Sunteți pe pagina 1din 111

Ceiling Concealed

T E CHN I CA L MANUAL TM-FDBM-0515-C


Table of Contents

1. Model Name........................................................................................................... 1

2. Features................................................................................................................. 3

3. Specifications......................................................................................................... 4
General Data............................................................................................... 4
Safety Devices........................................................................................... 26

4. Selection Process................................................................................................. 28
Fan Performance Curve............................................................................ 28

5. Application Information......................................................................................... 52
Operating Range....................................................................................... 52
Refrigerant Diagram.................................................................................. 53
Controllers................................................................................................. 56

6. Installation............................................................................................................ 60

7. Wiring Diagram..................................................................................................... 72

8. Servicing & Maintenance..................................................................................... 87

9. Troubleshooting................................................................................................... 88

10. Dimensional Data................................................................................................. 92

11. Exploded View & Part List.................................................................................... 98

Note : Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.

Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning : Moving machinery and electrical power hazard. May cause severe personnel
injury or death. Disconnect and lock off power before servicing equipment.
1. Model Name
Indoor

FDB 10 C V1 M

Controller
M : Wired Controller

Power Supply
V1 : Single Phase, 220-240V, 50Hz

Series
C : C Series

Capacity Index
10 : Based on Btu/hr

Refrigerant
Blank : R22
N : R410A

Type of Air Conditioner


FDB : Ceiling Concealed
(Lower Static Pressure)
FDM : Ceiling Concealed
(Higher Static Pressure)
TM-FDBM-0515-C

1
Outdoor

R 10 C V1

Power Supply
V1 : Single Phase, 220-240V, 50Hz
Y1 : Three Phase, 380-415V, 50Hz

Series

C : C series
D : D series
F : F series

Capacity Index
10 : Based on Btu/hr

Refrigerant
Blank : R22
N : R410A

Type of Air Conditioner


R : Single Split Condensing Unit
TM-FDBM-0515-C

2
2. Features
Space Saving, Elegance and Prestige
The unit is installed above the ceiling with only the supply and return air grille exposed to view. This
ceiling concealed type of design has made it an “Evergreen” model without sacrificing the precious floor
space. The air-conditioned space will appear as elegant and prestigious as centralized air-conditioned
area but with only a fraction of the cost. This model is ideal for small offices, hotel rooms, hospitals and
restaurant applications.

Double Protection Drainage System


High humidity inside the ceiling area is always the main cause of water leaking. By introducing “Built
In” double drain pans solution, i.e. primary drain pan and secondary drain pan, water leaking will not
be a problem anymore. The high quality Polystyrene (PS) primary drain pan come with a layer of
thermal forming High Impact Polystyrene (HIPS) coating. The primary drain pan is specially designed,
with mould in gradient, for better condensate water drainage. Furthermore, the drain pan is made of
PS, which is a very good insulation material to prevent sweating. The secondary drain pan will act as
a drip pan to block any water that might be dripped down thus offering an additional protection to the
ceiling. In such a case, additional drain pan will not be necessary during installation which means more
cost saving. A drain socket is supplied to connect both drain pans to the drainage pipe.

Easy and Flexible Installation


The physical height of the unit is only 378mm or less depends on the model, it is therefore offering
greatest flexibility in selecting installation location.
With its special designed installation accessories, the installation job become easy and better air
distribution can be achieved without extra spending on duct works.

Easy Maintenance
The simple design concept has a friendly maintenance and servicing in mind. Just loosening a few
screws, remove secondary drain pan and drain guide, you can access to all the internal parts from the
bottom of the unit. No water will splash down when removing the secondary drain pan makes the
TM-FDBM-0515-C

servicing work never easier before.

Medium Static Pressure with a Low Noise Level


This series has a static pressure between 0 to 15 mmAq depend on duct work installation. The casing
is well insulated internally to reduce the noise level.

3
3. Specifications
Specification (R22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDB10CV1M FDB15CV1M
MODEL INDOOR UNIT
NON-STANDARD STATIC PRESSURE FDM10CV1M FDM15CV1M
OUTDOOR UNIT R10CV1 R15CV1
Btu/h 10,000 13,000
TOTAL COOLING CAPACITY
W 2,930 3,809
LOW ESP 903 1,277
TOTAL INPUT POWER W
HIGH ESP 924 1,331
LOW ESP 4.0 5.7
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
HIGH ESP 4.1 6.0
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 0.63 / 1.39 0.60 / 1.32
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
LOW ESP 33 / 30 / 25 36 / 33 / 28
SOUND PRESSURE LEVEL (H/M/L) dBA
HIGH ESP 36 / 35 / 33 40 / 38 / 33
HEIGHT mm/in 261 / 10.3
UNIT
WIDTH mm/in 765 / 30.1 905 / 35.6
DIMENSION
DEPTH mm/in 411 / 16.2
HEIGHT mm/in 376 / 14.8
PACKING
WIDTH mm/in 951 / 37.4 1091 / 43.0
DIMENSION
DEPTH mm/in 541 / 21.3
UNIT WEIGHT kg/lb 18 / 39.7 22 / 48.5
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
LOW HIGH l/s / CFM 142 / 300 241 / 540
STATIC AIR FLOW MEDIUM l/s / CFM 135 / 275 231 / 500
FAN LOW l/s / CFM 123 / 225 189 / 380
MOTOR ESP (H/M/L) Pa (in.wg.) 10 / 8 / 5 (0.04 / 0.03 / 0.02) 10 / 8 / 5 (0.04 / 0.03 / 0.02)
HIGH HIGH l/s / CFM 142 / 300 241 / 510
STATIC AIR FLOW MEDIUM l/s / CFM 135 / 285 231 / 490
FAN LOW l/s / CFM 123 / 260 189 / 400
MOTOR* ESP (H/M/L) Pa (in.wg.) 49 / 44 / 36 (0.20 / 0.18 / 0.15) 49 / 42 / 28 (0.20 / 0.17 / 0.11)
TYPE CENTRIFUGAL FAN
FAN
QUANTITY 1 2
MATERIAL GALVANIZED STEEL
INDOOR UNIT

DRIVE DIRECT
DIAMETER mm/in 164 / 6.46
LENGTH mm/in 202 / 7.95
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN LOW ESP 68 106
RATED INPUT POWER W
MOTOR HIGH ESP 89 160
RATED RUNNING LOW ESP 0.30 0.47
A
CURRENT HIGH ESP 0.40 0.78
LOW ESP 20 40
MOTOR OUTPUT W
HIGH ESP 38 72
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
COIL MATERIAL ALUMINIUM
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.115 / 1.238 0.143 / 1.542
ROW 3
FIN PER INCH 12 14
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 1
AIR AIR
LENGTH mm/in 560 / 22.05 700 / 27.56
QUALITY FILTER
SIZE WIDTH mm/in 195 / 7.68
THICKNESS mm/in 5 / 0.20
TM-FDBM-0515-C

CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

4
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series (CONT’D)
STANDARD STATIC PRESSURE FDB10CV1M FDB15CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDM10CV1M FDM15CV1M
OUTDOOR UNIT R10CV1 R15CV1
AIR FLOW l/s / CFM 453 / 960
SOUND PRESSURE LEVEL dBA 46 49
HEIGHT mm/in 540 / 21.3
UNIT
WIDTH mm/in 700 / 27.6
DIMENSION
DEPTH mm/in 250 / 9.8
HEIGHT mm/in 620 / 24.4
PACKING
WIDTH mm/in 810 / 31.9
DIMENSION
DEPTH mm/in 330 / 13.0
UNIT WEIGHT kg/lb 30 / 66 32 / 71
TYPE FLARE
PIPE
LIQUID mm/in 6.35 / 1/4
CONNECTION SIZE
GAS mm/in 9.52 / 3/8 12.7 / 1/2
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG20
DRIVE DIRECT
DIAMETER mm/in 401 / 15.8
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP23
INSULATION GRADE B
OUTDOOR UNIT

POWER SOURCE V/Ph/Hz 220-240 / 1 / 50


FAN MOTOR
RATED INPUT POWER W 52 74
RATED RUNNING CURRENT A 0.23 0.33
MOTOR OUTPUT W 19 30
MOTOR SPEED RPM 730 860
POLES 6
TYPE ROTARY
OIL TYPE ATMOS NM56M or SUNISO 4GDID
OIL AMOUNT cm3 / fl.oz. 320 / 11.3 350 / 11.8
INSULATION GRADE E
COMPRESSOR
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 30
RATED INPUT POWER W 783 1112
RATED RUNNING CURRENT A 3.5 5.0
LOCKED ROTOR AMP. A 19 21
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
COIL MATERIAL ALUMINUM (RAISE LANCE)
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.43 / 4.62
ROW 1
FIN PER INCH 20
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

5
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDB20CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDM20CV1M
OUTDOOR UNIT R18CV1 R20CV1
Btu/h 18,000 20,000
TOTAL COOLING CAPACITY
W 5,274 5,860
LOW ESP 1,907 1,892
TOTAL INPUT POWER W
HIGH ESP 1,945 1,930
LOW ESP 8.5 8.3
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
HIGH ESP 8.5
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 0.90 / 1.98 0.83 / 1.83
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL LOW ESP 38 / 37 / 35
(H/M/L) dBA
HIGH ESP 42 / 41 / 40
HEIGHT mm/in 261 / 10.3
UNIT
WIDTH mm/in 1065 / 41.9
DIMENSION
DEPTH mm/in 411 / 16.2
HEIGHT mm/in 376 / 14.8
PACKING
WIDTH mm/in 1251 / 49.3
DIMENSION
DEPTH mm/in 541 / 21.3
UNIT WEIGHT kg/lb 24 / 53
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
LOW HIGH l/s / CFM 330 / 703
STATIC AIR FLOW MEDIUM l/s / CFM 319 / 675
FAN LOW l/s / CFM 302 / 640
MOTOR ESP (H/M/L) Pa (in.wg.) 20 / 19 / 15 (0.08 / 0.07 / 0.06)
HIGH HIGH l/s / CFM 330 / 700
STATIC AIR FLOW MEDIUM l/s / CFM 319 / 675
FAN FAN LOW l/s / CFM 302 / 640
MOTOR* ESP (H/M/L) Pa (in.wg.) 49 / 45 / 41 (0.20 / 0.18 / 0.17)
TYPE CENTRIFUGAL FAN
INDOOR UNIT

QUANTITY 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
DIAMETER mm/in 164 / 6.46
LENGTH mm/in 202 / 7.95
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT LOW ESP 132
FAN MOTOR W
POWER HIGH ESP 170 181
RATED RUNNING LOW ESP 0.54 0.58
A
CURRENT HIGH ESP 0.79 0.82
LOW ESP 60
MOTOR OUTPUT W
HIGH ESP 80
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
COIL MATERIAL ALUMINIUM
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.176 / 1.892
ROW 3
FIN PER INCH 12
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 1
AIR
FILTER LENGTH mm/in 860 / 33.86
SIZE WIDTH mm/in 195 / 7.68
THICKNESS mm/in 5 / 0.20
TM-FDBM-0515-C

CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

6
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series (CONT’D)
STANDARD STATIC PRESSURE FDB20CV1M
MODEL INDOOR UNIT
NON-STANDARD STATIC PRESSURE FDM20CV1M
OUTDOOR UNIT R18CV1 R20CV1
AIR FLOW l/s / CFM 614 / 1300
SOUND PRESSURE LEVEL dBA 52 51
HEIGHT mm/in 654 / 25.7
UNIT
DIMENSION WIDTH mm/in 855 / 33.7
DEPTH mm/in 328 / 12.9
HEIGHT mm/in 693 / 27.3
PACKING
WIDTH mm/in 990 / 39.0
DIMENSION
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 43 / 94.8
TYPE FLARE
PIPE
LIQUID mm/in 6.35 / 1/4
CONNECTION SIZE
GAS mm/in 15.88 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 457 / 17.9
TYPE INDUCTION
QUANTITY 1
OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP23


INSULATION GRADE F
FAN MOTOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 77
RATED RUNNING CURRENT A 0.34
MOTOR OUTPUT W 32
MOTOR SPEED RPM 680
POLES 8 6
TYPE ROTARY
OIL TYPE SUNISO-4GSI/FREOL-K56
OIL AMOUNT cm3 / fl.oz. 600 / 20.3
INSULATION GRADE E
COMPRESSOR
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 40 35
RATED INPUT POWER W 1698 1672
RATED RUNNING CURRENT A 7.37 7.34
LOCKED ROTOR AMP. A 36 41
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
COIL MATERIAL ALUMINUM
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.51 / 5.49
ROW 1
FIN PER INCH 20
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

