SPECIFICATION

SIEMENS MTO ITEM No.: E6


INSTRUMENT CABLE:1P X 1.5 mm2
CU/MT/XLPE/OS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
No. of Pairs 1 Insulation: Black、White
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2
Fire Barrier Tape Performance
Material: Mica Tape Electrical characteristics
100% wrapping over the conductor 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.1
Insulation 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Material: XLPE 3.Spark test A.C. voltage value(kV): 6
Nom. Thickness(mm): 0.6 4.A.C. high voltage test for 1min(kV): 2.0
Approx. Dia. over insulation(mm): 3.7 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Binder tape 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Material: Mylar-tape
100% wrapping over the assembly
Drain wire
Material: Tinned copper wire
Cross-Sectional Area(mm2): 0.5 Physical characteristics
Overall Screen 1.Min. bending radius(mm)
Material: Al-foil(Al layer inside) a)during installation: 194
100% wrapping over the mylar tape b)after installation: 162
Bedding 2.Max. pulling tension for conductor(kN): 0.315
Material: LSZH 3.Construction test: AS/NZS 5000.3
Nom. Thickness(mm): 0.9 4.Fire resistant test: IEC 60331
Approx. Dia. over bedding(mm): 10.8 AS/NZS 1660.5.5
Armour 5.Flame retardant test: IEC 60332-3-22
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 0.9
Approx. Dia. over armour(mm): 12.6
Outer Sheath Packing information
Material: LSZH 1.Max. length per drum(m): 200
Nom. Thickness(mm): 1.3 2.Drum size(H x W x L)(mm): 710 x 400 x 710
Min. Thickness(mm): 0.84 3.Gross weight per drum(kg): 140
Approx. Dia. of cable(mm): 16.2
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 425.0
Order Quantity(m): 200
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-33A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: E2
INSTRUMENT CABLE:2P X 1.5 mm2
CU/MT/XLPE/ISOS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
No. of Pairs 2 Insulation: Black、White with numbering
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2 Performance
Fire Barrier Tape Electrical characteristics
Material: Mica Tape 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
100% wrapping over the conductor 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Insulation 3.Spark test A.C. voltage value(kV): 6
Material: XLPE 4.A.C. high voltage test for 1min(kV): 2.0
Nom. Thickness(mm): 0.6 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Approx. Dia. over insulation(mm): 3.7 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Individual Screen
Material: Al-foil(Al layer inside)
100% wrapping over the individual pair
Drain wire
Material: Tinned copper wire
Cross-Sectional Area(mm2): 0.5 Physical characteristics
Overall Screen 1.Min. bending radius(mm)
Material: Al-foil(Al layer inside) a)during installation: 289
100% wrapping over the mylar tape b)after installation: 241
Bedding 2.Max. pulling tension for conductor(kN): 0.420
Material: LSZH 3.Construction test: AS/NZS 5000.3
Nom. Thickness(mm): 1.1 4.Fire resistant test: IEC 60331
Approx. Dia. over bedding(mm): 17.7 AS/NZS 1660.5.5
Armour 5.Flame retardant test: IEC 60332-3-22
Material: Galvanized steel wire
Dia. of Armour wire: 1.25
Approx. Dia. over braid(mm): 20.2
Outer Sheath
Material: LSZH Packing information
Nom. Thickness(mm): 1.5 1.Max. cable length per drum(m): 800
Min. Thickness(mm): 1.00 2.Drum size(H x W x L)(mm): 1250 x 710 x 1250
Approx. Dia. of cable(mm): 24.1 3.Gross weight per drum(kg): 830
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 900.0
Order Quantity(m): 800
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-34A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: E3
INSTRUMENT CABLE:8P X 1.5 mm2
CU/MT/XLPE/ISOS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
No. of Pairs 8 Insulation: Black、White with numbering
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2 Performance
Fire Barrier Tape Electrical characteristics
Material: Mica Tape 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
100% wrapping over the conductor 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Insulation 3.Spark test A.C. voltage value(kV): 6
Material: XLPE 4.A.C. high voltage test for 1min(kV): 2.0
Nom. Thickness(mm): 0.6 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Approx. Dia. over insulation(mm): 3.7 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Individual Screen
Material: Al-foil(Al layer inside)
100% wrapping over the individual pair
Drain wire
Material: Tinned copper wire
Cross-Sectional Area(mm2): 0.5 Physical characteristics
Overall Screen 1.Min. bending radius(mm)
Material: Al-foil(Al layer inside) a)during installation: 436
100% wrapping over the mylar tape b)after installation: 363
Bedding 2.Max. pulling tension for conductor(kN): 1.680
Material: LSZH 3.Construction test: AS/NZS 5000.3
Nom. Thickness(mm): 1.3 4.Fire resistant test: IEC 60331
Approx. Dia. over bedding(mm): 28.3 AS/NZS 1660.5.5
Armour 5.Flame retardant test: IEC 60332-3-22
Material: Galvanized steel wire
Dia. of Armour wire: 1.6
Approx. Dia. over braid(mm): 31.5
Outer Sheath
Material: LSZH Packing information
Nom. Thickness(mm): 1.7 1.Max. cable length per drum(m): 700
Min. Thickness(mm): 1.16 2.Drum size(H x W x L)(mm): 1800 x 1120 x 1800
Approx. Dia. of cable(mm): 36.3 3.Gross weight per drum(kg): 1510
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 1960.0
