Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To
Name (Model) Application Source Density Pressure Flow Heads Streams Source
Required
AREA DE VENTAS Demand (HW) 1405.8 534.6 0.181 12 38.8 7 250 25.1
114.3
Contractor Information
Name of Contractor: P&R Arquitectos Consultores
Design
Remote Area Name AREA DE VENTAS
Occupancy Classification
Special Heads
Location
Source W1
Notes
Supply Analysis
Residual Available
Static Pressure Flow Total Demand Required Pressure
Node at Source Pressure Pressure
(psi) (gpm) (gpm) (psi)
(psi) (psi)
W1 140.7 125 2000 139.3 534.6 114.3
Hoses
Inside Hose Flow / Standpipe Demand (gpm) 250
Sprinklers
Ovehead Sprinkler Flow (gpm) 284.6
Other
Required Margin of Safety (psi) 0
Graph Labels
Values
Label Description
Flow (gpm) Pressure (psi)
S1 Supply point #1 - Static 0 140.7
S2 Supply point #2 2000 125
S3 Supply point #3 3000 106
D1 Elevation Pressure 0 15.1
D2 System Demand 534.6 114.3
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
Overhead
P1 214.3 11.2 0.181 64.3 12 0.222 47.6 18
Sprinkler
Overhead
P2 214.3 11.2 0.181 64.3 12 0.191 40.9 13.4
Sprinkler
Overhead
P3 214.3 11.2 0.181 64.3 12 0.234 50.2 20.1
Sprinkler
Overhead
P4 214.3 11.2 0.181 64.3 12 0.181 38.8 12
Sprinkler
Overhead
P5 120 5.6 0.15 18 10.3 0.159 19.1 11.6
Sprinkler
Overhead
P6 214.3 11.2 0.181 64.3 12 0.211 45.2 16.3
Sprinkler
Overhead
P7 214.3 11.2 0.181 64.3 12 0.2 42.9 14.7
Sprinkler
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)