Sunteți pe pagina 1din 126



GEH-6131

*(,QGXVWULDO6\VWHPV

Innovation Series ™

Medium Voltage – GP Type H Drives

User’s Guide
Publication: GEH-6131
Issued: 1999-07-13

Innovation Series ™

Medium Voltage – GP Type H Drives

User’s Guide
© 1999 General Electric Company, USA.
All rights reserved.

Printed in the United States of America.

These instructions do not purport to cover all details or variations in equipment, nor to provide
every possible contingency to be met during installation, operation, and maintenance. If further
information is desired or if particular problems arise that are not covered sufficiently for the
purchaser’s purpose, the matter should be referred to GE Industrial Systems, Salem, Virginia,
USA.
This document contains proprietary information of General Electric Company, USA and is
furnished to its customer solely to assist that customer in the installation, testing, operation,
and/or maintenance of the equipment described. This document shall not be reproduced in whole
or in part nor shall its contents be disclosed to any third party without the written approval of GE
Industrial Systems.

PC is a registered trademark of International Business Machines Corporation.


Windows is a registered trademark of Microsoft Corporation.
Innovation Series™ is a trademark of General Electric Company.
Safety Symbol Legend

Indicates a procedure, practice, condition, or


statement that, if not strictly observed, could
result in personal injury or death.

Indicates a procedure, practice, condition, or


statement that, if not strictly observed, could
result in damage to or destruction of
equipment.

Note
Indicates an essential or important procedure, practice, condition, or statement.

Safety Symbol Legend • a


This equipment contains a potential hazard of electric
shock or burn. Only personnel who are adequately
trained and thoroughly familiar with the equipment and
the instructions should install, operate, or maintain this
equipment.

Isolation of test equipment from the equipment under


test presents potential electrical hazards. If the test
equipment cannot be grounded to the equipment under
test, the test equipment’s case must be shielded to
prevent contact by personnel.

To minimize hazard of electrical shock or burn,


approved grounding practices and procedures must be
strictly followed.

To prevent personal injury or equipment damage caused


by equipment malfunction, only adequately trained
personnel should modify any programmable machine.

b • Safety Symbol Legend


Contents
Chapter 1 Overview 1-1
Introduction............................................................................................................................ 1-1
Introduction to Drive.............................................................................................................. 1-2
Clean Power Input ................................................................................................... 1-2
High Power Factor, Nearly Perfect Sinusoidal Input Currents ................................ 1-3
Nearly Perfect Sinusoidal Output Voltages ............................................................. 1-4
Hardware Overview ............................................................................................................... 1-4
Software Overview................................................................................................................. 1-9
Technical Characteristics ....................................................................................................... 1-9
Cell Specifications ................................................................................................... 1-9
Safety Precautions and Warnings .......................................................................... 1-11
Technical Assistance............................................................................................................ 1-12
Related Documents .............................................................................................................. 1-13

Chapter 2 Functional Description 2-1


Introduction............................................................................................................................ 2-1
Theory of Operation............................................................................................................... 2-2
Introduction.............................................................................................................. 2-2
Power Circuitry........................................................................................................ 2-2
Basic Operation.................................................................................................................... 2-11
Cell Control System ............................................................................................................. 2-14
Drive Control Rack .............................................................................................................. 2-16
Common Electrical/Mechanical Specifications ................................................................... 2-18

Chapter 3 Control Terminal Board I/O and Fuses 3-1


Introduction............................................................................................................................ 3-1
DIN Rail I/O........................................................................................................................... 3-1
I/O Fuses ................................................................................................................................ 3-2
Application Control I/O ......................................................................................................... 3-2
Digital Inputs.......................................................................................................................... 3-3
Specifications........................................................................................................... 3-3
Digital Outputs (Relays) ........................................................................................................ 3-3
Solid State Relay Driver......................................................................................................... 3-4
Analog Inputs......................................................................................................................... 3-5
Analog Outputs ...................................................................................................................... 3-6
Meter Driver Outputs ............................................................................................................. 3-7
Tachometer Interface ............................................................................................................. 3-8
Contactor Control Pilot Relays and Status Indication ............................................................ 3-9
Local and System Fault String Inputs .................................................................................. 3-11
Logic Control Power Supply................................................................................................ 3-12
Potentiometer Power Supply................................................................................................ 3-13
Local Toolbox Port .............................................................................................................. 3-13

Contents • i
Test Lead Pass-Through Hole .............................................................................................. 3-13
Keypad RS232 Transceivers ................................................................................................ 3-13

Chapter 4 Drive Diagnostic Interface 4-1


Introduction............................................................................................................................ 4-1
Overview................................................................................................................................ 4-2
Using the Pushbuttons............................................................................................................ 4-2
Reading the Display ............................................................................................................... 4-4
Changing the Display Units ..................................................................................... 4-6
Adjusting the Display Contrast ................................................................................ 4-7
Status Screen .......................................................................................................................... 4-7
Reading the Meters .................................................................................................. 4-7
Alternate Status Screen .......................................................................................................... 4-8
Using the Menus .................................................................................................................... 4-9
Viewing and Resetting Faults ................................................................................................ 4-9
Editing Parameters ............................................................................................................... 4-10
Parameter Backup ................................................................................................................ 4-11
Restoring Parameters ............................................................................................. 4-12
Comparing Current Parameters to Backup ............................................................ 4-12
Tuning the Drive.................................................................................................... 4-13
Firmware and Hardware Information................................................................................... 4-14
Protecting the Keypad .......................................................................................................... 4-15
Modifying the Privileges........................................................................................ 4-16

Chapter 5 Preventive Maintenance 5-1


Introduction............................................................................................................................ 5-1
Schedule, Record, and Materials............................................................................................ 5-2
Maintenance Schedule ............................................................................................. 5-2
Maintenance Record ................................................................................................ 5-2
Tools/Materials Needed ........................................................................................... 5-2
Fan and Blower Airflow Check.............................................................................................. 5-3
Power-Off Checks.................................................................................................................. 5-3
Before Starting Maintenance ................................................................................... 5-3
Dust Removal .......................................................................................................... 5-4
Loose Connections................................................................................................... 5-4
Damaged Insulation ................................................................................................. 5-5
Inspecting Fiber Ends............................................................................................................. 5-5
Contactors and Relays.............................................................................................. 5-7
Printed Wiring Boards ............................................................................................. 5-7
Short-Circuit Damage .............................................................................................. 5-7

Chapter 6 Component Replacement 6-1


Introduction............................................................................................................................ 6-1
Before Starting ....................................................................................................................... 6-2
Replacing Printed Wiring Boards .......................................................................................... 6-2
Handling Precautions ............................................................................................... 6-2
Replacement Procedures.......................................................................................... 6-3
Removing and Installing Cells ............................................................................................... 6-4

Appendix A Warranty and Renewal Parts A-1


Introduction................................................................................................................... ........ A-1
Identifying the Part........................................................................................................... ..... A-1
Renewal Parts List .................................................................................................. A-2
Part Number Structure ............................................................................................ A-2
Warranty Terms ................................................................................................................. ... A-4
How to Order Parts ............................................................................................................. .. A-4
Data Nameplate....................................................................................................... A-4
Intelligent Part Number........................................................................................... A-6

Appendix B Drive Parts List B-1


Control Cabinet ......................................................................................................................B-1

Appendix C Cell Specifications C-1

Appendix D Optional Cell Tester D-1


Introduction........................................................................................................................... D-1
Required Equipment.............................................................................................................. D-1
Procedure For Testing an Installed Cell ................................................................................ D-2
Solid State Variable Voltage Source ..................................................................................... D-3
Introduction............................................................................................................. D-3
Protective Circuits................................................................................................... D-4
Operation ................................................................................................................ D-4
Troubleshooting ...................................................................................................... D-5
Specifications.......................................................................................................... D-7

Glossary of Terms G-1

Index I-1

Contents • iii
Chapter 1 Overview

Introduction
This manual describes the General Purpose (GP) Type H, non-regenerative model of
General Electric’s Innovation SeriesTM medium voltage AC drive. The purpose of
the manual is to assist the user in the operation and maintenance of this drive.
This chapter introduces drive features and defines the manual contents. Its purpose
is to present a general product overview and provide important reference information
for the reader in the following format:

Section Page

Introduction to Drive....................................................................................................2
Hardware Overview.....................................................................................................4
Software Overview ......................................................................................................9
Technical Characteristics .............................................................................................9
Technical Assistance..................................................................................................12
Related Documents ....................................................................................................13

Chapter 2: Functional Description describes the theory of the Innovation Series


Type H drive. The purpose is to provide basic information that will help a user
understand the components of the drive and how they interface.
Chapter 3: Terminal Board I/O and Fuses describes the interface for customer
interaction with the drive.
Chapter 4: Drive Diagnostic Interface (Keypad) explains the use of the keypad, how
to read its display, configure the settings and parameters, and view the faults.
Chapter 5: Preventive Maintenance provides a schedule and procedure for
maintaining and servicing the drive.
Chapter 6: Component Replacement describes how to shut down the drive and
proceed with replacing boards and power cells.
Chapter 7: Faults and Troubleshooting provides a list of faults, fault numbers, and
descriptions.
Appendix A: Warranty and Renewal Parts explains how to identify a part from its
nameplate, presents the terms and conditions of the warranty, and provides
information on how to order parts.
Appendix B: Drive Parts List

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-1


Appendix C: Functions and Parameters describes functions and parameters
encountered in the drive.
Appendix D: Cell Specifications
Appendix E: Drive Specifications
Appendix F: Wizards
Appendix G: Block Diagrams
Glossary

Introduction to Drive
The Type H Medium Voltage GP drive is a multilevel Insulated Gate Bipolar
Transistor (IGBT) based pulse width modulated (PWM) inverter. It is designed for
high performance and efficient control of variable speed, medium voltage induction
motors.
The drive system provides the following power quality characteristics:
• Clean power input
• High power factor
• Nearly perfect sinusoidal output

Clean Power Input


The drive meets the most stringent IEEE 519 1992 requirements for voltage and
current harmonic distortion, even if the source capacity is no larger than the drive
rating. The drive protects other online equipment (such as computers, telephones,
and lighting ballasts) from harmonic disturbances. The drive also prevents
interaction with other variable speed drives. Clean power input eliminates the need
for time consuming harmonic resonance analyses and costly harmonic filters. Figure
1-1 illustrates input waveforms for typical 6-pulse, 12-pulse, and Type H waveforms.

