
UOP Manways and Auxiliary Nozzles
(continued)
Ventilation
– Required for safety on horizontal vessels > 10'
diameter
– Locate on top, at the end opposite the manway
– Minimum sizes
≥ 10' diameter 4" nozzle
> 15' diameter 6" nozzle
> 25' diameter 8" nozzle
EDS-2004/GS-100
Ventilation nozzles are provided to safe the vessel for operators to enter the vessel
when the unit is shut down for inspection and repair. A fan or air mover is usually
provided to increase air flow through the vessel.
UOP Manways and Auxiliary Nozzles
(continued)
EDS-2004/GS-101
When provided with a drain, the vessel must also be provided with an equal or
larger sized vent. The vent is used to avoid pulling a vacuum when the vessel is
drained.
Vertical Separator Sizing
Without a Disentraining Device
EDS-2004/GS-102
Residence time requirements do not influence the required vessel diameter. The
necessary residence time is provided by lengthening the vessel. Because of its
footprint and vessel and support structure costs, horizontal vessel lengths are usually
set at 3 x D. This gives the most economical vessel. Residence time requirements,
therefore, influence the diameter, footprint, and support costs. The same is not true
for as vertical vessel. Added length does not affect the footprint or the support costs
(for a relatively short vessel).
Vertical Separator Sizing
Without a Disentraining Device (continued)
EDS-2004/GS-103
Vertical Separator Sizing
Without a Disentraining Device (continued)
TL = tangent length
Vapor/Liquid Separation
With Mesh Blanket
1′ 0″ Minimum
6″ 1′ 0″ Minimum
EDS-R01-3422
EDS-2004/GS-105
The space between the bottom of the mesh blanket and the inlet nozzle is required
for good separation of the hydrocarbon liquid from the vapor.
SD-R01-04
EDS-2004/GS-106
Criteria for Vertical Vessel Sizing
EDS-2004/GS-107
Vertical vessels without mesh blankets use the same basic design equations as used
for horizontal vessels.
QV = feet3/second
QL = gallons/minute
0 .5
Q µ
D = 0.23 2 L L
gD PV (ρ L − ρ V )
EDS-2004/GS-108
Level Instrument Nozzles
Vessel
Nozzle Vessel
Nozzle
Displacer Displacer
Float Float
Instrument Instrument
Gauge Gauge
Glass Glass
Pipe
Column
UOP has standardized on the use of pipe columns for the installation of level
instrumentation. Bridles are an acceptable alternate.
Gauge glasses are normally used because they provide a positive, visual indication
of the fluid level. Magnetic level indicators are used in some services where the
consequences of a failure and leak are serious. Examples are high pressure, toxic,
corrosive, or low vapor pressure services. Services that cloud the gauge glass,
making visual observation of the liquid level impossible, may also use a magnetic
level indicator. One drawback of the magnetic system is dependency upon a
mechanical system. There is no way to confirm the proper level is being shown.
Level Instruments
Span and Nozzle Size
Arrangements and Nozzles for Displacer Float Instruments and Gauge Glasses
Displacer Float Gauge
Instruments Glasses
Max. Span
Between Max.
Vessel Min. Vessel Max. Float Min. Vessel Nominal
Nozzles Nozzle Size Length Nozzle Size Length
Separate 15' 0" 1½" 10' 0" 1" 5' 6"
Connections (4600) (3048) (1650)
Bridle 9' 0" 1½" 5' 0" 1½" 5' 6"
Installation (2700) (1524) (1650)
Pipe Column 15' 0" 2" 10' 0" 2" 5' 6"
Installation (4600) (3048) (1650)
EDS-2004/GS-110
Level Float Dimensions
The maximum length is based upon rigidity and differential thermal expansion of
the vessel and the level glass connection.
Level Float Dimensions
(continued)
SD-R01-18
EDS-2004/GS-112
The maximum length is based upon rigidity and differential thermal expansion of
the vessel and the level glass connection.
Level Gauge Dimensions
SD-R01-19
EDS-2004/GS-113
This chart is based upon Jurguson series 10 and 20 level gauges. The chart is for the
bottom connection below (under) the level glass.
Level Gauge Dimensions
SD-R01-19
EDS-2004/GS-114
This chart is based upon Jurguson series 10 and 20 level gauges. The chart is for the
bottom connection off of the side of the level glass.
Vortex Breakers
EDS-2004/GS-115
Vortex breakers eliminate the tendency of liquid flow into a nozzle to form a
tornado (vortex) of spinning liquid. A vortex, if formed, will have a tendency to re-
entrain the separated light phase vapor or liquid.