7
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDB25CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDM25CV1M
OUTDOOR UNIT R20CV1 R25CV1
Btu/h 22,000 25,000
TOTAL COOLING CAPACITY
W 6,446 7,325
LOW ESP 1,921 2,625
TOTAL INPUT POWER W
HIGH ESP 1,941 2,625
LOW ESP 8.4 11.6
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
HIGH ESP 8.6 11.7
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 1.40 / 3.08 1.10 / 2.43
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
LOW ESP 40 / 39 / 35
SOUND PRESSURE LEVEL (H/M/L) dBA
HIGH ESP 41 / 40 / 36
HEIGHT mm/in 261 / 10.3
UNIT
DIMENSION WIDTH mm/in 1200 / 47.2
DEPTH mm/in 411 / 16.2
HEIGHT mm/in 376 / 14.8
PACKING
DIMENSION WIDTH mm/in 1386 / 54.6
DEPTH mm/in 541 / 21.3
UNIT WEIGHT kg/lb 26 / 57.3
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
LOW HIGH l/s / CFM 345 / 730
STATIC AIR FLOW MEDIUM l/s / CFM 311 / 660
FAN LOW l/s / CFM 270 / 580
MOTOR ESP (H/M/L) Pa (in.wg.) 20 / 18 / 11 (0.08 / 0.07 / 0.04)
HIGH HIGH l/s / CFM 345 / 730
STATIC AIR FLOW MEDIUM l/s / CFM 311 / 660
FAN
FAN LOW l/s / CFM 274 / 580
MOTOR* ESP (H/M/L) Pa (in.wg.) 49 / 43 / 30 (0.20 / 0.17 / 0.12)
TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
INDOOR UNIT

DRIVE DIRECT
DIAMETER mm/in 164 / 6.46
LENGTH mm/in 202 / 7.95
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR RATED INPUT POWER LOW ESP 161
W
HIGH ESP 181
RATED RUNNING LOW ESP 0.70
A
CURRENT HIGH ESP 0.82
LOW ESP W 80
MOTOR OUTPUT
HIGH ESP 90
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM
COIL THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.203 / 2.187
ROW 3
FIN PER INCH 12
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 1
AIR
LENGTH mm/in 995 / 39.17
FILTER
SIZE WIDTH mm/in 195 / 7.68
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT
TM-FDBM-0515-C

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

8
Specification (R-22)
Ceiling Concealed Type - FDBM- C Series (CONT’D)
STANDARD STATIC PRESSURE FDB25CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDM25CV1M
OUTDOOR UNIT R20CV1 R25CV1
AIR FLOW l/s / CFM 614 / 1300 755 / 1600
SOUND PRESSURE LEVEL dBA 51 52
HEIGHT mm/in 654 / 25.7 756 / 29.8
UNIT WIDTH mm/in 855 / 33.7
DIMENSION
DEPTH mm/in 328 / 12.9
HEIGHT mm/in 693 / 27.3 793 / 31.2
PACKING WIDTH 990 / 39.0
DIMENSION mm/in
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 43 / 94.8 50 / 110
TYPE FLARE
PIPE
LIQUID mm/in 6.35 / 1/4 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 15.88 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 455 / 17.9
TYPE INDUCTION
QUANTITY 1
FAN MOTOR INDEX OF PROTECTION (IP) IP23
INSULATION GRADE F
OUTDOOR UNIT

POWER SOURCE V/Ph/Hz 220-240 / 1 / 50


RATED INPUT POWER W 77 121
RATED RUNNING CURRENT A 0.34 0.53
MOTOR OUTPUT W 32 60
MOTOR SPEED RPM 680 840
POLES 6
TYPE ROTARY
OIL TYPE SUNISO 4GSI /FREAOL-K56 ATMOS NM56M OR SUNISO 4GDID
OIL AMOUNT cm3 / fl.oz. 600 / 20.3 700 / 24.6
INSULATION GRADE E
COMPRESSOR
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 35 50
RATED INPUT POWER W 1683 2323
RATED RUNNING CURRENT A 7.44 10.35
LOCKED ROTOR AMP. A 41 56
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
COIL
MATERIAL ALUMINUM (RAISE LANCE)
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.51 / 5.49 0.61 / 6.58
ROW 1
FIN PER INCH 20
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

9
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDM30CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDB30CV1M
OUTDOOR UNIT R28CV1 R30CV1
Btu/h 28,000 30,000
TOTAL COOLING CAPACITY
W 8,204 8,790
HIGH ESP 3,104 3,410
TOTAL INPUT POWER W
LOW ESP 3,015 3,321
HIGH ESP 15.5 14.6
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
LOW ESP 15.5 14.2
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 1.75 / 3.86 2.00 / 4.41
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL HIGH ESP 46 / 44 / 42
dBA
(H/M/L) LOW ESP 41 / 40 / 39 / 36
HEIGHT mm/in 378 / 14.9
UNIT
WIDTH mm/in 929 / 36.6
DIMENSION
DEPTH mm/in 541 / 21.3
HEIGHT mm/in 415 / 16.3
PACKING
WIDTH mm/in 1126 / 44.3
DIMENSION
DEPTH mm/in 631 / 24.8
UNIT WEIGHT kg/lb 42 / 92.6
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
SUPER HIGH l/s / CFM 425 / 900
HIGH HIGH l/s / CFM 392 / 830
STATIC AIR FLOW
MEDIUM l/s / CFM 359 / 760
FAN
MOTOR LOW l/s / CFM 335 / 710
ESP (SH/H/M/L) Pa (in.wg.) 206 / 167 / 127 / 880.8 / 0.7 / 0.5 / 0.4)
SUPER HIGH l/s / CFM 425 / 900
LOW HIGH l/s / CFM 392 / 830
STATIC AIR FLOW 359 / 760
FAN MEDIUM l/s / CFM
FAN MOTOR* LOW l/s / CFM 335 / 710
ESP (SH/H/M/L) Pa (in.wg.) 49 / 39 / 29 / 20 (0.2 / 0.16 / 0.12 / 0.08)
TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
INDOOR UNIT

DRIVE DIRECT
DIAMETER mm/in 214 / 8.43
LENGTH mm/in 203 / 8.00
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT HIGH ESP 306
W
FAN MOTOR POWER LOW ESP 217
RATED RUNNING HIGH ESP 1.36
A
CURRENT LOW ESP 0.95
HIGH ESP 150
MOTOR OUTPUT W
LOW ESP 85
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
COIL MATERIAL ALUMINIUM (CORR. BARE FIN)
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.28 / 3.01
ROW 3
FIN PER INCH 12
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 2
AIR AIR
LENGTH mm/in 449 / 17.68
QUALITY FILTER
TM-FDBM-0515-C

SIZE WIDTH mm/in 305 / 12.01


THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

10
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series (CONT’D)
STANDARD STATIC PRESSURE FDM30CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDB30CV1M
OUTDOOR UNIT R28CV1 R30CV1
AIR FLOW l/s / CFM 808 / 1712
SOUND PRESSURE LEVEL dBA 54 56
HEIGHT mm/in 756 / 29.8
UNIT
DIMENSION WIDTH mm/in 855 / 33.7
DEPTH mm/in 328 / 12.9
HEIGHT mm/in 793 / 31.2
PACKING
DIMENSION WIDTH mm/in 990 / 39.0
DEPTH mm/in 416 / 16.4
UNIT WEIGHT kg/lb 57 / 126
TYPE FLARE VALVE
PIPE
LIQUID mm/in 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 15.88 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 455 / 18
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP23
INSULATION GRADE F
OUTDOOR UNIT

POWER SOURCE V/Ph/Hz 220-240 / 1 / 50


FAN MOTOR
RATED INPUT POWER W 124
RATED RUNNING CURRENT A 0.54
MOTOR OUTPUT W 66
MOTOR SPEED RPM 874
POLES 6 6
TYPE ROTARY TWIN ROTARY
OIL TYPE SUNISO 4GSI ATMOS NM32A1
OIL AMOUNT cm3 / fl.oz. 1050 / 36 900 / 30
INSULATION GRADE E
COMPRESSOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 60
RATED INPUT POWER W 2674 2980
RATED RUNNING CURRENT A 13.6 12.7
LOCKED ROTOR AMP. A 62 66
MATERIAL INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
MATERIAL ALUMINIUM (RAISE LANCE)
COIL
THICKNESS mm/in 0.10 / 0.004
FIN FACE AREA m2/ft2 0.61 / 6.58
ROW 2
FIN PER INCH 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

11
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDM40CV1M
MODEL INDOOR UNIT
NON-STANDARD STATIC PRESSURE FDB40CV1M
OUTDOOR UNIT R35DV1 R40DY1
Btu/h 35,000 40,000
TOTAL COOLING CAPACITY
W 10,255 11,720
HIGH ESP 3,341 3,441
TOTAL INPUT POWER W
LOW ESP 3,293 3,393
HIGH ESP 16.2 [5.8]
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
LOW ESP 15.91 [7.41]
POWER SOURCE 220-240 / 1 / 50 380-415 / 3 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 1.90 / 4.19 2.50 / 5.51
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL HIGH ESP dBA 51 / 49 / 45 / 41
(H/M/L) LOW ESP 43 / 41 / 40 / 38
HEIGHT mm/in 378 / 14.9
UNIT
WIDTH mm/in 1045 / 41.1
DIMENSION
DEPTH mm/in 541 / 21.3
HEIGHT mm/in 415 / 16.3
PACKING
WIDTH mm/in 1245 / 49.0
DIMENSION DEPTH mm/in 631 / 24.8
UNIT WEIGHT kg/lb 44 / 97
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
SUPER HIGH l/s / CFM 519 / 1110
HIGH
500 / 1060
STATIC AIR FLOW HIGH l/s / CFM
FAN MEDIUM l/s / CFM 467 / 990
MOTOR LOW l/s / CFM 425 / 900
ESP (SH/H/M/L) Pa (in.wg.) 206 / 176 / 127 / 93 (0.8 / 0.7 / 0.5 / 0.4)
SUPER HIGH l/s / CFM 519 / 1110
LOW
AIR FLOW HIGH l/s / CFM 500 / 1060
STATIC
FAN MEDIUM l/s / CFM 467 / 990
FAN LOW l/s / CFM 425 / 900
MOTOR*
ESP (SH/H/M/L) Pa (in.wg.) 49 / 39 / 29 /20 (0.20 / 0.16 / 0.12 / 0.08)
TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
INDOOR UNIT

DRIVE DIRECT
DIAMETER mm/in 214 / 8.43
LENGTH mm/in 203 / 8.00
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT HIGH ESP 384
FAN MOTOR POWER W
LOW ESP 336
RATED RUNNING HIGH ESP A
1.75
CURRENT LOW ESP 1.46
HIGH ESP 180
MOTOR OUTPUT W
LOW ESP 120
POLES 4
MATERIAL SEAMLESS INNER SMOOTH COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (CORR. BARE FIN)
COIL
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.31 / 3.34
ROW 3
FIN PER INCH 14
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 2
AIR AIR
LENGTH mm/in 507 / 19.96
QUALITY FILTER
TM-FDBM-0515-C

SIZE WIDTH mm/in 305 / 12.01


THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
12
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series (CONT’D)

STANDARD STATIC PRESSURE FDM40CV1M


MODEL INDOOR UNIT
NON-STANDARD STATIC PRESSURE FDB40CV1M
OUTDOOR UNIT R35DV1 R40DY1
AIR FLOW l/s / CFM 1605 / 3400
SOUND PRESSURE LEVEL dBA 58
HEIGHT mm/in 852 / 33.5
UNIT
WIDTH mm/in 1030 / 40.6
DIMENSION mm/in
DEPTH 400 / 15.7
HEIGHT mm/in 1010 / 39.8
PACKING
WIDTH mm/in 1180 / 46.5
DIMENSION
DEPTH mm/in 514 / 20.2
UNIT WEIGHT kg/lb 78 / 172 85 / 187
TYPE FLARE VALVE
PIPE
LIQUID mm/in 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 19.05 / 3/4
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 610 / 24
TYPE INDUCTION
OUTDOOR UNIT

QUANTITY 1
INDEX OF PROTECTION (IP) IP54
FAN MOTOR INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 257
RATED RUNNING CURRENT A 1.10
MOTOR OUTPUT W 145
MOTOR SPEED RPM 625
POLES 8
TYPE SCROLL
OIL TYPE SUNISO 3GS MINERAL OIL
OIL AMOUNT cm3 / fl.oz. 1242 / 42 1400 / 47
COMPRESSOR INSULATION GRADE B F
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
CAPACITOR µF 60 N/A
RATED INPUT POWER W 2700 2800
RATED RUNNING CURRENT - 1Ø [3Ø] A 13.35 [4.85]
LOCKED ROTOR AMP. - 1Ø [3Ø] A 97 [48]
MATERIAL INNER GROOVE COPPER
COIL TUBE DIAMETER mm/in 9.52 / 3/8 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011 0.23 / 0.009
MATERIAL ALUMINIUM (CORRUGATED)
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.87 / 9.36 0.85 / 9.15
ROW 1 2
FIN PER INCH 16 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