Source Current Source Current


Source Current

Source Voltage
Source Voltage Source Voltage

Typical 6-pulse Typical 12-pulse Innovation Series Type H


Input Waveform Input Waveform Input Waveform

Figure 1-1 Harmonic distortion waveform comparison.

1-2 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Typical harmonic distortion of the source current is 25% for 6-pulse, 8.8% for 12-
pulse and 0.8% for the Type H drives. The corresponding voltage distortion with a
typical source impedance are 10% for 6- pulse, 5.9% for 12-pulse and 1.2% for the
drive.

Note The above comparisons were done using a typical 1,000 hp current source
drive (6- and 12-pulse modes) and a Type H drive operating from a 1100 kVA
5.75% impedance source.

High Power Factor, Nearly Perfect Sinusoidal Input


Currents
Power factor is a measure of the fraction of current that produces real power to the
load. Typically, power factor is given as a percentage. A high power factor (95%)
Variable Frequency Drive (VFD) makes better use of its input line current demand in
producing real power to the motor than a VFD operating at a low power factor
(30%). VFDs having low power factor often generate square-wave shaped line
currents. This can lead to harmonics and other associated resonance problems.
The Type H drive draws nearly perfect sinusoidal input currents having a power
factor that exceeds 95% throughout the entire speed range without the use of external
power factor correction capacitors. This eliminates utility penalties for power factor
and demand charges, and improves voltage regulation. In addition, feeders,
breakers, and transformers are not overloaded with reactive power. Low speed
applications specifically benefit from the Type H drive since a high and stable power
factor is maintained throughout the entire speed range using a standard induction
motor. Figure 1-2 below compares graphs of power factor versus percent speed for
the Type H drive and a typical phase controlled SCR (Silicon Controlled Rectifier,
also known as a Thyristor) drive.

100

90

80
Innovation Series
Medium Voltage
70
Type-H AC Drive
Percent Power 60 Series Drive
Factor 50

40 Phase-controlled
SCR Drive
30

20

10 Percent Speed
20 27 33 40 47 53 60 67 73 80 87 93 100

Figure 1-2 Plot of Power Factor vs. Percent Speed comparing Innovation Series Type H and
typical phase controlled SCR drive.

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-3


Nearly Perfect Sinusoidal Output Voltages
The design of the Type H variable frequency drive inherently provides a sinusoidal
output without the use of external output filters. This means that the drive provides a
low-distortion output-voltage waveform that generates no appreciable audible motor
noise. In addition, there is no need to derate the motors (the drive can be applied to
new or existing 1.0 service factor motors). Similarly, VFD induced torque pulsations
are eliminated (even at low speeds), therefore reducing the stress on mechanical
equipment. Common mode voltage stress and dV/dt stress are also minimized.

Typical
Phase C Output
Output
Current Time
Time
Current

Figure 1-3 Nearly sinusoidal output current waveform from an Innovation Series Type H
drive.

Hardware Overview
Figure 1-4 depicts a typical sectional type cabinet line-up. Each VFD normally
consists of four cabinet sections:
• Bypass Contactor (optional)
• Input Power and Option
• Transformer/Blower
• Cell
• Power Output/Control
Points of Separation
Input Disconnect Switch
Output Control

Bypass CDS1

Contactor Air Duct Covers (Optional)


Meters,
PB4
Keypad,
and
Scratch
Pad

VFD
Contactor

Bypass Input Power Power Output


Contactor Cabinet and Cell Cabinet
Transformer Cabinet and Control Cabinet
Cabinet Option Blower Section
(Optional) Section

Figure 1-4 Typical Drive Lineup

1-4 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Note For 600 hp and below, the Innovation Series Type H drive is available in a
single cabinet with compartments for all of the sections shown above. These drives
have lifting bolts and fork truck lifting tubes for proper handling.

Note Hardware torque specifications are given in the Installation and Startup
Guide, GEH 6130. For liquid cooled drives, refer to GEH-6132.

The Bypass Contactor Cabinet is an optional cabinet that provides all necessary
control and hardware for full voltage bypass operation.
The Input Power and Option Cabinet houses the input terminals, the disconnect
switch and fuses. Various input/output options are also supplied in this section (such
as meters and associated hardware).
The Transformer/Blower Cabinet houses the input phase shifting transformer and
surge suppression which supplies 3-phase voltages to the output cells (refer to Figure
1-5). This cabinet contains a secondary tap board which is used as a connection
point between the various secondary windings and the output cells. This tap board is
supplied so that the Transformer Cabinet can be easily separated from the Cell
Cabinet. Surge suppression is supplied as a standard in this cabinet. The cooling
blowers are also supplied in this section.
The Cell Cabinet houses between three and six cells per output phase. Each output
phase voltage is the series sum of the horizontal cell voltages (refer to Figure 1-6).
Each cell can be disconnected and removed from the cabinet by disconnecting the 3-
phase input power, the two output connections, the fiber-optic cable, and a retaining
bolt. All cells are electrically and mechanically identical, so that they may be
interchanged. Each cell contains its own control boards that communicate with the
system through an isolated link using fiber-optic cables.
The Power Output/Control Cabinet houses the control boards (refer to Figure 1-7)
as well as the VFD output connections.

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-5


Air Duct Covers
(Optional)

TB

CT1 CT2 Low Voltage BLWR2

Wire Way
MTR2
MTR1 BLWR1 BLWR2
MTR2
Blower/Motor
Assembly
(Redundant
Blower Shown)

Terminal
Board
Access

Input Primary
Connections
w/Surge Arrestors
Transformer

Fork Truck
Lifting Tubes

-5%, 0%, and


+5% Taps

Figure 1-5 Inside view of typical transformer/blower cabinet.

In some sectional drives, the blower must be removed/replaced from the top of the
drive cabinet. In these installations, be sure to allow ample vertical clearance for fan
servicing (and removal) between the top of the cabinet and the ceiling
(approximately 26.5 inches). To remove the fan(s), the optional air duct cover must
be removed and the fan “tub” assembly must be lifted vertically from the cabinet. If
the optional duct covers are not used, then plenum/duct connections must be
removable to allow proper access for servicing and replacement of fans and
associated components.

1-6 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


A1 A2 A3 A4 A5
T2 T1 T2 T1 T2 T1 T2 T1 T2 T1

B1 B2 B3 B4 B5
T2 T1 T2 T2 T2 T1

C1 C2 C3 C4 C5
T2 T1 T2 T1 T2 T1 T2 T1 T2 T1

Figure 1-6 Inside view of a typical cell cabinet (cell sizes 1 or 2).

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-7


Meters or
Scratch Pad

Standard
Output
Terminals
Control
Rack

Fiber-
Optic Hub
Board

Figure 1-7 External and internal views of a typical power output/control cabinet.

1-8 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Software Overview
The drive application program consists of functional software modules (building
blocks). They combine to perform according to system requirements. Block
definitions and configuration parameters (see Appendix C) are stored in EEPROM.
Variables are stored in RAM.
Tuneup and diagnostic software is transparent to the user. Operator control is
provided as menu driven selections on the door mounted interface unit (DDI, See
Chapter 4) The drive continually monitors performance and outputs the results to the
DDI display as animated meters, icons and digital values. Additional menus allow
the operator to examine and reset any detected fault.
An optional Windows-based configuration, tuneup, and monitoring package is
available for use on a connected personal computer (PC). This Control System
Toolbox provides online help functions, including parameter diagrams. Refer to the
toolbox manual, GEH-6401, for details.

Technical Characteristics
Cell Specifications
The drive system is offered in several basic cell sizes (current ratings), grouped to
provide output operating voltages of 2400 V ac (3 cells in series), 3300 V ac (4 cells
in series), 4160 V ac (5 cells in series), or 4800 V ac (6 in series). Appendix D
provides the basic specifications associated with all cell combinations.
The drive is offered in additional cell sizes (current ratings) for higher voltage
applications. These high voltage cells are grouped to provide operating voltages of
6000 V ac (5 cells in a series) and 6600 V ac (6 cells in a series). Refer to Appendix
D for 6000 V ac and 6600 V ac cell specifications.

Note Output current ratings are a function of the selected cell size. Input current
ratings are a function of the transformer size associated with each hp rating. Note
that all specifications are subject to change without notice.

The individual output cells are located in the Cell Section. All cells are electrically
and mechanically identical, so that they may be interchanged. Each cell contains its
own control boards that communicate with the system through a fiber-optic link.
This link is the only connection between the cells and the master control located in
the Control Section, thus each cell is fully isolated from the main control.
A switching power supply located on the Cell Control Board (refer to Figure 1-8)
allows the control power to be derived from the individual 3-phase secondary
connections of the transformer. This power supply is fully operational between 250
and 510 V ac.

Note For high-voltage cells, the power supply is fully operational between 375 V ac
and 750 V ac. For liquid cooled drives, refer to GEH-6132.

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-9


The Control Section contains printed circuit boards that provide central control of the
Innovation Series Type H drive system. The Control Section is physically and
electrically isolated from all medium voltage for safety.
Control for each of the output cells is provided via a fiber-optic communications link
between the Master Link Board and the Cell Control Board located within each
output cell.
Appendix D gives length and weight information for many common configurations
of the drive, based on 60 Hz input power at the voltages listed. If applications
require inputs at 50 Hz or voltages above 5 kV, sizes and weights may increase.

Underside
View (View
Y-Z)

Front View Side View


Detent Lock
“Not Safe"
"Not Safe”
Bus Voltage
Bus Voltage
Monitor
LED
Y Z

R2A R1A

T1
T2 T1
Fiber Optic
Link IGBT
Connection Gate Driver Board

Cell Control
Cell Control Board
Board
F11 F12 F13 F13

A B C
Š Lnk ON
Š Q1
Š Q2
Š Q3
Input Cell Power Š Q4
from T1 Š Bypass Close-up View of
Š Cell Fault Diagnostic LEDs

Figure 1-8 Typical air-cooled Innovation Series Type H AC power cell (top, side, and front views).

Note The bus voltage monitor (shown in Figure 1-8) remains illuminated down to
at least 50 V dc.

1-10 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Safety Precautions and Warnings
The drive is designed with considerable thought to personal safety. However, as
with any piece of high power equipment, there are numerous internal connections
that maintain potentially lethal voltages. In addition, the heat sinks and many other
internal components are thermally hot. The warnings shown below should be
followed when working in or near the drive system.