Raising the vortex breaker for two liquid phase cases allows for possible “slugs” of
the heavy phase.
Vortex Breakers
Four Way
3 - 3/4" x 1/4" Bars Baffle
Spaced at 120º 2D
8" Dia.
for 3" 2D
6" Dia.
under 3"
D
D
4"
2" 3"
D D
2D 2D
8" Four Way
Baffle
D
D Pipe D D Pipe
4"
4" Pipe 2" 2" 3"
H H H
D D
H = as specified
Use raised vortex breakers in the hydrocarbon liquid phase when a heavier liquid is
present. This reduces the possibility of the heavy liquid phase being carried over in
the light hydrocarbon liquid.
The raised vortex breaker is set about 4-6 inches (100-150 mm) above the bottom of
the vessel.
Vortex Breakers
(continued)
EDS-2004/GS-117
EDS-2004/GS-118
This is a vortex breaker used for liquid withdrawal on the side of an unlined vertical
vessel.
Vortex Breakers
(continued)
EDS-2004/GS-119
This is a vortex breaker used for liquid withdrawal on the side of an alloy lined
vertical vessel.
Vortex Breakers
(continued)
EDS-2004/GS-120
Inlet Distributors
EDS-2004/GS-121
Inlet distributors are used to change the direction of flow to accomplish some degree
of momentum separation of phases.
Subcooled
Below the bubble point temperature, i.e., an input of heat does not result in any
vaporization.
Bubble Point
The liquid temperature at which the first vaporization occurs, i.e., bubbles appear.
This is also the temperature at which the last vapor would condense.
Dew Point
The vapor temperature at which the first condensation occurs (depends upon the
relative humidity, too). This is also the temperature at which the last liquid would
vaporize.
Inlet Distributors
(continued)
EDS-2004/GS-122
Slotted pipe distributors reduce the velocity, still the vessel, and provide a change in
direction of flow. The light phase preferentially exits at the top of the slot, and the
heavy phase exits preferentially at the bottom of the slot.
The type of inlet shown on slide #20, an elbow, has less flowing area ( 1 x pipe
cross section) than the slot used by UOP (2 or 3 x pipe cross section); therefore, a
higher exiting velocity, perhaps creating a mixing turbulence around the pipe exit.
Obviously, this works against separation. On the other hand, the higher velocity and
sharp turning radius (as compared to a slot) enhances momentum separation.
Additionally, the minimum dimension of the elbow is much greater than that of the
slot; therefore, it is less likely to plug. The slot, however, allows flow to exit the
distributor along the full diameter rather than at one discrete point as with the
elbow. This aids gravity separation because particles can exit the distributor nearer
their ultimate “destination”.
In most vessels, the inlet piping is small to maintain or even increase velocities and
limit phase separation(s). In a separator inlet we want to promote phase separation,
hence a larger pipe and slot area (for gravity separation at low velocities) and
direction changes (to promote momentum separation at higher velocities).
Inlet Distributors
(continued)
Intermittent slots, rather than narrow slots, are used to avoid plugging and minimize
any venturi effect.
Facing the slots towards the nearest head results in flow exiting towards the head,
turning and coming back to the inlet pipe before proceeding down the vessel. Only
the direct distance between the inlet and outlet is used in the design calculations.
The actual path, as explained above, is much longer, meaning smaller particles are
able to settle out.
Inlet Distributors
(continued)
EDS-2004/GS-124
This distributor also changes the direction of flow and accomplishes some
momentum separation.
Subcooled Liquid Distributors
Bottom Entry
EDS-2004/GS-125
Subcooled Liquid Distributors
Bottom Entry (continued)
SD-R00-55
EDS-2004/GS-127
Use of a slot (vs. an elbow) means a lower inlet velocity and less turbulence, hence better gravity
separation. The slot also allows fluid to enter over more of the vessel’s diameter, with the lighter
phases tending to make the turn and exit the slot nearer the top than the heavier fluids, already
beginning the separation process.
π
Area (actual ) = D p 2 , ∴ using only Dp2 to determine the required slot area gives a larger,
conservative area4 to provide. Dp2 is used as the area to provide in the following equations.
For vapor/liquid/liquid: 2D p 2 2D p 2
w= (inches ) or (mm )
D v − 12 D v − 300
The total area of the single slot is more than twice the pipe area.