13
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series
STANDARD STATIC PRESSURE FDM50CV1M FDM60CV1M
MODEL INDOOR UNIT
NON-STANDARD STATIC PRESSURE FDB50CV1M FDB60CV1M
OUTDOOR UNIT R50DY1 R61DY1
Btu/h 50,000 60,000
TOTAL COOLING CAPACITY
W 14,650 17,580
HIGH ESP 5,067 7,010
TOTAL INPUT POWER W
LOW ESP 4,984 7,005
HIGH ESP [8.7] [11.5]
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
LOW ESP [10.77] [14.14]
POWER SOURCE V/Ph/Hz 380-415 / 3 / 50
REFRIGERANT TYPE R-22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 2.45 / 5.40 4.80 / 10.58
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL HIGH ESP 53 / 52 / 50 / 47 55 / 53 / 50 / 47
dBA
(H/M/L) LOW ESP 46 / 44 / 43 / 42 48 / 47 / 46 / 45
HEIGHT mm/in 378 / 14.9
UNIT
WIDTH mm/in 1299 / 51.1 1499 / 59.0
DIMENSION
DEPTH mm/in 541 / 21.3
HEIGHT mm/in 415 / 16.3
PACKING
WIDTH mm/in 1497 / 59.0 1701 / 67.0
DIMENSION
DEPTH mm/in 631 / 24.8
UNIT WEIGHT kg/lb 50 / 110 56 / 123
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
SUPER HIGH 750 / 1590 779 / 1650
HIGH HIGH l/s / CFM 722 / 1530
651 / 1380
STATIC AIR FLOW
MEDIUM l/s / CFM 604 / 1280 675 / 1430
FAN
MOTOR LOW l/s / CFM 571 / 1210 609 / 1290
ESP (SH/H/M/L) Pa (in.wg.) 176 / 157 / 137 / 108 (0.7 / 0.6 / 0.6 / 0/4) 176 / 157 / 137 / 98 (0.7 . 0.6 / 0.6 / 0.4)
SUPER HIGHl/s / CFM 750 / 1590 779 / 1650
LOW
HIGH l/s / CFM 651 / 1380 722 / 1530
STATIC AIR FLOW
FAN MEDIUM l/s / CFM 604 / 1280 675 / 1430
FAN
MOTOR* LOW l/s / CFM 571 / 1210 609 / 1290
ESP (SH/H/M/L) Pa (in.wg.) 78 / 59 / 39 / 20 (0.31 / 0.24 / 0.16 / 0.08) 69 / 49 / 29 / 20 (0.28 / 0.20 / 0.12 / 0.08)
INDOOR UNIT

TYPE CENTRIFUGAL FAN


QUANTITY 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
DIAMETER mm/in 214 / 8.43
LENGTH mm/in 203 / 8.00
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) 20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
HIGH ESP 603 610
FAN MOTOR RATED INPUT W
POWER LOW ESP 520 605
RATED RUNNING HIGH ESP 2.60 2.68
A
CURRENT LOW ESP 2.20 2.68
HIGH ESP 400 500
MOTOR OUTPUT W
LOW ESP 210 320
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM
COIL THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.40 / 4.31 0.47 / 5.06
ROW 3
FIN PER INCH 14
TYPE WASHABLE SARANET FILTER (OPTIONAL)
AIR QUANTITY pc 2
AIR mm/in
LENGTH 634 / 24.96 734 / 28.90
TM-FDBM-0515-C

QUALITY FILTER
SIZE WIDTH mm/in 305 / 12.01
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

14
Specification (R-22)
Ceiling Concealed Type - FDBM-C Series (CONT’D)
STANDARD STATIC PRESSURE FDM50CV1M FDM60CV1M
INDOOR UNIT
MODEL NON-STANDARD STATIC PRESSURE FDB50CV1M FDB60CV1M
OUTDOOR UNIT R50DY1 R61DY1
AIR FLOW l/s / CFM 1605 / 3400 1793 / 3800
SOUND PRESSURE LEVEL dBA 58 61
HEIGHT mm/in 852 / 33.5
UNIT
WIDTH mm/in 1030 / 40.6
DIMENSION
DEPTH mm/in 400 / 15.7
PACKING HEIGHT mm/in 1010 / 39.8
WIDTH mm/in 1180 / 46.5
DIMENSION
DEPTH mm/in 514 / 20.2
UNIT WEIGHT kg/lb 88 / 194 105 / 231
TYPE FLARE VALVE
PIPE
LIQUID mm/in 9.52 / 3/8 12.7 / 1/2
CONNECTION SIZE
GAS mm/in 19.05 / 3/4
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 610 / 24
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP54
OUTDOOR UNIT

INSULATION GRADE F
FAN MOTOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 257 272
RATED RUNNING CURRENT A 1.10 1.28
MOTOR OUTPUT W 145
MOTOR SPEED RPM 625
POLES 8
TYPE SCROLL
OIL TYPE MINERAL OIL (SONITEX 200LT)
OIL AMOUNT cm3 / fl.oz. 1400 / 47 1705 / 57.7
INSULATION GRADE F -
COMPRESSOR POWER SOURCE V/Ph/Hz 380-415 / 3 / 50
CAPACITOR µF N/A
RATED INPUT POWER W 4207 6128
RATED RUNNING CURRENT - 1Ø [3Ø] A [7.47] [10.18]
LOCKED ROTOR AMP. - 1Ø [3Ø] A [59] [74]
MATERIAL INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276 9.52 / 3/8
THICKNESS mm/in 0.23 / 0.009
MATERIAL ALUMINIUM (COPRRUGATED)
COIL
THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m2/ft2 0.85 / 9.15 0.87 / 9.36
ROW 2 3
FIN PER INCH 18 16
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

15
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series
INDOOR UNIT FDMN10CV1M FDMN15CV1M
MODEL
OUTDOOR UNIT RN10FV1 RN15FV1
Btu/h 9,000 12,000
TOTAL COOLING CAPACITY
W 2,638 3,517
TOTAL INPUT POWER W 970 1,430
TOTAL RUNNING CURRENT - 1Ø [3Ø] A 4.35 6.41
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 0.80 / 1.76 0.83 / 1.83
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL (H/M/L) dBA 33 / 30 / 26 37 / 34 / 29
HEIGHT mm/in 261 / 10.3
UNIT
WIDTH mm/in 765 / 30.1 905 / 35.6
DIMENSION
DEPTH mm/in 411 / 16.2
HEIGHT mm/in 376 / 14.8
PACKING mm/in
WIDTH 951 / 37.4 1091 / 43.0
DIMENSION
DEPTH mm/in 541 / 21.3
UNIT WEIGHT kg/lb 18 / 40 22 / 49
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
S. HIGH l/s / CFM - -
HIGH HIGH l/s / CFM 118 / 250 193 / 410
AIR
STATIC FLOW MEDIUM l/s / CFM 111 / 235 174 / 370
FAN
MOTOR LOW l/s / CFM 99 / 210 118 / 250
ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)
FAN TYPE CENTRIFUGAL FAN
QUANTITY 1 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
INDOOR UNIT

DIAMETER mm/in 160 / 6.30


LENGTH mm/in 202 / 7.95
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) NA
INSULATION GRADE E B
FAN MOTOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 61 107
RATED RUNNING CURRENT A 0.27 0.48
MOTOR OUTPUT W 30 50
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (CORR. FIN)
COIL mm/in
THICKNESS 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.115 / 1.238 0.143 / 1.542
ROW 3
FIN PER INCH 18
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 1
AIR AIR
LENGTH mm/in 560 / 22.05 700 / 27.56
QUALITY FILTER
SIZE WIDTH mm/in 195 / 7.68
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
TM-FDBM-0515-C

THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION


5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

16
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series(CONT’D)
INDOOR UNIT FDMN10CV1M FDMN15CV1M
MODEL
OUTDOOR UNIT RN10FV1 RN15FV1
AIR FLOW l/s / CFM 438 / 927 390 / 827
SOUND PRESSURE LEVEL dBA 46 48
HEIGHT mm/in 550 / 21.7
UNIT
WIDTH mm/in 658 / 25.9
DIMENSION
DEPTH mm/in 273 / 10.7
HEIGHT mm/in 580 / 22.8
PACKING
WIDTH mm/in 775 / 30.5
DIMENSION
DEPTH mm/in 355 / 14.0
UNIT WEIGHT kg/lb 28 / 61.7 29 / 63.9
TYPE FLARE
PIPE LIQUID mm/in 6.35 / 1/4
CONNECTION SIZE
GAS mm/in 9.52 / 3/8 12.7 / 1/2
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 370 / 14.6
TYPE INDUCTION
QUANTITY 1
OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP23


INSULATION GRADE B
FAN MOTOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 50 51
RATED RUNNING CURRENT A 0.22 0.23
MOTOR OUTPUT W 20
MOTOR SPEED RPM 930 920
POLES 6
TYPE ROTARY
OIL TYPE HAF68D1 NMOCZe-Gles RB68EP
OIL AMOUNT cm3 / fl.oz. 330 / 11.2 320 / 10.8
INSULATION GRADE E
COMPRESSOR
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 35
RATED INPUT POWER W 859 1272
RATED RUNNING CURRENT A 3.86 5.7
LOCKED ROTOR AMP. A 18.0 24.5
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.2 / 0.0079
MATERIAL ALUMINUM
COIL THICKNESS mm/in 0.1 / 0.0039
FIN FACE AREA m2/ft2 0.33 / 3.55 0.32 / 3.44
ROW 1 2
FIN PER INCH 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

17
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series
INDOOR UNIT FDMN20CV1M FDMN25CV1M
MODEL
OUTDOOR UNIT RN20CV1 RN25CV1
Btu/h 18,000 21,000
TOTAL COOLING CAPACITY
W 5,275 6,155
TOTAL INPUT POWER W 1,870 2,150
TOTAL RUNNING CURRENT - 1Ø [3Ø] A 8.26 9.56
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-410A
REFRIGERANT CHARGE kg/lb 1.45 / 3.20 1.65 / 3.64
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL (H/M/L) dBA 38 / 36 / 34 40 / 39 / 36
HEIGHT mm/in 261 / 10.3
UNIT
WIDTH mm/in 1065 / 41.9 1200 / 47.2
DIMENSION
DEPTH mm/in 411 / 16.2
HEIGHT mm/in 376 / 14.8
PACKING
WIDTH mm/in 1251 / 49.3 1386 / 54.6
DIMENSION
DEPTH mm/in 541 / 21.3
UNIT WEIGHT kg/lb 24 / 53 26 / 57
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
S. HIGH l/s / CFM - -
HIGH AIR HIGH l/s / CFM 269 / 570 326 / 690
STATIC l/s / CFM 263 / 558 311 / 660
FLOW MEDIUM
FAN
LOW l/s / CFM 227 / 480 253 / 536
MOTOR
ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)
FAN TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
DIAMETER mm/in 160 / 6.30
INDOOR UNIT

LENGTH mm/in 202 / 7.95


TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) NA
INSULATION GRADE B E
FAN MOTOR
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
RATED INPUT POWER W 133 164
RATED RUNNING CURRENT A 0.61 0.74
MOTOR OUTPUT W 80 100
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (SLIT FIN)
COIL THICKNESS mm/in 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.176 / 1.892 0.203 / 2.187
ROW 3
FIN PER INCH 18
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 1
AIR LENGTH mm/in 860 / 33.86 995 / 39.17
FILTER SIZE WIDTH mm/in 195 / 7.68
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
TM-FDBM-0515-C

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR


4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

18
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series(CONT’D)
INDOOR UNIT FDMN20CV1M FDMN25CV1M
MODEL
OUTDOOR UNIT RN20CV1 RN25CV1
AIR FLOW l/s / CFM 675 / 1430 755 / 1600
SOUND PRESSURE LEVEL dBA 49 52
HEIGHT mm/in 654 / 25.7
UNIT
WIDTH mm/in 855 / 33.7
DIMENSION
DEPTH mm/in 328 / 12.9
HEIGHT mm/in 693 / 27.3
PACKING
WIDTH mm/in 990 / 39.0
DIMENSION
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 43 / 94.8 47 / 103.6
TYPE FLARE
PIPE
CONNECTION SIZE LIQUID mm/in 6.4 / 1/4
GAS mm/in 12.7 / 1/2 15.9 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 455 / 17.9
TYPE INDUCTION
QUANTITY 1
OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP23


INSULATION GRADE F
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR
RATED INPUT POWER W 78 121
RATED RUNNING CURRENT A 0.34 0.53
MOTOR OUTPUT W 32 61
MOTOR SPEED RPM 710 840
POLES 6
TYPE ROTARY
OIL TYPE FV50S
OIL AMOUNT cm3 / fl.oz. 670 / 22.7
INSULATION GRADE E
COMPRESSOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 50
RATED INPUT POWER W 1659 1865
RATED RUNNING CURRENT A 7.31 8.29
LOCKED ROTOR AMP. A 32
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.2 / 0.0079
MATERIAL ALUMINUM
COIL THICKNESS mm/in 0.1 / 0.0039
FIN FACE AREA m2/ft2 0.51 / 5.49 0.50 / 5.38
ROW 1 2
FIN PER INCH 20 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