Transportation and Material Issues

When transporting the Innovation Series Type H


drive system, the truck bed must be even and flat.
Before unloading, be sure that the concrete pad is
level for storage as well as permanent positioning.

Indoor equipment is not weatherproof and must be


protected. If it is necessary to temporarily store it
in an outdoor area, refer to Receiving, Handling,
and Storage of Innovation Series Equipment (GEI-
100256)

When using fork trucks to move the Innovation


Series Type H drive or its components, be sure to
use the lifting tubes designed for this purpose.
Never use fork trucks to lift cabinets that are not
equipped with lifting tubes. Be sure that the fork
truck tines are the appropriate length.

Never store flammable material in, on or near the


drive enclosure. This includes equipment
drawings and manuals.

Never run the drive with cabinet doors open. Also,


never leave the Transformer Cabinet doors open -
it reduces cooling to the drive.

Never shut off the blower power and leave the


main power on. This may cause the drive to
overheat and cause severe damage to the system.

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-11


Electrical Issues

Never connect or disconnect any meters, wiring or


printed circuit boards while the drive is energized.

Always use extreme caution when handling or


measuring components that are inside the
enclosure. Be careful to prevent meter leads from
shorting together or from touching other
terminals.

Never assume that by switching off the input


disconnect, that all of the voltage is removed from
inside the cabinet. Voltage is still present on the
terminals of the input disconnect. Also, there may
be voltages present that are applied from other
external sources.

Never remove safety shields (marked with a HIGH


VOLTAGE sign) or attempt to measure points
beneath the shields.

Additional safety precautions and warnings appear throughout this manual. These
important messages should be followed to reduce the risk of personal injury or
equipment damage.

Technical Assistance
For assistance contact:

General Electric Company


Product Service Engineering
1501 Roanoke Blvd.
Salem, VA 24153-6492 USA
Phone: 1-540-387-7595
Fax: 1-540-387-8606

1-12 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Related Documents
The following publications also apply to your Innovation Series Medium Voltage GP
Type H drive and may assist in understanding the system:

• Receiving, Handling, and Storage of Innovation Series Equipment


(GEI-100256)
• Installation and Startup (GEH-6130)
• Control System Toolbox for Configuring an Innovation Series Drive
(GEH-6401)

GEH-6131 MV-GP Type H Drives Chapter 1 Overview • 1-13


Notes

1-14 • Chapter 1 Overview GEH-6131 MV-GP Type H Drives


Chapter 2 Functional Description

Introduction

This chapter describes the theory of the Innovation Series Medium Voltage – GP
Type H. The purpose is to provide basic information that will help a user understand
the components of the drive and how they interface. This chapter contains the
following information:

Section Page

Theory of Operation............................................................................................................ .......2


Basic Operation................................................................................................................ ........11
Cell Control System .................................................................................................................14
Drive Control Rack ..................................................................................................................16
Common Electrical/Mechanical Specifications .......................................................................18

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-1


Theory of Operation
Introduction
The drive provides variable speed operation by converting utility power at a fixed
frequency and fixed voltage to variable frequency, variable voltage power. This
conversion is done electronically, without moving parts. Unlike older drives, the
Type H drive does not force the user to accept unpleasant by-products of this
conversion process. Specifically, the drive:
• Does not inject significant harmonic distortion into the plant’s distribution
system. No power filters are required. No interference to sensitive equipment
or resonance problems with power factor capacitors will occur.
• Presents a high power factor to the utility, typically 95% or better throughout the
speed range. No power factor correction is required.
• Does not require any derating of the motor due to output harmonics. No
additional motor heating is produced versus operation directly from the utility.
• Does not produce torque pulsations that can excite mechanical resonances.
• Causes no noticeable increase in acoustic noise from the motor, versus operation
directly from the utility.
• Causes no appreciable additional stress to the motor insulation, versus operation
directly from the utility.
• Allows unrestricted use of rated motor torque throughout the speed range,
subject only to the thermal limitations of the motor.
• Is completely modular in construction. A defective module can be replaced in
minutes. The GE Innovation Series Toolbox or the built-in keypad can be used
to diagnose any failures.

Power Circuitry
Note The examples used in this section refer to drives having low-voltage (460 V
ac) cells. High-voltage cell systems have different values.

Medium voltage levels are obtained by adding together the outputs of multiple
low-voltage power cells. The low-voltage power cells are simplified variations of
standard Pulse Width Modulated (PWM) drives, which have been built in high
volume for many years.
Figure 2-1 shows the input transformer topology for a 2400 volt drive. Three power
cells connected in series drive each motor phase. The groups of power cells are wye-
connected with a floating neutral. Each cell is powered by an isolated secondary
winding of an integral isolation transformer. The nine secondaries are each rated for
480 V ac at one ninth of the total power. The power cells and their secondaries are
insulated from each other and from ground for the full output voltage of the drive.
For a 3300 volt drive, Figure 2-1 would be extended to have four power cells in
series in each phase, with 12 secondaries on the integral isolation transformer. For a
4160 volt drive, there would be five power cells in series in each phase, with 15
secondaries on the integral transformer.

2-2 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


Each cell is a static power converter. It is capable of receiving input power at 480 V
ac 3-phase, 50/60 Hz and delivering that power to a single-phase load at any voltage
up to 480 V ac and at any frequency up to 120 Hz.
With three power cells in series per phase, a drive can produce as much as 1440 V ac
line-to-neutral. With five power cells in series per phase, the drive can produce as
much as 2400 V ac line-to-neutral, or 4160 V ac line-to-line.
The power cells all receive commands from one central controller. These commands
are passed to the cells over fiber-optic cables in order to maintain 5 kV isolation.
The transformer secondaries that supply the power cells in each output phase are
wound to obtain a small difference in phase angle between them. This cancels most
of the harmonic currents drawn by the individual power cells so that the primary
currents are nearly sinusoidal. The power factor is always high - typically 95% at
full load.
The schematic of a typical power cell is shown Figure 2-2. In this example, a
3-phase diode rectifier, fed by the 480 V ac secondary, charges a DC capacitor bank
to about 600 V dc. The DC voltage feeds a single-phase H-bridge of IGBTs.

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-3


Special Transformer with +20° Power
9 Isolated Secondaries Cell
(15 for 4,160 VAC) * See note A1
below.

+20° Power
Cell
* See note below.
B1

+20° Power
Cell
* See note below.
C1

0° Power
Cell
Input Power * See note A2
3-phase AC below.
(Any Voltage)
0° Power
Cell
* See note below.
B2

0° Power
Cell
* See note below. C2

-20° Power
Cell
* See note A3
below.

-20° Power
Cell
* See note below.
B3

-20° Power
Cell
* See note below.
C3

2400 VAC
Induction
* Transformer Phase Shift = (60 degrees) / (# of cells per phase) Motor

Figure 2-1 Input transformer topology of Innovation Series Type H AC drive (3 cells, 2400 V
ac).

At any instant of time, each cell has only three possible output voltages. If Q1 and
Q4 are on, the output will be +600 Vs from T1 to T2. If Q2 and Q3 are on, the
output will be -600 V. Finally, if either Q1 and Q3 or Q2 and Q4 are on, the output
will be 0 V.
With three power cells per phase, the circuit of Figure 2-2 can produce seven distinct
line-to-neutral voltage levels (±1800, ±1200, ±600, or 0 V). With five cells per
phase, 11 distinct voltage levels are available. The ability to generate many different
voltage levels allows the drive to produce a very accurate approximation of a
sinusoidal output waveform.

2-4 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


Dedicated 460 VAC IGBTs Q1-Q4
Winding on Power Q1 Q3
Transformer
+

1
T2
Power Output
2 of Cell
+
Q2 Q4 T1
3

Local Fiber Optic Signals to


Control Local Control Circuits and from Master
Power Control

Figure 2-2 Schematic of a typical power cell (low voltage cell).

Figure 2-3 shows how these waveforms are generated for the case of three cells per
phase. First, a reference signal is created for each phase. These signals are
scaled-down replicas of the ideal waveform to be approximated. In Figure 2-3, RA is
the reference signal for phase A. This reference signal is then compared with three
triangular carrier signals, oscillating at 600 Hz. Figure 2-3 shows conditions when
the output frequency is 60 Hz, so that there are exactly 10 carrier cycles per
reference cycle. The three carriers are identical except for successive phase shifts of
60 degrees (based on the carrier frequency). Carrier phase shift is computed based
on the following equation:
Carrier Phase Shift = (180 degrees) / (# of cells per phase)
Whenever the reference is greater than the first (unshifted) carrier, the signal L1 is
high; otherwise L1 is low. L1 is used to control the pair of transistors Q1 and Q2 in
cell A1 (see the left pair of transistors in Figure 2-2). Whenever the reference is
greater than the inverse of the first carrier, the signal R1 is low; otherwise R1 is high.
R1 is used to control the pair of transistors Q3 and Q4 in cell A1 (see the right pair of
transistors in Figure 2-2).
The difference between L1 and R1 gives the output waveform of cell A1, shown in
Figure 2-3 for Phase A as A1.
In a similar manner, the reference signal is compared with the second carrier (shifted
60 degrees) and its inverse to generate control signals L2 and R2 for the transistors in
cell A2. The output waveform of cell A2 is shown as A2.
Finally, the reference signal is compared with the third carrier (shifted 240 degrees)
and its inverse to generate control signals L3 and R3 for the transistors in cell A3. The
output waveform of cell A3 is shown as A3.
The sum of the output voltages from cells A1, A2 and A3 produces the A-to-neutral
output voltage of the drive, shown in Figure 2-3 as AN. There are seven distinct
voltage levels. Note that this voltage is defined between terminal A and the floating
neutral inside the drive, not the motor neutral.

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-5


RA

L1
R1
A1

L2
R2
A2

L3
R3
A3

AN

Figure 2-3 Waveforms for phase A.

Figure 2-4 shows the same signals for Phase B. The three carriers are identical to
Figure 2-3. The reference RB is also identical to Figure 2-3, except that it is delayed
by 120 degrees (at the reference frequency).
The sum of the output voltages from cells B1, B2 and B3 produces the B-to-neutral
output voltage of the drive, shown in Figure 2-4 as BN.
Figure 2-5 repeats the two line-to-neutral voltages AN and BN. The numerical
difference between AN and BN forms the line-to-line voltage impressed on the motor,
and is shown in Figure 2-5 as AB.