Order Quantity(m): 700
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-35A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: E4
INSTRUMENT CABLE:12P X 1.5 mm2
CU/MT/XLPE/ISOS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
No. of Pairs 12 Insulation: Black、White with numbering
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2 Performance
Fire Barrier Tape Electrical characteristics
Material: Mica Tape 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
100% wrapping over the conductor 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Insulation 3.Spark test A.C. voltage value(kV): 6
Material: XLPE 4.A.C. high voltage test for 1min(kV): 2.0
Nom. Thickness(mm): 0.6 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Approx. Dia. over insulation(mm): 3.7 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Individual Screen
Material: Al-foil(Al layer inside)
100% wrapping over the individual pair
Drain wire
Material: Tinned copper wire
Cross-Sectional Area(mm2): 0.5 Physical characteristics
Overall Screen 1.Min. bending radius(mm)
Material: Al-foil(Al layer inside) a)during installation: 510
100% wrapping over the mylar tape b)after installation: 425
Bedding 2.Max. pulling tension for conductor(kN): 2.520
Material: LSZH 3.Construction test: AS/NZS 5000.3
Nom. Thickness(mm): 1.5 4.Fire resistant test: IEC 60331
Approx. Dia. over bedding(mm): 33.6 AS/NZS 1660.5.5
Armour 5.Flame retardant test: IEC 60332-3-22
Material: Galvanized steel wire
Dia. of Armour wire: 1.6
Approx. Dia. over braid(mm): 36.8
Outer Sheath
Material: LSZH Packing information
Nom. Thickness(mm): 1.8 1.Max. cable length per drum(m): 500
Min. Thickness(mm): 1.24 2.Drum size(H x W x L)(mm): 1600 x 900 x 1600
Approx. Dia. of cable(mm): 42.5 3.Gross weight per drum(kg): 1900
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 2500.0
Order Quantity(m): 500
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-36A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: D5
INSTRUMENT CABLE:12T X 1.5 mm2
CU/MT/XLPE/ISOS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
No. of Triads 12 Insulation: Red、Black、White with numbering
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2 Performance
Fire Barrier Tape Electrical characteristics
Material: Mica Tape 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
100% wrapping over the conductor 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Insulation 3.Spark test A.C. voltage value(kV): 6
Material: XLPE 4.A.C. high voltage test for 1min(kV): 2.0
Nom. Thickness(mm): 0.6 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Approx. Dia. over insulation(mm): 3.7 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Individual Screen
Material: Al-foil(Al layer inside)
100% wrapping over the individual triad
Drain wire
Material: Tinned copper wire
Cross-Sectional Area(mm2): 0.5 Physical characteristics
Overall Screen 1.Min. bending radius(mm)
Material: Al-foil(Al layer inside) a)during installation: 574
100% wrapping over the mylar tape b)after installation: 478
Bedding 2.Max. pulling tension for conductor(kN): 2.520
Material: LSZH 3.Construction test: AS/NZS 5000.3
Nom. Thickness(mm): 1.6 4.Fire resistant test: IEC 60331
Approx. Dia. over bedding(mm): 37.8 AS/NZS 1660.5.5
Armour 5.Flame retardant test: IEC 60332-3-22
Material: Galvanized steel wire
Dia. of Armour wire: 2.0
Approx. Dia. over braid(mm): 41.8
Outer Sheath
Material: LSZH Packing information
Nom. Thickness(mm): 1.9 1.Max. cable length per drum(m): 300
Min. Thickness(mm): 1.32 2.Drum size(H x W x L)(mm): 1600 x 1000 x 1600
Approx. Dia. of cable(mm): 47.8 3.Gross weight per drum(kg): 1140
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 3400.0
Order Quantity(m): 300
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-37A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: D6
2
CONTOL CABLE: 4C X 4 mm
CU/MT/XLPE/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.5
IEC 60331、IEC 60332-3-22
Cable Construction Color
Insulation: White with black numbering
No. of Cores 4
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 6 Outer sheath: Red(UV-Stabilised)
Approx. Conductor Dia.(mm): 3.12 Performance
Class of Conductor: Class 2 Electrical characteristics
Fire Barrier Tape 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 4.61
Material: Mica Tape 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
100% wrapping over the conductor 3.Spark test A.C. voltage value(kV): 6
Insulation 4.A.C. high voltage test for 5min(kV): 3.5
Material: XLPE
Nom. Thickness(mm): 0.7
Approx. Dia. over insulation(mm): 4.9
Bedding
Material: LSZH Physical characteristics
Nom. Thickness(mm): 1.0 1.Min. bending radius(mm)
Approx. Dia. over bedding(mm): 15.2 a)during installation: 240
Armour b)after installation: 200
Materia of Armour: Galvanized steel wire 2.Max. pulling tension for conductor(kN): 1.680
Dia. of Armour wire: 0.8 3.Construction test: AS/NZS 5000.3
Approx. Dia. over armour(mm): 16.8 4.Fire resistant test: IEC 60331
Outer Sheath AS/NZS 1660.5.5
Material: LSZH 5.Flame retardant test: IEC 60332-3-22
Nom. Thickness(mm): 1.4
Min. Thickness(mm): 0.92
Approx. Dia. of cable(mm): 20.0 Packing information
O.D. tolerance(%): ±8 1.Max. cable length per drum(m): 1500
Approx. weight of cable(kg/km): 695.0 2.Drum size(mm): 1400 x 710 x 1400
Order Quantity(m): 1500 3.Gross weight per drum(kg): 1160

