XL project 2018 DCDU-12B allocation

v1.2

HUAWEI TECHNOLOGIES CO., LTD.


CONTENT

1. Cabinet 3900 A Ver B


2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 2


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 3


Cabinet 3900 A Ver B - 2 system
Existing just 2 DCDU
DCDU-03C (Existing) Note :
-This scenario for solution P1 “pentaband + RRU 3971
(DCS+LTE)+RRU 3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 2 DCDU existing
- there is one new DCDU-12B
-DCDU-12B insert it under DCDU-01 cabinet RFC base on
illustration picture (orange color)
-DCDU-12B connect handle 2 system must use two pair power
DCDU-01 (Existing) cable 25mm2 + MCB 80 A

DCDU-12B (Insert new DCDU)


Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 4


Cabinet 3900 A Ver B - 2 system
Existing just 3 DCDU

DCDU-03C (Existing) Note :


-This scenario for solution P1 “pentaband + RRU 3971
(DCS+LTE)+RRU 3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
DCDU-12B (Insert new DCDU) -There is 3 DCDU existing
- there is one new DCDU-12B swap DCDU-01
-DCDU-12B insert it under EMUA/EMUB base on illustration
picture (orange color)
NEXT INSERT DCDU-12B (Insert new DCDU) -Next insert new DCDU 12B under DCDU 12B in APM cabinet as
illustration picture (yellow color)
DCDU-01 (Existing) -DCDU-12B connect handle 2 system must use two pair power
cable 25mm2 + MCB 80 A

DCDU-12B (Existing)

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 5


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 6


Cabinet 3900 A Ver D - 2 system
Existing just 2 DCDU
DCDU-12C (Existing) Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 2 DCDU existing
- there is one new DCDU-12B
-DCDU-12B inserted above DCDU-12A RFC base on illustration picture
(orange color)
-DCDU-12B connect handle 2 system must use two pair power cable
DCDU-12B (Insert - New DCDU) 25mm2 + MCB 80 A

DCDU-12A (Existing)

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 7


Cabinet 3900 A Ver D - 2 system
Existing just 3 DCDU
DCDU-12C (Existing) Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
DCDU-12B (Insert new DCDU) -There is 3 DCDU existing
- there is one new DCDU-12B
-DCDU-12B insert it under EMUA/EMUB base on illustration picture
(orange color)
NEXT INSERT DCDU-12B (Insert new DCDU) -Next insert new DCDU 12B under DCDU 12B in APM cabinet as
illustration picture (yellow color)
DCDU-12B (Existing) -DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A
DCDU-12A (Existing)

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 8


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 9


Cabinet 3900 L Ver B - 2 system
Existing just 2 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 2 DCDU existing
- there is one new DCDU-12B
-DCDU-12B inserted under DCDU-01 base on illustration picture (orange
DCDU-01 (Existing) color)
-DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A

Port Allocation for DCDU-12B as bellow


DCDU-01 (Existing)

load 0 load 1 load 2 load 3 load 4 load 5


DCDU-12B (New DCDU)
RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 10


Cabinet 3900 L Ver B - 2 system
Existing just 2 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 3 DCDU existing
- there is one new DCDU-12B
-DCDU-12B inserted under DCDU-12B base on illustration picture (orange
DCDU-01 (Existing) color)
-Next insert new DCDU 12B under DCDU 12B as illustration picture
(yellow color)
-DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A

DCDU-01 (Existing)

DCDU-12B (Existing)
Port Allocation for DCDU-12B as bellow

DCDU-12B (New DCDU)


load 0 load 1 load 2 load 3 load 4 load 5
RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
NEXT INSERT DCDU-12B (Insert new DCDU) sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 11


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 12


Cabinet 3900 L Ver D - 2 system
Existing just 2 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 2 DCDU existing
- there is one new DCDU-12B
DCDU-12A (Existing) -DCDU-12B inserted under DCDU-12A base on illustration picture (orange
color)
-DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A

