Designer: ___; Date: Oct 23 2019

Project: _______________ Checker: ___; Date: Oct 23 2019


Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Steel U Tub with Composite Slab


Ultimate Design

Live Load Distribution Factors

Design Standard:
AASHTO LRFD 8th Edition, 2017
No Interim Revisions
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Live Load Distribution Factors were not calculated since the option was not selected in the design
request.
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Steel U Tub with Composite Slab


Ultimate Design

1. Demands

Design Standard:
AASHTO LRFD 8th Edition, 2017
No Interim Revisions
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Summary of Positive Moment Demands

Location Combination Moment Moment Moment Moment Mu


MNonComp MCompLongT MCompShortT (zero if neg)

Left Exterior Str-I6 -11kN-m 0kN-m 209kN-m 198kN-m


Girder

Interior girder 1 Str-I1 31kN-m 0kN-m 25kN-m 56kN-m

Right Exterior Str-I6 -11kN-m 0kN-m 209kN-m 198kN-m


Girder

Summary of Negative Moment Demands

Location Combination Moment Moment Moment Moment Mu


MNonComp MCompLongT MCompShortT (zero if pos)

Left Exterior Str-I1 -16kN-m 0kN-m -274kN-m -289kN-m


Girder

Interior girder 1 Str-I6 22kN-m 0kN-m -34kN-m -12kN-m

Right Exterior Str-I1 -16kN-m 0kN-m -274kN-m -289kN-m


Girder

Summary of Demands Controlling Shear D/C

The reported shear values are per one web in the direction of the inclined web.

Location Combination Shear Vu Torsion Tu

Left Exterior Girder Str-I6 Max 1969kN 605kNm

Interior girder 1 Str-I6 Max 1790kN 664kNm

Right Exterior Str-I6 Max 1969kN 605kNm


Girder
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Steel U Tub with Composite Slab


Ultimate Design

2. Resistance

Design Standard:
AASHTO LRFD 8th Edition, 2017
No Interim Revisions
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Geometry and Materials - Left Exterior Girder

ϕf = 1,00 tt = 51 mmn Ixxbeam = 47.096.928.928 mm^4


ϕv = 1,00 bt = 381 mm Sxxbeamtop = 62.758.345 mm^3
f'cslab = 27,6 MPa fyt = 344,7 MPa Sxxbeambot = 82.575.324 mm^3
Ecslab = 24855,6 MPa αweb = 11,20 deg Dvert = 1219 mm
fy = 413,7 MPa tw = 25 mm
bslab = 3626 mm fyw = 344,7 MPa
hslab = 305 mm tb = 51 mm
th = 75 mm bb = 1219 mm
Art = 0 mm^2 fyb = 344,7 MPa
Arb = 0 mm^2 Es = 199948,0 MPa
Crt = 0 mm h = 1650 mm
Crb = 0 mm Does web has longitudinal stiffeners? - No
,
Length of web measured along the web: 𝐷 = ∝
= ,
= 1242,8 𝑚𝑚
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

,
Thickness of web measured horizontally: 𝑡 = = = 25,89 𝑚𝑚
∝ ,

The beam moment of inertia and section moduli were calculated based on effective bottom flange
width derived as:

𝑏𝑏𝑒𝑓𝑓 = 𝑚𝑖𝑛 𝑏 ; 0.2𝐿 = min(1219 ; 0.2 × 55000) = 1219𝑚𝑚

Cross Section Proportion Limits

Verify web inclination:

tan 𝛼 = tan 11,20 = 0,19 ≤ = 0.25 O.K. LRFD 6.11.2.1.1

Verify web proportions:

= = 49 ≤ 150 O.K. LRFD eq. 6.11.2.1.2-1

Verify top flange proportions:

= ×
= 4 ≤ 12.0 O.K. LRFD eq. 6.11.2.2-1

𝑏 ≥ => 381 ≥ = 207 O.K. LRFD eq. 6.11.2.2-2

𝑡 ≥ 1.1𝑡 => 51 ≥ 1.1 × 25 = 28 O.K. LRFD eq. 6.11.2.2-3

Plastic Section Properties

Plastic Moment Capacity for Positive Bending

Per LRFD D6.1 the forces in longitudinal reinforcement are conservatively neglected.