As noted on an earlier slide, vapor/liquid/liquid separation aims toward the back head for greater
effective length than considered in design. If the liquid amounts are about equal, the outlets are at
opposite ends of the vessel and the inlet is in the center of the vessel. Aiming the inlet slots to the
sides of the vessel maximizes the length of all of the flow paths. The incoming flow is not directed
towards either outlet.
Horizontal Pipe Distributor
for Horizontal Vessels
Liquid/Liquid Distributor
(approximately. equal volume liquids)
EDS-2004/GS-128
2D p 2 2D p 2
W= (inches ) or W= (mm)
D v − 17 D v − 430
Tee Distributor for Vertical Vessels
EDS-2004/GS-129
The outlet of the distributor must direct the flow parallel to the liquid surface, not
down into the liquid. This is to avoid entrainment of the liquid falling through the
gas. The liquid is to contact and flow down the wall with a minimum of splashing.
Tee Distributor for Vertical Vessels
(continued)
EDS-2004/GS-130
Separation Phase Examples
PHASES EXAMPLE
Vapor/Liquid Separator
Flash Drum
Liquid/Liquid Caustic Settler
Desalter
Vapor/Liquid/Liquid Hydrotreater Separator
Wet Overhead Receiver
Vapor/Solid FCC Regenerator
Liquid/Solid Slurry Separator
EDS-2004/GS-131
The FCC regenerator separates regeneration flue gas from FCC catalyst.
The FCC slurry separator concentrates entrained FCC catalyst from the Main
Column Bottoms stream to the Slurry Settler bottoms.
Vessel Configuration
Separators - Vertical
EDS-2004/GS-132
Vessel Configuration
Separators - Horizontal
EDS-2004/GS-133
In horizontal vessels, the relatively shallow liquid, and the large liquid/vapor
interface area, provides for better vapor and second liquid separation.
Horizontal vessels are also more effective separators because the continuous
medium flows slowly and horizontally, perpendicular to the direction of separation
(vertically) and the terminal velocity direction. Therefore, it does not tend to
counteract the particle’s terminal velocity.
Vessel Configuration
Separators - Spherical
EDS-2004/GS-134
Spherical separators are rarely used because the liquid level response changes
rapidly as the level rises and falls. This is due to the rapidly changing cross-
sectional area.
Vessel Configuration
Separators
PROCESS VESSEL
CONDITIONS CONFIGURATION
High Vapor Rate Vertical Vessel
Low Liquid Rate (makes efficient use of the vessel
One Liquid Phase cross section)
Low Vapor Rate Horizontal Vessel
High Liquid Rate (vertical vessel may be considered)
One Liquid Phase
No Vapor Phase Horizontal Vessel
Two Liquid Phases
EDS-2004/GS-135
Compressor suction drums are vertical because the flow is nearly all vapor, with a
small amount of entrained liquid, and because the liquid level responds rapidly to
changes in the liquid flow, triggering an alarm.
A horizontal vessel is used for two liquid/no vapor separation for ease of separation.
The densities of the two fluids are normally close, making separation more difficult.
In a vertical vessel, where the terminal velocity and the continuos phase motion are
both on the same axis, this may prove to be especially difficult.
Vessel Configuration
Separators
(continued)
PROCESS VESSEL
CONDITIONS CONFIGURATION
Vapor Phase Present Horizontal Vessel with
Two Liquid Phases Drop Leg (Boot)
Low Heavy Liquid Phase Rate
Vapor Phase Present Horizontal with Baffled
Two Liquid Phases Outlet for the Heavy
Low Light Liquid Phase Rate Liquid
Vapor Phase Present Horizontal with 2 Baffled
Two Liquid Phases Outlets
Liquid Phases Equal Rates
EDS-2004/GS-136
The top case on the slide is the sample problem we worked earlier.
Types of Vessels
Vapor/Liquid Separator
Tangent Length
M.R. M.R.
Vapor Out
A B F C
Min. Min.
Inlet Distributor
C
L
I.D.
150
Min.
D
Example:Overhead Receiver Liquid Out
SD-R03-05
EDS-2004/GS-137
This vessel configuration may or may not be provided with a mesh blanket.
Types of Vessels
Liquid/Liquid Separator
Tangent Length
M.R. M.R.
Vapor Out
Feed
A B D E
Min.
Inlet Distributor
I.D.
CL
6"
Min.