RB

L1
R1
B1

L2
R2
B2
L3
R3
B3

BN

Figure 2-4 Waveforms for phase B.

2-6 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


AN

BN

AB

Figure 2-5 Waveforms for line-to-line voltage.

1,000 HP, 2,400 VAC Motor at Full Speed, Full Load

Motorvoltage,
Motor line-to-neutral Line-to-neutral
Peak = Voltage, Peak = 2,000 Volts
2,000 Volts,
Motor phase A Motor Phase
current, A Current,
Peak Peak
= 348.9841 = 348.9841 Amps
Amps

Figure 2-6 Output waveforms, 2400 volt drive at full load.

Figure 2-6 shows motor voltage and current waveforms for a 2400 V ac drive rated
at 1000 hp. The voltage shown is between phase A and the motor neutral (not the
same as the drive neutral). The motor current is in phase A during full-load
operation. A quantitative measure of the waveform quality is its Total Harmonic
Distortion, or THD. The THD generated when using an Innovation Series Type H
drive is always less than five percent.
Figure 2-7 shows the input voltage and current waveforms for the same drive as in
Figure 2-6, under the same conditions. The perfect sine wave in Figure 2-7 is the
voltage into the special input transformer, measured between phase A and the neutral
of the wye-connected primary. The other waveform represents the current into phase
A of the same winding.

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-7


Figure 2-7 Input waveforms for a 2400 volt drive at full load.

The current waveforms drawn from the power source by the drive are also good
approximations to true sine waves, due to the harmonic cancellation obtained with
the phase-shifted secondary windings of the transformer. The THD of the input
currents with a drive is also always less than 5 percent.
In Figure 2-7 the the input current lags the input voltage by less than 15 degrees at
full load. This represents a power factor better than 96 percent. The drive always
maintains a high power factor, typically better than 95 percent throughout the speed
and load range.
The waveforms shown in Figure 2-2 through Figure 2-7 represent the worst case for
the drive when there are only 3 cells per phase. When the number of cells increases,
as in 3300 volt or 4160 volt drives, the waveforms become considerably cleaner.
Figure 2-8 shows the motor voltage and current for a 4160 volt drive at full power,
while Figure 2-9 shows the input voltage and current for the same drive and load.

Figure 2-8 Motor A-B voltage and current in phase C at full load for a 4160 volt drive.

Figure 2-9 Input A-B voltage and current in phase C at full load for a 4160 volt drive.

2-8 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


The block diagram in Figure 2-10 shows how the drive control circuits are
organized. The power cells receive commands and return status information via
duplex fiber-optic cables, using serial communication at a speed of 5 Megabaud.
The local communication circuits in each power cell are slaves; the only transmit in
response to an incoming message. These messages originate on one of the Master
Link Boards (MLB), which can initiate a transmission. Each MLB has three
communication channels and controls three power cells, one in each output phase.
The three power cells connected to one MLB have all the same stage number.
Master Link #1 controls power cells A1, B1 and C1; while Master Link #2 controls
power cells A2, B2 and C2; and so forth.
The MLBs all plug into a single motherboard called the Fiber-optic Hub Board
(FOHB). The FOHB has slots for as many as six MLBs, which will accommodate a
4160 V AC drive with spare cells as shown. Drives with fewer than 18 power cells
will have one or more V acant slots on the FOHB.
The FOHB provides +5 volt DC power to the MLBs, and also a set of timing signals
derived from a crystal oscillator. These timing signals cause all of the MLBs to
transmit simultaneously, once every 10.4 microseconds. The transmitted message
contains 11 bits (two start bits, eight data bits, and one stop bit), and is delivered in
less than four microseconds. The power cells then send back a similar message in
response, which arrives within an additional 4 microseconds. During the remaining
2.4 microseconds, the MLBs check that every transmission is complete and has the
correct parity. If an error is detected a link fault is generated.
For a 4160 volt drive with five power cells per phase, there are five pairs of carrier
waves displaced by multiples of 36 degrees. For a 2400 volt drive with three power
cells per phase, there are three pairs of carrier waves displaced by multiples of 60
degrees. The carrier waves are compared with reference signals to generate PWM
control signals for the power cells.
The FOHB also contains several digital registers, which store data determining the
drive configuration. Such data include:
• the phase displacement needed for the carrier waves
• the power cells that have been bypassed.
The FOHB contains a multiplexing scheme that allows the microprocessor to
interrogate each power cell in sequence for diagnostics.
The FOHB connects by ribbon cable to the BPIR Digital Interface Card. The BPIR
is connected to the BICR Bridge Interface Card and to the DSPX microprocessor
card via the backplane (CABP) on the cardrack. The BICR collects feedback signals
such as motor voltage and current.

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-9


Figure 2-10 Block diagram of Innovation Series Type H control structure for 4160 volt drive.

2-10 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


Basic Operation
The basic electrical diagrams for all Innovation Series Medium Voltage – GP Type
H systems are similar. One critical component of all Type H drives is the power cell.
Either 3, 4, 5, or 6 power cells are operated in series to develop the required system
voltage (refer to Figure 2-11 and Figure 2-12). Appendix D provides cell
specification details for the drive system.

Table 2-1. Cell Specification Details


Number of Line-to-line Total Number of Hp Range Available Power Cell Sizes
Power Cells Voltage (V Cells in Drive
Per Phase AC)
3 2,400 9 200-1,750 00A, 0A, 1A, 2A, 3A, 4A, 5A, 5B
4 3,300 12 300-2,250 00A, 0A, 1A, 2A, 3A, 4A, 5A, 5B
5 4,160 15 300-3,000 00A, 0A, 1A, 2A, 3A, 4A, 5A, 5B
L6A, L7A
6 6,600/7,200 18 500-10,000 0H, 1H, 2H, 3H, 4H, 5H, 6H, 8H

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-11


Cell A4 Cell A5
Fiber- Fiber-
optic optic

4 Cells Cell B4 Cell B5 5 Cells


Added for Fiber- Fiber- Added for
3,300V AC optic optic 4,160V AC

Cell C4 Cell C5
Fiber- Fiber-
optic optic
LINK A LINK B LINK C LINK A LINK B LINK C

Spare Slot for Redundant


Cell Option
Master Link Master Link
Board Board
6 1 6 1
6 1 6 1 6 1

PL4 PL5 PL6

FU1
2 FOHB
TB1
To HFPR Fiber-optic
3 Hub Board
TB1 1

7 -24V

6 COM
To HFPR
1 +24V PL1 PL2 PL3
6 1 6 1 6 1
TB1 6 1 6 1 6 1
Master Link PL Master Link Master Link
Board 1 50 Board Board

LINK A LINK B LINK C LINK A LINK B LINK C LINK A LINK B LINK C


Cell A1 Cell A2 Cell A3
Fiber-optic Fiber-optic Fiber-optic
Data Link Data Link Data Link

Cell B1 Cell B2 Cell B3


Fiber-optic Fiber-optic Fiber-optic
Data Link Data Link Data Link
3 Cells
Added for
2,400V AC Cell C1 Cell C2 Cell C3
Fiber-optic Fiber-optic Fiber-optic
Data Link Data Link Data Link

Ribbon Cable

Figure 2-11 Typical Fiber-Optic Hub Board/Master Link Board Connection Diagram

2-12 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


4
4
A1 A1

4 M M
4
B1 L B1 L
B B
4
1 4 1
C1 C1

3 1
A2 A2

3 M 1 M
B2 L B2 L
B B
3 1
2 2
C2 C2

2 2
F
A3 A3
I
B
2 M 2 M E
B3 L B3 L R
B B |
2 3 2 3 O C
Input Power 3-phase C3 C3 P O
AC (Any Voltage) T N K
5 5 I T E
A4 A4 R
C Y
O P
5 M 5 M
H L A
B4 L B4 L
B B U D
5 4 5 4 B R
C4 C4 A
B C
7 O K
6 A
A5 A5
R
M 7 M D
6
B5 L B5 L
B B
7
6 5 5
C5 C5

7
A6

7 M
B6 L
B
7
6
C6

Voltage Voltage
Attenu- Attenu-
Legend ator ator

1 - No Phase Shift 4160 V AC


Induction 4160 V AC
2 - Phase Leading (Min) Induction
3 - Phase Leading (Med) Motor
Motor
4 - Phase Leading (Max)
5 - Phase Lagging (Min)
6 - Phase Lagging (Med)
7 - Phase Lagging (Max)

Figure 2-12 Typical Power Circuit (18 and 15 Secondary Configurations Shown).

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-13


Cell Control System
All power cells are controlled in exactly the same manner. The Cell Control Board
(CCB) resides within the power cell (refer to Figure 2-13 and illustrations in Chapter
1) and accept all communication from the Master Link Boards in the Control Cabinet
via fiber-optic links. The IGBT Gate Driver Board (refer to Figure 2-13 and
illustrations in Chapter 1) interfaces the CCB to the IGBT power switches.
Depending on the options ordered with the basic drive, a bypass SCR Driver Board
(refer to Figure 2-13 and illustrations in Chapter 1) may also be resident to each cell.
With the bypass option, the control can bypass a failed cell so that the remaining
cells in each series leg can be operated at a reduced (combined) output voltage level.
This bypass feature is implemented automatically following a trip due to a cell fault
condition as long as communication with the cell is maintained.

Note The Bypass SCR Driver Board is identical for all sizes of Innovation Series
Type H cells.

Control power for the gate driver board and the bypass board is supplied from a
switching power supply resident on the Cell Control Board.