19
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series

INDOOR UNIT FDMN30CV1M


MODEL
OUTDOOR UNIT RN28CV1
Btu/h 26,000
TOTAL COOLING CAPACITY
W 7,620
TOTAL INPUT POWER W 2,892
TOTAL RUNNING CURRENT - 1Ø [3Ø] A 12.8
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE R-410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 1.80 / 3.97
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 41 / 38 / 34
HEIGHT mm/in 285 / 11.2
UNIT
WIDTH mm/in 932 / 36.7
DIMENSION
DEPTH mm/in 600 / 23.6
HEIGHT mm/in 343 / 13.5
PACKING
WIDTH mm/in 1138 / 44.8
DIMENSION
DEPTH mm/in 690 / 27.2
UNIT WEIGHT kg/lb 40 / 88
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
S.HIGH l/s / CFM 401 / 850
HIGH HIGH
AIR l/s / CFM 382 / 810
STATIC
FAN FLOW MEDIUM l/s / CFM 363 / 770
MOTOR LOW l/s / CFM 335 / 710
ESP (H/M/L) Pa (in.wg.) 98 / 78 / 68 / 59 (0.39/0.31/0.28/0.24)
FAN TYPE CENTRIFUGAL FAN
INDOOR UNIT

QUANTITY 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
DIAMETER mm/in 185 / 7.28
LENGTH mm/in 203 / 7.99
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
FAN MOTOR POWER SOURCE 220-240 / 1 / 50
RATED INPUT POWER W 269
RATED RUNNING CURRENT A 1.28
MOTOR OUTPUT W 320
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
COIL
THICKNESS mm/in 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.24 / 2.62
ROW 3
FIN PER INCH 18
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 2
AIR AIR mm/in 456 / 17.95
LENGTH
QUALITY FILTER mm/in
SIZE WIDTH 210 / 8.27
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
TM-FDBM-0515-C

4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

20
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series (COND’T)
INDOOR UNIT FDMN30CV1M
MODEL
OUTDOOR UNIT RN28CV1
AIR FLOW l/s / CFM 808 / 1712
SOUND PRESSURE LEVEL dBA 54
HEIGHT mm/in 756 / 29.8
UNIT
WIDTH mm/in 855 / 33.7
DIMENSION
DEPTH mm/in 328 / 12.9
HEIGHT mm/in 793 / 31.2
PACKING WIDTH mm/in 990 / 39.0
DIMENSION
DEPTH mm/in 416 / 16.4
UNIT WEIGHT kg/lb 57 / 125.7
TYPE FLARE VALVE
PIPE
LIQUID mm/in 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 15.88 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 455 / 17.9
TYPE INDUCTION
OUTDOOR UNIT

QUANTITY 1
INDEX OF PROTECTION (IP) IP23
INSULATION GRADE F
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR
RATED INPUT POWER W 124
RATED RUNNING CURRENT A 0.54
MOTOR OUTPUT W 66
MOTOR SPEED RPM 874
POLES 6
TYPE SCROLL
OIL TYPE FV50S
OIL AMOUNT cm3 / fl.oz. 1130 / 38
INSULATION GRADE E
COMPRESSOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
CAPACITOR µF 45
RATED INPUT POWER W 2499
RATED RUNNING CURRENT A 10.98
LOCKED ROTOR AMP. A 63
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
COIL MATERIAL ALUMINIUM
THICKNESS mm/in 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.61 / 6.58
ROW 2
FIN PER INCH 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

21
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series
INDOOR UNIT FDMN40CV1M
MODEL
OUTDOOR UNIT RN35DV1 RN40DY1
Btu/h 32,000 39,000
TOTAL COOLING CAPACITY
W 9,379 11,430
TOTAL INPUT POWER W 3,287 4,287
TOTAL RUNNING CURRENT - 1Ø [3Ø] A 15.2 [7.4]
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
REFRIGERANT TYPE R-410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
REFRIGERANT CHARGE kg/lb 2.00 / 4.41 2.32 / 5.11
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL (H/M/L) dBA 52 / 49 / 47 / 45
HEIGHT mm/in 315 / 12.4
UNIT
WIDTH mm/in 1257 / 49.5
DIMENSION
DEPTH mm/in 638 / 25.1
HEIGHT mm/in 355 / 14.0
PACKING
WIDTH mm/in 1461 / 57.5
DIMENSION DEPTH mm/in 727 / 28.6
UNIT WEIGHT kg/lb 49 / 108
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
S.HIGH l/s / CFM 604 / 1280
HIGH AIR HIGH l/s / CFM 547 / 1160
STATIC FLOW
FAN MEDIUM l/s / CFM 496 / 1050
FAN
MOTOR LOW l/s / CFM 434 / 920
ESP(H/M/L) Pa (in.wg.) 118 / 96 / 78 / 61 (0.47 / 0.39 / 0.31 / 0.24)
TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
DRIVE DIRECT
DIAMETER mm/in 214 / 8.43
LENGTH mm/in 203.2 / 8.00
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP21
FAN MOTOR INSULATION GRADE B
INDOOR UNIT

POWER SOURCE V/Ph/Hz 220-240 / 1 / 50


RATED INPUT POWER W 503
RATED RUNNING CURRENT A 2.27
MOTOR OUTPUT W 470
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
COIL mm/in 0.11 / 0.0043
THICKNESS
FIN FACE AREA m2/ft2 0.34 / 3.61
ROW 3
FIN PER INCH 18
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 2
AIR AIR
LENGTH mm/in 608 / 23.94
QUALITY FILTER
SIZE WIDTH mm/in 230 / 9.06
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
TM-FDBM-0515-C

3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

22
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series (COND’T)
INDOOR UNIT FDMN40CV1M
MODEL
OUTDOOR UNIT RN35DV1 RN40DY1
AIR FLOW l/s / CFM 1605 / 3400
SOUND PRESSURE LEVEL dBA 58
HEIGHT mm/in 852 / 33.5
UNIT
WIDTH mm/in 1030 / 40.6
DIMENSION DEPTH mm/in 400 / 15.7
HEIGHT mm/in 1010 / 39.8
PACKING
WIDTH mm/in 1180 / 46.5
DIMENSION DEPTH mm/in 514 / 20.2
UNIT WEIGHT kg/lb 86 / 190 95 / 209
TYPE FLARE VALVE
PIPE
LIQUID mm/in 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 15.88 / 5/8
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 610 / 24
TYPE INDUCTION
QUANTITY 1
OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP54


INSULATION GRADE B F
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR
RATED INPUT POWER W 257
RATED RUNNING CURRENT A 1.10
MOTOR OUTPUT W 145
MOTOR SPEED RPM 625
POLES 8
TYPE SCROLL
OIL TYPE POE OIL
OIL AMOUNT cm3 / fl.oz. 1242 / 42 1951 / 66
INSULATION GRADE E
COMPRESSOR POWER SOURCE V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
CAPACITOR µF 60 N/A
RATED INPUT POWER W 2527 3527
RATED RUNNING CURRENT - 1Ø [3Ø] A 11.83 [6.28]
LOCKED ROTOR AMP. - 1Ø [3Ø] A 97 [64]
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
COIL MATERIAL ALUMINIUM (CORR. FIN)
THICKNESS mm/in 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.85 / 9.15
ROW 2
FIN PER INCH 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

23
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series
INDOOR UNIT FDMN50CV1M FDMN60CV1M
MODEL
OUTDOOR UNIT RN50DY1 RN61DY1
Btu/h 45,000 55,000
TOTAL COOLING CAPACITY
W 13,189 16,120
TOTAL INPUT POWER W 4,931 5,758
TOTAL RUNNING CURRENT - 1Ø [3Ø] A [8.5] [9.4]
POWER SOURCE V/Ph/Hz 380-415 / 3 / 50
REFRIGERANT TYPE R-410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE & TXV
REFRIGERANT CHARGE kg/lb 2.10 / 4.63 2.90 / 6.39
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 52 / 51 54 / 52 / 50 / 46
HEIGHT mm/in 378 / 14.9
UNIT
WIDTH mm/in 1299 / 51.1 1499 / 59.0
DIMENSION
DEPTH mm/in 541 / 21.3
HEIGHT mm/in 415 / 16.3
PACKING WIDTH mm/in 1497 / 59.0 1701 / 67.0
DIMENSION
DEPTH mm/in 631 / 24.8
UNIT WEIGHT kg/lb 50 / 110 56 / 123
INDOOR CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4
S. HIGH l/s / CFM 675 / 1430 812 / 1720
HIGH
AIR HIGH l/s / CFM 623 / 1320 732 / 1550
STATIC
FLOW MEDIUM l/s / CFM 580 / 1230 632 / 1340
FAN
LOW l/s / CFM 533 / 1130 552 / 1170
MOTOR ESP (H/M/L) Pa (in.wg.) 147 / 126 / 109 / 92 (0.59 / 0.50 / 0.44/ 0.37) 147 / 120 / 90 / 69 (0.59 / 0.48 / 0.36 /0.28)
FAN
TYPE CENTRIFUGAL FAN
QUANTITY 2
MATERIAL GALVANIZED STEEL
INDOOR UNIT

DRIVE DIRECT
DIAMETER mm/in 214 / 8.43
LENGTH mm/in 203.2 / 8.00
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR
RATED INPUT POWER W 515 659
RATED RUNNING CURRENT A 2.32 2.91
MOTOR OUTPUT W 480 600
POLES 4
MATERIAL COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
COIL
THICKNESS mm/in 0.11 / 0.0043
FIN FACE AREA m2/ft2 0.40 / 4.40 0.47 / 5.16
ROW 3
FIN PER INCH 18 20
TYPE WASHABLE SARANET FILTER (OPTIONAL)
QUANTITY pc 2
AIR AIR
LENGTH mm/in 634 / 24.96 734 / 28.90
QUALITY FILTER
SIZE WIDTH mm/in 305 / 12.01
THICKNESS mm/in 5 / 0.20
CASING COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
TM-FDBM-0515-C

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR


4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

24
Specification (R-410A)
Ceiling Concealed Type - FDMN-C Series(COND’T)

INDOOR UNIT FDMN50CV1M FDMN60CV1M


MODEL
OUTDOOR UNIT RN50DY1 RN61DY1
AIR FLOW l/s / CFM 1442 / 3056
SOUND PRESSURE LEVEL dBA 60 65
HEIGHT mm/in 852 / 33.5
UNIT
WIDTH mm/in 1030 / 40.6
DIMENSION mm/in
DEPTH 400 / 15.7
HEIGHT mm/in 1010 / 39.8
PACKING
WIDTH mm/in 1180 / 46.5
DIMENSION DEPTH mm/in 514 / 20.2
UNIT WEIGHT kg/lb 98 / 216 105 / 231
TYPE FLARE VALVE
PIPE mm/in
LIQUID 9.52 / 3/8
CONNECTION SIZE
GAS mm/in 15.88 / 5/8 19.05 / 3/4
TYPE PROPELLER
QUANTITY 1
FAN MATERIAL ASG 20
DRIVE DIRECT
DIAMETER mm/in 610 / 24
TYPE INDUCTION
QUANTITY 1
OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP54


INSULATION GRADE F
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
FAN MOTOR
RATED INPUT POWER W 276
RATED RUNNING CURRENT A 1.34
MOTOR OUTPUT W 145
MOTOR SPEED RPM 625
POLES 8
TYPE SCROLL
OIL TYPE COPELAND ULTRA 32-3 MAF
OIL AMOUNT cm3 / fl.oz. 1656 / 56 1591 / 56
INSULATION GRADE E
COMPRESSOR POWER SOURCE V/Ph/Hz 380-415 / 3 / 50
CAPACITOR µF N/A
RATED INPUT POWER W 4140 4823
RATED RUNNING CURRENT - 1Ø [3Ø] A [7.28] [7.99]
LOCKED ROTOR AMP. - 1Ø [3Ø] A [74]
MATERIAL INNER GROOVE COPPER
TUBE DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.23 / 0.009
MATERIAL ALUMINIUM (CORR. FIN)
COIL
THICKNESS mm/in 0.10 / 0.004
FIN FACE AREA m2/ft2 0.85 / 9.15 0.84 / 9.04
ROW 2 3
FIN PER INCH 18
CASING COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW:
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION,
THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION
5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
TM-FDBM-0515-C

25
Safety Device - R-22 Series
STANDARD STATIC PRESSURE FDM30CV1M
INDOOR UNIT
MODEL NON STANDARD STATIC PRESSURE FDB30CV1M
OUTDOOR UNIT R30CV1
TYPE NC
HIGH PRESSURE SWITCH OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 124 / 18
CLOSE kPa / psi 193 / 28
PHASE SEQUENCER, 1Ø <3Ø> YES
DISCHARGE THERMOSTAT SETTING °C / °F 125 / 257