F
Light Liquid Out
Example: HP Separator G
Heavy Liquid Out SD-R02-07
EDS-2004/GS-139
SD-R00-44
EDS-2004/GS-140
On the right side, the baffle heights are set so the HL goes under the first baffle and
over the second baffle, while the first baffle keeps the LL out. The HL is driven
over the second baffle by the head of liquid (HL + LL) on the left side of the first
baffle.
The design baffle heights are set so the HL and LL spill over their respective baffles
at the same time.
The inlet distributor is located midway between the two baffles, with the slots
oriented towards the vessel wall, so the HL and LL flow paths, and time for
separation, are both the same. The baffles are 2D apart, so each flow path is D long.
The vapor space clearance on the highest baffle is 0.25D, the same space used for
other separators.
Types of Vessels
Vapor/Liquid/Liquid Separator
Low Light Liquid Rate
SD-R00-45
EDS-2004/GS-141
In this configuration, the light liquid leaves the vessel via a trough and a side-
mounted nozzle to minimize turbulence.
Again, the vapor space above the highest baffle has a depth of at least 0.25D, just as
for other separator designs.
The heavy and light liquid baffle heights are set so that both the heavy and light
liquids spill over their respective baffles at the same time.
The light liquid outlet nozzle is flush with, or even extends slightly below, the
bottom of the “trough”. The “trough” also slopes towards the outlet. Both of these
features allow full drainage of the “trough”.
The distributor slot faces the rear head of the vessel to maximize the flowpath
length, hence the separation time.
Vapor/Liquid Separator
A
I.D.
E B
Vortex Breaker
C
Access Opening
Vertical vessels without mesh blankets are used when liquid entrainment in the
vapor phase is not a critical design parameter.
Vertical vapor/liquid/liquid separators are only used when the available space does
not allow installation of a horizontal separator.
Small Vertical Separators
Mesh Blanket A
B 3" Min.
Inlet Distributor
E C
O.D.
Vortex Breaker
D
ID of 30 inch or less
Elevation of 5 feet or less
Example: Reciprocating Compressor Suction Drum SD-R02-08
EDS-2004/GS-143
EDS-2004/GS-144
Mist Eliminators
Purpose
Types
Theory and Typical Installations
Size Criteria
EDS-2004/GS-145
Mist Eliminators
(continued)
Efficiency
Pressure Drop
Fabrication and Installation
Material of Construction
Sample Problem
EDS-2004/GS-146
Purpose of Mist Eliminators
EDS-2004/GS-147
EDS-2004/GS-148
Mist eliminators (mesh blankets) are used to increase the efficiency of vapor/liquid
separation to improve the vapor purity or to recover liquid from the vapor.
Capacity increases are possible because a mist eliminator can coalesce and remove
droplets much too small for gravity separation at the elevated velocity that goes
with the higher throughput. The higher velocity means less time in the vessel,
therefore, less time for droplets to settle out at their terminal velocity. A velocity
increase, therefore, means an increase in the minimum size of particle that will be
gravity separated and more entrained material will be carried out of the vessel. A
mist eliminator compensates, and more, for the velocity increase. The same size
vessel can be used for much higher throughput. This works for separation of liquid
droplets.
Benefits of Mist Eliminators
(continued)
EDS-2004/GS-149
Corrosion occurs due to the formation of aqueous, corrosive solutions made possible
by water carryover. Elimination of the liquid water prevents acid formation.
EDS-2004/GS-150
Examples are:
AIR COOLER
Liquid may
M
be swept
along with
Liquid condenses
the vapor.
from the vapor
WATER CONDENSER
NET GAS
OVERHEAD
RECEIVER
LIQUID
WATER SD-R00-28
EDS-2004/GS-151
Mechanisms That Cause Entrainment
Mechanical
sprays
evaporation
surface
trays and
column packings
Condensation
on surface
from saturated
vapor
chemical
reaction
Here are the typical droplet sizes created by common entrainment mechanisms.
Droplet Size
EDS-2004/GS-153
What are some of the factors that can affect droplet sizes?
EDS-2004/GS-155
Decide if Mist Eliminator is Required
EDS-2004/GS-156
EDS-2004/GS-157
Process requirements must be evaluated relative to the additional cost of the mist
eliminator (mesh blanket, coalescing blanket) installation.
Vanes
Centrifugal Elements
Filters
Mesh Blankets
Perforated Plates
Electrostatic Precipitators
EDS-2004/GS-158
Characteristics of Vanes
EDS-2004/GS-160
Vertical Separator
With Vane Mist Extractor
EDS-2004/GS-161
Vane Element Mist Extractor
Cross Section
EDS-2004/GS-162
The vapor flows through the vanes and liquid droplets get caught in the drainage
traps, coalesce into larger droplets and, eventually, drain out of the device.
