S i n g l e m o d u l e a n d ‘1 + N’ ( e x p a n d a b l e )
UNINTERRUPTIBLEPOWERSYSTEM
User Manual
Please accept our thanks for giving us the privilege to serve you by choosing a Liebert
make ‘UPS’.
If this is your first Liebert UPS, we hope it is the beginning of a long relationship
which delivers value to your organisation. If you already own and use a Liebert, we are
doubly honoured by your decision of continuing this relationship.
It is our constant endeavour to partner you for the growth and success of your business.
This philosophy is reflected in our Mission statement “To deliver value through Air
& Power Quality solutions to achieve customer delight”. Please do give us
feedback to help us realize our Mission.
This manual contains information concerning the installation, operation and maintenance
of the Series 7400 1Phase Uninterruptible Power System (UPS) for the single module
and one plus one Systems.
All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or his
agent) before being put into service. Failure to observe this condition will invalidate any
implied warranty.
The Series 7400 1Phase UPS has been designed for Commercial / Industrial use only.
The Series 7400 1Phase UPS is not designed for direct use in any life support
application.
If you encounter any problem with the procedures contained in this manual you should
seek immediate assistance from Emerson Network Power (India) Pvt. Ltd. Sales Office
from whom the equipment was purchased. Alternatively contact the Emerson Network
Power (India) Pvt. Ltd. Customer Service & Support department at the address shown
below:
ZONAL OFFICES
MUMBAI
B 414-424, Bhaveshwar Arcade,
(opp. Shreyas cinema), LBS Road,
Ghatkopar(W), MUMBAI – 400 086
NEW DELHI
18 / 14, WEA, Pusa Lane, Karol Baug;
NEW DELHI 110 005
KOLKOTA
77 A, Raja Basant Roy Road,
KOLKOTA – 700 029
BANGALORE
501, C Wing, Mittal Towers,
No.6, MG Road, BANGALORE – 560 001
BARODA JAMSHEDPUR
39 / 2, Arunodaya Society, Kashi kunj, Road no. 2, Gr. Floor
Alkapuri, BARODA-390 005 Contractor’s area, Bistupur;
JAMSHEDPUR – 831 001
Tel : 0265-314296, 330383
Fax: 0265-314296, 330383 Tel : 0657-437549
Fax: 0657-437549
CHANDIGARH LUCKNOW
SCO-198 / 199 / 200, 206, Sriram Tower, Ashok Marg
Sector – 34A, Near Labour Chowk, LUCKNOW
CHANDIGARH
Phone : 0522-201467
Phone: 0172-662 873 Pager : 9628-555091
Mobile: 9814100901 Mobile: 9839025563
CHENNAI NAGPUR
No. 22, First Floor, Gopal Krishna Road, 203, Ganga Apts,
T. Nagar, CHENNAI – 600 017 13, Giripeth
NAGPUR 400 010
Tel : 044 - 8231742, 8221063, 8228996
Fax: 044 - 8231742 Phone / Fax : 0712 – 540423, 548551
COCHIN PUNE
Lakshmini No. 36 / 2684, B-6, Shri Dwarka co-op. Society,
Veluthamma House, Azad Road, 467/ C1, Hare Krishna Mandir Path,
Kaloor, COCHIN 682017 Model Colony, Off University Road,
PUNE – 411006
GUWAHATI
South Savania, Ashram Road,
Ulubari, GUWAHATI 781 007
WARNING
WARNING
As with other types of high power equipment, dangerous voltages are present within
the UPS and battery enclosure. The risk of contact with these is minimised as the live
component parts are housed behind a hinged, lockable door. Further internal safety
screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner,
following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and
should be carried out only by trained personnel.
BATTERIES
TEST EQUIPMENT
When the battery is under charge, it is earth-referenced about its mid-point –e.g. if
the battery s being charged at 460V the battery extremities will be at +230V and –
230V with respect to neutral (earth). When using mains-powered test equipment
such as oscilloscopes in the UPS voltage area, always use a differential mode of
operation to disconnect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) it is recommended that protection
be worn to prevent eye damage, should an electric ware be struck by mishandling or severe
electrical fault.
Some of the power components are very heavy. If their removal is necessary, ensure that
sufficient manpower is available; otherwise use adequate mechanical handling equipment.
When working in the general area of the UPS where high voltages are present, a second
person should be standing-by to assist and summon help in case of accident.