INDOOR UNIT STANDARD STATIC PRESSURE FDM40CV1M


MODEL NON STANDARD STATIC PRESSURE FDB40CV1M

OUTDOOR UNIT R35DV1 R40DY1

TYPE NC

HIGH PRESSURE SWITCH OPEN kPa / psi 2937 / 426


CLOSE kPa / psi 2413 / 350

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 124 / 18

CLOSE kPa / psi 193 / 28

PHASE SEQUENCER, 1Ø <3Ø> NA <YES>

DISCHARGE THERMOSTAT SETTING °C / °F NA <130 / 266>

STANDARD STATIC PRESSURE FDM50CV1M


INDOOR UNIT
MODEL NON STANDARD STATIC PRESSURE FDB50CV1M

OUTDOOR UNIT R50DY1

TYPE NC

HIGH PRESSURE SWITCH OPEN kPa / psi 2937 / 426

CLOSE kPa / psi 2413 / 350

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 124 / 18

CLOSE kPa / psi 193 / 28


PHASE SEQUENCER, 1Ø <3Ø> <YES>

DISCHARGE THERMOSTAT SETTING °C / °F <130 / 266>

STANDARD STATIC PRESSURE FDM60CV1M


INDOOR UNIT
NON STANDARD STATIC PRESSURE FDB60CV1M
MODEL
OUTDOOR UNIT R61DY1

TYPE NC

HIGH PRESSURE SWITCH OPEN kPa / psi 2937 / 426

CLOSE kPa / psi 2413 / 350


TM-FDBM-0515-C

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 124 / 18

CLOSE kPa / psi 193 / 28


PHASE SEQUENCER, 1Ø <3Ø> <YES>

DISCHARGE THERMOSTAT SETTING °C / °F <130 / 266>

26
Safety Device - R-410A Series
INDOOR UNIT FDMN40CV1M
MODEL
OUTDOOR UNIT RN35DV1 RN40DY1

TYPE NC

HIGH PRESSURE SWITCH OPEN kPa / psi 4137 / 600

CLOSE kPa / psi 3310 / 480

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 48 / 7

CLOSE kPa / psi 152 / 22


PHASE SEQUENCER, 1Ø <3Ø> NA <YES>
DISCHARGE THERMOSTAT SETTING °C / °F NA <130 / 266>

INDOOR UNIT FDMN50CV1M FDMN60CV1M


MODEL
OUTDOOR UNIT RN50DY1 RN61DY1

TYPE NC
HIGH PRESSURE SWITCH OPEN kPa / psi 4137 / 600

CLOSE kPa / psi 3310 / 480

SAFETY TYPE NC
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi 48 / 7

CLOSE kPa / psi 152 / 22


PHASE SEQUENCER, 1Ø <3Ø> <YES>

DISCHARGE THERMOSTAT SETTING °C / °F <130 / 266>


TM-FDBM-0515-C

27
4. Selection Process

Fan Performance Curve


FDM10CV1M
(High Static Blower)

7.00

LOW MED HIGH


6.00

5. 00
External Static Pressure, (mm w.g.)

4.00

3.00

2.00

1.00

0.00
200.00 250.00 300.00 350.00 400.00 450.00

Flowrate, (CFM)
TM-FDBM-0515-C

28
Fan Performance Curve
FDM15CV1M
(High Static Blower)

7.00

LOW MED HIGH


6.00

5.00
External Static Pressure, (mm w.g.)

4.00

3.00

2.00

1.00

0.00
300.00 350.00 400.00 450.00 500.00 550.00 600.00 650.00 700. 00 750.00 800.00

Flowrate, (CFM)
TM-FDBM-0515-C

29
Fan Performance Curve
FDM20CV1M
(High Static Motor)

7.00

6.00
LOW MED HIGH

5.00
External Static Pressure, (mm w.g.)

4.00

3.00

2.00

1.00

0.00
550.00 600.00 650.00 700.00 750.00 800.00 850.00 900.00 950. 00

Flowrate, (CFM)
TM-FDBM-0515-C

30
Fan Performance Curve
FDM25CV1M
(High Static Motor)

7.00

LOW MED HIGH


6.00

5.00
External Static Pressure, (mm w.g.)

4.00

3.00

2.00

1.00

0.00
400.00 450.00 500.00 550.00 600.00 650.00 700.00 750.00 800. 00 850.00 900.00

Flowrate, (CFM)
TM-FDBM-0515-C

31
Fan Performance Curve
FDM30CV1M
(High Static Blower)

13

12

11

10

9
Total Static Pressure, (mm w.g.)

0
400 500 600 700 800 900 1000 1100 1200

Flowrate, (CFM)
TM-FDBM-0515-C

32
Fan Performance Curve
FDM40CV1M
(High Static Blower)
13

12

11
Total Static Pressure, (mm w.g.)

10

0
400 500 600 700 800 900 1000 1100 1200 1300 1400

Flowrate, (CFM)
TM-FDBM-0515-C

33
Fan Performance Curve
FDM50CV1M
(High Static Blower)
15

14

13

12

11
Total Static Pressure, (mm w.g.)

10

0
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

Flowrate, (CFM)
TM-FDBM-0515-C

34
Fan Performance Curve
FDM60CV1M
(High Static Blower)
15

14

13

12

11

10
Total Static Pressure, (mm w.g.)

0
1200 1300 1400 1500 1600 1700 1800 1900 2000

Flowrate, (CFM)
TM-FDBM-0515-C

35
Fan Performance Curve
FDB10CV1M
(Low Static Motor)

5.00

4.50

LOW MED HIGH


4.00
External Static Pressure, (mm w.g.)

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0.00
100.00 150.00 200.00 250.00 300.00 350.00

Flowrate, (CFM)
TM-FDBM-0515-C

36
Fan Performance Curve
FDB15CV1M
(Low Static Motor)

5.00

4.50

LOW MED HIGH


4.00
External Static Pressure, (mm w.g.)

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0.00
200.00 250.00 300.00 350.00 400.00 450.00 500.00 550.00 600. 00 650.00

Flowrate, (CFM)
TM-FDBM-0515-C

37
Fan Performance Curve
FDB20CV1M
(Low Static Motor)

5.00

4.50

LOW MED HIGH


4.00
External Static Pressure, (mm w.g.)

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0.00
450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00

Flowrate, (CFM)
TM-FDBM-0515-C

38
Fan Performance Curve
FDB25CV1M
(Low Static Motor)

5.00

4.50

LOW MED HIGH


4.00
External Static Pressure, (mm w.g.)

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0.00
450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00 850. 00

Flowrate, (CFM)
TM-FDBM-0515-C

39
Fan Performance Curve
FDB30CV1M
(Low Static Blower)

5
Total Static Pressure, (mm w.g.)

0
550 650 750 850 950 1050

Flowrate, (CFM)
TM-FDBM-0515-C

40
Fan Performance Curve
FDB40CV1M
(Low Static Blower)
5

4
Total Static Pressure, (mm w.g.)

0
850 950 1050 1150 1250 1350

Flowrate, (CFM)
TM-FDBM-0515-C

41
Fan Performance Curve
FDB50CV1M
(Low Static Blower)

4
Total Static Pressure, (mm w.g.)

0
1100 1200 1300 1400 1500 1600 1700

Flowrate, (CFM)
TM-FDBM-0515-C

42
Fan Performance Curve
FDB60CV1M
(Low Static Blower)
6

5
Total Static Pressure, (mm w.g.)

0
1400 1500 1600 1700 1800 1900

Flowrate, (CFM)
TM-FDBM-0515-C

43
Fan Performance Curve
FDMN10CV1M

3.5

3.0

H
M
L
2.5
External Static Pressure, (mm w.g.)

2.0

1.5

1.0

0.5

0.0
TM-FDBM-0515-C

100 200 300 400

Flowrate, (CFM)

44
Fan Performance Curve
FDMN15CV1M

3.5

3.0

H
M

L
2.5
External Static Pressure, (mm w.g.)

2.0

1.5

1.0

0.5
TM-FDBM-0515-C

0.0
300 350 400 450 500

Flowrate, (CFM)

45
Fan Performance Curve
FDMN20CV1M

3.5

3.0

H
M
L
2.5
External Static Pressure, (mm w.g.)

2.0

1.5

1.0

0.5

0.0
TM-FDBM-0515-C

400 500 600 700

Flowrate, (CFM)

46
Fan Performance Curve
FDMN25CV1M

3.5

3.0

H
M
L
2.5
External Static Pressure, (mm w.g.)

2.0

1.5

1.0

0.5

0.0
TM-FDBM-0515-C

400 500 600 700 800

Flowrate, (CFM)

47
Fan Performance Curve
FDMN30CV1M

14

12
SH
H

L M

10
External Static Pressure, (mm w.g.)

0
TM-FDBM-0515-C

200.00 400.00 600.00 800.00 1000.00 1200.00

Flowrate, (CFM)

48
Fan Performance Curve
FDMN40CV1M

15

SH
H
M

L
Total Static Pressure, (mm w.g.)

10

0
TM-FDBM-0515-C

600 800 1000 1200 1400 1600

Flowrate, (CFM)

49
Fan Performance Curve
FDMN50CV1M

25

20

SH

M
Total Static Pressure, (mm w.g.)

15

10

0
TM-FDBM-0515-C

1000 1200 1400 1600 1800

Flowrate, (CFM)

50
Fan Performance Curve
FDMN60CV1M

25

20
SH
H

M
Total Static Pressure, (mm w.g.)

15

10

0
TM-FDBM-0515-C

1000 1200 1400 1600 1800 2000 2200

Flowrate, (CFM)

51
5. Application Information
Ensure the operating temperature is in allowable range.

Cooling Only

52
High ambient
unit
46
! Caution :
Outdoor temp. (°CDB)

Standard
35 point The use of your air conditioner
outside the range of working
temperature and humidity can
19
result in serious failure.

Low ambient kit

-5

15 24
Indoor temp. (°CWB)

Note :

Standard operating range.

With High ambient unit. (Optional item)


Please refer to local dealer for unit of this specification.

With Low ambient kit. (Optional item)


Please refer to local dealer for unit of this specification.
TM-FDBM-0515-C

52
Model : (Indoor) FDB10CV1M, FDM10CV1M, FDB15CV1M, FDM15CV1M,
FDB20CV1M, FDM20CV1M, FDMN10CV1M, FDMN15CV1M,
FDMN20CV1M, FDMN25CV1M
(Outdoor) R10CV1, R15CV1, R20CV1, RN10FV1, RN15FV1, RN18CV1,
RN20CV1, RN25CV1

Model : (Indoor) FDB25CV1M, FDM25CV1M, FDMN30CV1M


(Outdoor) R20CV1, R25CV1, RN28CV1
TM-FDBM-0515-C

53
Model : (Indoor) FDM30CV1M, FDB30CV1M;
(Outdoor) R28CV1, R30CV1

Model : (Indoor) FDM40CV1M, FDB40CV1M, FDM50CV1M, FDB50CV1M,


FDM60CV1M, FDB60CV1M;
(Outdoor) R35DV1, R40DY1, R50DY1, R61DY1

TM-FDBM-0515-C

54
Model : (Indoor) FDMN40CV1M, FDMN50CV1M, FDMN60CV1M;
(Outdoor) RN35DV1, RN40DY1, RN50DY1, RN61DY1
TM-FDBM-0515-C

55
Controller

DSLM8

3
2 4
1 MODE
TURBO SWING QUIET

5
8 TIMER
OVERRIDE
TIMER
ON
TIMER
OFF SLEEP

7 6
9 10
11

Operating Guide

1 MODE Button
Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to
see in which mode the control is set. *AUTO and DRY are available for selected models only.

2 TURBO Fan Speed


Press the Turbo key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo
fan speed and back to previous fan speed, press the Turbo key once again. For the unit that does
not have TURBO fan speed it will show high fan speed.

3 SWING Function
Press SWING button to activate the swing function. Press it again to deactivate it.

4 QUIET Fan Speed


Press the Quiet key once to activate Quiet fan speed. Quiet symbol will be shown. To disable Quiet
fan speed and back to previous fan speed, press the Quiet key once again. For the unit that does
not have QUIET fan speed it will show low fan speed.

5 “ ” or “ ” Set Temperature Button


Press the temperature button and set the temperature of your choice by pressing “ ” or “ ” button
once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to
30°C (60°F to 86°F). When the Option 20 - 30ºC is set, the temperature range limit is set to 20ºC to
30ºC (68°F to 86°F). Pressing both keys simultaneously will toggle the temperature setting between
ºC and ºF.
TM-FDBM-0515-C

6 SLEEP Function
Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid
during sleep function.

56
7 “ON TIMER” and “OFF TIMER”
The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF
TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1
Table 1.1: Timer ON and Timer OFF key press and event sequence.

TIMER ON KEY TIMER OFF KEY


ON Timer 1 ON Timer 2 OFF Timer 1 OFF Timer 2
Deactivated Deactivated Deactivated Deactivated
Activated Deactivated Activated Deactivated
Deactivated Activated Deactivated Activated
Activated Activated Activated Activated

All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.
Set Event 1 and Event 2 Timers
Process for Timer ON and Timer OFF is the same.
1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or
OFF 1 will blink)
2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is
currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)
3. Press Timer ON/OFF key again to confirm. (Day will blink next)
4. Press UP or DOWN to select the day.
5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)
4. Press UP or DOWN to change the hour.
5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)
6. Press UP or DOWN to change the minute.
7. Press Timer ON/OFF key again to confirm the minute.
Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately
after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will
automatically exits from setting mode and no changes will be made.
ON/OFF timer will be checked every 1 minute.
It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the
effective timer will be treated with priority as stated in Table 1.2.
Example:
ON TMR 2 settings: DAY – TUE, TIMER – 5.00pm
OFF TMR 1 settings: DAY – TUE, TIMER – 5.00pm
Outcome when RTC reaches 5.00pm on TUE:
- when unit is on, no respond.
- when unit is off, unit will trigger to on.

