Sunteți pe pagina 1din 12

IV CONDUCTOR ACCESSORIES

Guranteed Technical
III To be filled by the Bidder
Particular
A. MID SPAN COMPRESSION JOINTS 161 kV Line
TAG CORPORATION,
Thiruneermalai road,
1 Maker's name and country
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
2 Type Compression
3 Suitable for (Conductor size) (mm) Ø20.6
Materials of joint with reference of ISS to which it
4 conforms
a) Aluminium alloy sleeve Al.alloy (Type-63400, IS:733)
5 Shape of cross-section
a) Before compression Hollow circular
b) After compression Hexagonal
6 Outside diameter of sleeves
a) Before compression
i) Aluminium alloy (mm) Ø38±1
b) After compression
Aluminium alloy (mm)
i) Corner to corner (mm) 37±0.5
ii) Surface to surface (mm) 32±0.5
7 Inside diameter of sleeves
a) Before compression
i) Aluminium alloy (mm) Ø23±0.5
8 Length of sleeves
a) Before compression
i) Aluminium alloy (mm) 670±5
b) After compression
i) Aluminium (mm) 745±5
9 Weight of sleeve in
i) Aluminium alloy (kg.) 1.27 kg (Approx.)
Breaking strength of the mid span joint as percentage
10 of ultimate tensile strength of Not less than 95% of Conductor UTS
conductor (%)
Conductivity of the compression joint expressed as
11 percentage of the conductivity of equivalent length >100 %
of the conductor(%)
Whether compression and non-compression joints
12 marked on the sleevs. Yes

Slip strength of mid span compression joints


13 expressed as % of UTS of conductors. Not less than 95% of Conductor UTS

14 Details of die set required for making joint. No


Type of greece and capacity of Hydraulic
15 compressor for making joints. IEC : 60685

Suitable for passing through the sleeve of stringing


16 block. -

Reference of manufacturers' drawing and


17 catalogue no. etc TAG/E/MSCJ/E336

Reference of ISS or any other international standard to


18 which the midspan joints conform, if IEC : 61284
any
Certification Mark (ISI/BS/or Any other
19 International Standard) -

20 Packing details Standard

B. REPAIR SLEEVE
TAG CORPORATION,
Thiruneermalai road,
1 Maker's name and country
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
2 Type Compression
3 Suitable for Conductor size (mm) Ø20.6
4 Shape of cross-section
a) Before compression Hollow circular
b) After compression Hexagonal
5 Inside diameter of sleeves (mm)
Before compression Ø23±0.5
6 Outside diameter of sleeve
a) Before compression (mm) Ø38±1
b) After compression
i) Corner to corner 37±0.5
ii) Surface to surface 32±0.5
7 Length of sleeve
a) Before compression (mm) 250±5
b) After compression (mm) 278±5
8 Weight of sleeve 0.48
Conductivity of the repair sleeve expressed as
9 percentage of the equivalent length of Bare >100 %
conductor (%)
10 Material and standard to which conforming Aluminium purity
Breaking strength as % of UTS of conductor
11 Not less than 95% of Conductor UTS

Resistance as percentage of measured resistance of


12 equivalent length of conductor Not more then 75%

13 Details of die set for making joint -


14 Capacity of compressor for making joint -
Whether suitable to pass through stringing blocks
when installed on conductor during tension stringing if
15 -
not state the protective device needed
to make it suitable.
Certification mark (ISI/BS/Any International
16 Institution. -

Reference of ISS or any other international


17 standard specification to which the repair sleeves shall IEC : 61284
conform, if any
18 Reference of drawing and catalogue no. etc. TAG/E/RS/016
19 Packing details, Standard
C. VIBRATION DAMPERS
TAG CORPORATION,
Thiruneermalai road,
1 Maker's name & Country
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
2 Type 4R-Stock bridge
3 Suitable for conductor size and Type (mm) Ø20.6

4 Total weight of each damper (kg) 2.54 kg (Approx).

Damper mass Big - 142 mm


5 Dimension of balancing weights (mm) Damper mass Small - 120 mm

Damper mass Big - 1.08 kg


6 Weight of each balancing weight (kg) Damper mass Small - 0.92 kg

7 Tolerance in balancing weights (+/-%) ±3%


8 Messenger cable
(a) Stranding and wire diameter 19/2.11
(b) UTS of each strand 135 kg/sq.mm (MIN).
(c) Ultimate bending strength
Slipping strength of cable w.r.t. each balancing
9 weight 2.5 kN