2-14 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


Output
Power
Bypass SCR
Driver Board
SCR1 PL3
T2 T1
Ribbon Cable

PL1

DDE
NOTE: Each semiconductor
is shown as one device for
DDD
simplicity, but may actually
be several parallel devices.
L1 L2

Optional Output
Bypass Circuit

Q3
Q4

Ribbon Cable

PL1 PL2
Q1 F10 Q2

Fiber Optic
Data Link

IGBT Gate
Driver

Cell Control
Board

S2
TAS2B

TAS2A

PL1
C1 C2
3
DDC 12
11

DDB 2
10
1
DDA 8

4
F12 F13
F11 F3
7

F2 6
Input Power 5
from T1 F1

Figure 2-13 Typical Low-voltage Power Cell with Optional Bypass

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-15


Drive Control Rack
The Innovation Series control rack is located within the control enclosure. The
following is a brief functional description of the cards used in the control. Refer to
Figure 2-14.
CABP The Control Assembly Backplane is a multi-layer printed wiring board
which provides the interconnect for the printed wiring assemblies inserted into it.
DSPX This card is the Central Processing Unit (CPU) for the drive. It is the primary
controller for the bridge and motor regulators and gating functions. In addition, the
DSPX supports interfaces to bridge and customer input/output (I/O) as well as serial
interfaces to the keypad programmer and to the GE Control System Toolbox
interface. Indicating lights are provided on the DSPx card for fault and status
indication as follows:

Fault Light
Solid Red - Drive Trip Fault Detected
Blinking Red - Drive Warning Detected
Light Off - Drive OK, No Faults or Warnings Detected

Status Light
Light Off - Drive Off ... Not Ready
Solid Green - Drive Off ... Ready to Run
Slow Blinking Green - Drive On ... Pre-Conditioned
Fast Blinking Green - Drive On ... Running

BAIA The bridge application interface board plugs directly into the backplane and
interfaces with the BICR, DSPX, and LAN printed wiring boards. It contains
customizable I/O that can be tailored for specific applications, however it is not
required for bridge I/O. ATBA Application I/O terminal board interfaces to the
BAIA card.
BICR The bridge interface card monitors input and output voltage with attenuator
strings consisting of voltage dividers and voltage clamps. BICR measures motor
phase B and C output current with Hall Effect current sensors. It also contains I/O
interfaced through CTBC card for internal bridge I/O (blowers, thermal switches,
etc.)
BPIR This Digital interface card provides a 15V to 5V digital bus interface between
the Fiber-Optic Hub Board (FOHB) and the Bridge Interface Card (BICR).
RAPA The Rack Power Supply Card accepts a 48V 25Khz square wave input
from the High Frequency Power Supply Card (HFPR). The RAPA converts this
voltage to provide the rack with +/- 18-24V, +/-15V, +5V, +/-12V and +24V
which is used to power cards in the control.
HFPR The High Frequency Power Supply converts 48 V ac to a 48 volt 25Khz
square wave output. This output voltage is used to power Rack Power Supply Card
(RAPA) and the Fiber-optic Hub Board (FOHB).

2-16 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


FOHB The Fiber-optic Hub Board (FOHB) implements basic cell hardware control,
protection, and diagnostics. The FOHB functions are interfaced with the control
through the BPIR Digital interface card and are passed between the BICR and the
BPIR through CABP backplane. This board may contain from three to six plug-in
Master Link Boards depending on the operating output voltage (system voltage).
This board contains the fiber-optic transmitter/receiver system used for
communication with the cells. A separate switching power supply on the FOHB
supplies all the necessary power to the FOHB and the Master Link Boards. See
Table 2-1 to determine the number of MLBs. The number of MLBs is equal to the
number of power cells per phase.

Note Although each printed circuit slot (PL1 through PL6) on the FOHB is
dedicated to particular cell inputs, the Master Link Boards themselves are identical.

HFPR
TB1 HIGH FREQUENCY
POWER SUPPLY HFPL1

HFPL2 CTBC
FAPL1
COOLING SYSTEM AND
+24 VDC
FAPL2 DRIVE SPECIFIC I/O

-24 VDC

TO CARD
RACK FAN

IBM
COMP ATBA
CABP
APPLICATION BACKPLANE BAIA RAPA BICR BPIR
CARD BASIC LOCAL RACK
I/O APPL. POWER TEST
I/O I/F SUPPLY PTS

DEDICATED TOOL
INTERFACE (RS232)

TB1

DSPX OPTION
CPU SLOT

FLT
STAT TB2
(OPTIONAL)
METERS

KEYPAD

CARD RACK FAN


DEDICATED
KEYPAD
INTERFACE

DRIVE DRIVE VOLTAGE


INSYNC MICROPROCESSOR AND CURRENT
DRIVE/LOCAL EXTENDED
FEEDBACK
I/O APPLICATIONS
WIRING

Figure 2-14 Typical Control System Overview

GEH-6131 MV-GP Type H Drives Chapter 2 Functional Description • 2-17


Common Electrical/Mechanical Specifications
Table 2-2 lists common electrical (and mechanical) specifications for all standard
Innovation Series Type H drive systems. Note that the drive specifications may be
changed without notice.

Table 2-2 Common Specifications for Standard Innovation Series Type H Drives

Item Description
Hp range 200-1750 hp (2400 V AC)
300-2250 hp (3300 V AC)
300-3000 hp (4160 V AC)
400-3500 hp (4800 V AC)
500-3000 hp (6000 V AC) 1
500-3500 hp (6600/7200 V AC) 1
Input voltage tolerance +10%, -5% from nominal 3-phase at rated output
Input power factor 0.95 at all speeds
Speed range 0-120 Hz (motor dependent)
Overload capability 110% for 1 minute
Harmonics Rating Conforms to IEEE 519 standards
Output torque 0-60 Hz variable, 5-60 Hz constant (motor limited)
Enclosure NEMA 1 ventilated
Ambient temperature 0-40° C
Humidity 95% non-condensing
Altitude 3300 feet above mean sea level or less
Dust contamination <100 micron @ 6.5 mg/cu. ft.
Gas contamination <4 PPB reactive chlorides and sulfides
1-
High voltage cells

2-18 • Chapter 2 Functional Description GEH-6131 MV-GP Type H Drives


Chapter 3 Control Terminal Board I/O
and Fuses

Introduction
This section provides an overview of the control terminal board and customer control
connection points within the drive. For more detailed information refer to the
board’s GEI.
This section is in the following format:

Section Page

DIN Rail I/O................................................................................................................... ............1


I/O Fuses ...................................................................................................................... ..............2
Application Control I/O ........................................................................................................ .....2
Digital Inputs................................................................................................................. .............3
Digital Outputs (Relays) ....................................................................................................... .....3
Solid State Relay Driver.............................................................................................................4
Analog Inputs.................................................................................................................. ...........5
Analog Outputs ................................................................................................................. .........6
Meter Driver Outputs ........................................................................................................... ......7
Tachometer Interface ........................................................................................................... ......8
Contactor Control Pilot Relays and Status Indication ................................................................9
Local and System Fault String Inputs ......................................................................................11
Logic Control Power Supply....................................................................................................1 2
Potentiometer Power Supply....................................................................................................13
Local Toolbox Port ..................................................................................................................13
Test Lead Pass-Through Hole ..................................................................................................13
Keypad RS232 Transceivers ....................................................................................................13

DIN Rail I/O


The DIN rail mounted I/O connection point within the drive is located to the left of
the control rack. It consists of I/O card (ATBA card assembly) and feed through
terminal blocks. These terminal blocks are CSA approved for 600V and 45A, and
can receive wires from 20 – 8 AWG.

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-1
Terminal Block Names Description
115E 115V external connections
115I 115V internal drive connections
ETBH External high-level signals (50 – 115 V)
ETBL External low-level signals (less than 50 V)

• Refer to system elementary for ATBA and CTBC connections


• See Appendix C: I/O Functions section for more information on drive I/O

I/O Fuses
Supplier No. GE Part No. Rating Function
MOL2 323A2391P50 2 A, 250 V External I/O fuse
MOL4 323A2396P59 4 A, 250 V Internal I/O fuse

Application Control I/O


All drive products in the GE Innovation Series of drives contain the same basic set of
control interface Inputs and Outputs. For maximum application flexibility, the use of
the I/O by the software is configurable where possible.

• 6 Digital Inputs
• 3 Relay Outputs
• 1 Solid State Relay Driver
• 2 Analog Inputs
• 2 Analog Outputs
• 4 Meter Driver Outputs
• 1 Digital Tachometer Input with Power Supply
• 1 Drive Output Contactor Pilot Relay and Status Input
• System Fault String Input
• Local Fault String Input
• 24vdc Logic Power Supply
• +/- 15vdc Potentiometer Reference Supply
• Isolated RS232 Communications Port for PC Tool
• RS232 Communications Port for Drive Diagnostic Interface
• Local ISBus for Control IO Expansion
• System ISBus for connection to Remote Application Control Hardware

3-2 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Digital Inputs
Six (6) discrete logic inputs are provided for control logic interface to the drive
control. The inputs are isolated and differential, and are designed for use with
115vac, 24vdc-105vdc circuits. The use of the inputs by software is configurable
through the Toolbox or through the DDI keypad. Software filters are provided.

Table 3-1 ATBA Terminal Board Connections

Name Number
Digital Input 1+ 14
Digital Input 1- 16
Digital Input 2+ 18
Digital Input 2- 20
Digital Input 3+ 22
Digital Input 3- 24
Digital Input 4+ 26
Digital Input 4- 28
Digital Input 5+ 30
Digital Input 5- 32
Digital Input 6+ 34
Digital Input 6- 36

Specifications
Input Voltage 115 Vac Ù10% (50/60hz sinusoidal)
24-105 Vdc

Minimum Isolation 2500Vrms for 1 sec


Maximum Load (Draw) 20 mA
Maximum Leakage 0.75 mA.

Typical Turn-On Time 3.5 ms


Typical Turn-Off Time 2.5 ms

Digital Outputs (Relays)


Three (3) separately controlled Form C relay contacts are provided for discrete
outputs. Software control of the relays is configurable through the Toolbox or
through the DDI keypad.

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-3
Table 2-2 ATBA Terminal Board Connections

Name Number
R1NO 13
R1COM 17
R1NC 21
R2NO 25
R2COM 29
R2NC 33
R3NO 34
R3COM 35
R3NC 36

Contact Ratings
115 Vac (50/60hz sinusoidal) 0.6A resistive/inductive
24 Vdc, 2A non-inductive, 0.6A inductive.

Pickup Time
Typical 3 ms
Maximum 24 ms

Dropout Time
Typical 5 ms
Maximum 24 ms

Note The relays are de-energized when reset or powered-down.

If contacts are used with an inductive load, the


load must have a suppresser to limit voltage
transients to <300Vpk.

Solid State Relay Driver


A relay driver circuit for use with the isolated +24vdc power supply is provided for
control of a 24 V dc, 10 mA solid state relay. This is particularly useful for control
circuits which demand a high number of relay operations which would otherwise be
limited by the lifetime of standard mechanical relays. Software control of the solid
state relay driver is configurable through the Toolbox or through the DDI keypad.