Calculate forces in elements:

𝑃 = 0.85𝑓 𝑏 ℎ = 0.85 × 27,6 × 3626 × 305 = 25926,3𝑘𝑁

𝑃 = 2 × 𝑓 𝑏 𝑡 = 2 × 344,7 × 381 × 51 = 13344,7𝑘𝑁

𝑃 = 2 × 𝑓 𝐷𝑡 = 2 × 344,7 × 381 × 51 = 21765,6𝑘𝑁

𝑃 = 𝑓 𝑏 𝑡 = 344,7 × 1219 × 51 = 21351,5𝑘𝑁


Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Calculate position of plastic neutral axis:

Since 𝑃 + 𝑃 ≥ 𝑃 + 𝑃 = 21351,5 + 21765,6 = 43531,3𝑘𝑁 ≥ 13344,7 + 25926,3 = 39270,9𝑘𝑁


plastic neutral axis is located in the web.

, , ,
𝑌= +1 = + 1 = 108𝑚𝑚 measured verticaly from
,
top of web

Calculate distances from the element force to the plastic neutral axis.

ℎ 305
𝑑 = +𝑡 +𝑌 = + 75 + 108 = 335𝑚𝑚
2 2
𝑡 51
𝑑 = +𝑌= + 108 = 133𝑚𝑚
2 2
𝑡 51
𝑑 = + 𝐷𝑣𝑒𝑟𝑡 − 𝑌 = + 1219 − 108 = 1137𝑚𝑚𝑛
2 2
𝑃
𝑀 = (𝑌 + (𝐷𝑣𝑒𝑟𝑡 − 𝑌 ) ) + (𝑃 𝑑 + 𝑃 𝑑 + 𝑃 𝑑 )
2𝐷𝑣𝑒𝑟𝑡
1 21765,6
= (108 + (1219 − 108) )
1000 2 × 1219

+ (25926,3 × 335 + 13344,7 × 133 + 21351,5 × 1137) = 45872,4𝑘𝑁𝑚

Verify ductility requirement per LRFD 6.10.7.3-1. Per LRFD C6.10.7.3-1 neglect haunch and per LRFD
6.11.2.1.1 use distance along web when calculating Dt.

𝐷 ≤ 0.42𝐷 => 488 ≤ 0.42 × 1649 = 693 O.K.

Depth of web in compression measured vertically at positive plastic moment per LRFD D6.3.2.

𝐷𝑣𝑒𝑟𝑡 𝑡 𝑏 𝑓 − 2𝑡 𝑏 𝑓 − 0.85𝑓 𝑏 ℎ − 𝑓 (𝐴 + 𝐴 )
𝐷 = +1
2 2𝑓 𝑡 𝐷
1219 51 × 1219 × 344,7 − 2 × 51 × 381 × 344,7 − 0.85 × 27,6 × 3626 × 305 − 413,7 × (0 + 0)
=
2 2 × 344,7 × 25 × 1242,8

+ 1 = 108𝑚𝑚

Plastic Moment Capacity for Negative Bending


Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Calculate forces in elements:

𝑃 = 𝑓 𝑏 𝑡 = 344,7 × 1219 × 51 = 21351,5𝑘𝑁

𝑃 = 2 × 𝑓 𝐷𝑡 = 2 × 344,7 × 381 × 51 = 21765,6𝑘𝑁

𝑃 = 2𝑓 𝑏 𝑡 = 2 × 344,7 × 381 × 51 = 13344,7𝑘𝑁

𝑃 =𝑓𝐴 = 413,7 × 0 = 0,0𝑘𝑁

𝑃 =𝑓𝐴 = 413,7 × 0 = 0,0𝑘𝑁

Calculate position of plastic neutral axis:

Since 𝑃 + 𝑃 ≥ 𝑃 + 𝑃 + 𝑃 => 21351,5 + 21765,6 = 43117,1𝑘𝑛 ≥ 13344,7 + 0,0 + 0,0 =


13344,7𝑘𝑁 plastic neutral axis is located in the web.

, , , ,
𝑌= +1 = + 1 = 834𝑚𝑚 measured vertically from
,
top of web

Calculate distances from the element force to the plastic neutral axis.