Vane Mist Eliminators
EDS-2004/GS-163
Momentum separation.
Characteristics of Centrifugal Elements
EDS-2004/GS-164
“Centrifugal” forces generated throw the high density material against a collection
device where particles or drops are concentrated and removed from the system.
Low density material rises in the center.
Small particle separation is not very efficient, although some new high efficiency
cyclone separators have recently become available.
Centrifugal elements are most often used to separate solids from a vapor stream.
The cyclones in FCC Reactors and Regenerators are, perhaps, the most common
example in refineries. Third-Stage Separators in FCC flue gas systems use many
mini-cyclones to remove fines before the vapor stream enters the expander.
Characteristics of Centrifugal Elements
(continued)
EDS-2004/GS-165
Slugs of liquids or solids may overwhelm centrifugal elements and get carried
through.
Centrifugal Elements
SD-R00-46
EDS-2004/GS-166
Characteristics of Filters
EDS-2004/GS-167
The efficiency of filters relates to the pore size and the diameter of the suspended
droplets or solid particles.
Characteristics of Filters
(continued)
Filters may consist of group(s) of cartridges and a system to split the flow among
them.
Horizontal Filter Separator
Flanged
Head
Liquid Out
SD-R02-47
EDS-2004/GS-169
Horizontal filter separators require regular maintenance and are rarely used.
The filter elements catch any solids in the stream. The filters are cleaned at
turnaround. Access is provided by removing the vessel head.
The filter elements also act as coalescers, holding small droplets and combining
them with other droplets. Large liquid droplets fall to the bottom of the vessel. In
the bottom of the vessel, separation is by gravity, just as described earlier. The
liquid level is usually low and only one vapor phase is present.
Vapor and the remaining entrained liquid pass to the center of the filter and are
carried to the next section of the vessel. A mist eliminator is provided at the vapor
outlet to “scrub” small droplets from the outgoing vapor.
The system can begin with a solid/liquid/vapor mix and end with a clean vapor.
Perforated Plates or Staggered Baffles
EDS-2004/GS-170
“Sticky” materials pass through. Staggered baffles are used at the inlet to Demex
resin settlers. Further separation is provided by a system of sloped vanes.
Electrostatic Precipitators
EDS-2004/GS-171
Electrostatic separators are highly efficient but capital and utility expenses are high.
They are sometimes used in FCC Units to remove catalyst fines from Regenerator
flue gas when environmental constraints are severe.
Characteristics of Mesh Blankets
EDS-2004/GS-172
Mesh blankets are highly efficient for the separation of liquid droplets out of vapor
streams down to about 5 micron particle diameters.
EDS-2004/GS-173
They work well over a wide range of operating conditions, but drops can be re-
entrained if the velocities go too high. This will be addressed in the design
procedures.
Characteristics of Mesh Blankets
(continued)
EDS-2004/GS-174
Mesh blankets are easily installed in new and revamped services and vessels.
Mesh Blanket Installation Sites
Knockout Drums
Separators
Absorbers
Scrubbers
Distillation Columns or Towers
Steam Systems
EDS-2004/GS-175
Specific services include compressor suction drums, amine scrubbers, and fuel gas
knockout drums.
Installing mesh blankets in knockout drums and separators reduces (greatly) the size
of the vessel needed if only gravity separation were used.
Mesh blankets reduce the overhead loss in absorbers and remove particles entrained
in scrubber liquid.
Mesh blankets improve the vapor stream purity and increase the capacity of
distillation (fractionation) columns.
In steam systems, mesh blankets help “ensure” the presence of dry steam.
Typical Mesh Blanket Installations
Suction Drum
Secondary Separator
SD-R00-29
EDS-2004/GS-176
Typical Mesh Blanket Installations
(continued)
SD-R01-30
EDS-2004/GS-177
Horizontal Mesh
Blanket
Products Separator
SD-R01-48
EDS-2004/GS-178
SD-R01-24
EDS-2004/GS-179
Mesh blankets are highly efficient for drop diameters over 5 microns.
The vertical vane type is a little less efficient that the horizontal vane type because
the liquid falls into the rising vapor stream and some re-entrainment may occur.
Separation Steps
SD-R01-23
EDS-2004/GS-180
The mesh blanket combines small drops into larger drops which exit the bottom of
the blanket and separate from the vapor by gravity.