Table 2-3 ATBA Terminal Board Connections

Name Number
DRVR 11

3-4 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Specifications
Input Voltage 24 Vdc (from 24vdc Logic Control Power Supply)
Maximum Load (Draw) 20 mA

Note No additional current limit protection is provided for this circuit. Care must
be taken to avoid direct connection of the 24 V dc logic control power to common
(shorted circuit).

Note This circuit is intended for use only with the 24 V dc Logic Control Power
Supply, provided at ATBA card terminals 33 or 37.

24 Vdc Logic
ATBA
Control Power
Point 33
or 35

Drive Control User’s


Electronics Solid State
Relay Device

Software
ATBA
Controlled
Point 11

Logic Control
Power Common

Figure 3-1 Typical Solid State Relay Driver Circuit Connections

Analog Inputs
Two (2) bipolar (+/-10 v) analog input channels are provided. Each channel uses a
differential amplifier followed by a VCO (Voltage Controlled Oscillator). The use
of the analog inputs by software is configurable through the Toolbox or through the
DDI keypad. Filters, scaling, and offset, as well as programmable signal loss
detection are provided in software.

Table 3-4 ATBA Terminal Board Connections

Name Number
AI1+ 38
AI1- 40
AI2+ 44
AI2- 46

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-5
Net Sensor Accuracy 0.3 %
Offset Drift (25 - 65 deg C Ù) 0.009 %/C
Gain Drift (25 - 65 deg C Ù) 0.005 %/C
Input Impedance
Single Ended 4090 Ò
Differential 8180 Ò
Resolution -12.45 to +12.45 Vdc = 0 to 2 Mhz
Common Mode Range 30 Vdc (plus 10 Vdc signal)
Minimum Slew Rate 0.5 V/uS
Maximum Bandwidth 3-5 kHz

For convenience in setting the software based offset and gain of the analog inputs,
test points are provided on the front panel of the BAIA card (located in the control
rack assembly). These test points are buffered to help prevent damage when
connecting metering equipment.

Test Points
AIN1 buffered analog input 1
AIN2 buffered analog input 2
AINCOM common for analog inputs

A burden resistance (approx. 500ohm) is available on the BAIA card for each circuit
via a berg jumper to convert a 4-20 mA input to ≈2-10Vdc. If not using the 4-20ma,
the berg jumper should be on the VIN set of berg pins. Each jumper has an “A” and a
“B” setting as detailed below. Only one setting should be selected for each jumper.

Berg jumpers

JP5A, VIN - Analog Input 1 in +/-10vdc Mode


JP5B, 4-20ma - Analog Input 1 in 4-20ma Mode

JP6A, VIN - Analog Input 2in +/-10vdc Mode


JP6B, 4-20ma - Analog Input 2 in 4-20ma Mode

Note: Because the bias & gain vary slightly from card to card, it is recommended
that the circuit be recalibrated each time the BAIA card is replaced.

Analog Outputs
Two (2) bi-polar, 10vdc analog outputs are supplied for drive variable indication and
process control. The outputs are single-ended, 12 bit D/A (digital to analog)
converters, referenced to ACOM. The outputs are short-circuit protected to prevent
circuit inadvertent damage. The use of the analog outputs by software is
configurable through the Toolbox or through the DDI keypad. Filters, scaling, and
voltage offset are provided in software.

3-6 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Table 3-5 ATBA Terminal Board Connections

Name Number
AO1 52
ACOM 54
AO2 58
ACOM 60
Voltage ±10 volts
Ampacity 7.5 mA
Resolution 12 bit
DC offset less than or equal to 25 mV
Output Impedance less than or equal to 30 Ohms
Linearity 0.1% of full scale
Gain Error <.5% of full scale (least significant 2 bits)

Note Under reset conditions the D/A outputs are forced to 0 volts.

Note When using the analog outputs it is recommended that these are fed into
differential inputs - the return side of the outputs is isolated from the chassis by a
resistance (10K) which can cause false readings of the output (due to noise or current
loops) if the input is sensing with reference to chassis.

Note Because the bias and gain vary slightly from card to card, it is recommended
that the circuit be recalibrated each time the card is replaced.

Meter Driver Outputs


Four (4) bi-polar, 10 V dc analog outputs are provided intended to drive optional
door mounted meters. Two of the analog outputs are driven by 12 bit D/A‘s. The
remaining two drivers are supplied by converting a PWM signal from the drive
control CPU (DSPX) card to a –10 V to +10 V, 5 mA signal. The meter driver
outputs are available only from the CABP card connector J8. The control of the
meter driver outputs by software is configurable through the Toolbox or through the
DDI keypad. Scaling and voltage offset are provided in software.

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-7
Table 3-6 CABP Backplane Card Connector J8

Name Pin Number


no connection 1
no connection 2
DCOM 3
MTR4P 4
MTR3P 5
MTR2P 6
MTR1P 7
DCOM 8

D/A Outputs (Meter 1 and Meter 2 outputs)


Voltage ±10 volts
Ampacity 7.5 mA
Resolution 12 bit
DC offset less than or equal to 25 mV
Output Impedance less than or equal to 30 Ohms
Linearity 0.1% of full scale
Gain Error <.5% of full scale (least significant 2 bits)

PWM Outputs (Meter 3 and Meter 4 outputs)


Voltage ±10 volts
Ampacity 5 mA
Resolution 24kHz, 10 bit duty cycle, Filtered PWM Signal **
Accuracy 10%

** Note A 1 kHz, 1st order filter is applied to the PWM meter driver signal
outputs.

Note Under reset conditions the D/A outputs is forced to 0 volts. The signal status
of the PWM signals is undefined during reset.

Note Because the bias and gain vary slightly from card to card, it is recommended
that the circuit be recalibrated each time the card is replaced.

Tachometer Interface
A quadrature encoder with marker interface is provided to the control electronics for
motor speed feedback and incremental position indication. The interface is good for
standard, differential 5 or 15 V dc signal encoders without circuit re-configuration.
A 15 V dc, 150 mA isolated power supply is also supplied for powering the encoder
electronics.

3-8 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Table 3-7 ATBA Terminal Board Connections

Name Number
A 41
/A 43
B 47
/A 49
MKR 51
/MKR 53
+15 57
TACHCOM 59

Tachometer Input Signal


Signal Voltage +3.5 vdc to +15 vdc (square-wave)
Signal Load (Draw) < 4.0 mA per Channel
Maximum Frequency 125 kHz
Input Isolation Minimum of 2500Vrms for 1 sec
Recommended Cable BELDEN 9773 **

Tachometer Power Supply


Voltage +15vdc
Ampacity 150mA maximum

** Note The inputs have a cable termination impedance made from a series R_C
circuit of 100Ò and 0.0047 uF.

Contactor Control Pilot Relays and Status Indication


A contactor pilot relay, MA, is provided which is intended to control the drive output
contactor (if supplied). An MA sense input is provided which can be used with an
interlock on the output contactor to inhibit bridge firing if the output contactor does
not pick up when commanded. The MA pilot relay and sense connections are
available on the DIN mounted ATBA card, as well as on the CABP back-plane card
connector J1.
A second contactor pilot relay, MB is also provided, but is not typically used only on
source converters. No dedicated sense input is provided for the MB contactor.
The Local and System fault string inputs are hardware AND’ed to provide a master
enable for the MA and MB contactor pilot relays. Dropping out either or both of
these inputs ensures that the MA and MB contactor pilot relays will drop out.
Hardware configuration assures that bridge firing will be disabled before the MA or
MB contactors drop out.
Limited configuration of the software control for the relays is available through the
Toolbox or through the DDI keypad.

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-9
Table 3-8 Circuit Connections

Name Description Backplane ATBA


Connection Connection
MBNO Contactor B Normally Open J1 - 4 none
MABCOM Contactor A/B Common J1 - 3 none
MANO Contactor A Normally Open J1 - 1 1
MACOM Contactor A Common 3
MANC Contactor A Normally Closed 5
MA+ Contactor A Feedback + J1 - 5 7
MA- Contactor A Feedback - J1 - 6 9

MA Contactor Pilot (Form C) .6 Amp @ 125 VAC


.6 Amp @ 110 VDC
2 Amp @ 30 VDC
MA Sense Input
Voltage 24 to 115V AC/DC
Loading 4 - 10 Ma. Pk.

MB Contactor Pilot (Form A) .6 Amp @ 125 VAC


.6 Amp @ 110 VDC
2 Amp @ 30 VDC

Note To facilitate wiring of standard drive and source components at the factory,
the contactor pilot relays have been wired to a harness-able plug on the backplane, as
well as to the ATBA terminal board card. This presents the opportunity for potential
wiring errors if the circuit is not understood. It is recommended that either the
ATBA terminal board connections, or the backplane J1 plug be used, but not both.

3-10 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
J1-4

Contactor MB
Pilot Relay ATBA
J1-3

J1-1
1

Contactor MA
Pilot Relay
3

Drive Control
Electronics 5

J1-5
7
Contactor MA
Feedback

J1-6
9

The contactor MA and MB pilot relay “normally


open” contacts are wired to BOTH the ATBA card
and to the J1 plug on the backplane. One side of
these contacts is electrically tied together
(MABCOM).

The feedback sensing for the MA contactor is


wired to BOTH the ATBA card and to the J1 plug
on the backplane.

Local and System Fault String Inputs


Two circuits are provided for a hardwired, fail-safe shut down the drive. The circuit
consists of two independent isolated relays which are effectively “AND-ed” together
such that loss of either input will result in a drive control shut-down. The first input,
the Local Fault String is intended to be used for hardwired circuits specific to the
drive (i.e. mechanical over-speed, over-travel limits, lock-out, etc.). The second
circuit, the System Fault String is intended to be used in circuits common to multiple
drives in a system (i.e. system x-stop).

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-11
Table 3-9 ATBA Terminal Board Connections

Name Number
S115v 2
S24V 4
SCOM 6
L115V 8
L24V 10
LCOM 12

These inputs have three terminals (24 V, 115 V and Common) found on the DIN rail
mounted ATBA card. Typical connections are between the common and one of the
voltage terminals. The inputs are independently isolated, so one string can be
operated at 24 V while the other is operated at 115 V. One of the specified voltages
must be applied to both inputs for normal operation. The state of the inputs are
reported back to the control for sequencing and diagnostics. Dropping out either or
both of these inputs while the drive is running will sequence a controlled shutdown.

