Sunteți pe pagina 1din 9

Wiring Diagram - Elite RS and eLAN RS Panels

Wiring Diagram: Elite RS and eLAN RS Panels


Connections and specifications for all A and H series models VF3731-00

This wiring diagram describes models of the VES A and H Series Elite RS and eLAN RS Panel. All models of the A Series
Elite RS and eLAN RS Panel support Apollo loop protocol. All models of the H Series Elite RS and eLAN RS Panel
support Hochiki loop protocol. All models provide 1 and 2 loop operation.
Reference Wiring Diagram Models for part numbers and descriptions of all fire control panels included in this document.
The operation of this product is intended for indoor use only.

Contents

Fascia View .................................................... 2 Power Output Circuits ............................... 6

Wire Gauge .................................................... 2 Limited Energy Circuits ............................. 6

Related Documentation ............................ 2 Supervised Circuits .................................... 6

A Series Documents ................................... 2 Signaling Line Circuits .............................. 6


H Series Documents ................................... 2 Notification Appliance Circuit ................ 7
Connection Diagram .................................. 3 NAC Output Parameters ............................. 7

Elite RS Models ............................................ 3 Maximum Current Ratings .......................... 7


Single and Dual Circuit Synchronization ..7
A Series Models .......................................... 3
H Series Models .......................................... 3 Communication Circuits ........................... 8

eLAN RS Models .......................................... 4 Phone Line Connections ............................ 8


RS485 Serial Bus ......................................... 8
A Series Models .......................................... 4
eNET Terminals ............................................ 8
H Series Models .......................................... 4
Relay Circuits ................................................ 9
Main Supply Circuit .................................... 4
Line Connection .......................................... 4
24V OUT and AUX 24V ............................... 9
Power Supply .............................................. 5 If You Need Help ........................................... 9
Rechargeable Battery Circuit ................. 5
Ground Fault Indications ......................... 6

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 1 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Fascia View
The figure below illustrates the fascia view of the Elite RS and eLAN RS Panel:
Figure 1-1
Elite RS and eLAN RS Fascia View

38 39 40 41

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R

P2R
L1R

L2R
P1T

P2T
L1T

L2T

E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -

24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN

Fire More Events


1
General
AC Power On
Disablement
4 ? 2
Pre-Alarm General Trouble

On Test Power Trouble 3

Supervisory JP1
Delay Active

AC Power On NAC Trouble Exit Enter

Enable Access
Re-Sound Alarm Panel Sounder Lamp Programmable More More
Reset Fire Drill
Alarm Silence Silence Test Function Fire Events Events

PC
PC / Dialer Reset Watchdog Watchdog Contrast
Operated Reset

Battery
Connection AC POWER
+ - L N E

Wire Gauge
Connect 18 to 14 AWG wiring for all field terminations except the AC input. Connect 14 AWG wiring for line, neutral and
ground terminations of the AC input.

Related Documentation
The following documents shall be used to provide additional information for installing and operating A and H series
models of the Elite RS and eLAN RS Panel:

A Series Documents
• Elite RS Panel Installation Manual, A Series, VF3532-00, Rev. E01.XX
• Operating Instructions, A Series, VF3535-00, Rev. E01.XX
• Door Label, A Series, VF3534-00, Rev. E01.XX

H Series Documents
• Elite RS Panel Installation Manual, H Series, VF3529-00, Rev. E01.XX
• Operating Instructions, H Series, VF3535-00, Rev. E01.XX
• Door Label, H Series, VF3534-00, Rev. E01.XX
File: S8485, Part Number: VF3731-00
Revision E01.03, Date: 5/8/2014 2 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Connection Diagram
The figure below illustrates the connection diagram of the Elite RS and eLAN RS Panel:
Figure 1-2
Elite RS and eLAN RS Connection Diagram

Earth Ground NAC 1 SLC 1 SLC 2


10K EOL Resistor Zero-Ohm Resistor Zero-Ohm Resistor
VF1544-00 VF1544-00 VF1544-00
TELCO 1

NAC 2 Network
TELCO 2 10K EOL Resistor IN
VF1544-00

24V OUT Network Comms


24 VDC OUT RS485

AUX 24V
Relays
24 VDC

38 39 40 41

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R

P2R
L1R

L2R
P1T

P2T
L1T

L2T

E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -

24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN

Elite RS Models
This section describes A and H Series models of the Elite RS Panel.