1 General Description 1
1.1 Introduction 1
2 Operating Instructions 15
2.1 Introduction 15
2.1.1 Redundant Module System 15
2.1.2 Non Redundant Module System 15
2.1.3 General Notes 15
3 Installation (Electrical) 21
3.1 Introduction 21
3.1.1 Equipment Positioning and Environmental considerations 22
3.1.2 Raised floor installation 22
3.1.3 Battery Location 23
4.4 Remote Alarm Monitor (RAM) for Single Module and 1+1 UPS System
42
5 Maintenance 47
5.1 Introduction 47
6 Troubleshooting 51
6.1 Troubleshooting UPS systems 51
6.1.1 Operating parameters and limitations 51
6.1.2 General troubleshooting procedure 51
ANNEXURE 57
Chapter 1
General Description
1.1 Introduction
1.2.1 Redundant vs The one-plus-one system comprises two standard 7400 series UPS
modules which are modified to allow their outputs to be connected
Non-Redundant
in parallel. These can then be used in a “redundant” or “non-
configuration redundant” configuration as explained below.
Bypass
Supply
UPS
Mains (a.c) (d.c) (a.c) STATIC
RECTIFIER INVERTER Output
Supply SWITCH Supply
(d.c)
BATTERY
1.2.2 7400 Module As previously mentioned, each of the two modules forming the
Design one-plus-one system is basically a standard single module 7400
series UPS. This section describes an individual module’s
operating principles - the effects of the additional parallel control
facilities on the standard module are described later.
During normal operation both the rectifier and inverter sections are
active and provides regulated load power whilst simultaneously
float charging the battery. In the event of a mains power failure,
the rectifier becomes inoperative and the inverter is powered solely
from the battery. Critical load power is maintained under these
conditions until the battery is fully discharged, whereupon the UPS
shuts down. The end of battery discharge is assumed when the
battery voltage falls to 320Vdc. In case of 80 to 125 kVA, 1 PH
models the end of discharge is taken as 330Vdc.
The period for which the load can be maintained following a mains
power failure is known as the system’s ‘Autonomy Time’ and is
dependent upon both the battery A/Hr capacity and the applied
percentage load. It is usual in larger installations to provide an
alternative UPS input power source from a stand-by generator
when the mains supply fails. Once such a generator has been
brought on-line, and the UPS input power has been re-established,
the batteries immediately begin to recharge. Modern generators
can be started and brought on-line very quickly and where such a
facility is incorporated into the UPS installation it results in short
battery discharge periods and correspondingly rapid recharge
times.
Maintenance Bypass
Isolator
Maintenance Bypass Line
UPS
Mains STATIC
RECTIFIER INVERTER Output
Supply SWITCH Supply
Input Output
Isolator Isolator
Battery
Breaker
BATTERY
Battery
Breaker
BATTERY
1.2.3 Bypass Supplies The circuit block annotated ‘Static Switch’ in figure 2 contains an
electronically controlled switching circuit, which enables the critical
load to be connected either to the Inverter output or to a Bypass
power source via the ‘static bypass line’. Normally, the load is
connected to the inverter; but in the event of a UPS overload, or
inverter failure, it is automatically transferred to the static bypass
line due to static switch action. Note that the Bypass supply should
be in normal condition and enabled.
1.2.4 UPS Power Figure 2 illustrates what is known as the “Split Bypass”
Switch configuration. This is the standard configuration for all 1PH Models
Configuration In the “Split Bypass” configuration the static bypass line is switched
by a separate isolator to a dedicated ‘Bypass’ power source which
also feeds the maintenance bypass line.
The power switch locations in the various 7400 models are shown
in Figure 3.
1.2.5 Battery Circuit The battery is connected to the DC Busbar through a circuit
breaker fitted inside the battery Cabinet / Rack or located adjacent
Breaker
to the batteries where a battery Cabinet / Rack is not used. This
circuit breaker is closed manually, but it contains an undervoltage
release coil which enables it to be tripped from the UPS control
electronics following certain detects for faults. It also has a
magnetic trip facility for overload protection.
I2 I3 I4 I1
Output Maintenance Static Input
Isolator Bypass Bypass Isolator
Isolator Isolator I4 I3 I2 I1
Output Maintenance Static Input
Isolator Bypass Bypass Isolator
Isolator Isolator
830 900
I4 I3 I2 I1
I4 I3 I2 I1 Output Maintenance Static Input
Output Maintenance Static Input
Isolator Bypass Bypass Isolator
Isolator Bypass Bypass Isolator
Isolator Isolator
Isolator Isolator
1250 1400
I2 I3 I1
Output Maintenance Input
Isolator Bypass Isolator
Isolator I4 I3 I1
Output Maintenance Input
Isolator Bypass Isolator
Isolator
830 900
I4 I3 I1
I4 I3 I1
Output Maintenance Input
Output Maintenance Input
Isolator Bypass Isolator Isolator Bypass Isolator
Isolator Isolator
1250 1400
60/ 70 kVA 105 kVA
1.2.6 One plus One When two of the standard 7400 modules just described are
Parallel connected together to form a one-plus-one system, each module
is fitted with an additional circuit board which allows the two
Control
modules to communicate with each other. Communication takes
place via a single ribbon cable connected between the modules as
illustrated in figure 4.