Separation Steps
SD-R01-42
EDS-2004/GS-181
Coalescing Separation Theory
EDS-2004/GS-182
Coalescing Separation Theory
(continued)
EDS-2004/GS-183
When droplets move down the wire, they probably do not contact and combine with
one another, until a cross wire is reached.
One drop reaches a cross wire and is stopped. The following drop strikes it and they
combine. When the new drop grows large enough, it spills over the obstructing wire
and continues down the original wire (or falls off the mesh blanket).
Coalescing Separation Theory
(continued)
EDS-2004/GS-184
Coalescing Separation Theory
(continued)
EDS-2004/GS-185
Droplet Capture Mechanisms
SD-R01-26a
EDS-2004/GS-186
Droplet Capture Mechanisms
(continued)
SD-R01-26b
EDS-2004/GS-187
Droplet Capture Mechanisms
(continued)
Only some, not all, particles encounter the wire and are captured. Design cannot be
depended upon to remove particles that are this small.
Typical Layer of Wire Mesh
SD-R00-43
EDS-2004/GS-189
The typical mesh blanket consists of several layers of intertwined wire mesh.
Mesh Blanket Construction
EDS-2004/GS-190
Typical Layer of Wire Mesh
WIRE
WIRE SURFACE
DIAMETER DENSITY AREA VOIDS
3 2 3
STYLE (in) (lbs/ft ) (ft /ft ) (%)
A 0.011 9 85 98.0
B 0.011 5 45 99.0
C 0.011 12 110 97.7
EDS-2004/GS-191
Typical Layer of Wire Mesh
(continued)
Style A
– General purpose mesh used when there
are no special requirements
Style B
– Used where fouling (such as coking) or solids
are probable
• Wire directions alternated
• Has largest open area
EDS-2004/GS-192
Typical Layer of Wire Mesh
(continued)
Style C
– Heavy duty, general purpose mesh used where
excellent separation efficiency is required.
– Herringbone pattern and alternating crimp
directions reduce sheltering of wires behind
other wires and increase wire surface area
(for more droplet impingement) with a
minimal change in voidage.
EDS-2004/GS-193
UOP Severe Duty Mesh
EDS-2004/GS-194
Severe duty mesh blankets were originally used to remove entrained corrosive
liquids from fuel gas to minimize corrosion and fouling of burners in fired heaters.
Installed horizontally
EDS-2004/GS-195
The exit layer has very fine wires tightly spaced which provides maximum
disentrainment of particles under 5 microns diameter.
Severe Duty Mesh
3 - 3" Zones - Total 9" Thick
WIRE
WIRE SURFACE
DIAMETER DENSITY AREA VOIDS
LAYER (in) (lbs/ft3) (ft2/ft3) (%)
Exit 0.006 8 140 98.4
Middle 0.011 9 85 98.0
Entrance 0.011 5 45 99.0
EDS-2004/GS-196
Installed Thickness
EDS-2004/GS-197
Generally increasing the mesh thickness has little effect on improving separation or
allowing a flow increase. As noted later, the “K” value used in finding the optimal
velocity is not a function of the mesh thickness; therefore, the optimal velocity and,
for a given diameter, the mass flow rate does not change.
Size Criteria
EDS-2004/GS-198
Mesh blankets operate well over a wide range of flow rates. At very low velocities,
small diameter drops follow the vapor and do not impinge on the wires of the
blanket. At very high velocities, the vapor pulls the drops off the wires and re-
entrainment results.
Size Criteria
(continued)
EDS-2004/GS-199
The “scrubbing” action in the lower part of the mesh is similar to what occurs on
fractionation trays.
Size Criteria
(continued)
EDS-2004/GS-200
Mesh blankets are most efficient at velocities just below the point where re-
entrainment begins to take place. This is the maximum throughput permitted before
re-entrainment. The efficiency drops rapidly once re-entrainment begins to occur.
Size Criteria
(continued)
EDS-2004/GS-201
Optimum performance and range occur when the mesh blanket is designed to
operate at 70% of the “optimum design” rate. This allows for some variation in
throughput without a significant loss of efficiency.
Optimum Velocity
EDS-2004/GS-202
The optimum velocity results in the highest pressure drop, but that is only on the
order of one inch of water.
Mesh Blanket Efficiency
EDS-2004/GS-203
This slide and the following slide illustrate the ability of wire mesh to accommodate
a wide range of flows. This makes it very tolerant of turndowns or variations in
flow.