A Series Models
One loop A Series models include the No Communication VF0850, the Non-Expandable, No Communication VF0870, the
eNet Interface VF0855, the Integrated Dialer VF0856, the Non-Expandable, Integrated Dialer VF0876 and the eNet
Interface & Integrated Dialer VF0857.
Two loop A Series models include the No Communication with Loop Expansion Module VF0860, the eNet Interface with
the Loop Expansion Module VF0865, the Integrated Dialer with the Loop Expansion Module VF0866 and the eNet
Interface & Integrated Dialer with the Loop Expansion Module VF0867.

H Series Models
One loop Hochiki models include the No Communication VF0810, the Non-Expandable, No Communication VF0830, the
Integrated Dialer VF0816, the Non-Expandable, Integrated Dialer VF0836 and the eNet Interface & Integrated Dialer
VF0817.
Two loop Hochiki models include the No Communication with Loop Expansion Module VF0820, the eNet Interface
VF0825, the Integrated Dialer VF0826 and the eNet Interface & Integrated Dialer VF0827.

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 3 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

eLAN RS Models
This section describes A and H Series models of the eLAN RS Panel.

A Series Models
One loop models include the No Communication VF0950, the Non-Expandable, No Communication VF0970, the eNet
Interface VF0955, the Integrated Dialer VF0956, the Non-Expandable, Integrated Dialer VF0976 and the eNet Interface
& Integrated Dialer VF0957.
Two loop models include the No Communication with Loop Expansion Module VF0960, the eNet Interface with the
Loop Expansion Module VF0965, the Integrated Dialer with the Loop Expansion Module VF0966 and the eNet
Interface & Integrated Dialer with the Loop Expansion Module VF0967.

H Series Models
One loop models include the No Communication VF0910, the Non-Expandable, No Communication VF0930, the eNet
Interface VF0915, the Integrated Dialer VF0916, the Non-Expandable, Integrated Dialer VF0936 and the eNet Interface
& Integrated Dialer VF0917.
Two loop models include the No Communication with Loop Expansion Module VF0920, the eNet Interface VF0925, the
Integrated Dialer VF0926 and the eNet Interface & Integrated Dialer VF0927.

Main Supply Circuit


The main supply circuit includes specifications for the line connection and the power supply:

Line Connection

Terminals Description Voltage Current

L AC Line 115 VAC @ 50/60 Hz 2.1 A max

230 VAC @ 50/60 Hz 1.1 A max

N AC Neutral

G Earth Ground

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 4 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Power Supply

Parameter Description

Rating 115 VAC @ 250 VA


230 VAC @ 250 VA

AC Input Fuse 3 A, 250 VAC, Slow-Blow, 5 x 20 mm

Input (Supervised) 115 VAC 50/60 Hz or


230 VAC 50/60 Hz

Transfer Voltage 115 VAC transfer @ 75 VAC,


230 VAC transfer @ 160 VAC

Rechargeable Battery Circuit

Parameter Description

Standby-Battery Type Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries

Standby-Battery Charging Two standby batteries wired in series

Charge Current Fast charge: 1.25 A


Trickle charge: 1.25 A (voltage limited)

Output Current 0 - 4 Amps

Standby-Operating Time 24 Hours

Battery Charge Voltage 27.6 VDC

Maximum Current Draw 4 Amps


From Batteries

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 5 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Ground Fault Indications


A ground fault indication occurs when 30K Ohms or less exists between earth-ground and the following field terminals of
the Elite RS Panel:
• 24V OUT
• AUX 24V
• NAC 1and NAC 2
• SLC1 and SLC2
• NET
• COMMS

Power Output Circuits


Special application outputs are provided on the NAC 1 and NAC 2 terminals of the Elite RS Panel:

Limited Energy Circuits


All circuits of the Elite RS Panel are power limited except AC input/output and battery.