Note: - Modifying a standard module for use with a one-plus-one system also
involves replacing certain other circuit boards with modified versions, and
relocating certain minor assemblies. This means that although it is not
impossible to modify an existing 7400 module to form part of a one-plus-one
system it is not a straightforward proposition.
Synchronisation:
As the outputs from both UPS modules are connected together to
provide a single load supply, it is imperative that the inverters are
fully synchronised both in frequency and phase. This is achieved by
digitally locking the two inverter control oscillators. Similarly, as has
already been mentioned, it is necessary for the inverters to be
synchronised to the bypass supply to enable a “no-break” transfer
to be achieved when the static switch transfers the load to the
bypass supply. The inverter control oscillators are therefore not
only locked together but are also made to track the bypass
frequency.
Current sharing:
The parallel control circuit compares the module’s output current
with that of its partner and is thereby able to effect current sharing
between the modules by making fine adjustments of an individual
module’s output voltage.
Redundancy configuration:
A link in the parallel control logic determines whether the one-plus-
one system operates in a “redundant” or “non-redundant”
configuration. If a non-redundant mode is selected the two static
switch sections are effectively locked together in that both the
static switches are turned off or on by a single control signal. Thus
if one module develops a fault, when running, its static switch
control logic will transfer its output from the inverter to the static
bypass line and simultaneously send a signal to the static switch
control logic in the second module to do likewise. This does not
happen if the system is configured as a redundant system, in
which case the second module is allowed to continue supplying the
load from its inverter when the first module trips its inverter off line.
Reverse current:
A reverse current monitor circuit detects current flowing into, rather
than out of, the module’s output terminals. Such a condition can
arise if a module develops an internal power fault or if for some
reason the two modules become unbalanced, and is liable to
further damage the module and also degrade the load supply. If a
reverse current is detected the inverter on the affected module is
immediately shut down and load transferred to the bypass supply
depending on the system redundancy configuration.
Bypass
Supply
Mains STATIC
RECTIFIER INVERTER
Supply SWITCH
BATTERY
UPS
Output
Supply
BATTERY
Mains STATIC
RECTIFIER INVERTER
Supply SWITCH
Bypass
Supply
Bypass
Supply
Mains STATIC
RECTIFIER INVERTER
Supply SWITCH
UPS
Control
Logic
BATTERY Output
Supply
Mains STATIC
RECTIFIER INVERTER
Supply SWITCH
Bypass
Supply
1.2.7 Common Battery A “Common battery” option kit contains a DCCT (DC Current
Transformers) which are fitted to the battery power lines and
monitored by the parallel control logic. Each module monitors its
battery charge current and compares it with the charge current
provided by the other module. This enables a module to match its
charge current to that of its partner by effecting fine voltage control
over the rectifier section.
Vo Io OFF
= =
f B ((•)) ON
1.2.8 Operator Control The operator control panel is divided into three functional areas;
‘Mimic indications’, Control switches’, and ‘LCD display panel’.
Panel
Mimic Indications
Six LEDs are mounted on a single line
diagram to represent the various UPS
power paths. These LEDs, which are
annotated in figure7, show the current UPS
Uninterruptible Power System operational status and should be
LS3 interpreted as detailed below.
10
Vo Io OFF
f B ((•)) ON
S1 S2 S3 S4 S5 LS7 S7 LS8 S6 S8
Control switches
Seven tactile switches are located on the Operator Panel, together
with an emergency stop push button which is fitted with a safety
cover to prevent inadvertent operation.
11
There are two LEDs contained within the switch panel area:
LS7 Alarm:
This led accompanies the audible alarm warning when any alarm
condition is initiated. The audible warning can be cancelled by the
reset switch (S5) but LS7 will only extinguish after the alarmed
condition has reverted to normal.
12
LCD Display
*** ALARM *** OVER TEMPERATURE A DIP switch fitted to the display
microprocessor board enables the displayed
language to be easily selected to English,
*** ALARM *** OVERLOAD
French, Italian, Spanish or German.
*** ALARM *** BATTERY CB OPEN The lower row of characters are used to
display metered parameters; which include
*** ALARM *** OUTPUT CB OPEN output (or bypass) voltage, frequency, or
current together with battery current &
voltage and autonomy time for SMF
*** ALARM *** BYPASS CB OPEN
batteries only.