Contact information Customer Approved By


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-38A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: D7
2
INSTRUMENT CABLE:1P X 1.5 mm
CU/XLPE/OS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Pairs 1 Insulation: Black、White


Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Light blue(UV-Stabilised)
Class of Conductor: Class 2
Insulation Performance
Material: XLPE Electrical characteristics
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.1
Approx. Dia. over insulation(mm): 2.9 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Drain wire 3.Spark test A.C. voltage value(kV): 6
Material: Tinned copper wire 4.A.C. high voltage test for 1min(kV): 2.0
Cross-Sectional Area(mm2): 0.5 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Binder tape 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Material: Mylar-tape
100% wrapping over the assembly
Overall Screen
Material: Al-foil(Al layer inside)
100% wrapping over the mylar tape Physical characteristics
Bedding 1.Min. bending radius(mm)
Material: LSZH a)during installation: 158
Nom. Thickness(mm): 0.9 b)after installation: 132
Armour 2.Max. pulling tension for conductor(kN): 0.210
Material of Armour: Galvanized steel wire 3.Construction test: AS/NZS 5000.3
Dia. of Armour wire: 0.9 4.Flame retardant test: IEC 60332-3-22
Outer Sheath
Material: LSZH
Nom. Thickness(mm): 1.3 Packing information
Min. Thickness(mm): 0.84 1.Max. cable length per drum(m): 800
Approx. Dia. of cable(mm): 13.2 2.Drum size(H x W x L)(mm): 900 x 450 x 900
O.D. tolerance(%): ±8 3.Gross weight per drum(kg): 320
Approx. weight of cable(kg/km): 320.0
Order Quantity(m): 800

Contact information Customer Approved by


Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-39A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: D13
2
INSTRUMENT CABLE:1T X 1.5 mm
CU/XLPE/OS/LSZH/SWA/LSZH,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Triads 1 Insulation: Red、Black、White


Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Red(UV-Stabilised)
Class of Conductor: Class 2
Insulation Performance
Material: XLPE Electrical characteristics
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.1
Approx. Dia. over insulation(mm): 2.9 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Drain wire 3.Spark test A.C. voltage value(kV): 6
Material: Tinned copper wire 4.A.C. high voltage test for 1min(kV): 2.0
Cross-Sectional Area(mm2): 0.5 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Binder tape 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Material: Mylar-tape
100% wrapping over the assembly
Overall Screen
Material: Al-foil(Al layer inside)
100% wrapping over the mylar tape Physical characteristics
Bedding 1.Min. bending radius(mm)
Material: LSZH a)during installation: 168
Nom. Thickness(mm): 0.9 b)after installation: 140
Armour 2.Max. pulling tension for conductor(kN): 0.315
Material of Armour: Galvanized steel wire 3.Construction test: AS/NZS 5000.3
Dia. of Armour wire: 0.9 4.Flame retardant test: IEC 60332-3-22
Outer Sheath
Material: LSZH
Nom. Thickness(mm): 1.3 Packing information
Min. Thickness(mm): 0.84 1.Max. cable length per drum(m): 1000
Approx. Dia. of cable(mm): 14.0 2.Drum size(H x W x L)(mm): 1000 x 560 x 1000
O.D. tolerance(%): ±8 3.Gross weight per drum(kg): 440
Approx. weight of cable(kg/km): 355.0
Order Quantity(m): 800

Contact information Customer Approved by


Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-40A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F47
CONTROL CABLE: 3C X 2.5 + E 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Active cores Earth core
No. of Cores 3 1 Insulation: White with black numbering(1~3) + Green/yellow
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) Active cores Earth core
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Approx. Dia. over insulation(mm): 3.3 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Outer Sheath 3.Spark test A.C. voltage value(kV): 6
Material: PVC(5V-90) 4.A.C. high voltage test for 5min(kV): 2.5
Nom. Thickness(mm): 1.3
Min. Thickness(mm): 1.01
Approx. Dia. of cable(mm): 11.5
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 190.0 1.Min. bending radius(mm)
Order Quantity(m): 700 a)during installation: 115
b)after installation: 92
2.Max. pulling tension for conductor(kN): 0.700
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 900
2.Drum size(H x W x L)(mm): 800 x 400 x 800
3.Gross weight per drum(kg): 240

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-41A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F11
CONTROL CABLE: 5C X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Cores 5 Insulation: White with black numbering


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 3.Spark test A.C. voltage value(kV): 6
Outer Sheath 4.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 1.3
Min. Thickness(mm): 1.01
Approx. Dia. of cable(mm): 13.0
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 230.0 1.Min. bending radius(mm)
Order Quantity(m): 2600 a)during installation: 130
b)after installation: 104
2.Max. pulling tension for conductor(kN): 0.875
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 2600
2.Drum size(H x W x L)(mm): 1400 x 900 x 1400
3.Gross weight per drum(kg): 330

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-42A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F3
CONTROL CABLE: 6C X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Cores 6 Insulation: White with black numbering


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 3.Spark test A.C. voltage value(kV): 6
Outer Sheath 4.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 1.3
Min. Thickness(mm): 1.01
Approx. Dia. of cable(mm): 14.5
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 265.0 1.Min. bending radius(mm)
Order Quantity(m): 400 a)during installation: 145
b)after installation: 116
2.Max. pulling tension for conductor(kN): 1.050
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 400
2.Drum size(H x W x L)(mm): 800 x 400 x 800
3.Gross weight per drum(kg): 170

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-43A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F4
CONTROL CABLE: 8C X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Cores 8 Insulation: White with black numbering