Table 1.2: Timer Priority

Priority Timer
1 (Highest) ONTMR2
2 OFFTMR2
3 ONTMR1
4 (Lowest) OFFTMR1
Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.
TM-FDBM-0515-C

57
8 OVERRIDE Function
Press the OVERRIDE key once will activate the override function for 1 hour. An indicator
“OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours.
An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function.
After the override timer is completed, the override function is deactivated and the logo is OFF. All
other timers will be resumed.

9 FAN Speed Function


Fan speed can be changed via pressing the FAN key:
Low > Med > High > Auto > Low >

10 ON/OFF Button
Starting Operation:
- Press the ON/OFF button, the LCD will show full display and the unit is turned on.
Stopping Operation:
- Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.

11 Real-time Clock (RTC) Display


RTC is shown on screen during the unit ON or OFF except for power failure or error code.

Set RTC Setting


1. Press RTC key one time will activate RTC setting mode. (Day will blink)
2. Press UP or DOWN to select the day.
3. Press RTC again to confi rm the day. (Hour will blink next)
4. Press UP or DOWN to change the hour.
5. Press RTC again to confi rm the hour. (Minute will blink next)
6. Press UP or DOWN to change the minute.
7. Press RTC again to confi rm the minute.
RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting the
RTC, it will automatically exits from setting mode and no changes will be made on the setting.

12 Hardware Setting
The unit has 4 jumpers option to control the board function.
Table 2.0: Summary of Hardware Settings

OPTION With Jumper Without Jumper

Set Temp. Range from 16˚C-30˚C


Set Temp. Range Set Temp. Range from 20˚C-30˚C
(Default)

Disable turbo and quiet fan speed


TURBO_QUIET Enable turbo and quiet fan speed
(Default)

Reserved Reserved Reserved


Reserved Reserved Reserved
TM-FDBM-0515-C

58
Operating State And Fault Table
Wired Remote Control (Universal Board)
Cooling

Error Code at 7 Segment Display Operation / Faulty Indication


Blink E1 Room sensor contact open / short
Blink E2 Indoor coil sensor contact open
Blink E3 Outdoor coil sensor contact open
Blink E4 Compressor overload/ Indoor coil sensor
short/Outdoor coil sensor short
Blink E5 Gas leak
Blink E6 Pump faulty

Phase Sequencer
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device
(phase sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases
are not connected correctly, the phase sequencer operates, and the unit will not start. This devise is
located in the control box of the outdoor unit.

The following table shows the LED indicator light for phase sequencer under normal operation and fault
conditions.

LED_PWR LED_S LED_T


LEDs Error Indication
(Red) (Yellow) (Yellow)
Normal Operation On - -
Reverse Phase Blink Blink Blink
T Phase Missing On - Blink
S Phase Missing On Blink -
R Phase Missing Blink - -
R Phase Missing (Main Power) System Off
Overload Blink Blink On
Sensor Missing Blink Blink -
High Pressure On On -
Low Pressure On - On

Notes: 1. “-” means LED off.


2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common)
and 81(NO) will cut off.
3. The unit will check the discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
TM-FDBM-0515-C

59
6. Installations
Installation Guideline
Safety Precautions

WARNING
• Installation and maintenance should be performed by quali�ed persons who are familiar with local code
and regulation, and experienced with this type of appliance.
• All field wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.
• Confirm that the unit has been switched OFF before installing or servicing the unit.
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which
may result in fire hazards.
• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios,
to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static
may be heard even when more than 1m away}.

CAUTION
Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.

• Ensure that drainage piping is connected properly.


If the drainage piping is not connected properly, it may cause water leakage which will
dampen the furniture.
• Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
• Ensure that the unit’s panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

• Sharp edges and coil surfaces are potential locations which may cause injury hazards.
Avoid from being in contact with these places.
• Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning
automatically when power resumes, posing a hazard to service personnel or the user.
• Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic
panel to melt or deform as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.

• IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
• Do not use joined and twisted wires for incoming power supply.

NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic
products shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment
of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with
TM-FDBM-0515-C

relevant local and national legislation. Air conditioners must be treated at a specialized treatment
facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will
help to prevent potential negative consequences for the environment and human health. Please
contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with
relevant local and national legislation.

60
Installation Diagram

Indoor Unit

Hanger

Return Duct

Supply Duct
Wrap the insulated pipe with
the finishing tape from bottom to top
Drain Piping Thermal Insulation
Air Intake

Air Intake

Air Discharge Outdoor Unit


TM-FDBM-0515-C

61
Installation Of Indoor Unit
The indoor unit must be installed such that there is
no short circuit of the cool discharge. Respect the
W
installation clearance. Do not put the indoor unit
where there is direct sunlight on unit. The location is
suitable for piping and drainage and it must have a
large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong
Model L mm (inch) W mm (inch)
to withstand the weight.
FDB10CV1M, FDM10CV1M, FDMN10CV1M 741 (29.2) 225 (8.9)
FDB15CV1M, FDM15CV1M, FDMN15CV1M 881 (34.7) 225 (8.9)
See Detail
Insulation material
(field supply)
FDB20CV1M, FDM20CV1M, FDMN20CV1M 1041 (41.0) 225 (8.9)
Air inlet side
Air outlet side
FDB25CV1M, FDM25CV1M, FDMN25CV1M 1176 (46.3) 225 (8.9)
FDMN30CV1M 959 (37.8) 339 (13.3)
FDM30CV1M, FDB30CV1M 956 (37.6) 256 (101)
Aluminium tape Aluminium tape FDMN40CV1M 1264 (49.8) 401 (15.8)
(Field supply) (Field supply)
FDM40CV1M, FDB40CV1M 1076 (42.4) 256 (10.1)
Field Supply
FDM50CV1M, FDB50CV1M, FDMN50CV1M 1326 (52.2) 256 (10.1)
FDM60CV1M, FDB60CV1M, FDMN60CV1M 1526 (60.1) 256 (10.1)
Washer for hanger bracket
(Attached)
Provide clearance for servicing ease and optimal
Tighten air flow as shown in the diagram.

Detail A
300mm
Center distance of axle (see drawing below) or more

L
10mm

300mm* or more Ceiling

2300mm or more
Floor
* Can be smaller than 300mm if ceiling is removable.

Ceiling Concealed Drain Piping Work


10mm (0.39”)

Bottom of the unit


Slant

or more or more
100 100

Drain trap

Do not leave in water

Insulate securely Unit: mm

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
TM-FDBM-0515-C

• Ensure the drain pipe is securely insulated.


• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

62
Installation Of The Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve
maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements:
• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor
condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow
sufficient space for maintenance around the unit.

• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air
intake or discharge.
• The location must be well ventilated, so that the unit can draw in and distribute of air thus lowering the
condensing temperature.

• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.

• The location must not be susceptible to dust or oil mist.

Installation Clearances
Dimension Note: If there is any obstacle higher than 2m, or if
A B C D
there is any obstruction at the upper part of the unit,
Minimum Distance, 300 1000 300 500 please allow more space than the figure indicated in
mm (in) (11.8) (39.4) (11.8) (19.7) the above table.

A B
C D
TM-FDBM-0515-C

Discharge air

Service access
Return air

Return air
Obstacle
Obstacle

Obstacle
Obstacle

63
Refrigerant Piping
Allowable Pipe Length and Elevation
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends
increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a
result, the compressor may become defective. Always choose the shortest path and follow the
recommendations as tabulated below:

For R22
Standard Static Pressure FDB10CV1M FDB15CV1M FDB20CV1M FDB25CV1M
Indoor
Model Non-Standard Static Pressure FDM10CV1M FDM15CV1M FDM20CV1M FDM25CV1M
Outdoor R10CV1 R15CV1 R20CV1 R25CV1
Max. allowable length, m 12 12 15 15
Max. allowable elevation, m 5 5 8 8
6.35 6.35 6.35 9.52
Liquid pipe size, mm/(in)
(1/4”) (1/4”) (1/4”) (3/8”)
9.52 12.70 15.88 15.88
Gas pipe size, mm/(in)
(3/8”) (1/2”) (5/8”) (5/8”)

Standard Static Pressure FDM30CV1M FDM40CV1M FDM50CV1M FDM60CV1M


Indoor
Model Non-Standard Static Pressure FDB30CV1M FDB40CV1M FDB50CV1M FDB60CV1M
Outdoor R28CV1 R30CV1 R35DV1 R40DY1 R50DY1 R61DY1
Max. allowable length, m 15 25 45 45 45 35
Max. allowable elevation, m 8 8 25 25 25 15
9.52 9.52 9.52 9.52 9.52 12.70
Liquid pipe size, mm/(in)
(3/8”) (3/8”) (3/8”) (3/8”) (3/8”) (3/8”)
15.88 15.88 19.05 19.05 19.05 19.05
Gas pipe size, mm/(in)
(5/8”) (5/8”) (3/4”) (3/4”) (3/4”) (3/4”)

For R410A
Indoor FDMN10CV1M FDMN15CV1M FDMN20CV1M FDMN25CV1M
Model
Outdoor RN10FV1 RN15FV1 RN20CV1 RN25CV1
Max. allowable length, m 20 20 20 20
Max. allowable elevation, m 10 10 10 10
6.35 6.35 6.35 6.35
Liquid pipe size, mm/(in)
(1/4”) (1/4”) (1/4”) (1/4”)
9.52 12.70 12.70 15.88
Gas pipe size, mm/(in)
(3/8”) (1/2”) (1/2”) (5/8”)

Indoor FDMN30CV1M FDMN40CV1M FDMN50CV1M FDMN60CV1M


Model
Outdoor RN28CV1 RN35DV1 RN40DY1 RN50DY1 RN61DY1
Max. allowable length, m 15 45 45 45 35
Max. allowable elevation, m 8 25 25 25 15
9.52 9.52 9.52 9.52 9.52
Liquid pipe size, mm/(in)
(3/8”) (3/8”) (3/8”) (3/8”) (3/8”)
15.88 15.88 15.88 15.88 19.05
Gas pipe size, mm/(in)
(5/8”) (5/8”) (5/8”) (5/8”) (3/4”)
TM-FDBM-0515-C

64
Piping Works And Flaring Technique
Figure A
• Do not use contaminated or damaged copper Cutting copper tube
tubing. If any piping, evaporator or condenser had
1/4t
been exposed or had been opened for 15 seconds
or more, the system must be vacuumed.
Generally do not remove plastic, rubber plugs and
brass nuts from the valves, fittings, tubing and
coils until it is ready to connect suction or liquid
line into valves or fittings.
• If any brazing work is required, ensure that Figure B
nitrogen gas is passed through coil and joints
while the brazing work is being done. This will
eliminate soot formation on the inside wall of Remove burr
copper tubings.
• Cut the pipe stages by stages, advancing the
blade of pipe cutter slowly. Extra force and a
deep cut will cause more distortion of pipe and
therefore extra burr. See Figure A. Figure C
• Remove burrs from cut edges of the pipes with Copper tube D
remover. See Figure B. Hold the pipe on top Swaging block

A
position and burr remover at lower position to
prevent metal chips from entering the pipe. This
will avoid unevenness on the flare faces which
will cause gas leak.
• Insert the flare nuts, mounted on the connection
parts of both the indoor unit and outdoor unit, Ø Tube, D A (mm)
into the copper pipes.
Inch mm Imperial Rigid
• The exact length of pipe protruding from the top (Wing-nut Type) (Clutch Type)
surface of the swaging block is determined by
the flaring tool. See Figure C. 1/4" 6.35 1.3 0.7
• Fix the pipe firmly on the swaging block. Match the 3/8" 9.52 1.6 1.0
centers of both the swaging block and the flaring 1/2" 12.70 1.9 1.3
punch, then tighten the flaring punch fully.
5/8" 15.88 2.2 1.7
Piping Connection To The Units 3/4" 19.05 2.5 2.0
• Align the center of the piping and tighten the
flare nut sufficiently with fingers. See Figure D.
Figure D
• Finally, tighten the flare nut with torque wrench Flare joint Flared tube
until the wrench clicks.
• When tightening the flare nut with the torque
wrench, ensure that the tightening direction
follows the arrow indicated on the wrench.
Indoor piping Flare nut
• The refrigerant pipe connection are insulated by
closed cell polyurethane.