*** ALARM *** RECTIFIER OFF OR FAILED Warning and alarm messages are displayed
on the upper row of characters. The ALARM
*** ALARM *** UPS ON MAINTENANCE BYPASS
led and audible warning accompany all
alarm messages but are not activated by
warning messages. In all cases, the
*** ALARM *** INVERTER UNSYNCHRONISED
message automatically resets when the
alarmed (or warning ) condition reverts to
*** ALARM *** BATTERY ON LOAD normal.
1.2.9 Battery Circuit For all kVA Models battery circuit breaker can be provided either in
auxiliary cubicle or in a separate box. This box is designed to be
Breaker
wall mounted and is connected between the UPS and battery bank.
1.2.10 Battery Cabinet / The batteries associated with the UPS are generally housed in a
purpose built cabinet / rack located alongside, but not attached to
Rack
the main UPS equipment.
13
1.3.1 General In common with other types of high power equipment, dangerous
voltages are present within the UPS and battery enclosure. The risk
of contact with these voltages is minimised as the live component
parts are housed behind a hinged, lockable door. Further internal
safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in
the normal manner, following the recommended operating
procedures.
1.3.3 Test Equipment When the battery is charge it is earth-referenced about it is mid-
point -e.g. if the battery is being charged at 432V the battery
extremities will be at +216V and - 216V with respect to neutral
(earth). When using mains-powered test equipment such as
oscilloscopes in the UPS high voltage area, always use a differential
mode of operation to avoid the need to disconnect the oscilloscope
frame earth.
1.3.4 Personnel When working inside the UPS (trained personnel only) it is
recommended that protection be worn to prevent eye damage,
should an electrical arc be struck by mishandling or severe
electrical fault.
When working in the general area of the UPS where high voltages
are present, a second person should be standing-by to assist and
summon help in case of accident.
14
Chapter 2
Operating Instructions
2.1 Introduction
Stopping:
When the first module is stopped its static bypass is inhibited
because the load will be fully maintained by the inverter of the
second module. When shutting down the second module, the
static bypass lines of both modules will be turned on as soon as its
inverter is stopped. That is, both modules will provide load power
through their paralleled bypass lines.
Stopping:
The load will be transferred to the static bypass lines in both
modules simultaneously as soon as the inverter stops in the first
module to be shut down.
2.1.3 General Notes Note 1: All the user controls and indicators mentioned these in these procedures
are identified in chapter 1.
Note 3: The 7400 series UPS incorporates an optional automatic boost charge
facility which can be used in systems containing non-sealed lead-acid batteries.
If this type of battery is used in your installation you may notice that the battery
charger voltage will be greater than its nominal 432Vdc when the mains supply
returns from a prolonged outage. This is the normal response of the boost
charge facility: the charger voltage should return to normal after a few hours.
15
This procedure should be followed when turning on the one-plus-one system from a
fully powered down condition - i.e. where the load is not being initially supplied through
the internal Maintenance Bypass supply.
2. Close the input Isolator (and Static Mimic panel LEDs LS1 LS3 and LS5
Bypass Isolator, if separate). should illuminate immediately, to
indicate that the load is being supplied
through the static bypass line.
3. Wait 20 seconds then close the Mimic panel LED LS2 should illuminate
battery circuit breaker: This is and LS7 (alarm) should extinguish.
located inside the battery cabinet (if
used) or is otherwise located
adjacent to the battery racks
4. Press the battery metering selector The display should indicate a positive (+)
switch [B]. battery charging current.
16
2. Close the input isolator (and static Mimic panel LEDs LS1 and LS3 should
bypass isolator if separate. For 110V illuminate immediately, to indicate that
systems Static bypass isolator is the input and bypass supplies are
mounted in auxiliary cubicles). healthy.
3. Wait 20 seconds then close the Mimic panel LED LS2 should illuminate.
battery circuit breaker.
4. Press the battery metering selector The display should indicate a positive (+)
switch [B] (S4). battery charging current.
5. Press the Inverter OFF pushbutton Mimic panel LED LS4 should extinguish
(S6).
6. Close the Output Isolator Mimic panel LED LS5 should illuminate to
indicate that load is connected to the
static bypass line.
7. Open the Maintenance Bypass Mimic panel LEDs LS4 (Inverter OK)
Isolator on both modules then and LS6 (Load on Inverter) should
Press the Inverter ON switch (S7) on illuminate after approximately 30
both modules. seconds. (NB: In a Non-Redundant
Module system LS6 will not illuminate
(Note: The inverters of both modules are on the first module to be started until
inhibited if either modules’ Maintenance you reach this point in starting the
second module).
Bypass Isolator is closed).
LS5 should extinguish at the same
time as LS6 illuminates.
17
2. Press the Inverter OFF switch (S6) on Mimic panel LEDs LS4 and LS6 should
both modules extinguish on both modules and LS5
should illuminate to show that the load
has been transferred to the static
bypass line.