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 3.Spark test A.C. voltage value(kV): 6
Outer Sheath 4.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 1.4
Min. Thickness(mm): 1.09
Approx. Dia. of cable(mm): 15.2
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 340.0 1.Min. bending radius(mm)
Order Quantity(m): 2700 a)during installation: 152
b)after installation: 122
2.Max. pulling tension for conductor(kN): 1.400
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 2700
2.Drum size(H x W x L)(mm): 1400 x 710 x 1400
3.Gross weight per drum(kg): 1040

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-44A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F6
CONTROL CABLE: 12C X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Cores 12 Insulation: White with black numbering


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 3.Spark test A.C. voltage value(kV): 6
Outer Sheath 4.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 1.5
Min. Thickness(mm): 1.18
Approx. Dia. of cable(mm): 17.6
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 470.0 1.Min. bending radius(mm)
Order Quantity(m): 2600 a)during installation: 176
b)after installation: 141
2.Max. pulling tension for conductor(kN): 2.100
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 2600
2.Drum size(H x W x L)(mm): 1600 x 1000 x 2600
3.Gross weight per drum(kg): 1340

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-45A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F45
CONTROL CABLE: 2C X 2.5 + E 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Active cores Earth core
No. of Cores 2 1 Insulation: White with black numbering(1~2) + Green/yellow
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) Active cores Earth core
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Approx. Dia. over insulation(mm): 3.3 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Outer Sheath 3.Spark test A.C. voltage value(kV): 6
Material: PVC(5V-90) 4.A.C. high voltage test for 5min(kV): 2.5
Nom. Thickness(mm): 1.3
Min. Thickness(mm): 1.01
Approx. Dia. of cable(mm): 11.3
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 155.0 1.Min. bending radius(mm)
Order Quantity(m): 6000 a)during installation: 113
b)after installation: 90
2.Max. pulling tension for conductor(kN): 0.525
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 3000
2.Drum size(H x W x L)(mm): 1250 x 630 x 1250
3.Gross weight per drum(kg): 440

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-46A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F42
CONTROL CABLE: 4C X 2.5 + E 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Active cores Earth core
No. of Cores 4 1 Insulation: White with black numbering(1~4) + Green/yellow
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) Active cores Earth core
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Approx. Dia. over insulation(mm): 3.3 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Outer Sheath 3.Spark test A.C. voltage value(kV): 6
Material: PVC(5V-90) 4.A.C. high voltage test for 5min(kV): 2.5
Nom. Thickness(mm): 1.3
Min. Thickness(mm): 1.01
Approx. Dia. of cable(mm): 13.0
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 230.0 1.Min. bending radius(mm)
Order Quantity(m): 1500 a)during installation: 130
b)after installation: 104
2.Max. pulling tension for conductor(kN): 0.875
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 1500
2.Drum size(H x W x L)(mm): 1120 x 630 x 1120
3.Gross weight per drum(kg): 430

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-47A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F43
CONTROL CABLE: 8C X 2.5 + E 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Active cores Earth core
No. of Cores 8 1 Insulation: White with black numbering(1~8) + Green/yellow
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) Active cores Earth core
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Approx. Dia. over insulation(mm): 3.3 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Outer Sheath 3.Spark test A.C. voltage value(kV): 6
Material: PVC(5V-90) 4.A.C. high voltage test for 5min(kV): 2.5
Nom. Thickness(mm): 1.4
Min. Thickness(mm): 1.09
Approx. Dia. of cable(mm): 16.7
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 370.0 1.Min. bending radius(mm)
Order Quantity(m): 7200 a)during installation: 167
b)after installation: 134
2.Max. pulling tension for conductor(kN): 1.575
3.Construction test: AS/NZS 5000.3
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. length per drum(m): 2400
2.Drum size(H x W x L)(mm): 1600 x 1000 x 1600
3.Gross weight per drum(kg): 1020

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-48A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F48
CONTROL CABLE: 3C X 2.5 + E X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Active cores Earth core Insulation: White with black numbering(1~3) + Green/yellow
No. of Cores 3 1
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation Active cores Earth core
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 3.3 3.Spark test A.C. voltage value(kV): 6
Bedding 4.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 1.0
Approx. Dia. over bedding(mm): 10.4
Armour
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 0.8 Physical characteristics
Approx. Dia. over armour(mm): 12.1 1.Min. bending radius(mm)
Outer Sheath a)during installation: 156
Material: PVC(5V-90) b)after installation: 125
Nom. Thickness(mm): 1.3 2.Max. pulling tension for conductor(kN): 0.700
Min. Thickness(mm): 0.84 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 15.6 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. Weight of cable(kg/km): 430.0
Order Quantity(m): 700

Packing information
1.Max. length per drum(m): 700
2.Drum size(H x W x L)(mm): 1000 x 560 x 1000
3.Gross weight per drum(kg): 400

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-49A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F27
CONTROL CABLE: 4C X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Insulation: White with black numbering(1~4)
No. of Cores 4
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Material: XLPE(X-90) 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Nom. Thickness(mm): 0.6 3.Spark test A.C. voltage value(kV): 6
Approx. Dia. over insulation(mm): 3.3 4.A.C. high voltage test for 5min(kV): 2.5
Bedding
Material: PVC(5V-90)
Nom. Thickness(mm): 1.0
Approx. Dia. over bedding(mm): 10.4
Armour
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 0.8 Physical characteristics
Approx. Dia. over armour(mm): 12.1 1.Min. bending radius(mm)
Outer Sheath a)during installation: 156
Material: PVC(5V-90) b)after installation: 125
Nom. Thickness(mm): 1.3 2.Max. pulling tension for conductor(kN): 0.700
Min. Thickness(mm): 0.84 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 15.6 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. Weight of cable(kg/km): 430.0
Order Quantity(m): 700