Velocity vs. Removal Efficiency
Style A, 6" Mesh Blanket
SD-R01-34
EDS-2004/GS-204
This curve indicates a wide capacity range for efficiencies over 95%.
K vs. Pressure
EDS-2004/GS-205
K vs. Pressure
EDS-2004/GS-206
Mesh Blanket Size Criteria
AREA = CFSactual/Vdesign
Dv
Mesh diameter = (4 * AREA/π)0.5
K is a function of pressure
θ θ
Up to 36 inch 36 in to 72 inch
Diameter Diameter
Mesh blankets can be sloped to provide increased capacity, although this is rarely
used.
The ∆P increase due to flooding, i.e., forcing the flow through liquid on the
underside of the mesh, is less pronounced because the liquid concentrates on the
lower part of the mesh. Vapor then passes, preferentially, through the remainder of
the mesh.
Rather than use sloped mesh blankets, the vessel could be expanded, but that is
costly.
For mesh blankets smaller than the vessel, the blanket is put into a “can” over the
outlet and flow is forced to pass through the blanket to exit. Alternatively, the
vessel can be swedged.
Size Criteria for a Sloped
Mesh Blanket
ρ l - ρ g 0 .5
Vθ = KΘ
ρg
KΘ = K + 0.3 SINΘ
EDS-2004/GS-209
Using the above equation yields a higher optimal velocity over the vessel cross
section. This considers the fact that the mesh is at an angle, therefore, the surface of
the mesh is a greater area than the vessel cross section. Flow passing through the
mesh will tend to pass through perpendicular to the mesh surface, not axially along
the vessel. The greater mesh surface area means the vapor velocity is actually less
than it is in the vessel cross section. Therefore, it will still be okay even if the
vessel velocity is greater than VOptimal. At Vθ (above), the velocity over the mesh is
okay.
Although the ∆P through the mesh is small, it is sufficient to cause the low density
vapor stream to change direction and follow the lowest ∆P path - straight through
the mesh rather than at an angle.
Mesh Blanket Location
for Vertical Vessels
SD-R02-32
EDS-2004/GS-210
SD-R02-33
EDS-2004/GS-211
The coalescing blanket is to be far enough from the inlet that any turbulence has
damped out.
Pressure Drop
2
0.193fctad g Vact
∆PD =
g ce 3
SD-R01-35
EDS-2004/GS-213
Pressure Drop
EDS-2004/GS-214
Pressure Drop for Entrainment Load
A B A B C
1.0 1.0
D
C
0.1 0.1
00.1 0.01
0.1 0.2 0.3 0.4 0.5 0.1 0.2 0.3 0.4 0.5
A 2200 lb/hr•ft2
Vact. Vact.
B 935 lb/hr•ft2
( )
dl - dg 0.5
dg C 160 lb/hr•ft2
( )
dl - dg 0.5
dg
Style B, 6 inch thick mesh blanket D 16.5 lb/hr•ft2 Style C, 6 inch thick mesh blanket
DPL for style “A” is the average of styles “B” and “C.” SD-R03-36
EDS-2004/GS-215
EDS-2004/GS-216
SD-R01-37
EDS-2004/GS-217
The support method must ensure that flow cannot bypass the mesh blanket.
Provide a support grid on the downstream side of all mesh blankets. This grid both
supports the mesh and prevents any part of the mesh from being carried downstream
if it separates. This is particularly important if there is downstream mechanical
equipment, such as a compressor.
Typical Vertical Arrangement
of a Sectional Mesh Blanket
SD-R02-38
EDS-2004/GS-218
Coalescing blankets are installed against a support ring with the flow pushing the
blanket against the ring. The ring is left open at the bottom to allow unimpeded
flow of the heavy liquid phase, and drainage of the vessel.
Provide one manway in horizontal vessels, with a vent at the other end. Be sure the
mesh blanket can be assembled and disassembled from the manway side only.
Disassembly is needed to provide access to the rest of the vessel, for example,
during inspection. The flow direction should tend to push the mesh against the
support ring rather than pull it away (straining, even breaking the twist ties). The
manway would be on the downstream side of the mesh blanket to allow
assembly/disassembly. It is also a better place, considering cleanliness, hence
safety. Finally, it is normally the largest, and least obstructed portion of the vessel,
facilitating entry. It also allows immediate access to the vapor outlet mesh blanket,
if one is present. Wherever it is placed, insure the manway is in a safe, accessible
location. It is not to open into the vessel at the drop leg, where someone entering
could fall into the drop leg, or at an internal obstruction such as the inlet distributor
or vapor mesh blanket, that limits accessibility.
