Documente Academic
Documente Profesional
Documente Cultură
This wiring diagram describes models of the VES A and H Series Elite RS and eLAN RS Panel. All models of the A Series
Elite RS and eLAN RS Panel support Apollo loop protocol. All models of the H Series Elite RS and eLAN RS Panel
support Hochiki loop protocol. All models provide 1 and 2 loop operation.
Reference Wiring Diagram Models for part numbers and descriptions of all fire control panels included in this document.
The operation of this product is intended for indoor use only.
Contents
Fascia View
The figure below illustrates the fascia view of the Elite RS and eLAN RS Panel:
Figure 1-1
Elite RS and eLAN RS Fascia View
38 39 40 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R
P2R
L1R
L2R
P1T
P2T
L1T
L2T
E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -
24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN
Supervisory JP1
Delay Active
Enable Access
Re-Sound Alarm Panel Sounder Lamp Programmable More More
Reset Fire Drill
Alarm Silence Silence Test Function Fire Events Events
PC
PC / Dialer Reset Watchdog Watchdog Contrast
Operated Reset
Battery
Connection AC POWER
+ - L N E
Wire Gauge
Connect 18 to 14 AWG wiring for all field terminations except the AC input. Connect 14 AWG wiring for line, neutral and
ground terminations of the AC input.
Related Documentation
The following documents shall be used to provide additional information for installing and operating A and H series
models of the Elite RS and eLAN RS Panel:
A Series Documents
• Elite RS Panel Installation Manual, A Series, VF3532-00, Rev. E01.XX
• Operating Instructions, A Series, VF3535-00, Rev. E01.XX
• Door Label, A Series, VF3534-00, Rev. E01.XX
H Series Documents
• Elite RS Panel Installation Manual, H Series, VF3529-00, Rev. E01.XX
• Operating Instructions, H Series, VF3535-00, Rev. E01.XX
• Door Label, H Series, VF3534-00, Rev. E01.XX
File: S8485, Part Number: VF3731-00
Revision E01.03, Date: 5/8/2014 2 of 9
Wiring Diagram - Elite RS and eLAN RS Panels
Connection Diagram
The figure below illustrates the connection diagram of the Elite RS and eLAN RS Panel:
Figure 1-2
Elite RS and eLAN RS Connection Diagram
NAC 2 Network
TELCO 2 10K EOL Resistor IN
VF1544-00
AUX 24V
Relays
24 VDC
38 39 40 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R
P2R
L1R
L2R
P1T
P2T
L1T
L2T
E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -
24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN
Elite RS Models
This section describes A and H Series models of the Elite RS Panel.
A Series Models
One loop A Series models include the No Communication VF0850, the Non-Expandable, No Communication VF0870, the
eNet Interface VF0855, the Integrated Dialer VF0856, the Non-Expandable, Integrated Dialer VF0876 and the eNet
Interface & Integrated Dialer VF0857.
Two loop A Series models include the No Communication with Loop Expansion Module VF0860, the eNet Interface with
the Loop Expansion Module VF0865, the Integrated Dialer with the Loop Expansion Module VF0866 and the eNet
Interface & Integrated Dialer with the Loop Expansion Module VF0867.
H Series Models
One loop Hochiki models include the No Communication VF0810, the Non-Expandable, No Communication VF0830, the
Integrated Dialer VF0816, the Non-Expandable, Integrated Dialer VF0836 and the eNet Interface & Integrated Dialer
VF0817.
Two loop Hochiki models include the No Communication with Loop Expansion Module VF0820, the eNet Interface
VF0825, the Integrated Dialer VF0826 and the eNet Interface & Integrated Dialer VF0827.
eLAN RS Models
This section describes A and H Series models of the eLAN RS Panel.
A Series Models
One loop models include the No Communication VF0950, the Non-Expandable, No Communication VF0970, the eNet
Interface VF0955, the Integrated Dialer VF0956, the Non-Expandable, Integrated Dialer VF0976 and the eNet Interface
& Integrated Dialer VF0957.
Two loop models include the No Communication with Loop Expansion Module VF0960, the eNet Interface with the
Loop Expansion Module VF0965, the Integrated Dialer with the Loop Expansion Module VF0966 and the eNet
Interface & Integrated Dialer with the Loop Expansion Module VF0967.
H Series Models
One loop models include the No Communication VF0910, the Non-Expandable, No Communication VF0930, the eNet
Interface VF0915, the Integrated Dialer VF0916, the Non-Expandable, Integrated Dialer VF0936 and the eNet Interface
& Integrated Dialer VF0917.
Two loop models include the No Communication with Loop Expansion Module VF0920, the eNet Interface VF0925, the
Integrated Dialer VF0926 and the eNet Interface & Integrated Dialer VF0927.
Line Connection
N AC Neutral
G Earth Ground
Power Supply
Parameter Description
Parameter Description
Standby-Battery Type Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries
Supervised Circuits
All circuits of the Elite RS Panel are supervised except relay terminals for TROUBLE, FIRE, SUPERVISORY and
TELCO.
Terminals of 24 V OUT and AUX 24 V are not supervised for open circuit conditions, but are supervised for ground faults
and short circuits.
Terminals Description
SLC1 IN, SLC1 OUT Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
and SLC2 IN, SLC2 OUT Style 4.
Parameter Description
Regulated Continuous Current Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.
Regulated Pulsed Current: Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.
Special Application 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.
Synchronization Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device VF1539-00 to the output of each
Synchronization Module installed.
The Elite-RS Panel provides internal device synchronization between the
outputs of NAC 1 and NAC 2 when operating NAC devices from Gentex,
Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.
Communication Circuits
Phone Line Connections
Terminal Description
Terminal Rating
eNET Terminals
Terminal Rating
Relay Circuits
Parameter Description
Operation Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).
Terminal Description