Pipe Size Torque


(mm/in) (Nm/ft-lb)
6.35 (1/4") 18 (13.3)
TM-FDBM-0515-C

9.52 (3/8") 42 (31.0)


12.70 (1/2") 55 (40.6)
15.88 (5/8") 65 (48.0) Torque wrench
Spanar
19.05 (3/4") 78 (57.6)

65
Vacuuming And Charging
Vacuuming is necessary to eliminate all moisture and air from the system.
Vacuuming The Piping And The Indoor Unit • Open the gas cylinder and low pressure
Except for the outdoor unit which is pre-charged charging valve.
with refrigerant, the indoor unit and the refriger- • When the required refrigerant quantity is
ant connection pipes must be air-purged pumped into the unit, close the low pressure
because the air containing moisture that remains side and the gas cylinder valve.
in the refrigerant cycle may cause malfunction of • Disconnect the service hose from service port.
the compressor. Put back the service port cap.
• Remove the caps from the valve and the
service port.
Allen key Refrigerant Piping
• Connect the center of the charging gauge to Flare nut
the vacuum pump.
• Connect the charging gauge to the service port
of the 2-way valve.
• Start the vacuum pump. Evacuate for approxi-
mately 30 minuted. The evacuation time varies Service Port Outdoor Unit 3 ways valve
with different vacuum pump capacity. Confirm
that the charging gauge needle has moved
towards - 760mmHg.
LOW PRESSURE GAUGE HIGH PRESSURE GAUGE
-760mmHg
Caution GAUGE MANIFOLD

• If the gauge needle does not move to HANDLE LO HANDLE HI (ALWAYS CLOSED)
-760mmHg, be sure to check for gas leaks CHARGE HOSE
(using the refrigerant detector) at fl are type CHARGE HOSE VACUUM PUMP
ADAPTER FOR
connection of the indoor and outdoor unit and COUNTER FLOW
repair the leak before proceeding to the next PREVENTION
LIQUID
step. VALVE
CHECK
• Close the valve of the changing gauge and GAS VALVE VALVE
(3-WAY)
stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 CONFIGURATION OF AIR PURGE
BY CHARGING
way) and liquid valve (2 way) (in anti-clockwise
direction) with 4mm key for hexagon sacked
screw. LOW PRESSURE GAUGE HIGH PRESSURE GAUGE

-760mmHg GAUGE MANIFOLD


Charge Operation
This operation must be done by using a gas HANDLE LO HANDLE HI (ALWAYS CLOSED)
cylinder and a precise weighing machine. The CHARGE HOSE
CHARGE HOSE
additional charge is topped-up into the outdoor
unit using the suction valve via the service port. CHECK
VALVE
• Remove the service port cap. LIQUID
• Connect the low pressure side of the charging VALVE
GAS VALVE
gauge to the suction service port center of the (3-WAY)
cylinder tank and close the high pressure side
CONFIGURATION OF AIR PURGE
of the gauge. Purge the air from the service BY CHARGING
hose.
• Start the air conditioner unit.
TM-FDBM-0515-C

66
Additional Charge
The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then
additional charge after vacuuming is not necessary. When the piping length is more than 7.5m, use
the table below.

For R22

Standard Static Pressure FDB10CV1M FDB15CV1M FDB20CV1M FDB25CV1M FDM30CV1M


Indoor
Model Non-Standard Static Pressure FDM10CV1M FDM15CV1M FDM20CV1M FDM25CV1M FDB30CV1M

Outdoor R10CV1 R15CV1 R20CV1 R25CV1 R28CV1 R30CV1

Additional charge [g/m] 16 16 16 39 41 55

Standard Static Pressure FDM40CV1M FDM50CV1M FDM60CV1M


Indoor
Non-Standard Static Pressure FDB40CV1M FDB50CV1M FDB60CV1M
Model
Outdoor R35DV1 R40DY1 R50DY1 R61DY1

Additional charge [g/m] 54 55 54 102

For R410A

Indoor FDMN10CV1M FDMN15CV1M FDMN20CV1M FDMN25CV1M FDMN30CV1M


Model
Outdoor RN10FV1 RN15FV1 RN20CV1 RN25CV1 RN28CV1
Additional charge [g/m] 18 18 20 20 33

Indoor FDMN40CV1M FDMN50CV1M FDMN60CV1M


Model
Outdoor RN35DV1 RN40DY1 RN50DY1 RN61DY1
Additional charge [g/m] 23 26 23 32

Example:
FDB10CV1M / FDM10CV1M & R10CV1 with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 16[g/m]
= 88[g]
TM-FDBM-0515-C

67
Special Precaution When Charging Unit With Scroll Compressor
These precautions are intended for use with Scroll compressors only with R22 and R410A refrigerants
but are not applied to others competitive Scroll compressors.
Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there
is insufficient refrigerant in the system or if refrigerant is added too slowly. Operation with low suction
pressure will quickly lead to very high discharge temperatures. While this process is happening, the
scrolls are not being well lubricated – scrolls depend on the oil mist in the refrigerant for lubrication.
A lack of lubrication leads to high friction between the scroll flanks and tips and generates additional
heat. The combination of heat of compression and heat from increased friction is concentrated in a
small localized discharge area where temperatures can quickly rise to more than 300°C. These extreme
temperatures damage the Scroll spirals and the orbiting Scroll bearing. This damage can occur in less
than one minute especially on larger compressors. Failure may occur in the first few hours or the damage
done during field charging may show up some time later. Other typical field charging problems include
undercharging, overcharging, moisture or air in the system etc. In time each one of these problems can
cause compressor failure.
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory
job is:-
1. Set of service gauges 4. Vacuum gauge
2. Hoses 5. Scales
3. Vacuum pump 6. Thermometer

The proper refrigerant charge should follow the volume as recommended by manufacturer and
recommendation should be followed by the installer.
1. Charging procedures – Single phase compressors
Evacuate the system to -760mmHg. To reduce evacuation time, use short, large diameter hoses an
connect to unrestricted service ports on the system. Quality of vacuum cannot be determined by time
– a reliable vacuum gauge must be used. (etc. electronic vacuum gauge)
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the
liquid line charging port until refrigerant no longer flows or until the correct charge has been weighed
in. If additional charge is required start the system and slowly bleed liquid into the suction side until
the system is full.
It recommends charging liquid in a CONTROLLED manner into the suction side until the
system is full. This recommendation does not hold true for reciprocating compressors where liquid
charging into the suction side could cause severe damage.
Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not
fall below 25 psig (1.7 bar) at any time during the charging process.

Invert cylinder
Dip-pipe without dip-pipe

Liquid withdrawal
TM-FDBM-0515-C

! CAUTION
• Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder
valve and Manifold valve “A” are both open.

68
There are many ways of charging liquid in a “controlled
manner” into the suction side:-
1. Use valve A on the manifold gauge set
2. Use the valve on the refrigerant cylinder
3. Charge through a Shredder valve
4. Use a hose with a Shredder valve depressor
5. Charge into the suction side at some distance
from the compressor
A 6. All of the above

2. Charging procedures – Three phase compressors


The fundamental procedure is the same as for single phase models but the compressor can run in
the wrong direction on starting. If this happens reverse any two phases and start again. Short term
reverse rotation will not damage the compressor.
All Specter compressors have internal discharge temperature protectors which are very effective in
preventing dangerously high discharge temperatures during charging. The protection module will trip
and lock the compressor out for 30 minutes. It is not normally necessary to wait 30 minutes for the
module to reset. When the compressor has cooled down the module can be reset by breaking the
power supply to the control circuit. Very often the serviceman does not understand why the module
tripped and uses a jumper wire to bypass it. He continues to charge the system and removes the
jumper when charging is complete. The compressor may or may not run with the protector back in the
circuit but it is certain that the compressor has been damaged and premature failure is inevitable.
TM-FDBM-0515-C

69
Special Precautions When Dealing With Refrigerant R410A Unit

(1) What is New Refrigerant R410A?


R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of
this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper
installation / servicing is essential.

(2) Components
Mixture weight composition R32(50%) and R125(50%)

(3) Characteristic
• R410A liquid and vapour components have different compositions when the fluid
evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition
of the refrigerang mixture left in the system will change and subsequently affect the system
performance. DO NOT add new refrigerant to leaked system. It is recommended that the system
should be evacuated thoroughly before recharging with R410A.
• When refrigerant R410A is used, the composition will differ depending on whether it is in
gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn
from the cylinder or can. This is to make certain that only original composition of R410A is being
charged into the system.
• POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for
R22 compressor. Extra precaution must be taken not to expose the R410A system too long to
moist air.

(4) Check List Before Installation / Servicing


• Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make
sure to temporarily cover the ends of the tubing prior to installation.
• Compressor oil
No additional charge of compressor oil is permitted.
• Refrigerant
No other refrigerant other that R410A
• Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
i) Gauge manifold and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v) Flare tools
vi) Refrigerant recovery machine

(5) Handling and Installation Guildelines


Like R22 system, the handling and installation of R410A system are closely similar. All
precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing
using nitrogen, and thorough leak check and vacuuming are equally important requirements.
However, due to it hydroscopic POE oil, additional precautions must be taken to ensure optimum
and trouble free system operation.
(a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant
system to moist air. Residual POE oil in the piping and components can absorb moisture from
the air.
(b) Ensure that the compressor is not exposed to open air for more than the recommended time
TM-FDBM-0515-C

specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when
the compressor is about to be brazed.
(c) The system should be thoroughly vacuumed to 1.0 Pa (700mmHg) or lower. This vacuuming
level is more stringent than R22 system so as to ensure no incompressible gas and moisture
in the system.

70
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is
to ensure that only the original composition of R410A is being delivered into the system. The liquid
composition can be different from the vapor composition.

Dip-pipe Invert cylinder


without dip-pipe

Liquid
withdrawal

e) Normally, the R410A cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However
, if the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at
the bottom.
TM-FDBM-0515-C

71
7. Wiring Diagrams
Indoor Unit
Model : FDB10CV1M, FDM10CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : R10CV1

72
Indoor Unit
Model : FDMN10CV1M

Outdoor Unit
Model : RN10FV1
TM-FDBM-0515-C

73
Indoor Unit
Model : FDB15CV1M, FDM15CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : R15CV1

74
Indoor Unit
Model : FDMN15CV1M

Outdoor Unit
Model : RN15FV1
TM-FDBM-0515-C

75
Indoor Unit
Model : FDB20/25CV1M, FDM20/25CV1M

Outdoor Unit
Model : R18/20/25CV1
TM-FDBM-0515-C

76
Indoor Unit
Model : FDMN20/25CV1M

Outdoor Unit
Model : RN20/25CV1
TM-FDBM-0515-C

77
Indoor Unit
Model : FDM30CV1M, FDB30CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : R28CV1

78
Indoor Unit
Model : FDMN30CV1M
TM-FDBM-0515-C

Outdoor Unit
Model : RN28CV1

79
Indoor Unit
Model : FDM30CV1M, FDB30CV1M

1 PHASE E
220~415VAC 50 Hz OR N
208~230VAC 60 Hz L

TM-FDBM-0515-C

Outdoor Unit
Model : R30CV1

80
Indoor Unit
Model : FDM40CV1M, FDB40CV1M

1 PHASE E
220~415 VAC 50 Hz OR N
208~230 VAC 60 Hz L
TM-FDBM-0515-C

Outdoor Unit
Model : R35DV1

81
Indoor Unit
Model : FDMN40CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : RN35DV1

82
Indoor Unit
Model : FDM40/50CV1M, FDB40/50CV1M

E
N
380~415 V T
3PH 50Hz S
R
TM-FDBM-0515-C

Outdoor Unit
Model : R40/50DY1

83
Indoor Unit
Model : FDMN40/50CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : RN40/50DY1

84
Indoor Unit
Model : FDM60CV1M, FDB60CV1M

E
N
380~415 V T
3PH 50Hz S
R
TM-FDBM-0515-C

Outdoor Unit
Model : R61DY1

85
Indoor Unit
Model : FDMN60CV1M

TM-FDBM-0515-C

Outdoor Unit
Model : RN61DY1

86
8. Servicing and Maintenance

Warning: Disconnect from main supply before servicing the air conditioner

The unit is designed to give long life operation with minimum maintenance required. However, it should
be regularly checked and the following items should be given due attention.

Components Maintenance Procedures Recommended Schedule


Air Filter 1. Remove any dust adhering to the filter by using a At least once every 2 weeks.
(Indoor Unit) vacuum cleaner or wash in lukewarm water (below More frequently if necessary.
40˚C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto
the unit.
3. Note: Never use gasoline, volatile substances or
chemicals to clean the filter.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it At least once every 2 weeks.
with a soft cloth soaked in lukewarm water (below More frequently if necessary.
40˚C) and a neutral detergent solution.
2. Note: Never use gasoline, volatile substances or
chemicals to clean the indoor unit.
Condense Drain 1. Check the cleanliness and clean it if necessary. Every 3 months.
Pan & Pipe 2. Check the condensate water flow.
Indoor Fan Check if there is any abnormal noise. If necessary.
Indoor / Outdoor 1. Check and remove the dirt between the fins. Every month.
Coil 2. Check and remove any obstacles which hinder air flow
through the indoor or outdoor.
Power Supply 1. Check the running current and voltage for indoor and Every 2 months.
outdoor unit.
2. Check the electrical wiring and tighten the wire onto the Every year.
terminal block if necessary.
Compressor No maintenance needed if refrigerant circuit remains Every 6 months.
sealed. However, check for refrigerant leak at joint and
fitting.
Compressor Oil Oil is factory charged. Not necessary to add oil if circuit No maintenance required.
remains sealed.
Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.