4. Open the Output Isolator on both Mimic panel LED LS5 should
modules. extinguish on both modules.
5. On each module - Open the battery All the operator panel led indications
circuit breaker followed by the input and messages should extinguish as
Isolator (and Static Bypass Isolator if the mains driven internal power
separate. For 110V systems Static supplies decay.
bypass isolator is mounted in
auxiliary cubicles).
WARNING
18
This procedure should be followed only if the one-plus-one AND LOAD are to be
completely powered down.
1. Press the Inverter OFF switch (S6) Mimic panel LEDs - LS4 and LS6 should
on both modules. extinguish and LS5 should illuminate to
show that the load has been transferred
to the static bypass line.
2. Open the battery circuit breaker. Mimic panel LEDs LS2 should
extinguish.
3. Open the input isolator (and static All the operator panel led indications and
bypass isolator also. For 110V messages should extinguish as the
systems Static bypass isolator is mains driven internal power supplies
mounted in auxiliary cubicles). decay.
IMPORTANT
The Maintenance Bypass Isolator may be operated at any time when the UPS is
powered down to connect / disconnect each load to the raw maintenance bypass
supply if required.
Emergency Stop
The emergency stop pushbutton is located behind a hinged safety shield to prevent
inadvertent operation. When this switch is pressed both modules are electronically
shut down and both battery circuit breakers are tripped. Power is removed from the
critical load, but pressing the emergency stop pushbutton will not remove the
modules’ input mains supply unless an external contactor, controlled via the
emergency stop pushbutton, is fitted in the mains supply line.
19
20
Chapter 3
Installation Procedure
3.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the
commissioning engineer
WARNING
WARNING
BATTERY HAZARDS
Ø Special care should be taken when working with the batteries associated
with this equipment. When connected together, the battery terminal voltage
will exceed 400Vdc and is potentially lethal.
Ø If electrolyte comes into contact with the skin, the affected area should be
washed immediately.
Because every site has its peculiarities, it is not the aim of this
chapter to provide step-by-step installation instructions, but to act
as guide as to the general procedures and practices that should be
observed by the installing engineer.
21
3.1.1 Equipment The UPS cabinets can be moved by fork lift or crane. Fork lift
apertures are provided in the sides of the base plate and are
positioning and
accessible after removing blanking covers fitted to the side panel
environmental ventilation grills. Roof - mounted eye- bolts are fitted to enable the
considerations cabinet to be crane-handled. These can be removed once the
equipment has been finally positioned.
WARNING
Clearances
To allow adequate cooling air flow, you should position the
equipment with the following space around the back and sides.
22
3.1.3 Battery Location In 25kVA to 125 kVA module installations the batteries associated
with the UPS equipment are usually contained in a purpose-built
battery cabinet/ rack which sits alongside the main UPS equipment.
Sealed, maintenance-free batteries are normally used in this type
of installation.
Pedestals are required for the battery cabinets when they are
located on raised floors, in the same way as for the UPS cabinets.
Where battery racks are used, they should be sited and assembled
in accordance with the battery manufacturer’s recommendations.
In general, batteries require a well ventilated, clean and dry
environment at reasonable temperatures to obtain efficient battery
operation.
Before you install the UPS hardware you should carry out the
following preliminary checks:
23
Note: If ‘side’ cable entry is to be used ensure that the blanking plates are
removed before finally fixing the cabinet position.
CAUTION
24
WARNING
3.3.1 Cable Entry Cables can enter the UPS modules and battery cabinet either from
below or through either side. Side entry is made possible by
removing blanking pieces fitted in the side ventilation grills to reveal
the cable entry holes. This cable entry method allows the
equipment to be positioned on a solid floor without the need for
cable trenching and also allows cables to pass from one module to
the other when positioned side-by-side.
3.3.2 Cable Rating When connected as a one-plus-one Non Redundant system, the
UPS modules’ input and output cables must be rated to suit the
supported load rather than the individual module’s power rating.
This is due to the possibility of connecting the full load to the mains
via the Maintenance Bypass line of one module.
25 53 49 227 109 68
40 85 78 364 174 110
50 106 98 455 217 136
60 128 117 546 261 163
80 167 153 727 348 216
90 190 173 818 391 240
105 219 199 955 457 279
125 261 237 1136 544 331
25
3.3.3 Cable In the 25-40kVA UPS 1 PH models the input mains / bypass cables,
Connections UPS output cables and battery cables are connected to busbars
located behind a safety cover just below the power isolator
switches -as shown in figure 11. A terminal block is used for
connecting the control cables to the battery circuit breaker and the
external emergency stop facility.
For the 50 to 125 kVA 1PH models the power cables are connected
either directly to their respective circuit breakers or to busbars,
which are themselves, connected to the circuit breakers. See figure
12 – 14.