𝑑 =ℎ + 𝑡 − 𝐶 + 𝑌 = 305 + 75 − 0 + 834 = 1214𝑚𝑚

𝑑 =ℎ +𝑡 −𝐶 + 𝑌 = 305 + 75 − 0 + 834 = 1214𝑚𝑚

𝑡 51
𝑑 =𝑌+ = 834 + = 859𝑚𝑚
2 2
𝑡 51
𝑑 = 𝐷𝑣𝑒𝑟𝑡 − 𝑌 + = 1219 − 834 + = 411𝑚𝑚
2 2
𝑃
𝑀 = (𝑌 + (𝐷𝑣𝑒𝑟𝑡 − 𝑌) ) + (𝑃 𝑑 + 𝑃 𝑑 + 𝑃 𝑑 + 𝑃 𝑑 )
2𝐷𝑣𝑒𝑟𝑡
1 21765,6
= (834 + (1219 − 834) )
1000 2 × 1219

+ (0,0 × 1214 + 0,0 × 1214 + 13344,7 × 859 + 21351,5 × 411) = 27768,4𝑘𝑁𝑚

Depth of web in compression measured vertically at negative plastic moment per LRFD D6.3.2.
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

𝐷𝑣𝑒𝑟𝑡
𝐷 = 2 × 𝑓 𝑡 𝑏 + 2 × 𝑓 𝑡 𝐷 + 𝑓 (𝐴 + 𝐴 ) − 𝑓 𝑡 𝑏
2 × 2𝑓 𝑡 𝐷
1219
= (2 × 344,7 × 51 × 381 + 2 × 344,7 × 25 × 1243
2 × 2 × 344,7 × 25 × 1243
+ 413,7 × (0 + 0) − 344,7 × 51 × 1219) = 385𝑚𝑚

Elastic Section Properties


.
Short term modular ratio 𝑛 = = = 8,04
.

Long term modular ratio 𝑛 = 3,00𝑛 = 3,00 × 8,04 = 24,13

𝐴 = 2 × 𝑡 𝑏 + 𝑡 𝐷 + 𝑡 𝑏 = 2 × 51 × 381 + 25 × 1243 + 51 × 1219 = 163782𝑚𝑚

𝐼 47096928928
𝑦 = = = 570𝑚𝑚
𝑆 82575324

𝐴 =ℎ 𝑏 = 305 × 3626 = 1105966𝑚𝑚

ℎ 305
𝑦 = 𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 + = 51 + 1219 + 75 + = 1498𝑚𝑚
2 2

ℎ = 𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 = 51 + 1219 + 51 = 1321𝑚𝑚

ℎ = 𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 + ℎ = 51 + 1219 + 75 + 305 = 1650𝑚𝑚

𝐴 1105966
𝐴 =𝐴 + = 163782 + = 301265𝑚𝑚
𝑛 8,04

𝐴 =𝐴 +𝐴 +𝐴 = 163782 + 0 + 0 = 163782𝑚𝑚

Short Term Composite Section - Positive Bending

Center of gravity (measured from the bottom) and moment of inertia:

𝐴 1105966
𝐴 𝑦 +𝑛 𝑦 163782 × 570 + × 1498
8,04
𝑑 = = = 993𝑚𝑚
𝐴 1105966
𝐴 + 163782 +
𝑛 8,04
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

𝐼 𝐴
𝐼 =𝐼 +𝐴 𝑑 −𝑦 + + 𝑑 −𝑦
𝑛 𝑛
8.727.671.518
= 47.096.928.928 + 163782 × (993 − 570) +
8,04
1105966
+ × (993 − 1498) = 112.430.654.280𝑚𝑚
8,04

Steel based short term section modulus at bottom flange of the composite section for positive bending.

𝐼 112430654280
𝑆 = = = 113.171.020𝑚𝑚
𝑑 993

Steel based short term section modulus at top flange of the composite section for positive bending.

𝐼 112430654280
𝑆 = = = 343.465.403𝑚𝑚
𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 − 𝑑 51 + 1219 + 51 − 993

Concrete based short term section modulus at top of slab of the composite section for positive bending.

𝐼 𝑛 112.430.654.280 × 8,04
𝑆 = =
𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 + ℎ −𝑑 51 + 1219 + 75 + 305 − 993
= 1.377.575.373𝑚𝑚

Hybrid factor Rh for positive flexure.