10 Natural frequency of the damper (hz)


(a) First resonance 16.5±2
(b) Second resonance 21±2
(c) Third resonance 34±2
(d) Fourth resonance 50±2
The number of damper required per span
11 (suspension/tension)
(a) Span lengths (mtrs) 100 250 390 400 440 1100
As per placement chart
(b) Nos. of dampers (nos.) As per placement chart
Position of fixing damper on the conductor from
12 the clamp mouth
(a) At tension points
i) First damper (mm) As per placement chart
ii) Second damper, (mm) As per placement chart
iii) Third damper (mm) As per placement chart
(b) At suspension points
i) First damper (mm) As per placement chart
ii) Second damper (mm) As per placement chart
iii) Third damper (mm) As per placement chart
13 Clamping torque (kg m) 6 kgm
Minimum fatigue strength in no. of cycles at +/-1
14 mm amplitude at
(a) Resonant frequency of line conductor
(b) Highest resonant frequency of vibration
damper 10 Million cycles

Clamp slipping strength of vibration damper


15 (kg)
(a) Before fatigue test 2.5 kN
(b) After undergoing fatigue test without re-
torquing the bolts. 2.0 kN

(a) Diagram showing power dissipated by the damper


16 in watts for various vibration frequencies -
& amplitudes (watts)
(b) Diagram showing the vibration energy for conductor
bundle for various frequencies under -
varied winds and spans
Magnetic power loss per damper at 600 amp. 50
17 Hz AC current (watts) Not more than 1 Watts

18 Material and conforming

a) Clamp - Al.alloy (TYPE-4600, IS:617),


a) Clamp b) Messenger cable c) Damper weight b) Messenger cable - High strength steel,
c) Damper weight - Cast iron (IS: 210).

Quantity of zinc and standard to which conforming


19 IS0 : 1461

20 Galvanization
(a) method of galvanization
i) Spring washers Electro galvanizing
ii) Other spare parts Hot - dip galvanizing
(b) no. of dips
i) One minute Ferrous components - 6 Dips
Ferrous washers - 4 Dips
ii) Half minute -
(c) minimum weight of zinc coating (g/sq. m)
i) Casting 610 gm/m2
ii) Wires 305 gm/m2
Certification Mark (ISI/BS/or any other
21 International Standard) -

22 Packing details
i) Marking Standard
ii) Standard to which conforming -

V OPGW ACCESSORIES
A. SUSPENSION ASSEMBLY -
1 Manufacturer's name & address -
2 Type -
3 Material -
Drawing no. (give complete details and dimension
4 including no. of components) -

Reference of Indian Standard specification to which


5 conform -

Minimum slip strength with respect to earth wire


6 -

7 Minimum ultimate breaking strength -


8 Galvanising -
(a) Spring washers -
(b) Other ferrous parts -
(c) weight of zinc (g/sq. m) -
(d) no. of dips -
i) one minute -
ii) half minute -
(e) Quality of zinc and standard to which
conforming -

Fixing arrangement of clamp on the ground wire /


9 OPGW -
Whether the limb of the U-bolt has been long enough
10 to accommodate the leg of the flexible -
copper bond (Y/N)
Total drop of the suspension assembly from the
11 centre point of the attachment to the centre point of the -
ground wire (mm)
Certification Mark (ISI/BS/Any other International
12 Standard) -

13 Total weight of assembly (kg) -


Method of manufacture adopted e.g. forging or
14 casting -

15 Packing details -
16 Other details, if any -

B. TENSION ASSEMBLY
1 Manufacturer's name & address -
2 Type -
3 Material -
(a) Body -
(b) Bolts and nuts -
Drawing no. and dimension
4 and no. of co -

Reference of Indian Standard specification / IEC to


5 which conforms -

6 Minimum slip strength -


7 Minimum ultimate breaking strength -
8 Brinnel hardness of steel -
9 Galvanising -
(a) Spring washers -
(b) Other ferrous parts -
(c) weight of zinc (g/sq. m) -
(d) no. of dips -
i) one minute -
ii) half minute -
(e) Quality of zinc and standard to which
conforming -