3.3.4 Cabling Once the equipment has been finally positioned and secured,
connect the power cables as described in the following procedure.
Procedure Study the connection diagrams in figures 19 & 20 and positively
identify the diagram relevant to your equipment before
commencing cabling.
WARNING
Do not attempt to close the Battery Circuit
Breaker before the equipment has been
commissioned
26
MODULE 1 MODULE 2
CN3 CN3
CN2 CN2
CN1 CN1
I2 I3 I4 I1
NU RU NI RI SI TI NS RS
- +
I4 I3 I2 I1
RI SI TI
NU RU NS RS
28
I1
I4 I3 I2
RU NU RS NS RI SI TI + -
I4 I3 I2 I1
U2 N2
U3 N3 NI UI VI WI
I1
I3 I2
+ -
I1
I3 I2
RI SI TI
NS RS
NU RU
I1
I3 I2
RU
NU NS RS RI SI TI + -
I1
I3 I2
N2 N3 N2 U2 U3 RI SI TI + -
A battery circuit breaker box houses the battery circuit breaker and
its controller board and is used to connect the battery to the UPS in
installations where the batteries are not contained in the standard
battery cabinet. It is most likely used with 60–125 kVA UPS models.
UPS CABINET
BATTERY CABINET
I2 I3 I4 I1
Battery CB
Interface Bd
(100202120003)
1 2 3 4 5
NU RU NI RI SI TI NS RS
- +
+
+ ve
- ve
Figure 19: Battery C.B. box connections for 25-40kVA 1Ph UPS
32
Note: The polarity of the battery connections in the 25 - 40 kVA UPS cabinets
are reversed for 50 - 125kVA UPS modules.
UPS CABINET
BATTERY CABINET
I4 I3 I2 I1
Battery CB
Interface Bd
(100202120003)
1 2 3 4 5
U2 N2
U3 N3 N1 U1 V1 W1
+ ve
- ve
Figure 20: Battery C/B box connections for a typical 105 kVA 230V 1 PH UPS
33
34
Chapter 4
Optional Equipment
Several items of optional equipment are available for fitting to the
7400 series UPS for the use by the customer as required.
35
4.1.1 AS400 Interface Two D-type connectors are provided on the Interface Board to
Board Outputs enable the above signals to be connected to the AS400 computer.
One connector, CN1, has 9 pins and the other, CN2, has 15.
Figure 21 provides pin-out details for these connectors.
Note: Use one connector only -i.e. don’t use both connectors simultaneously.
Note: When using the above contacts for remote alarm annunciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
4.1.2 Remote Control The Interface Board has facilities to accept two remote control
Inputs inputs, as shown in figure 21. One remote input allows the inverter
to be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a standby generator when the input mains supply
fails and the generator frequency is unstable.
4.1.3 Calibration When fitting the AS400 interface board to the 7400 series, ensure
that link SH - 1 is in position 1 - 2.
36
TB - M2 Control Inputs
AS400 INTERFACE BOARD Synchro
Part No. 100215120003 2 off
3
4
5 Inverter
off
TB - M1
1
2
Mains or Rectifier
RL1-2 Failure
3
4
5
RL2-2 Load on Inverter
6
7
8
9
10
SH1 11
1 2 3 Load on Mains
RL4-2
12
13
14
Load on Maintenance
RL5-2 Bypass
CN1 CN2
15
AS400 Outputs
R L 1-1
CN1-9 Mains or Rectifier
CN2-9 Failure
R L 2-1
CN1-8
Load on Inverter
CN2-2
R L 3-1
CN1-7
Low Battery
CN2-10
R L 4-1
CN1-6
Load on Mains
CN2-3
R L 5-1
CN1-5
Common (0V)
CN2-11
Note: When using the above contacts for remote alarm annuciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
4.2.1 Remote Control The Interface Board has facilities to accept two remote control
Inputs inputs, as shown in figure 22. One remote input allows the inverter
to be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a stand by generator when the input mains supply
fails and the generator frequency is unstable.
4.2.2 Calibration When fitting the AS400 interface board to the 7400 series, ensure
that link SH-1 is in position 1-2.
38
CN1
M2 M3 M4 M5
1 7 1 7 1 7 1 7
1 Common 1 Common
RL7 RL2
2 Mains or Rectifier 2 Mains or Rectifier
Failure Failure
RL9 RL4
3 UPS On 3 UPS On
RL6 RL1
4 Low Battery 4 Low Battery
RL8 RL3
5 Load on Mains 5 Load on Mains
Outputs from M2 - M5 to
Remote Alarm or AS400
39
4.3.1 Alarm Outputs Two remote alarm boards, shown in figure 23 & 24, similar in
function and differing only in their connections to the terminal
blocks M1 - M3, enable the alarm signals generated within the UPS
to be connected by means of volt-free changeover relay contacts
to a remote monitoring device.