DCDU-12A (Existing) Port Allocation for DCDU-12B as bellow

DCDU-12B (New DCDU) load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 13


Cabinet 3900 L Ver D - 3 system
Existing just 2 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971
(DCS+LTE)+RRU 3952 (3G) +RRU 3938 (GSM) “
-solution P2 (AAU 3911) + RRU 3938 (GSM)
-There is 3 DCDU existing
-DCDU-12B inserted under DCDU-12B base on illustration
picture (orange color)
DCDU-12A (Existing)
-Next insert new DCDU 12B under DCDU 12B as illustration
picture (yellow color)
-DCDU-12B connect handle 2 system must use two pair
power cable 25mm2 + MCB 80 A

DCDU-12A (Existing)

DCDU-12B (Existing)
Port Allocation for DCDU-12B as bellow
DCDU-12B (New DCDU)
load 0 load 1 load 2 load 3 load 4 load 5
RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
NEXT INSERT DCDU-12B (Insert new DCDU)
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 14


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 15


Cabinet DBS3900- 2 system
Existing just 1 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
DCDU-12b (Existing) 3952 (3G)“
-solution P2 (AAU 3911),
-There is 1 DCDU 12B existing
- there is one new DCDU-12B
DCDU-12B (New DCDU)
-DCDU-12B inserted under EMUA/EMUB base on illustration picture
(orange color)
-DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 16


Cabinet DBS3900- 3 system
Existing just 2 DCDU
Note :
-This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
DCDU-12b (Existing) 3952 (3G)“
-solution P2 (AAU 3911),
-There is 2 DCDU 12B existing
DCDU-12b (Existing)
- there is one new DCDU-12B
-DCDU-12B inserted under DCDU-12B base on illustration picture (orange
color)
DCDU-12B (New DCDU)
-Next insert new DCDU 12B under DCDU 12B as illustration picture
(yellow color)
-DCDU-12B connect handle 2 system must use two pair power cable
25mm2 + MCB 80 A
NEXT INSERT DCDU-12B
(Insert new DCDU)

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 17


1. Cabinet 3900 A Ver B
2. Cabinet 3900 A Ver D
3. Cabinet 3900 L Ver B
4. Cabinet 3900 L Ver D
5. Cabinet DBS3900
6. Cabinet 3900 AL

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 18


Cabinet 3900 AL Ver D - 2 system
Existing just 2 DCDU
Note :
DCDU-12C (Existing) -This scenario for solution P1 “pentaband + RRU 3971 (DCS+LTE)+RRU
3952 (3G), GSM using MRFU “
-solution P2 (AAU 3911), GSM using MRFU
-There is 2 DCDU existing
- there is one new DCDU-12B
DCDU-12B (Insert new DCDU)
-DCDU-12B insert it base on illustration picture (orange color)
-Next insert new DCDU 12B beside DCDU 12B illustration picture
(yellow color)
-DCDU-12B connect handle 2 system must use two pair power cable
NEXT INSERT DCDU-12B (Insert new DCDU)
25mm2 + MCB 80 A
DCDU-12C (Existing)

Port Allocation for DCDU-12B as bellow

load 0 load 1 load 2 load 3 load 4 load 5


RU 1800 RU 1800 RU 1800 RU 2100 RU 2100 RU 2100
sector 0 sector 1 sector 2 sector 0 sector 1 sector 2

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 19


Cabinet 3900 AL Ver D - 2 system
Existing just 2 DCDU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 20


Cabinet 3900 AL Ver D - 2 system
Existing just 2 DCDU
NO Cable Installation Position
Connect the cord end terminal of NEG (-) DC power
Input Power Cable for the DCDU-12C (in the cable to negative output MCB & cord end of RTN (+)
1&3
BTS3900AL DC cabinet) power cable to the positive output copper bar at
rectifier
Connect the cord end terminal of NEG (-) DC power
Input Power Cable for the DCDU 12b (in the cable to negative output MCB & cord end of RTN (+)
2
BTS3900AL DC cabinet) power cable to the positive output copper bar at
rectifier

POWER JUNCTION BOX

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 21


Thank you
www.huawei.com

Copyright©2013 Huawei Technologies Co., Ltd. All Rights Reserved.


The information contained in this document is for reference purpose only, and is subject to
change or withdrawal according to specific customer requirements and conditions.