10 Total weight of complete assembly (kg) -


Breaking strength of tension clamp as % of
11 breaking load of ground wire -

Resistivity as % of equivalent length of ground wire


12 -
Whether lugs along with necessary nuts and bolts for
13 jumper connections will be supplied (Y/N) -

Angle of Jumper terminal with the vertical plate


14 (degree) -

Whether the bolt holding the jumper is sufficiently long


and will be provided with washers, nuts and locking
15 -
nuts etc., for fixing one lug of the flexible
copper bond (Y/N0)
Certification Mark (ISI/BS/or Any other
16 International Standard) -

17 Packing details -
18 Other details, if any -
C. VIBRATION DAMPERS
1 Maker's name & Country -
2 Type -
3 Suitable for earth wire of size (mm) -
Material with reference of ISS to which it conforms
4 -
(a) Clamp -
(b) Messenger cable -
(c) Weight -
Reference of manufacturer's drawing and
5 catalogue no. etc. -

6 Total weight of each damper (kg) -


7 Dimensions of balancing weights (mm) -
8 Length of each balancing weight (mm) -
9 Weight of each balancing weight (kg) -
10 Tolerance in balancing weights (+%) -
11 Messenger cable -
(a) Stranding and wire diameter (mm) -
(b) Ultimate tensile strength (kg) -
(c) Ultimate bending strength (kg m) -
Slipping strength of stranded messenger cable with
12 respect to balancing weight (kg) -

(a) Diagram showing power dissipated by the


13 damper in watts for various vibration frequencies & -
amplitudes (watts)
(b) Diagram showing the vibration energy for various
frequencies under varied winds and spans -

14 Natural frequency of the damper


(a) Ist (Hz) -
(b) IInd (Hz) -
(c) IIIrd (Hz) -
(d) IVth -
The number of dampers required per span for
15 various span length -

(a) Span lengths (mtrs) 250m 390m 400m


440m 1100m -

(b) Nos. of dampers -


i) Suspension span -
ii) Tension span -
Position of fixing damper on the earth wire from
16 the clamp mouth -

(a) At tension points -


i) First damper (mm) -
ii) Second damper (mm) -
iii) Third damper (mm) -
(b) At suspension points -
i) First damper (mm) -
ii) Second damper (mm) -
iii) Third damper (mm) -
17 Clamping torque (kg m) -
Maximum possible dynamic strain on the earth wire
18 with recommended number of dampers -

Minimum fatigue strength at amplitude of +/- 0.5


19 mm in nos. of cycles at -

(a) Resonant frequency of Earth wire -


(b) Highest frequency of vibration dampers -
20 Clamp slipping strength of vibration damper -
(a) Before fatigue test -
(b) After fatigue test for 10 million cycles -
21 Weight of zinc coating in (gms/m2 ) -
(a) Spring washers -
(b) Bolts and nuts -
(c) Weights -
(d) Clamp -
(e) Messenger cable -
No. of dips of 1 minute duration which the damper
22 withstands under 'Preece Test' -

(a) Spring washers -


(b) Bolts and nuts -
(c) Weights -
(d) Clamp -
(e) Messenger cable -
23 Packing details -
Certificate Marks (ISI/BS/or Any other International
24 Standard) -

D) MIDSPAN COMPRESSION JOINT -


1 Maker's name & address -
2 Type -
3 Inside diameter of sleeve before compression -
4 Outside dimension of sleeve -
a)Before compression (mm) -
b)After compression (mm) -
i. Corner to corner (mm) -
ii. Surface to surface (mm) -
5 Length of sleeve -
a) Before compression (mm) -
b) After compression (mm) -
6 Weight of sleeve (kg) -
7 Slipping strength of mid span (%) -
joint, expressed as a percentage of -
Ultimate tensile strength -
8 Resistance of the compressed -
Unit expressed as a percentage -
of the Resistance of equivalent -
length of bare earth wire -
9 Material of s -
a) Material -
b) Standard to which conform -
c) Whether annealed properly -
d) Brinnel Hardness of material -
10 Galvanization -
a) Process -
b) Weight of zinc (g/sq. m) -
c) No. of dips -
i) one minute -
ii) half minute -
d)Quality of zinc and standard to which
conforming -