Per C6.10.1.10.1 the Dn is conservatively taken as the vertical distance from the neutral axis of the short
term composite section to the inside face of the bottom flange. Dni is converted from vertical distance to
inclined distance measured along the web.

𝐷 = max(0, 𝑑 − 𝑡 ) = max(0,993 − 51) = 943𝑚𝑚

𝐷 = min(𝐷 , 𝐷𝑣𝑒𝑟𝑡) = min(943,1219) = 943𝑚𝑚

𝐷 943
𝐷 = = = 960,9𝑚𝑚
cos ∝ cos 11,2

𝑓 344,7
𝜌 = min 1, = min 1, = 1,00
𝑓 344,7

2𝐷 𝑡 2 × 960,9 × 25
𝛽= = = 0,79
𝑡 𝑏 51 × 1219

12 + 𝛽(3𝜌 − 𝜌 ) 12 + 0,79 × (3 × 1,00 − 1,00 )


𝑅 = = = 1,00
12 + 2𝛽 12 + 2 × 0,79
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Check if strength of the web steel is higher than strength of the flanges steel:

𝑖𝑓𝑓 > min 𝑓 , 𝑓 𝑡ℎ𝑒𝑛 𝑅 = 1 => 344,7 = min(344,7,344,7) = 344,7 => 𝑅 = 1,00

Long Term Composite Section - Positive Bending

Center of gravity (measured from the bottom) and moment of inertia:

𝐴 1105966
𝐴 𝑦 +𝑛 𝑦 163782 × 570 + × 1498
24,13
𝑑 = = = 773𝑚𝑚
𝐴 1105966
𝐴 + 163782 + 24,13
𝑛

𝐼 𝐴
𝐼 =𝐼 +𝐴 𝑑 −𝑦 + + 𝑑 −𝑦
𝑛 𝑛
8.727.671.518
= 47.096.928.928 + 163782 × (773 − 570) +
24,13
1105966
+ × (773 − 1498) = 78.239.464.885𝑚𝑚
24,13

Steel based long term section modulus at bottom flange of the composite section for positive bending.

𝐼 78239464885
𝑆 = = = 101.207.887𝑚𝑚
𝑑 773

Steel based long term section modulus at top flange of the composite section for positive bending.

𝐼 78239464885
𝑆 = = = 142.839.733𝑚𝑚
𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 − 𝑑 51 + 1219 + 51 − 773

Composite Section - Negative Bending

Center of gravity (measured from the bottom) and moment of inertia:

𝐴 𝑦 + 𝐴 (𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 + ℎ − 𝐶 ) + 𝐴 (𝑡 + 𝐷𝑣𝑒𝑟𝑡 + 𝑡 + ℎ −𝐶 )
𝑑 =
𝐴 +𝐴 +𝐴
163782 × 570 + 0 × (51 + 1219 + 75 + 305 − 0) + 0 × (51 + 1219 + 75 + 305 − 0)
= = 570𝑚𝑚
163782 + 0 + 0
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

𝐼 =𝐼 +𝐴 𝑑 −𝑦 +𝐴 ℎ −𝐶 −𝑑
+𝐴 ℎ −𝐶 −𝑑
= 47.096.928.928 + 163782 × (570 − 570) + 0 × (1650 − 0 − 570)
+ 0 × (1650 − 0 − 570) = 47.096.928.928𝑚𝑚

Steel based section modulus at the top flange for negative bending:

𝐼 47.096.928.928
𝑆 = = = 62.758.345𝑚𝑚
ℎ −𝑑 1321 − 570

Steel based section modulus at the bottom flange for negative bending:

𝐼 47.096.928.928
𝑆 = = = 82.575.324𝑚𝑚
𝑑 570

Depth of web in compression measured vertically in elastic range for negative moment:

𝐷 = 𝑀𝑖𝑛 𝐷𝑣𝑒𝑟𝑡, 𝑀𝑎𝑥(0, 𝑑 − 𝑡 ) = 𝑀𝑖𝑛 1219, 𝑀𝑎𝑥(0,570 − 51) = 530𝑚𝑚

Flange Classification

Top flange slenderness:

𝐹 = 𝑀𝑎𝑥 0.5𝑓 , 𝑀𝑖𝑛 0.7𝑓 , 𝑓 = 𝑀𝑎𝑥 0.5 × 344,7, 𝑀𝑖𝑛(0.7 × 344,7,344,7) = 241,3𝑀𝑃𝑎

𝑏 381
𝜆 = = = 3,75
2𝑡 2 × 51

𝐸 199.948
𝜆 = 0.38 = 0.38 = 9,15
𝑓 344,7

𝐸 199.948
𝜆 = 0.56 = 0.56 = 16,12
𝐹 241,3

Bottom flange slenderness is evaluated within the 'Resistance of unstiffened bottom flange in
compression' calculation block. Calculate width of bottom flange between centerline of webs by
subtracting from total bottom flange width the width of the lips. The width of the lip is defined from
centerline web to the flange tip.

𝑏 = 𝑏 − 2𝑏 = 1219 − 2 × 38 = 1143
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Longitudinally unstiffened bottom flange local buckling coefficient for uniform normal stress k=4.0 and
for shear stress ks=5.34 per LRFD 6.11.8.2.2

Yield moment for composite section in positive flexure:

𝑀 = 13.000𝑁𝑚𝑚

𝑀 = −9.032.690𝑁𝑚𝑚

𝑀 𝑀
𝑀 = 𝑓 − − 𝑆
𝑆 𝑆
13.000 −9.032.690
= 344,7 − − × 113.171.020 = 39.024.421.668𝑁𝑚𝑚
82.575.324 101.207.887

𝑀 𝑀
𝑀 = 𝑓 − − 𝑆
𝑆 𝑆
13.000 −9.032.690
= 344,7 − − × 343.465.403 = 118.427.188.309𝑁𝑚𝑚
62.758.345 142.839.733

𝑀 = 𝑚𝑖𝑛 𝑀 ;𝑀 = 𝑚𝑖𝑛(39.024.421.668; 118.427.188.309) = 39.024.421.668𝑁𝑚𝑚

𝑀 =𝑀 +𝑀 +𝑀 = 13.000 + −9.032.690 + 39.024.421.668 = 39.015.401.978𝑁𝑚𝑚


= 39015𝑘𝑁𝑚

Yield moment for composite section in negative flexure:

𝑀 = 13.000𝑁𝑚𝑚

𝑀 = −9.032.690𝑁𝑚𝑚

𝑀 𝑀
𝑀 = 𝑓 + + 𝑆
𝑆 𝑆
13.000 −9.032.690
= 344,7 + + × 82.575.324 = 28.457.823.471𝑁𝑚𝑚
82.575.324 82.575.324

𝑀 𝑀
𝑀 = 𝑓 + + 𝑆
𝑆 𝑆
13.000 −9.032.690
= 344,7 + + × 62.758.345 = 21.626.159.902𝑁𝑚𝑚
62.758.345 62.758.345

𝑀 = 𝑚𝑖𝑛 𝑀 ;𝑀 = 𝑚𝑖𝑛(28.457.823.471; 21.626.159.902) = 21.626.159.902𝑁𝑚𝑚


Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

𝑀 = −𝑀 −𝑀 +𝑀 = −(13.000) − (−9.032.690) + 21.626.159.902


= 21.635.179.592𝑁𝑚𝑚 = 21635𝑘𝑁𝑚

𝑀 = −𝑀 − 𝑀 + 𝑀 = −(13.000) − (−9.032.690) + 21.626.159.902


= 21.635.179.592𝑁𝑚𝑚 = 21635𝑘𝑁𝑚

𝑀 = −𝑀 − 𝑀 + 𝑀 = −(13.000) − (−9.032.690) + 28.457.823.471


= 28.466.843.161𝑁𝑚𝑚 = 28467𝑘𝑁𝑚

Flange strength reduction hybrid factor Rh for negative flexure:

𝑆𝑖𝑛𝑐𝑒 𝑓 = 344,7𝑀𝑃𝑎 ≥ max 𝑓 = 344,7𝑀𝑃𝑎; 𝑓 = 344,7𝑀𝑃𝑎 = 344,7𝑀𝑃𝑎 => 𝑅 =1

Web load shedding factor. Per C6.10.1.10.2 RbPos for positive moment in composite sections is equal to
1.0. Calculate RbNeg for negative flexure per 6.10.1.10.2-3. DcNegi is converted from vertical distance to
inclined distance measured along the web.