Note: When using the above contacts for remote alarm annunciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
4.3.2 Remote Control Both board have facilities to accept two remote control inputs, as
Inputs shown in figures 23 and 24. One remote input allows the inverter to
be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a standby generator when the input mains supply
fails and the generator frequency is unstable.
15
M3
14 LOAD ON BYASS
13
12
11 BATTERY ON LOAD
10
9
8 MAINS FAILURE
7
6
5 OVERLOAD
4
3
2 OVER TEMPERATURE
SH1 1
1 2 3
15
M2
14 LOW BATTERY
13
12
11 MAINT. BYPASS ENABLED
10
9
8 INVERTER UNSYNCHRONISED
7
RELAY
6
5 COMMON ALARM
RELAY 4
3
2 UPS OK
M1 1
1 2 3 4 5
SYNCHRO INHIBIT
INVERTER ON/OFF
M1 1
MAINS VOLTAGE OK 2
3
4
RECTIFIER ACTIVE 5
6
7
BATTERY OK 8
9
10
PRE-ALARM END
11
OF DISCHARGE
12
13
INVERTER OK 14
15
M2 1
SYNCHRO OK 2
3
4
LOAD ON UPS 5
6
7
LOAD ON BYASS 8
9
10
OVER TEMPERATURE 11
12
13
OVERLOAD 14
15
M3 1
MAINT, BYPASS ENABLED 2
3
4
STATIC BYPASS ISOLATOR 5
CLOSED (SPLIT BYPASS) 6
7
8
OUTPUT SWITCH CLOSED
9
10
11 RELAY
SYNCHRO INHIBIT 12
13
INVERTER ON/OFF 14
RELAY
15
41
4.4 Remote Alarm Monitor (RAM) for Single Module & “1 + 1” UPS System.
There are total 9 alarms provided on the RAM. Each of the alarm
initiates an audible alarm warning. This is, however, subject to a
short time delay to prevent the warning being activated by transient
conditions. Pressing the reset push button cancels the audible
warning but the alarm indications remain until the condition is
rectified. A test push button is also provided to ensure that all the
LED’s are healthy.
Power Supply
The RAM contains a single-phase 230V a.c. mains driven power
supply. Power is applied through a standard two-pin mains
connector located at the backside of the RAM. This 2 pin male-
female type connector is marked as N L . The supply is rated
to approximately 10 watts and hence can be tapped from any
suitable source. This generates required DC power supply for
functional requirement of the RAM. Once AC power is available to
RAM, “POWER” indicating LED on RAM starts glowing. This
indicates that RAM is ready for operation. This power supply is
used to reproduce UPS mimic and display alarms.
42
Figure 25: Remote alarm monitors for single module and 1+1 configuration
43
M1
1
MAINS OK MIMIC STATUS LED – MAINS (BYPASS) VOLTS OK N 230V AC Supply
2
(BYPASS) MIMIC STATUS LED – LOAD ON BYPASS L
3 M2 -8
MIMIC STATUS LED – RECTIFIER ACTIVE 1
4
RECTIFIER MIMIC STATUS LED – INVERTER OUTPUT OK 2 M1 -2
5 M2 -5
ACTIVE 6
MIMIC STATUS LED – BATTERY OK 3 RM1
MIMIC STATUS LED – LOAD ON INVERTER (UPS) 4 M1 - 14
7 M1 -5
BATTERY 5
8 M1 -8
6
OK 9
10
END OF 11
DISCHARGE 12
13
INVERTER 14
OK 15
M3
1 TERMINALS OF RAM
MAINT. BYP. 2
ENABLED 3
4
STATIC BYPASS 5 NOTES:
ISOLATOR CLOSED 6
7
1. Short terminal with the help of suitable wire.
OUTPUT SWITCH 8
CLOSED
2. Note that if this supply is not available, RAM will not function
9
10 3. USF, 24 core, 1.5mm, multistrand cable for interconnection
SYNCHRO INHIBIT RELAY 11
12
between RAM and Output interface
INVERTER ON/OFF RELAY 13
4. Status of contacts is shown when relay is ‘Off’. Relay switches
‘On’ when signal is received as per the description
Figure 26: Interconnection diagram for single module RAM & Output Interface PCB
44
M3 M3
1 1
MAINT. BYP. MAINT. BYP.