Whether compression and non compression joints


11 marked on the sleeve (Y/N) -

Breaking strength of Mid span joint as of the


12 breaking load of ground wire % -

13 Details of die set for making joint -


Whether suitable to pass through stringing block when
installed on ground wire during tension stringing if not
14 -
state the protective device needed
to make it suitable.
Capacity of Hydraulic compressor for making joint
15 -
Certification mark (ISI/BS/Any international
16 Institution -

17 Drum no. and details and no. of components -


18 Packing details -
-
E) FLEXIBLE COPPER BONDS -
1 Maker's name & address -
2 Governing Standard -
3 Material & Standard -
4 No. of Strands -
5 Length -
6 Weight -
Slipping strength of lugs provided on either end of
7 earthing bond without any damage to earthing -
bond
Certification mark (ISI/BS/Any international
8 Institution -

Packing details (No. of bonding pices per package


9 and gross weight) -

V INSULATOR DISCS AND COMPLETE STRINGS

1 Type of insulator -
2 Maker's name,address and country -
3 Material and Governing standard -
Detailed dimensional drawing indicating tolerances for
4 each type of insulator disc enclosed (YES/NO -

5 Dimensions (Indicate tolerances also) -


a) Diameter (mm) -
i) Suspension -
ii) Tension -
b) Spacing (mm) -
i) Suspension -
ii) Tension -
c) Creepage distance (mm) -
i) Suspension -
ii) Tension -
6 Pin-ball-shank diameter (mm) -
a) Suspension insulator -
b) Tension insulator -
7 Colour -
a) Suspension -
b) Tension -
8 Electromechanical strength (KN) -
a) Suspension -
b) Tension -
9 Mechanical breaking strength (KN) -
a) Suspension -
b) Tension -
Power frequency one-minute withstand voltage -KV
10 (rms) -

a) Dry -
i) Suspension -
ii) Tension -
b) Wet -
i) Suspension -
ii) Tension -
Impulse 1.2x50 microsecond withstand voltage -KV
11 (peak) -

a) +ve Wave -
i) Suspension -
ii) Tension -
b) -ve Wave KV (peak) -
i) Suspension -
ii) Tension -
12 Power frequency flashover voltage -KV (rms) -
a) Dry -
i) Suspension -
ii) Tension -
b) Wet KV (rms) -
i) Suspension -
ii) Tension -
Impulse 1.2x50 microsecond flashover voltage KV
13 (peak) -

a) +ve Wave -
i) Suspension -
ii) Tension -
b) -ve Wave -
i) Suspension -
ii) Tension -
14 Power frequency puncture voltage KV (rms) -
a) Suspension -
b) Tension -
(ii) Corona extinction voltage KV (rms) -
a) Suspension -
b) Tension -
15 RIV at 10 KV (rms) -
a) Suspension (microvolts) -
b) Tension (microvolts) -
16 Weight of the Insulator disc (kg) -
a) Suspension -
b) Tension -
17 Locking device -
a) Type -
i) Suspension -
ii) Tension -
b) Material -
i) Suspension -
ii) Tension -
c) Standard to which conforming -
18 Socket and ball ended component -
a) Standard to which conforming -
b) Material and Standard to which conforming -
c) Galvan -
d) Quality of zinc and Standard to which
conforming -

e) Weight of zinc (g/m2 ) -


f) Number of one-minute dips -
Packing details (No. of disc insulators of each type
19 per package and gross weight) -

Certification mark (BIS/BS/Any National


20 Institution) -

VII INSULATOR STRINGS -


1 No. of insulator discs -
a) Single suspension 'I' -
b) Double suspension 'II' -
c) Single Tension -
d) Double Tension -
2 E.M. Strength - KN -
a) Single suspension -
b) Double suspension -
c) Single Tension -
d) Double Tension -
Power frequency one minute withstand voltage KV
3 (rms) -