𝐷 530
𝐷 = = = 540𝑚𝑚
cos ∝ cos 11,2

𝐸 199948
𝜆 = 5.7 = 5.7 × = 137,27
𝑓 344,7

2𝐷 𝑡 2 × 540 × 25
𝑎 = = = 0,44
𝑏 𝑡 1219 × 51

𝑎 2𝐷
𝑅 = 𝑚𝑖𝑛 1.0; 1 − −𝜆
1200 + 300𝑎 𝑡
0,44 2 × 540
= 𝑚𝑖𝑛 1.0; 1 − − 137,27 = 1,000
1200 + 300 × 0,44 25

Classify section for positive bending per 6.10.6.2.2. DcpPosi is converted from vertical distance to inclined
distance measured along the web.

𝐷 𝑦𝑒𝑙𝑙𝑜𝑤
𝐷 = = = 110𝑚𝑚
cos? cos 𝑂. 𝐾.
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

a) Bridge is not kinked (chorded) continuous or horizontally curved O.K.

𝑏) 𝑚𝑎𝑥 𝑓 ; 𝑓 = 𝑚𝑎𝑥(344,7; 344,7) = 344,7 ≤ 482,6𝑀𝑃𝑎 O.K.

×
𝑐) = = 8,65 ≤ 3.76 = 3.76 = 90,55 O.K.
,

𝑑) = = 48,93 ≤ 150 O.K.

e) Number of boxes in cross section satisfies LRFD Article 6.11.2.3 O.K.

» Section is classified as compact for positive flexure

>> St. Venant torsional shear stress shall be considered

Flexural Resistance - Composite Section in Positive Flexure

Compact Section - Nominal Flexural Resistance per 6.10.7.1.2

𝐷
𝑠𝑖𝑛𝑐𝑒 𝐷 = 488𝑚𝑚 > 0.1𝐷 = 0.1 × 1650 = 165𝑚𝑚 => 𝑀 = 𝑀 1.07 − 0.7
𝐷
488
= 45872,4 × 1.07 − 0.7 × = 39591,9𝑘𝑁𝑚
1650
𝑚𝑎𝑥(0; 𝑀 ) 197.904.260
𝐷𝑜𝑣𝑒𝑟𝐶 = = = 0,00 ≤ 1
𝜙 𝑀 1,00 × 39.591.894.830

O.K.

Flexural Resistance - Composite Section in Negative Flexure

Resistance of continuously braced top flange in tension per 6.11.8.1.2

𝑃 𝑀 𝑀 𝑀
𝑓 = 𝑚𝑎𝑥 0; − − −
𝐴 𝑆 𝑆 𝑆
−605.440 −15.509.518 0 −273.919.450
= 𝑚𝑎𝑥 0; − − − = 3,7𝑀𝑃𝑎
163782 62758345 62758345 62758345
𝑓 3,7
𝐷𝑜𝑣𝑒𝑟𝐶 = = = 0,011
𝜙 𝑅 𝑓 1,00 × 1,00 × 344,7
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

Resistance of unstiffened bottom flange in compression per 6.11.8.2.2

𝑇 −605.440.170
𝑓 = = = −3,27𝑀𝑃𝑎
2𝐴 𝑡 2 × 1823850 × 51

eq. 6.11.8.2.2-12

𝑓 −3,27
∆= 1− = 1− = 1,00
𝑓 344,7

eq. 6.11.8.2.2-11

𝐹 = min 𝑓 ; (∆ − 0.3)𝑓 = min(344,7 ; (1,00 − 0.3) × 344,7) = 241,27𝑀𝑃𝑎

eq. 6.11.8.2.2-13

𝑏 1143,0
𝜆 = = = 22,50
𝑡 50,8

eq. 6.11.8.2.2-8

𝐸𝑘 199948 × 4.0
𝜆 = 0.57 = = 27,46
𝑓 ∆ 344,7 × 1,00

eq. 6.11.8.2.2-9

𝐸𝑘 199948 × 4.0
𝜆 = 0.95 = 0.95 = 54,70
𝐹 241,27

eq. 6.11.8.2.2-10

𝑆𝑖𝑛𝑐𝑒 𝜆 = 22,50 ≤ 𝜆 = 27,46 => 𝐹 =𝑅 𝑅 𝑓 ∆= 1,00 × 1,00 × 344,7 × 1,00


= 344,69𝑀𝑃𝑎

eq. 6.11.8.2.2-2

𝐸𝑘 199947,98 × 5,34
𝑆𝑖𝑛𝑐𝑒 𝜆 = 22,50 ≤ 1.12 = 1.12 = 62,33 => 𝐹 = 0.58𝑓 = 0.58 × 345
𝑓 345
= 199,95𝑀𝑃𝑎
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