2 2
ENABLED 3 3 ENABLED
24V
4 4
ALARM SIGNAL LED – LOAD ON MAINTENANCE BYPASS
TERMINALS OF TERMINALS OF
INTERFACE PCB INTERFACE PCB
TERMINALS OF RAM
10
N
9
8
7
6
5
4
3
2
1
6
5
4
3
2
1
L
NOTES:
RM3 RM2 RM1
230V AC Supply
M1
M1
M1
M2
M1
M2
-8
-5
- 14
-5
-2
-8
Figure 27: Interconnection diagram for single module RAM and UPS Interface PCB 1+1 System
45
46
5.1 Introduction
5.3.1 Daily Checks Carry out a daily walk-by inspection of the UPS, checking the
following points:
47
5.3.2 Weekly Checks Carry out the following checks from the mimic panel and log the
results:
4. Measure and record the UPS output line currents. If these are
significantly different from the values previously logged then, if
possible, record the size, type and location of any additional
load connected to the UPS supply since the previous
inspection. This type of information could prove useful to the
troubleshooting engineer should a problem occur.
5.3.3 Annual Service The equipment should be thoroughly cleaned and the following
checks carried out annually. This entails working inside the
equipment in regions containing hazardous voltages.
3. Isolate the UPS input mains supply externally (also the bypass
supply if a split bypass is in use) and isolate the battery.
48
9. Start the UPS and transfer the load to the inverter following the
appropriate operating procedure.
5.3.4 Extended Service We recommend that ALL the input/output power cables and their
connections are checked periodically. As this requires the UPS to
be completely shut down such a check should be carried out on an
‘opportunity’ basis but at an interval not exceeding 2 years.
5.3.5 Battery The batteries used with the UPS are generally of a sealed, valve-
Maintenance regulated type, and the only maintenance requirement is to ensure
that the cells are kept clean and dry. Maintenance procedures
appropriate to both, valve-regulated and un-sealed batteries vary,
and should be obtained from the battery manufacturer.
49
50
Chapter 6
Troubleshooting
WARNING
51
Corrective Action
When all the indications have been noted, you should refer to the
following fault interpretation charts and carry out the actions
detailed against any led whose status is abnormal. If you are
unsure as to how to undertake the actions detailed - or if several
LED indications are abnormal and you are unable to distinguish
between the likely cause and affects - then seek immediate
assistance from an approved service agent.
Fault Reporting
Irrespective of whether fault rectification is successful or not, report
the fault occurrence to the nearest service agent - who will then
forward the details to the manufacturer. This type of customer
feedback is an important factor in maintaining high product
reliability, and also provides important data concerning the
equipment field performance.
CAUTION
LS5
= =
52
LS2 ON If this led is OFF it signifies that either the battery circuit
breaker is open or that the dc busbar voltage is below
320V dc. (For 80kVA to 125kVA models, this voltage is
330V dc ).
LS3 ON If this led is OFF it signifies either that the bypass supply
is not within acceptable tolerances or that the bypass
supply isolator is open.
53
LS5** OFF If this led is ON then it signifies that the load has been
transferred to the static bypass supply and the output
circuit breaker is closed. This indication should be
mutually exclusive with LS6 described below - check
out LS6 actions.
54
EMERGENCY STOP This alarm indicates that the UPS was shut down by means of
the local or remote (if fitted) emergency stop pushbutton which
of course is normally due to operator action - investigate why
the emergency stop pushbutton was pressed.
INVERTER OFF OR This alarm is active whenever the inverter is not producing its
FAILED correct output voltage; either because it has been switched
OFF or due to an internal fault.
BATTERY C/B OPEN This is a status indication only. Note that UPS if operating with
the battery circuit breaker open and the mains power fails then
the UPS output will also fail together with load power. Also
check battery fuses.
OUTPUT C.B. OPEN This is a status alarm. This output isolator must be selected
‘CLOSED’ at all times except when operating on the
maintenance bypass supply.
RECTIFIER OFF This alarm is active whenever the battery charger (rectifier) is
OR not producing its correct output voltage; due to either an input
FAILED supply failure, an internal fault, or an open input circuit breaker.
55
UPS ON This is a status warning that the load is being powered through
MAINTENANCE the maintenance bypass line and is unprotected from mains
BYPASS supply abbreviations. Due to the fact that the UPS power
supplies are fed by the input circuit breaker, this message will
disappear if the input isolator is opened (and bypass isolator
opened on a split bypass system) while the load is on
maintenance bypass supply.
INVERTER This warns that the inverter is not synchronised with the bypass
UNSYNCHRONISED supply, which is normally due to a problem with the bypass
supply being outside an acceptable frequency window. Do not
switch OFF the inverter when this alarm is active or the load will
experience a 20-millisecond power break.
LOAD ON BYPASS This is a status warning that the load is being powered through
the static bypass line and is unprotected from mains supply
aberrations.
56
ANNEXURE
TXR
SCVS
TXR Cubicle 2
or UPS 1 UPS 2
Cubicle 1 or
SVR
Battery
Sharing Kit
57