Dry/Wet -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
Power frequency flashover voltage KV (rms)
4 Dry/Wet -

i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
5 Impulse withstand voltage (dry) KV (peak) -
Positive wave -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
Negative wave -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
6 Impulse flashover voltage (dry) -
Positive wave - KV (peak) -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
Negative wave - KV (peak) -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) -
2) -
7 Corona extinction voltage - KV (rms) -
a) Dry/Wet - KV (rms) -
i) Suspension -
1) Single -
2) Double -
ii) Tension -
1) Single -
2) Double -
Maximum RIV for complete string i.e. including arcing
8 horns, clamps etc. at 154 KV (rms) (in -
microvolt)
a) Single Suspension -
b) Single Tension -
9 Creepage distance of complete string -
a) Single suspension -
b) Double suspension -
c) Single Tension -
d) Double Tension -
Detailed Dimensional drawing for insulator strings
10 with tolerances attached for: -

a) Single Suspension (I) YES/NO -


b) Double Suspension (II) YES/NO -
c) Single Tension YES/NO -
d) Double Tension YES/NO -
11 Weight (kg.) -
a) Single Suspension (I) -
b) Double Suspension (II) -
c) Single Tension -
d) Double Tension -
Maximum percentage of line to earth voltage across
insulator discs of insulator string for single (I),
12 -
double(II) suspension and double tension.

a) Ist insulator disc from line side -


b) 2nd insulator disc from line side -
c) 2nd last insulator disc from line side -
d) Last insulator disc from line side. -
Mechanical strength of complete insulator string
13 alongwith hardware fittings. -

a) Single Suspension insulator strings (I) -


b) Double Suspension insulator strings (II) -
c) Single Tension insulator strings -
d) Double Tension insulator strings -
Whether end user certificate in support of
14 performance attached. (YES/NO) -

15 Certification Mark (BIS/BS/Any National Institution) -


VIII HARDWARE FITTINGS
I. SUSPENSION CLAMP ASSEMBLY
1 Type Armour grip suspension type
TAG CORPORATION,
Thiruneermalai road,
2 Manufacturer's Name, address and country
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
3 Suitable for (Conductor size) Ø20.6
4 Governing standard IS : 2486

Detailed dimensioned drawings of each component


5 showing tole-rances, material and the standard to No
which conforming enclosed. YES/NO

6 Weight of suspension clamp (kg.) 3.61


a) Body 0.65 kg (Approx)
b) Supporting and clamping components 2.96 (Approx)
c) Total 3.61 (Approx)

7 Galvanization and standard to which conforming.

a) Spring washers Electro-galvanizing


b) Other ferrous parts Hot-dip galvanizing
c) Weight of zinc g/m2
Ferrous components - 610 gm/m2
Ferrous washers - 305 gm/m2
Ferrous components - 6 Dips
d) Number of one-minute dips Ferrous washers - 4 Dips
e) Quality of zinc and standard to which
conforming 99.95 % IS : 209

Minimum failing load (No deformation) (kg.) &


8 (KN) 70 kN

Slip strength at recommended tightening torque


9 (KN) 7 TO 22 kN (As per BS : 3288)

Whether clamp torque Vs slip curve enclosed


10 YES/NO No

11 Magnetic power loss at:


a) 500 amps Watts 1 Watt assembly
Whether a graph showing relation between power
12 losses in watts against current in amperes is -
enclosed YES/NO
13 Formed armour rod set
a) Type Preformed
TAG CORPORATION,
Thiruneermalai road,
b) Manufacturer's name, address and country
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
c) Suitable for (Conductor size) Ø20.6
d) No. of rods per set (No.) 11
e) Direction of lay RIGHT
f) Overall length after fitting on conductor (mm)

g) Actual length of each rod along its helix (mm) 1760


h) Diameter of each rod (mm) Ø6.35
i) Tolerance in
i) Diameter of each rod (+/- mm) ±0.1
ii) Length of each rod (+/- mm) ±16
iii) Difference of length between the longest and
shortest rod in a set (+/- mm) ±13

j) Type of aluminium alloy used for manufacture of


Formed armour rod set and standard to which Aluminum alloy
conforming
k) UTS of each rod (kg/mm2 ) 35
14 Elastomer for AGS clamps
a) Supplier TAG CORPORATION
b) Type EPDM
c) Moulded on insert YES/NO Yes
d) Shore hardness 65 TO 80
e) Temp. range for which designed (deg.C) 95
15 Particulars of insert
a) Type of aluminium alloy used for manufacturing of
insert and standard to which conforming. AL.ALLOY (TYPE-65032, IS: 733)

b) Manufacturing process Extrusion


Packing details (No. of suspension clamp/formed
16 armour rod set/elastomer etc. per package and gross Standard
weight of each package)
Whether end user certificate in support of
17 performance enclosed YES/NO -