Local/System Fault String Inputs


Voltage 24 or 115V AC/DC
Loading 20 ma Max.

The Local and System fault string inputs are hardware AND’ed to provide a master
enable for the MA and MB contactor pilot relays. Dropping out either or both of
these inputs ensures that the MA and MB contactor pilot relays will drop out.
Hardware configuration assures that bridge firing will be disabled before the MA or
MB contactors drop out.

Note One of the specified voltages must be applied to both the Local and System
Fault inputs for normal operation.

Logic Control Power Supply


A 24 V dc control logic power supply is provided intended for the purposes of
control I/O wiring to the drive electronics. The 24 V dc supply is derived from the
drive power DC bus, and thus is particularly useful for applications which are
sensitive to AC power dips. Two pairs of 24 V dc and common are provided to
facilitate wiring to multiple control circuits.

Table ATBA Terminal Board Connections

Name Number
+24V 33
24COM 35
+24V 37
24COM 39

3-12 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Logic Control Power Supply
Voltage 24 vdc
Ampacity 1.2 A maximum

Potentiometer Power Supply


A bi-polar 15 Vdc power supply is provided which is intended as a supply for a
speed reference potentiometer. The power supply is referenced to ACOM.

Table 3-10 ATBA Terminal Board Connections

Name Number
+15VPS 48
-15VPS 50
ACOM 54 or 60

Voltage Ù15vdc, Ù5%


Ampacity 7.5mA maximum (each supply)

Local Toolbox Port


A personal computer based Toolbox is available as an option for the sources and
drives. The basic connection for PC to the drive is a door mounted RS232
connection. (Standard cable GE PN 336A3582P1 is available).

Note Specific details of the Toolbox port cabling can be found in the Chapter 3:
Cabling and Connections in the Installation and Startup Guide, GEH-6130.

The toolbox is also used for programming the optional ACL application card if
supplied in the drive. The basic PC connection to the ACL is through Ethernet,
which may also be brought to the cabinet door. The drive (or source) can be
programmed over the Ethernet by effective going “through” the ACL. Since the
Ethernet is typically wired in a “star” configuration, the door mounted Ethernet jack
may actually be wired from the jack, back to a remote mounted Ethernet hub or
repeater. Then the Ethernet is wired from the hub back to the cabinet, and
subsequently to the ACL.

Test Lead Pass-Through Hole


The Test Lead Pass-Through Hole provides a mechanism to allow the use of test
and metering equipment with the enclosure door closed.

Keypad RS232 Transceivers


A dedicated serial communications port is provided for communications to the
standard DDI keypad interface. The interface consists of two RS232 drivers (TX,
TXEN) and one RS232 (RX) receiver. DDI connections are available on the CABP
backplane card through connector J10.

GEH-6131 MV-GP Type H Drives Chapter 3 Control Terminal Board I/O and Fuses • 3-13
Notes

3-14 • Chapter 3 Control Terminal Board I/O and Fuses GEH-6131 MV-GP Type H Drives
Chapter 4 Drive Diagnostic Interface

Introduction
Chapter 4 of this manual provides information to help the user understand how to
operate the Drive Diagnostic Interface (DDI). It is organized as follows:

Section Page

Overview....................................................................................................................... .............2
Using the Pushbuttons.......................................................................................................... ......2
Reading the Display ............................................................................................................ .......4
Status Screen .................................................................................................................. ............7
Alternate Status Screen ........................................................................................................ ......8
Using the Menus ................................................................................................................ ........9
Viewing and Resetting Faults ................................................................................................... .9
Editing Parameters ...................................................................................................................10
Parameter Backup ....................................................................................................................11
Firmware and Hardware Information.......................................................................................14
Protecting the Keypad ..............................................................................................................15

Note Screen displays presented in this chapter may not be identical to screen
displays on the user’s equipment.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-1


Overview
The keypad is a door-mounted, local control unit that enables you to:
• Monitor speed, current, power, and voltage
• Start and stop the drive
• Set and adjust configuration parameters
• Examine and reset fault conditions
• Commission the drive through wizards

Using the Pushbuttons


The keypad includes membrane-type pushbuttons that enable you to access drive
values and to control the drive. Tables 4-1 and 4-2 define the pushbutton functions
for menu navigation and drive control (see Figure 4-1).

 GE Innovation Series
Drive Health
Display: RPM feedback & State Icons
0.0 RPM -150 0% +150
Status screens provide
Motor current
both analog and digital 0.00 A rms 0% 75 +150
representation of drive Motor voltage
functions and values. 0.00 V rms 0% 75 +150

Menu screens provide Motor power


text-based access to 0.00 KW -150 0% +150

parameters, wizards,
and faults.
Navigation Drive Controls

Pushbuttons: Run (Green)


Reset
Organized into Status
Faults
functional groups:
Navigation buttons
for using the menu Menu
Remote
Jog
Stop (Red)
Local
Drive Control buttons
Speed
Run and Stop buttons
Escape Enter

Figure 4-1 Keypad (Front View)

4-2 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Table 4-1 Navigation Pushbuttons
Active*
Button Function
L R W

Displays the default Status Screen, which shows four parameters as digital numbers or bar
Status ä ä graphs. A set of Health icons (displayed at all times; see Drive Health and State Icons) provide
additional drive status information.
If pressed while displaying a Menu screen (see Menu Selections), displays the Main Menu.
Menu ä ä If pressed while displaying a Status screen, displays the
last Menu screen.
Menu Navigation: Used to highlight (reverse image) an item in a menu of options.
Entry of Numeric Parameter: Used to index through numbers (0-9, ., -) when editing a
ä ä ä parameter.
Entry of Option Parameter: Used to index through 1 – n choices.
(See Parameter Configuration.)
Menu Navigation: Right Arrow button displays the next selected level down in a menu tree.
Left Arrow button displays next level up in menu tree.

ä ä ä Wizard Navigation: Displays the previous or next wizard screen.


Entry of Numeric Parameter: Used to select a digit when editing a parameter.
Entry of Option Parameter or Command Execution: Not functional.
Menu Navigation: Displays the next level up in menu tree.
Escape ä ä ä Wizard Navigation: Exits wizard and displays the Main Menu.
Entry of Parameter: Displays the parameter list.
Menu Navigation: Displays the next level down in menu tree.

Enter ä ä ä Wizard Navigation: Selects the highlighted item on the wizard page for parameter editing or
command execution.
Entry of Parameter: Accepts editing of parameter.

* L = Local mode
R = Remote mode
W = While wizard is running

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-3


Table 4-2 Drive Control Pushbuttons
Active*
Button Function
L R W

ä ä
Reset
Resets faults.
Faults

Converter drives: Toggles direction of the drive for Run and Jog commands. The currently
ä selected direction is shown with an icon (see Drive Health and State Icons).
If pressed while in Remote mode, an error screen displays.

ä ä Toggles the mode of the drive between Local and Remote. The currently selected mode is
Remote
Local shown in the right side of the display with an R or an L (see Drive Health and State Icons).

Converter drives: Jogs drive in the selected direction at the configured jog speed.
Jog ä If pressed while in Remote mode, an error screen displays.

Converter drives: Increments/decrements the Local Speed Reference associated with the
ä keypad Run/Stop commands.
If pressed while in Remote mode, an error screen displays.

Local Run command.


ä If pressed while running in Remote mode, an error screen displays.

ä ä ä Local Stop command.

* L = Local mode
R = Remote mode
W = While wizard is running

Reading the Display


The keypad displays information as both text and animated graphics. There are two
types of content screens, selected by pressing the corresponding Navigation button:
Status and Menu.
The Status Screen is the default screen that displays after drive startup, following an
initialization screen. It uses animated meters with associated text to present drive
performance data. An alternate Status Screen can also be accessed (see Status
Screen).

4-4 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Text Identifying Animated Drive Health &
Drive Variable Meters State Icons:
Heartbeat
RPM feedback
0.0 RPM -150 0% +150
Control State
Motor current
0.00 A rms 0% 75 +150
Motor voltage Fault State
0.00 V rms 0% 75 +150
Drive Direction
Motor power
0.00 KW -150 0% +150
Motion

The Menu Screen lists and provides access to menu-based functions for adjusting
parameters, running wizards, and viewing faults (see Menu Selections).
Selectable Menu
Screens
Main Menu
Fault List
Drive catalog number (IPN) No icon
Wizards here means
Application data no fault.
Diagnostic and utility functions
General setup
I/O interface

The Drive Health and State Icons continually show on the right hand side of all
display screens. They indicate if the drive functioning correctly and its running state.
These icons are displayed in five functional groups on the status screen and shown in
Table 4-3.
You can change the display units and adjust the display contrast, if needed.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-5


Table 4-3 Drive Health and State Icons
Group Icon Indication Description
Communications Animated line (its center raises and lowers) shows that there is
OK communication between the keypad and the drive.
Heartbeat
Communications Animated metronome icon shows that the keypad is attempting to
not established establish communication with the drive, but cannot.

Drive can be controlled (start, stop, jog, direction, speed) locally from the
Local mode
keypad.

Control Drive control is from a remote station. This disables the local keypad
Remote mode
drive control functions (start, stop, jog, direction, speed).

Test mode The drive is performing selftest.

Blank Drive OK When no icon displays, the drive is operating correctly.

Abnormal Displayed when the drive has over-ridden parameters.

Fault State Alarm state Displayed when an alarm condition occurs.

Trip fault Displayed when a fault state occurs.


blinking

Forward rotation Indicates the direction of motion currently selected. This does not
necessarily match the direction of motion as viewed from the motor
Drive Direction shaft.
Reverse rotation

Drive not ready Mimic of the keypad Start button, displayed with a diagonal line through
to run the symbol to indicate that the drive is not running and cannot be started.

Motion Mimic of the keypad Start button. Indicates that the drive is not running,
Drive not running
but can be started (ready to run).
Animated motion icon, indicates that the drive is running (speed
Drive running feedback is not zero). The icon rotates in the direction selected by the
direction arrow (described in Table 5-1).

Changing the Display Units


1. To change the type of measurement units displayed:
2. From the Main Menu, select General Setup.
3. Select Display Units.
4. Select the display units parameter to edit it.
5. Highlight then select the preferred display units.

Press ENTER to accept, ESC to leave

Display units
New Value = Metric (SI)
Present Value = Metric (SI)

4-6 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Adjusting the Display Contrast

To adjust the display contrast:


1. From the Main Menu, select General Setup.
2. Then select: Keypad > Keypad Functions > Adjust Screen Contrast.
This displays the screen shown below.