Occasionally, it may be advisable to put a relief valve upstream of the mesh blanket
to guard the vessel against a pressure buildup if the mesh blanket plugs and does not
fail. This is, however, a very unlikely situation.
Typical Horizontal One-Piece
Mesh Blanket
SD-R02-39
EDS-2004/GS-219
In this installation detail, the mesh blanket hangs like a light fixture.
Installation and Removal from Top
3/4 inch
3/4 inch
1 1/2 inch x 1/4 inch plate ring
furnish in minimum number
of pieces to pass thru manway Spacers - 1/2 inch standard pipe
Nominal blanket
thickness +2 inch Grids (1 inch each)
Compression would decrease the mesh’s void volume, increasing the ∆P and,
possibly, reducing coalescing efficiency.
Installation and Removal from Bottom
1 inch
Bottom Grid
Tie Wire
1/4 inch Diameter Holes, 5 inch Centers
Annular Ring, 2 inch to 3 inch Wide
SD-R03-41
EDS-2004/GS-221
The mesh blanket must be able to pass the support ring. In most cases, the blanket
is assembled in sections to accomplish this.
Support Strength
EDS-2004/GS-222
Vertical blankets in liquid can plug and develop a higher liquid level on one side
than the other, possibly dislodging the mesh. Horizontal, vapor, blankets can
occasionally plug also.
Support Grids
EDS-2004/GS-223
Materials of Construction
Mesh Material
EDS-2004/GS-224
Mesh and coalescing blankets can corrode quickly in hostile environments because
the fine wires are exposed to the environment on all sides and have no corrosion
allowance.
Since mesh blankets have essentially no corrosion allowance, select the metallurgy
best suited to resist the corrosive environment. A corroded wire will break, making
coalescence impossible because droplets cannot travel down the wire and combine.
Therefore, use a high alloy, “corrosion-proof,” wire.
Before using any of these materials, confirm that they are compatible with the
internal atmosphere. Polyethylene and polypropylene may be damaged (destroyed)
in some hydrocarbon environments because they, too, are hydrocarbon based.
Materials of Construction
Support Grid Material
Austenitic Stainless
Monel
Carpenter 20
Hastelloy
Titanium
EDS-2004/GS-225
Sample Problem
EDS-2004/GS-226
Calculate Optimum Velocity
0.5
dl − dg
V = K
d g
0.5
50.1 − 0.147
V = 0.32
0.147
V = 5.9 ft/s
EDS-2004/GS-227
Vd = 0.7V
Vd = 0.7 (5.9) = 4.13 ft/s
EDS-2004/GS-228
257,760
AR =
0.147(3600 )4.13
A R = 117.9 ft 2
EDS-2004/GS-229
AR is the required cross sectional area of the mesh blanket exposed to the vapor
flow, not the area of the vessel.
Calculate Required
Mesh Blanket Diameter
0 .5
A
D = 2
π
0.5
117.9
D = 2 = 12.25 ft.
3.14
EDS-2004/GS-230
The final mesh blanket diameter is the calculated diameter available for vapor flow
plus an allowance for the support ring (2.5 inches x 2 = 5 inches or 0.42 feet).
In this example, the required diameter is 12.67 feet or 12 feet, 8 inches. This is the
diameter of the mesh blanket, not the vessel.
Estimated Pressure Drop
2
0.193fc tad g Vact
∆PD =
g ce 3
Vact = 4.13 ft s
a = 85 ft 2 ft 3
e = 0.98
EDS-2004/GS-231
d g Vact 0.147(4.13 )
Re ynolds Number = = = 821
aµ 85(0.0000087 )
EDS-2004/GS-232
(0.193)(0.20)(0.5)(85)(0.147)(4.13) 2
∆ PD =
32.2(0.98)3
EDS-2004/GS-233
257,760
Superficial Velocity, = 2186 lb/hr ⋅ ft 2
117.9
Vact 4.13
= = 0.224
0 .5 0 .5
dl − dg 50.1 − 0.147
dg 0.147
EDS-2004/GS-234
Superficial velocity is the mass flow rate divided by cross section area, i.e.,
(lb/hr)/ft2.
Space velocity is defined as mass flow rate divided by catalyst volume, i.e.,
(lb/hr)/ft3.
Estimated Pressure Drop
(continued)
EDS-2004/GS-235
2 2
Vact 4.13
∆P = 1.5 = 1.5 = 0.74 inches of water
VOptimal 5.9
EDS-2004/GS-236