eq. 6.11.8.2.2-5

𝑓 −3,27
𝐹 =𝐹 1− = 344,69 × 1 − = 344,65
𝜙 𝐹𝑐𝑣 1,00 × 199,95

eq. 6.11.8.2.2-1

𝑃 𝑀 𝑀 𝑀
𝑓 = 𝑚𝑖𝑛 0; + + +
𝐴 𝑆 𝑆 𝑆
−154.499 −15.509.518 0 −273.919.450
= 𝑚𝑖𝑛 0 ; + + + = −4,4𝑀𝑃𝑎
163782 82575324 82575324 82575324
𝑓𝑏𝑢𝐵𝑜𝑡 −4,4
𝐷𝑜𝑣𝑒𝑟𝐶𝑁𝑒𝑔𝐵𝑜𝑡 = = = 0,013
𝜙𝑓 𝐹𝑛𝑐 1,00 × 344,65

Controlling demand over capacity ratio for composite section in negative flexure

𝐷𝑜𝑣𝑒𝑟𝐶𝑁𝑒𝑔 = 𝑚𝑎𝑥 𝐷𝑜𝑣𝑒𝑟𝐶𝑁𝑒𝑔𝑇𝑜𝑝 ; 𝐷𝑜𝑣𝑒𝑟𝐶𝑁𝑒𝑔𝐵𝑜𝑡 = 𝑚𝑎𝑥(0,011 ; 0,013) = 0,013 ≤ 1.0


O.K.

Shear Resistance per 6.10.9.

As defined in the design request parameters the web panel does not have longitudinal stiffener. A web
panel is defined as section of the web between adjacent diaphragms or supports. A web subpanel length
is defined as a distance between adjacent transverse stiffeners or a distance between panel end and
adjacent transverse stiffener. If transverse stiffeners are not present the sub panel length is equal to the
panel length.

The length of the sub panel is d0=5500mm. This length does not satisfy criteria for stiffened end panels
per 6.10.9.1 and the panel is therefore classified as unstiffened. The shear resistance is evaluated per
6.10.9.2.

5 5
𝑘 =5+ = 5+ = 5,00; 𝑢𝑠𝑒 𝑘 = 5 𝑓𝑜𝑟 𝑢𝑛𝑠𝑡𝑖𝑓𝑓𝑒𝑛𝑒𝑑 𝑤𝑒𝑏𝑠 𝑝𝑒𝑟 6.10.9.2
𝑑 5500
𝐷 1243

𝐷 1243 𝐸𝑘 199948,0 × 5,00


𝑆𝑖𝑛𝑐𝑒 = = 48,93 ≤ 1.12 = 1.12 × = 60,31 => 𝐶 = 1.0
𝑡 25 𝑓 344,7

Convert St. Venant shear torsional stress into shear force Vtor.
Designer: ___; Date: Oct 23 2019
Project: _______________ Checker: ___; Date: Oct 23 2019
Item: Superstructure Ultimate Design; Request Name: Strength
Section Cut No. 1; Station: 0m; Location: After; Left Exterior Girder

𝑇 605.440.170
𝑓 = = = 6,5𝑘𝑠𝑖
2𝐴 𝑡 2 × 1823850 × 25

𝑉 = 𝑓 𝐷𝑡 = 6,5 × 1243 × 25 = 206.286𝑘𝑖𝑝

𝑉 = 0.58𝑓 𝐷𝑡 = 0.58 × 344,7 × 1243 × 25/1000 = 6312,0𝑘𝑁

𝑉 +𝑉 1969,4 + 206,3
𝐷𝑜𝑣𝑒𝑟𝐶 = = = 0,34 ≤ 1.0
𝜙 𝐶𝑉 1,00 × 1,00 × 6312,0
O.K.