Packing information
1.Max. length per drum(m): 700
2.Drum size(H x W x L)(mm): 1000 x 560 x 1000
3.Gross weight per drum(kg): 400

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-50A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F28
CONTROL CABLE: 5C X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Insulation: White with black numbering(1~5)
No. of Cores 5
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Material: XLPE(X-90) 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Nom. Thickness(mm): 0.6 3.Spark test A.C. voltage value(kV): 6
Approx. Dia. over insulation(mm): 3.3 4.A.C. high voltage test for 5min(kV): 2.5
Bedding
Material: PVC(5V-90)
Nom. Thickness(mm): 1.0
Approx. Dia. over bedding(mm): 11.4
Armour
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 0.8 Physical characteristics
Approx. Dia. over armour(mm): 13.0 1.Min. bending radius(mm)
Outer Sheath a)during installation: 165
Material: PVC(5V-90) b)after installation: 132
Nom. Thickness(mm): 1.4 2.Max. pulling tension for conductor(kN): 0.875
Min. Thickness(mm): 0.92 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 16.5 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. Weight of cable(kg/km): 495.0
Order Quantity(m): 2000

Packing information
1.Max. length per drum(m): 2000
2.Drum size(H x W x L)(mm): 1400 x 710 x 1400
3.Gross weight per drum(kg): 1100

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-51A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F30
CONTROL CABLE: 12C X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Insulation: White with black numbering(1~12)
No. of Cores 12
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Material: XLPE(X-90) 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Nom. Thickness(mm): 0.6 3.Spark test A.C. voltage value(kV): 6
Approx. Dia. over insulation(mm): 3.3 4.A.C. high voltage test for 5min(kV): 2.5
Bedding
Material: PVC(5V-90)
Nom. Thickness(mm): 1.0
Approx. Dia. over bedding(mm): 16.1
Armour
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 1.25 Physical characteristics
Approx. Dia. over armour(mm): 18.8 1.Min. bending radius(mm)
Outer Sheath a)during installation: 228
Material: PVC(5V-90) b)after installation: 182
Nom. Thickness(mm): 1.6 2.Max. pulling tension for conductor(kN): 2.100
Min. Thickness(mm): 1.08 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 22.8 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. Weight of cable(kg/km): 1010.0
Order Quantity(m): 2000

Packing information
1.Max. length per drum(m): 2000
2.Drum size(H x W x L)(mm): 1800 x 1120 x 1800
3.Gross weight per drum(kg): 2150

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-52A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F50
CONTROL CABLE: 12C X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is designed for areas where the integrity of the


electrical circuit is critical in maintaininig power supply applications can be
found in emergency lighting,control and power stations,fire alarm systems,
underground tunnels and so on.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
Insulation: White with black numbering(1~12)
No. of Cores 12
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Material: XLPE(X-90) 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Nom. Thickness(mm): 0.6 3.Spark test A.C. voltage value(kV): 6
Approx. Dia. over insulation(mm): 3.3 4.A.C. high voltage test for 5min(kV): 2.5
Bedding
Material: PVC(5V-90)
Nom. Thickness(mm): 1.0
Approx. Dia. over bedding(mm): 16.1
Armour
Material of Armour: Galvanized steel wire
Dia. of Armour wire: 1.25 Physical characteristics
Approx. Dia. over armour(mm): 18.8 1.Min. bending radius(mm)
Outer Sheath a)during installation: 228
Material: PVC(5V-90) b)after installation: 182
Nom. Thickness(mm): 1.6 2.Max. pulling tension for conductor(kN): 2.100
Min. Thickness(mm): 1.08 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 22.8 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. Weight of cable(kg/km): 1010.0
Order Quantity(m): 700

Packing information
1.Max. length per drum(m): 700
2.Drum size(H x W x L)(mm): 1250 x 630 x 1250
3.Gross weight per drum(kg): 800

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-53A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F46
2
INSTRUMENT CABLE:3P X 1.5 mm
CU/XLPE/ISOS/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
No. of Pairs 3 Insulation: Black、White with numbering
Conductor
Material: Plain annealed copper wire Bedding: Black
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Black(UV-Stabilised)
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 2.9 3.Spark test A.C. voltage value(kV): 6
Individual Screen 4.A.C. high voltage test for 1min(kV): 2.0
Material: Al-foil(Al layer inside) 5.Max.Mutual capacitance at 1kHz(nF/km): 150
100% wrapping over the individual pair 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Drain wire
Material: Tinned copper wire
2 0.5
Cross-Sectional Area(mm ):
Overall Screen
Material: Al-foil(Al layer inside) Physical characteristics
100% wrapping over the binder tape 1.Min. bending radius(mm)
Bedding a)during installation: 252
Material: PVC(5V-90) b)after installation: 210
Nom. Thickness(mm): 1.1 2.Max. pulling tension for conductor(kN): 0.630
Approx. Dia. over bedding(mm): 14.6 3.Construction test: AS/NZS 5000.3
Armour 4.Flame retardant test: IEC 60332-3-22
Material: Galvanized steel wire
Dia. of Armour wire: 0.9
Approx. Dia. over armour(mm): 16.5
Outer Sheath
Material: PVC(5V-90)
Nom. Thickness(mm): 1.5 Packing information
Min. Thickness(mm): 1.00 1.Max. cable length per drum(m): 1100
Approx. Dia. of cable(mm): 21.0 2.Drum size(H x W x L)(mm): 1400 x 710 x 1400
O.D. tolerance(%): ±8 3.Gross weight per drum(kg): 830
Approx. weight of cable(kg/km): 650.0
Order Quantity(m): 2200
Contact information Customer Approved by
Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-54A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: H8
CU/PVC Earthing Cable
1C X 6 mm2
Cross Drawing