Pre Start Up Maintenance


(After Extended Shut Down)

- Inspect thoroughly and clean indoor and outdoor units.


- Clean or replace air filters.
- Clean condensates drain line.
- Clean clogged indoor and outdoor coils.
- Check fan imbalance before operation.
- Tighten all wiring connections and panels.
- Check for refrigerant leakage.
TM-FDBM-0515-C

87
9. Troubleshooting
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply
before proceeding with the following troubleshooting procedures.
The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which
are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.

No Fau l t c o n d i t i o n s Po s s i b l e c au s es / c o r r ec t i v e ac t i o n s

1 The air conditioner unit will not resume after • The auto restart function is not functioning. Please
power failure. turn on the unit with the wireless / wired controller.

2 The compressor does not operate 3 minutes • Protection against frequent starting.
after the air conditioner unit is started. • Wait for 3 or 4 minutes for the compressor to start
operating by it self.

3 The airflow is too slow or room cannot be • The air filter is dirty.
cooled sufficiently. • The doors and windows are opened.
• The air suction and discharge of both indoor and
outdoor units are clogged or blocked.
• The regulated temperature or temperature setting
is not low enough.

4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,
which might have adhered onto the coil, may
cause odor.
• Contact your nearest dealer.

5 Condensation on the front air grille of the • This is caused by air humidity after an extended
indoor unit. period of operation.
• The set temperature is too low. Increase the
temperature setting and operate the unit at high
fan speed.

6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest
dealer. This might be due to tilted installation.

7 Hissing airflow sound from the air conditioner • Liquid refrigerant flowing into the evaporator coil.
unit during operation.

8 The wireless controller display is dim. • The batteries are discharged.


• The batteries are not correctly inserted.
• The assembly is not good.

9 Compressor operates continuously. • Dirty air filter. Clean the air filter.
• Temperature setting too low (cooling). Use higher
temperature setting.

10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower
temperature setting.
TM-FDBM-0515-C

88
Diagnostic Guidelines

By means of pressure reading :

Pressure

Data

A little high
Probable cause
A little low

Too high
Too low

Normal
Circuit

High side ● 1. Overcharged with refrigerant.


Low side ● 2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.

High side ● 1. Poor compression / no compression (compressor


Low side ● defective)
2. Reversing valve leaking.

High side ● 1. Undercharged with refrigerant.


Low side ● 2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.

High side ● 1. Outdoor fan blocked (cooling).


Low side ● 2. Outdoor coil dirty (cooling).
3. Non-condensable gases in refrigerant circuit (e.g. air)

High side ● 1. Air intake temperature of indoor unit too high.


Low side ●
TM-FDBM-0515-C

89
By Means Of Diagnostic Flow Chart :
Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting
failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes
“Insufficient cooling.

i) Diagnosis of Electric Circuit

TM-FDBM-0515-C

The most common causes of air conditioner failure to “start” are :


a) Voltage not within ±10% of rated voltage.
b) Power supply interrupted.
c) Improper control settings.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.

90
ii ) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform satisfactorily, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s
intake and discharge air as well as running current

Satisfactory operation with temperature difference of air intake & discharge of indoor unit
8°C to 13°C. *
( * value is for reference only )
TM-FDBM-0515-C

91
10. Dimensional Data
Indoor Unit
Model : FDB10CV1M, FDM10CV1M, FDMN10CV1M

All Dimensions are in mm

Indoor Unit
Model : FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M

Dimension A B C D E F G H
Model
FDB15CV1M, FDM15CV1M
TM-FDBM-0515-C

FDMN15CV1M 881.0 225.0 842.0 802.0 261.0 411.0 351.0 905.0


FDB20CV1M, FDM20CV1M
1041.0 225.0 1002.0 962.0 261.0 411.0 351.0 1065.0
FDMN20CV1M
FDB25CV1M, FDM25CV1M
FDMN25CV1M
1176.0 225.0 1137.0 1097.0 261.0 411.0 351.0 1200.0

All Dimensions are in mm

92
Indoor Unit
FDMN30CV1M
TM-FDBM-0515-C

93
Indoor Unit
Model : FDMN40CV1M

TM-FDBM-0515-C

94
Indoor Unit
FDM30/40/50/60CV1M, FDB30/40/50/60CV1M, FDMN50/60CV1M

Dimension
Model A B C D E F G H I
FDM30CV1M
FDB30CV1M 929.0 999.0 956.0 917.0 408.5 105.0 85.5 187.5 70.5
FDM40CV1M
FDB40CV1M 1045.0 1115.0 1072.0 1033.0 466.5 105.0 85.5 187.5 128.5
FDM50CV1M
FDB50CV1M 1299.0 1369.0 1326.0 1287.0 593.5 105.0 90.5 182.5 255.5
FDMN50CV1M
FDM60CV1M
FDB60CV1M 1499.0 1569.0 1526.0 1487.0 693.5 100.0 90.5 187.5 355.5
FDMN60CV1M

All dimension are in mm


TM-FDBM-0515-C

95
Outdoor Unit
Model: R10/15CV1
L K L

N
M

C
N
30
A C

O D G H
3

F
E
B

65
80

I J
19

Dimension A B C D E F G H I J K L M N O
R10/15CV1 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18

Note : All Dimension in mm

Outdoor Unit
Model: RN10/15FV1
H I
G

P
N
J

O
E F
D B C
A

L
M K

TM-FDBM-0515-C

Dimension
A B C D E F G H I J K L M N O P
Model
RN10/15FV1 550 658 51 11 273 16 14 470 96 299 94 60 14 133 8 8
All dimensions are in mm

96
Model: R18/20/25/28/30CV1
RN20/25/28CV1

Note : All Dimension in mm


MODEL A B C D E F G H I J K L M N O P Q R S T
R18/20CV1
RN20/25CV1 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
R25/28/30CV1
855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
RN28CV1

Model: R35DV1, R40/50/61DY1


RN35DV1, RN40/50/61DY1
142 746 142
22
448
22

60
TM-FDBM-0515-C

90.0 40.0

Note : All Dimension in mm

97
11. Exploded View & Part List
Model: FDB10CV1M, FDM10CV1M, FDMN10CV1M

6 1

NO. PARTS DESCRIPTION


1 TOP SIDE PANEL
2 FAN DECK
3 COIL
4 PRIMARY DRAIN PAN
5 SECONDARY DRAIN PAN
6 HANGER
7 CONTROL BOX

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
TM-FDBM-0515-C

98
Model: FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M

FRONT VIEW

NO. PARTS DESCRIPTION


1 TOP SIDE PANEL
2 FAN DECK
3 COIL
4 PRIMARY DRAIN PAN
5 SECONDARY DRAIN PAN
6 HANGER
7 CONTROL BOX

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
TM-FDBM-0515-C

99
Model: FDM30CV1M, FDB30CV1M, FDMN30CV1M

NO. PARTS DESCRIPTION


1 ASSY. PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 FILTER RAIL
10 FILTER RAIL, COVER
TM-FDBM-0515-C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

100
Model: FDM40CV1M, FDB40CV1M, FDMN40CV1M

NO. PARTS DESCRIPTION


1 ASSY.PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 ASSY. RAIL FILTER
10 ASSY. INS. COVER FILTER L/R
TM-FDBM-0515-C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

101
Model: FDM50CV1M, FDB50CV1M, FDMN50CV1M

NO. PARTS DESCRIPTION


1 ASSY. PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 ASSY., RAIL FILTER
TM-FDBM-0515-C

10 ASSY., COVER FILTER L/R

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

102
Model: FDM60CV1M, FDB60CV1M, FDMN60CV1M

NO. PARTS DESCRIPTION


1 ASSY. PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 ASSY., RAIL FILTER
10 ASSY., COVER FILTER L/R

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
TM-FDBM-0515-C

103
Model : R10/15CV1

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION


1 ASSY., BASE PAN 12 LEFT PANEL
2 ASSY., OUTDOOR COIL 13 RIGHT PANEL
3 VALVE BRACKET 14 ASSY., FRONT PANEL
4 COMPRESSOR 15 ASSY., CONTROL PANEL
5 ASSY., PARTITION 16 ASSY., VALVE COVER
6 SUCTION PIPE 17 ASSY., FRONT GRILLE
7 DISCHARGE PIPE 18 PLASTIC HANDLE
8 ASSY., CAP TUBE 19 INSULATION
9 BRACKET, FAN MOTOR PARTS NOT IN THE DIAGRAMS
10 FAN MOTOR CAPACITOR, FAN MOTOR
11 FAN BLADE CAPACITOR, COMPRESSOR

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
TM-FDBM-0515-C

104
Model : RN10/15FV1

2 1
3

17
6

16

15

7 8 9 10 11 12 13 14

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION


1 ASSY. OUTDOOR COIL 10 COMPRESSOR
2 TOP PANEL 11 DISCHARGE PIPE
3 FAN MOTOR BRACKET 12 SUCTION PIPE
4 ASSY PARTITION 13 ASSY. CAP TUBE
5 FAN MOTOR 14 VALVE BRACKET
6 FAN BLADE 15 ASSY. VALVE COVER
7 ASSY. FRONT GRILLE 16 ASSY. CONTROL PANEL
8 ASSY FRONT PANEL 17 RIGHT PANEL
9 ASSY BASE PAN

* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FDBM-0515-C

105
Model : R18/20CV1, RN20/25CV1

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION


1 ASSY., BASE PAN 13 TERMINAL COVER PANEL
2 ASSY., OUTDOOR COIL 14 DISCHARGE PIPE
3 MOTOR BRACKET 15 SUCTION PIPE
4 FAN MOTOR 16 ASSY., CAP TUBE
5 FAN BLADE 17 ASSY., VALVE COVER
6 VALVE BRACKET 18 ASSY., FRONT GRILLE
7 PARTITION 19 PLASTIC HANDLE
8 COMPRESSOR 20 SERVICE PANEL
9 BACK PANEL, RIGHT PARTS NOT IN THE DIAGRAMS
10 FRONT PANEL, LEFT CAPACITOR, FAN MOTOR
11 TOP PANEL CAPACITOR, COMPRESSOR
12 ASSY., CONTROL PANEL
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
TM-FDBM-0515-C

106
Model : R25/28/30CV1, RN28CV1

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION


1 ASSY., BASE PAN 12 TOP PANEL
2 ASSY., OUTDOOR COIL 13 ASSY., CONTROL PANEL
3 MOTOR BRACKET 14 TERMINAL COVER PANEL
4 FAN MOTOR 15 ASSY., VALVE COVER
5 FAN BLADE 16 ASSY., FRONT GRILLE
6 VALVE BRACKET 17 PLASTIC HANDLE, SIDE
7 PARTITION 18 DISCHARGE PIPE
8 COMPRESSOR 19 SUCTION PIPE
9 BACK PANEL, RIGHT 20 ASSY., CAP TUBE
10 SERVICE PANEL PARTS NOT IN THE DIAGRAMS
11 FRONT PANEL LEFT CAPACITOR, FAN MOTOR
TM-FDBM-0515-C

CAPACITOR, COMPRESSOR

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

107
Model : R35DV1, R40/50/61DY1, RN35DV1, RN40/50/61DY1

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION


1 ASSY., BASE PAN 16 MOTOR BRACKET
2 ASSY., COIL 17 FAN MOTOR
3 PALTE, FLARE VALVE 18 ASSY., FRONT PANEL
4 FLARE VALVE 3/8” 19 ASSY., CONTROL PANEL
5 FLARE VALVE 5/8” 20 SERVICE PANEL
6 PARTITION 21 FAN BLADE
7 COMPRESSOR 22 TOP PANEL
8 ACCUMULATOR 23 PLASTIC HANDLE
9 ASSY., CAPILLARY TUBE PARTS NOT IN THE DIAGRAMS
10 SUCTION PIPE PHASE SEQUENCER
11 TUBE ACCUMULATOR TO SUCTION HIGH PRESSURE SWITCH
12 DISCHARGE PIPE LOW PRESSURE SWITCH
13 INSULATION CAPACITOR, FAN MOTOR
14 BACK PANEL, RIGHT CAPACITOR, COMPRESSOR
TM-FDBM-0515-C

15 SIDE PANEL, LEFT TXV

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

108
w w w. d a i k i n . c o m . m y

GROUP ASSOCIATED (C&L) SDN BHD (109719-M)


Head Office: Tel: 03-7953 8388 Fax: 03-7956 4371
Email: sales_enquiry@daikin.com.my, customer_service@daikin.com.my
Branches: • Penang Tel: 04-331 1670 • Johor Tel: 07-557 7788
• Pahang Tel: 09-567 6778 • Perak Tel: 05-548 2307
• Melaka Tel: 06-288 1133 • Sabah Tel: 088-722 194
• Sarawak Tel: 082-333 299 • Negeri Sembilan Tel: 06-768 8969
• Kedah Tel: 04-733 0235 • Kelantan Tel: 09-747 4678

S-ar putea să vă placă și