Supervised Circuits
All circuits of the Elite RS Panel are supervised except relay terminals for TROUBLE, FIRE, SUPERVISORY and
TELCO.
Terminals of 24 V OUT and AUX 24 V are not supervised for open circuit conditions, but are supervised for ground faults
and short circuits.

Signaling Line Circuits


Authorized Signaling Line Circuits of this Fire Control Panel operate Apollo or Hochiki loop protocol.

Terminals Description

SLC1 IN, SLC1 OUT Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
and SLC2 IN, SLC2 OUT Style 4.

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 6 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Notification Appliance Circuit


The Elite RS Fire Control provides operation of Notification Appliance Circuits on the terminals of NAC 1 and NAC 2.

NAC Output Parameters

Parameter Description

Fuse Self-resetting 1.6 A electronic

Regulated Continuous Current Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.

Regulated Pulsed Current: Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.

Special Application 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.

Supervision EOL Device, VF1539-00

Synchronization Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device VF1539-00 to the output of each
Synchronization Module installed.
The Elite-RS Panel provides internal device synchronization between the
outputs of NAC 1 and NAC 2 when operating NAC devices from Gentex,
Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.

NFPA Operation Type Class B, Style Y

Maximum Current Ratings


The total sum of device loads in the NAC circuit must not exceed the maximum current specified for the Elite RS Panel
when operating in Continuous Regulated, Pulsed regulated or Special Application mode.
Reference NAC manufacturer data sheets for individual device loads and then compare the total sum to the maximum
current capability of the Elite RS Panel in regulated or special application mode.

Single and Dual Circuit Synchronization


NAC channels 1 and 2 of the Elite RS Panel provide single and dual circuit synchronization. Single circuit synchronization
provides a synchronized output on one of two NAC channels. Dual circuit synchronization provides a synchronized output
on both NAC channels.

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 7 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Communication Circuits
Phone Line Connections

Terminal Description

L1T TELCO Line 1 Tip

L1R TELCO Line 1 Ring

P1T TELCO Phone 1 Tip

P1R TELCO Phone 1 Ring

L2T TELCO Line 2 Tip

L2R TELCO Line 2 Ring

P2T TELCO Phone 2 Tip

P2R TELCO Phone 2 Ring

RS485 Serial Bus

Terminal Rating

COMMS (+) (+) Data 3.3 VDC @ 30 mA max

COMMS (-) (-) Data

eNET Terminals

Terminal Rating

NET OUT (+) (+) Data 3.3 VDC @ 30 mA max

NET OUT (-) (-) Data

NET IN (+) (+) Data 3.3 VDC @ 30 mA max

NET IN (-) (-) Data

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 8 of 9
Wiring Diagram - Elite RS and eLAN RS Panels

Relay Circuits

Parameter Description

Operation Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).

Current 1A maximum, volt free change over contact

Voltage 30 VDC max

Power Factor 1.0 PF

24V OUT and AUX 24V

Terminal Description

24V OUT Regulated 24 VDC @ 360 mA max

AUX 24V Regulated 24 VDC @ 360 mA max

If You Need Help


If you need technical support contact VES at (800) 274 - 9514 or e-mail techsupport@ves-network.com. VES technical
support is available Monday through Friday, 9:00 AM to 6:00 PM, Eastern Standard Time.

File: S8485, Part Number: VF3731-00


Revision E01.03, Date: 5/8/2014 9 of 9