Description

Application: These cables are intended for use in electrical installations


for earthing purpose

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6
Cable Construction Color

No. of Cores 1
Conductor
Material: Plain annealed copper wire Insulation: Green/yellow(Green with yellow strip)
2 6
Cross-Sectional Area(mm ):
Approx. Conductor Dia.(mm): 3.12
Class of Conductor: Class 2
Insulation Performance
Material: PVC(V-90) Electrical characteristics
Nom. Thickness(mm): 1.0 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 3.08
Min. Thickness(mm): 0.80 2.Min. Insulation Resistance at 20℃(MΩ•km): 10
Approx. Dia. of cable(mm): 5.3 3.Spark test A.C. voltage value(kV): 6
Approx. weight of cable(kg/km): 80.0 4.A.C. high voltage test for 5min(kV): 3.5
Order Quantity(m): 300

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 53
b)after installation: 42
2.Max. pulling tension for conductor(kN): 0.420
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6

Packing information
1.Max. cable length per drum(m): 300
2.Drum size(mm): 500 x 250 x 500
3.Gross weight per drum(kg): 60

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-55A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: H9
CU/PVC Earthing Cable
1C X 10 mm2
Cross Drawing

Description

Application: These cables are intended for use in electrical installations


for earthing purpose

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6
Cable Construction Color

No. of Cores 1
Conductor
Material: Plain annealed copper wire Insulation: Green/yellow(Green with yellow strip)
2 10
Cross-Sectional Area(mm ):
Approx. Conductor Dia.(mm): 4.05
Class of Conductor: Class 2
Insulation Performance
Material: PVC(V-90) Electrical characteristics
Nom. Thickness(mm): 1.0 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 1.83
Min. Thickness(mm): 0.80 2.Min. Insulation Resistance at 20℃(MΩ•km): 10
Approx. Dia. of cable(mm): 6.2 3.Spark test A.C. voltage value(kV): 6
Approx. weight of cable(kg/km): 120.0 4.A.C. high voltage test for 5min(kV): 3.5
Order Quantity(m): 300

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 62
b)after installation: 50
2.Max. pulling tension for conductor(kN): 0.700
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6

Packing information
1.Max. cable length per drum(m): 300
2.Drum size(mm): 500 x 250 x 500
3.Gross weight per drum(kg): 75

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-56A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: H3
CU/PVC Earthing Cable
1C X 35 mm2
Cross Drawing

Description

Application: These cables are intended for use in electrical installations


for earthing purpose

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6
Cable Construction Color

No. of Cores 1
Conductor
Material: Plain annealed copper wire Insulation: Green/yellow(Green with yellow strip)
2 35
Cross-Sectional Area(mm ):
Approx. Conductor Dia.(mm): 7.3
Class of Conductor: Class 2
Insulation Performance
Material: PVC(V-90) Electrical characteristics
Nom. Thickness(mm): 1.2 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 0.524
Min. Thickness(mm): 0.98 2.Min. Insulation Resistance at 20℃(MΩ•km): 10
Approx. Dia. of cable(mm): 9.9 3.Spark test A.C. voltage value(kV): 10
Approx. weight of cable(kg/km): 370.0 4.A.C. high voltage test for 5min(kV): 3.5
Order Quantity(m): 4000

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 99
b)after installation: 79
2.Max. pulling tension for conductor(kN): 2.450
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6

Packing information
1.Max. cable length per drum(m): 4000
2.Drum size(mm): 1250 x 630 x 1250
3.Gross weight per drum(kg): 1590

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-57A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: H4
CU/PVC Earthing Cable
1C X 35 mm2
Cross Drawing

Description

Application: These cables are intended for use in electrical installations


for earthing purpose

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6
Cable Construction Color

No. of Cores 1
Conductor
Material: Plain annealed copper wire Insulation: Yellow
2 35
Cross-Sectional Area(mm ):
Approx. Conductor Dia.(mm): 7.3
Class of Conductor: Class 2
Insulation Performance
Material: PVC(V-90) Electrical characteristics
Nom. Thickness(mm): 1.2 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 0.524
Min. Thickness(mm): 0.98 2.Min. Insulation Resistance at 20℃(MΩ•km): 10
Approx. Dia. of cable(mm): 9.9 3.Spark test A.C. voltage value(kV): 10
Approx. weight of cable(kg/km): 370.0 4.A.C. high voltage test for 5min(kV): 3.5
Order Quantity(m): 500

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 99
b)after installation: 79
2.Max. pulling tension for conductor(kN): 2.450
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6

Packing information
1.Max. cable length per drum(m): 500
2.Drum size(mm): 710 x 400 x 710
3.Gross weight per drum(kg): 240

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-58A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: H1
CU/PVC Earthing Cable
1C X 120 mm2
Cross Drawing

Description

Application: These cables are intended for use in electrical installations


for earthing purpose

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6
Cable Construction Color

No. of Cores 1
Conductor
Material: Plain annealed copper wire Insulation: Green/yellow(Green with yellow strip)
2 120
Cross-Sectional Area(mm ):
Approx. Conductor Dia.(mm): 9.8
Class of Conductor: Class 2
Insulation Performance
Material: PVC(V-90) Electrical characteristics
Nom. Thickness(mm): 1.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 0.153
Min. Thickness(mm): 1.34 2.Min. Insulation Resistance at 20℃(MΩ•km): 10
Approx. Dia. of cable(mm): 16.4 3.Spark test A.C. voltage value(kV): 15
Approx. weight of cable(kg/km): 1200.0 4.A.C. high voltage test for 5min(kV): 3.5
Order Quantity(m): 5000