Certification mark (BIS/BS/Any National


18 Institution). -

II. TENSION CLAMP ASSEMBLY


1 Type Compression
Manufacturer's name address and country TAG CORPORATION,
Thiruneermalai road,
2
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
3 Suitable for (conductor size) Ø20.6
4 Governing standard IS : 2486
Detailed dimensioned drawings of each component
showing tolerances, material and standard to which
5 No
conforming enclosed YES/NO

Materials composition and standard to which


6 conforming.
a) Outer Al.Alloy (TYPE-63400, IS:733)
b) Inner sleeve F.S (CL – II , IS : 2004)
7 Slip strength (KN) 95 % of CONDUCTOR UTS
8 Minimum failing load (KN) (No deformation) 95 % of CONDUCTOR UTS
9 Shape of cross section
a) Before compression (mm)
i) Aluminium alloy Hollow circular
b) After compression
i) Aluminium alloy Hexagonal
10 Dimensions of sleeve (mm)
a) Before compression (mm)
i) Aluminium alloy sleeve 38±1
b) After compression (mm)
i) Aluminium alloy sleeve 32±0.5
11 Length of sleeve
a) Before compression (mm)
i) Aluminium alloy sleeve 450
b) After compression (mm)
i) Aluminium alloy sleeve 500
12 Galvanisation
a) Process Hot - dip galvanizing & Electro galvanizing

b) Weight of zinc (g/sq.m) Ferrous components - 610 gm/m2


Ferrous washers - 305 gm/m2
c) No. of dips
i) 1 minute Ferrous components - 6 Dips
Ferrous washers - 4 Dips

ii) 1/2 minute -


d) Quality of zinc and standard to which
conforming. 99.95 % IS : 209

Whether compression and non-compression


13 (YES/NO) zones marked on the sleeves Yes

Electrical resistance of tension clamp as a % of


14 equivalent length of conductor. More than 75%

Details of dies and hydraulic compressor required for


15 compressing sleeves of tension clamp. -

Packing details (Nos. of tension clamp assembly per


16 package and gross weight) Standard

Whether end user certificate in support of


17 YES/NO performance enclosed -

Certification mark (BIS/BS/Any National


18 Institution) -

III. OTHER HARDWARE FITTINGS


TAG CORPORATION,
Thiruneermalai road,
1 Manufacturer's name, address and country.
Chrompet, Chennai - 600 044.
Tamil Nadu, INDIA.
Material, composition, mechanical strength and
2 standard to which conforming.
a) Anchor shackle F.S (CL - IV, IS: 2004)
b) Chain link F.S (CL - IV, IS: 2004)
c) Yoke plate M.S (IS:2062)
d) Arcing horn M.S (IS:2062)
e) Split pin S.S (AISI - 304)
f) Socket clevis F.S (CL - IV, IS: 2004)
g) Ball clevis F.S (CL - IV, IS: 2004)
h) Clevis-Clevis -
i) Clevis eye F.S (CL - IV, IS: 2004)
j) Ball hook -
k) Socket eye horn holder type F.S (CL - IV, IS: 2004)
l) Ball eye -
m) Twisted shackle -

3 Galvanisation and Standard to which conforming. ISO : 1461


a) Spring washers Electro galvanizing
b) Other ferrous parts Hot - dip galvanizing
Ferrous components - 610 gm/m2
c) Weight of zinc g/sq.m
Ferrous washers - 305 gm/m2
Ferrous components - 6 Dips Ferrous washers -
d) No. of one minute dips
4 Dips
e) No. of 1/2 minute dips. -

4 Quality of zinc and standard to which conforming. 99.95 % IS:209


Detailed dimensioned drawing of each fitting showing
5 tolerances, weight,strength etc. enclosed No
(YES/NO)
Whether components are interchangeable.
6 (YES/NO) Yes

Packing details of each fitting per package and


7 gross weight -

Whether end user certificate in support of


8 performance enclosed YES/NO -

Certification mark (BIS/BS/Any National


9 institution.) -

S-ar putea să vă placă și