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 164
b)after installation: 131
2.Max. pulling tension for conductor(kN): 8.400
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6

Packing information
1.Max. cable length per drum(m): 2000
2.Drum size(mm): 1400 x 710 x 1400
3.Gross weight per drum(kg): 2520

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-59A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: G2
2
INSTRUMENT CABLE:2P X 1.5 mm
CU/XLPE/ISOS/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color
No. of Pairs 2 Insulation: Black、White with numbering
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Black(UV-Stabilised)
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.3
Nom. Thickness(mm): 0.6 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 2.9 3.Spark test A.C. voltage value(kV): 6
Individual Screen 4.A.C. high voltage test for 1min(kV): 2.0
Material: Al-foil(Al layer inside) 5.Max.Mutual capacitance at 1kHz(nF/km): 150
100% wrapping over the individual pair 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Drain wire
Material: Tinned copper wire
2 0.5
Cross-Sectional Area(mm ):
Overall Screen
Material: Al-foil(Al layer inside) Physical characteristics
100% wrapping over the mylar tape 1.Min. bending radius(mm)
Outer Sheath a)during installation: 170
Material: PVC(5V-90) b)after installation: 142
Nom. Thickness(mm): 1.1 2.Max. pulling tension for conductor(kN): 0.420
Min. Thickness(mm): 0.84 3.Construction test: AS/NZS 5000.3
Approx. Dia. of cable(mm): 14.2 4.Flame retardant test: IEC 60332-3-22
O.D. tolerance(%): ±8
Approx. weight of cable(kg/km): 230.0
Order Quantity(m): 600

Packing information
1.Max. cable length per drum(m): 600
2.Drum size(H x W x L)(mm): 900 x 500 x 900
3.Gross weight per drum(kg): 200

Contact information Customer Approved by


Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-60A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F24
2
RS485 CABLE:1P X 1.5 mm
CU/XLPE/OS/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is used in machines,measuring instrument,and


control systems for the transmission of analogue and digit signals.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.3、IEC 61156-2
AS/NZS 3808、AS/NZS 1660
IEC 60332-1-2
Cable Construction Color

No. of Pairs 1 Insulation: Black、White


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 1.5
Approx. Conductor Dia.(mm): 1.59 Outer sheath: Black(UV-Stabilised)
Class of Conductor: Class 2
Insulation Performance
Material: XLPE Electrical characteristics
Nom. Thickness(mm): 0.6 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 12.1
Approx. Dia. over insulation(mm): 2.9 2.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Drain wire 3.Spark test A.C. voltage value(kV): 6
Material: Tinned copper wire 4.A.C. high voltage test for 1min(kV): 2.0
Cross-Sectional Area(mm2): 0.5 5.Max.Mutual capacitance at 1kHz(nF/km): 150
Binder tape 6.Max.Inductance to resistance ratio(L/R) (μH/Ω): 40
Material: Mylar-tape
100% wrapping over the assembly
Overall Screen
Material: Al-foil(Al layer inside)
100% wrapping over the binder tape Physical characteristics
Outer Sheath 1.Min. bending radius(mm)
Material: PVC a)during installation: 86
Nom. Thickness(mm): 0.9 b)after installation: 69
Min. Thickness(mm): 0.67 2.Max. pulling tension for conductor(kN): 0.210
Approx. Dia. of cable(mm): 8.6 3.Construction test: AS/NZS 5000.3
O.D. tolerance(%): ±8 IEC 61156-2
Approx. weight of cable(kg/km): 85.0 4.Flame retardant test: IEC 60332-1-2
Order Quantity(m): 1000
Packing information
1.Max. cable length per drum(m): 1000
2.Drum size(H x W x L)(mm): 710 x 400 x 710
3.Gross weight per drum(kg): 150

Contact information Customer Approved by


Address 27 Senoko way
Singapore 758060
Tel (65)6367 0107
Fax (65)6365 2963
Email sales@keystone-cable.com
Website www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-61A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: F49
POWER CABLE: 1C X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is primarily used for main power supply.It can be


installed in cable ducts,in cable trunking,on cable trays,and on cable
ladders.

Rated Voltage(V): 450/750


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.2、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660
IEC 60332-3-22
Cable Construction Color

No. of Cores 1 Insulation: Natural


Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01
Class of Conductor: Class 2 Performance
Insulation Electrical characteristics
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41
Nom. Thickness(mm): 0.6 3.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Approx. Dia. over insulation(mm): 3.3 4.Spark test A.C. voltage value(kV): 6
Outer Sheath 5.A.C. high voltage test for 5min(kV): 2.5
Material: PVC(5V-90)
Nom. Thickness(mm): 0.8
Min. Thickness(mm): 0.58
Approx. Dia. of cable(mm): 5.3
O.D. tolerance(%): ±8 Physical characteristics
Approx. Weight of cable(kg/km): 50.0 1.Min. bending radius(mm)
Order Quantity(m): 200 a)during installation: 53
b)after installation: 42
2.Max. pulling tension for conductor(kN): 0.175
3.Construction test: AS/NZS 5000.2
4.Flame retardant test: IEC 60332-3-22

Packing information
1.Max. cable length per drum(m): 200
2.Drum size(mm): 500 x 250 x 500
3.Gross weight per drum(kg): 40

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130708-62A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: A36
POWER CABLE: 3C X 2.5 + E X 2.5 mm2
CU/XLPE/PVC,Unarmoured
Cross Drawing

Description

Application:This cable is primarily used for main power supply.It can be


installed in cable ducts,in cable trunking,on cable trays,and on cable
ladders.

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6

Cable Construction Color


Phase cores Earth core Insulation: Red、White、Dark blue、Green/yellow
No. of Cores 3 1
Conductor
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation Phase cores Earth core
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41 7.41
Nom. Thickness(mm): 0.7 0.7 2.Max. Conductor A.C. resistance at 90℃(Ω/km): 9.45 9.45
Approx. Dia. over insulation(mm): 3.5 3.5 3.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Outer Sheath 4.Spark test A.C. voltage value(kV): 6 6
Material: PVC(5V-90) 5.A.C. high voltage test for 5min(kV): 3.5
Nom. Thickness(mm): 1.8 6.Current carrying capacities(A)
Min. Thickness(mm): 1.43 a)in air: 26
Approx. Dia. of cable(mm): 13.2 b)direct buried: 29
O.D. tolerance(%): ±8 c)buried in duct: 29
Approx. Weight of cable(kg/km): 240.0 *Ambient temperature:40℃;Ground temperature:25℃
Order Quantity(m): 700 Burying depth:1 m;Soil resistivity:1℃•m/w
7.Max. conductor temperature of 5s Short-circuit(℃): 250
8.Max. 1s Short-circuit rating(kA): 0.358
9.Reactance at 50Hz(Ω/km): 0.0988

Physical characteristics
1.Min. bending radius(mm)
a)during installation: 132
b)after installation: 106
2.Max. pulling tension for conductor(kN): 0.700
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6
Packing information
1.Max. cable length per drum(m): 700
2.Drum size(mm): 900 x 450 x 900
3.Gross weight per drum(kg): 230

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130709-01A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.
SPECIFICATION
SIEMENS MTO ITEM No.: A60
POWER CABLE: 3C X 2.5 + E X 2.5 mm2
CU/XLPE/PVC/SWA/PVC,Armoured
Cross Drawing

Description

Application:This cable is primarily used for main power supply.It can be


installed in cable ducts,in cable trunking,on cable trays,and on cable
ladders.

Rated Voltage(V): 600/1000


Rated Temperature(℃): 90
Generally refer to specification: AS/NZS 5000.1、AS/NZS 1125
AS/NZS 3808、AS/NZS 1660.5.6

Cable Construction Color


Phase cores Earth core Insulation: Red、White、Dark blue、Green/yellow
No. of Cores 3 1
Conductor Bedding: Black
Material: Plain annealed copper wire
Cross-Sectional Area(mm2): 2.5 2.5 Outer sheath: Black(UV-Stabilised)
Approx. Conductor Dia.(mm): 2.01 2.01 Performance
Class of Conductor: Class 2 Electrical characteristics
Insulation Phase cores Earth core
Material: XLPE(X-90) 1.Max. Conductor D.C. resistance at 20℃(Ω/km): 7.41 7.41
Nom. Thickness(mm): 0.7 0.7 2.Max. Conductor A.C. resistance at 90℃(Ω/km): 9.45 9.45
Approx. Dia. over insulation(mm): 3.5 3.5 3.Min. Insulation Resistance at 20℃(MΩ•km): 1000
Bedding 4.Spark test A.C. voltage value(kV): 6 6
Material: PVC(5V-90) 5.A.C. high voltage test for 5min(kV): 3.5
Nom. Thickness(mm): 1.0 6.Current carrying capacities(A)
Approx. Dia. over bedding(mm): 10.6 a)in air: 26
Armour b)direct buried: 29
Material of Armour: Galvanized steel wire c)buried in duct: 29
Dia. of Armour wire: 0.8 *Ambient temperature:40℃;Ground temperature:25℃
Approx. Dia. over armour(mm): 14.2 Burying depth:1 m;Soil resistivity:1℃•m/w
Outer Sheath 7.Max. conductor temperature of 5s Short-circuit(℃): 250
Material: PVC(5V-90) 8.Max. 1s Short-circuit rating(kA): 0.358
Nom. Thickness(mm): 1.8 9.Reactance at 50Hz(Ω/km): 0.0988
Min. Thickness(mm): 1.24
Approx. Dia. of cable(mm): 18.5 Physical characteristics
O.D. tolerance(%): ±8 1.Min. bending radius(mm)
Approx. Weight of cable(kg/km): 565.0 a)during installation: 222
Order Quantity(m): 1000 b)after installation: 185
2.Max. pulling tension for conductor(kN): 0.700
3.Construction test: AS/NZS 5000.1
4.Flame retardant test: AS/NZS 1660.5.6
Packing information
1.Max. cable length per drum(m): 1000
2.Drum size(mm): 1250 x 710 x 1250
3.Gross weight per drum(kg): 660

Contact Information Customer Approved by


Address: 27 Senoko way
Singapore 758060
Tel: (65) 6367 0107
Fax: (65) 6365 2963
Email: sales@keystone-cable.com
Website: www.keystone-cable.com
Spec.No Prepared by Checked by Approved by
S-130709-02A SongKunhua YuLei Patrick Li
NOTE:The information contained in this data sheet is subject to normal manufacturing tolerance, specifications are subject to change without notice.

S-ar putea să vă placă și