- CONTRAST ADJUSTMENT -

HOLD UP ARROW TO INCREASE


HOLD DOWN ARROW TO DECREASE

Press ESCAPE to Continue

3. Press the Escape button to save the contrast value and return to the previous
menu.

Status Screen
The Status screen displays four types of drive variables (parameters) using both text
and animated meters. Table 4-4 defines characteristics of the bar graphs for these
parameters.

Reading the Meters


A variable shown as a bar graph is over range when it is either greater than + 100%
or less than –100%. The over range mark is shown with a vertical bar through the bar
graph at the +100% and the –100% marks.

Not Over Range

-100% +100%
Over
Range

To change the range of the variables displayed on the Status Screen:


1. From the Main Menu, select General Setup > Keypad > Keypad Meters.
2. Select the Keypad Meter # Range (where # can be a 1, 2, 3, or 4) that is to be
changed.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-7


• Adjust the variable as follows:
• Use the Up or Down Arrow buttons to change the value.
• Press Enter to accept, or Escape to exit and keep the present setting.

Press ENTER to accept, ESC to leave

Keypad meter 1 range


New Value = -150 to +150
Present Value = -150 to +150

Table 4-4 Animated Meter Characteristics (Default) for the Status Screen
Bar Graph
Numeric Display Units in Bar Graph
Variable

RPM feedback Speed feedback in units of rpm (Spd_Fbk_Fil) Percent of applied top rpm (Motor_NT)
Motor current Magnitude of motor current (I_Mag_Fil) Percent of motor-rated current (Amps)
Motor voltage Magnitude of motor voltage (V_Mag_Fil) Percent of crossover voltage (Xover_Volts)
Motor power Motor shaft power (Mtr_Shft_Pwr) Percent of motor-rated power (Power)

To change the variables displayed on the Status Screen meters:


1. From the Main Menu, select General Setup > Keypad > Keypad Meters.
2. Select Keypad Meter # Sel that corresponds to the meter variable to be replaced.
3. Adjust the setting as follows:
• Use the Up or Down Arrow buttons to change the value.
• Press Enter to accept, or Escape to exit and keep the present setting.

Alternate Status Screen


The keypad has an alternate Status Screen that displays the following I/O:
• Status of the digital inputs
• Relay outputs
• Local and system fault string inputs
• Contactor command outputs
• Contactor feedback inputs
To toggle between the Meter Status Screen and the I/O Status Screen, press any of
the Arrow buttons.

4-8 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


The circle under each heading indicates the status of the corresponding I/O point, as
follows:

l = True
‰ = False

Display I/O Status

Input 1 2 3 4 5 6 LOC SYS CntA


Status

Output 1 2 3 4 CntA CntB


Status

Using the Menus


The keypad’s Main Menu leads to other menu screens, where data can be reviewed
and modified. The Main Menu can be accessed from any screen, as follows:
• If already in a Menu screen, press the Menu button.
• If in a Status screen, press the Menu button once or twice.
Use the Navigation buttons to move through the menus, select items, and adjust
values, as follows:
1. Press the Up or Down Arrow buttons to move through and highlight menu
items.
2. Press the Enter button to select a highlighted item
3. To return to a previous menu screen, press the Escape button, Left Arrow
button, or follow onscreen instructions.
4. When menu items require more than one:
a. Move to the next screen by highlighting the last item on the displayed
screen, then pressing the Down Arrow button once more.
b. If the last menu item is reached, then pressing the Down Arrow button will
wrap back to the first item on that menu.

Viewing and Resetting Faults


When the display indicates either a Trip or an Alarm fault (refer to Reading the
Display), you can view information and reset (clear) current faults, as follows:
1. From the Main Menu, select Fault List, then select Display Active Faults.

Note Faults are displayed in order of occurrence with the most recent fault at the
top.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-9


ACTIVE FAULT DISPLAY
50 Trip HtSink temp low, B
108 Brief DC bus voltage low
12 Trip Gnd flt, coarse
113 Trip Invalid board set
--- RESET FAULTS NOW ---

2. To view detail on a particular fault, select that fault (listed on the Active Fault
Display screen).

SELECTED FAULT - PRESS ESCAPE


HtSink temp low, B
000 04:40:11.008
The heat sink B temperature was too
low. The heatsink thermistor may be
missing or damage. Check input to
backplane connector J4 pins 3 & 4.

3. Reset the faults either of two ways:


• Select Reset Faults Now in the Fault Display screen.
• Press the Reset Faults button.
To view the drive’s Fault History (a list of previously cleared faults and fault
resets): Select Fault List > Display Fault History.

Note This display list may be multiple screens long.

FAULT HISTORY DISPLAY


0 Cleared Fault reset
108 Brief Clr DC bus voltage low
50 Trip HtSink temp low, B
108 Brief DC bus voltage low
12 Trip Gnd flt, coarse
113 Trip Invalid board set
--- RESET FAULTS NOW ---

Editing Parameters
There are two types of parameters that can be changed using the keypad:
• Option Parameters lists items (options) for you to select. For example,
True/False is an option parameter.
• Numeric Parameters lists valid digits that you select to create a number.
To edit a parameter from the keypad:
1. Select the parameter that is to be changed.
This displays the Parameter Configuration Screen . The New Value line will be
highlighted.

4-10 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Parameters
Fixed inertia = 10.0000 kg*m2
Variable inertia sel=Unused
Spd reg net gain = 50.0000 rad/s
Spd reg init val sel=Zero
Spd reg integral gn = 12.5000 rad/s
Spd reg neg err lim = 0.00000 RPM
Spd reg pos err lim = 0.00000 RPM

2. For an Option Parameter:


a. Use the Up or Down Arrow buttons to change the parameter.
b. Press the Enter button to accept the change or Escape to exit and keep the
present value.

Press ENTER to accept, ESC to leave

Regulator type
New Value = Torque, spd override
Present Value = Speed regulator

3. For a Numeric Parameter:


a. Use the Left or Right Arrow buttons to highlight the digit to be changed. If
you continue pressing the Left Arrow button after reaching the left-most
digit of the edit field, the field fills with blanks. Pressing Enter when the
entire number is blanked out saves a <No Value>.
b. Use the Up and Down Arrow buttons to index through the valid digits (0, 1,
2, 3, 4, 5, 6, 7, 8, 9, e, ., -). The e in the digit selection represents the start
of the exponent in scientific notation. If the e is used, all digits to the right
of the e make up the number’s exponent.

Press ENTER to accept, ESC to leave

Fixed inertia
New Value = 10.00000 kg*m2
Present Value = 10.00000 kg*m2
Low Limit = 0.0000000
High Limit = 3.4028239e38

When all of the digits have been changed, press Enter to accept the new value or
press Escape to exit and keep the present value.

Parameter Backup
It is good practice to keep a backup copy of the drive’s working parameter
configuration. You can then restore this file, if needed, or compare it with a re-
configured file to determine differences.
Saving Parameters. Save the active parameters to backup, as follows:
1. From the Main Menu, select Parameter Backup Functions then select Save
Parameters.
2. Press Enter to make a backup copy of the parameters or Escape to cancel.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-11


Note Each new backup overwrites the previous backup copy, which cannot then be
restored.

Save Parameters to Backup

Save current parameter values.

Press ENTER to continue. ESC cancels.

Restoring Parameters
To restore a parameter from backup, perform the following:
1. Stop the drive. (This function cannot be executed with the drive running.)
2. From the Main Menu, select Parameter Backup Functions then select Restore
Parameters From Backup.
3. Press Enter to restore the backup parameters or Escape to cancel.

Restoring parameters from a backup file


overwrites the currently active parameter values,
which cannot then be restored.

Press to restore Parameters from Backup

-- WARNING --
The active parameter values will be
replaced, and can not be recovered.

Press ENTER to continue. ESC cancels.

Comparing Current Parameters to Backup


This function compares the active parameter set to the backup parameter set, and
displays the differences.
Perform a parameter compare as follows:
1. From the Main Menu, select Parameter Backup Functions then select Compare
Current Parameters to Backup.
2. Use the Up and Down Arrow buttons to scroll through the list of backup
differences.
3. Press Escape to return to the previous menu.

4-12 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


BACKUP DIFFERENCES <More ↑ >
Capture period =Task 3 rate
Backup value =Task 2 rate
Normal stop mode =Ramp stop
Backup value =Coast stop
Simulated inertia = 10.0000 kg*m2
Backup value = 50.0000 kg*m2
<More ↓>

Tuning the Drive


The drive can be tuned using the keypad wizards. To access the wizards, perform the
following:
1. Recommended: Back up the currently active parameters (see Parameter
Backup) before each wizard is started. This enables you to easily restore
parameters if tuneup is exited or fails.
2. From the Main Menu, select Wizards, then select Start Wizard Menu.
During a complete tune-up process, you normally run all of the wizards in the order
displayed, from first to last.

Wizards
1) Drive Commissioning Wizard
2) Cell Test Wizard
3) Motor Control Tuneup Wizard
4) Speed Regulator tuneup Wizard
A) Panel Meter Setup Wizard
B) DAC Setup Wizard
C) Simulator Setup Wizard

Use the Up and Down Arrow keys to scroll to the desired wizard, then press Enter
to select and start it. (Pressing Escape returns to the Main Menu.)
The selected wizard displays a series of screens and prompts that guide you through
that part of the tuneup process.

Note The path taken by the wizard depends in part on the choices made. The same
wizard may ask different questions and execute different commands for different
applications.

Proceed through the wizard as prompted, using the following conventions:


• After starting a wizard, you should either complete or exit it before taking any
other action.
Note Some keypad pushbuttons do not function while a wizard is running.
However, the Stop button will always function.

• Pressing the Escape button exits the wizard, but any parameter edits made to
that point remain. (See Step 1.)
• Parameters presented in a wizard may be changed or left alone (as appropriate),
but all calculations and commands presented must be attempted.
• At each step, the wizard indicates whether you can proceed to the Next step
using the Right Arrow button or can back up to the Previous step, using Left
Arrow button. If the Next prompt does not appear, the command still must be
completed successfully.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-13


1) Drive Commissioning Wizard
Power Distribution Information:

What is the DC link Source?


Dc source =PWM voltage src

Prev Next

• When a command completes successfully, you cannot execute it again within


the same step. To repeat a command (for example, if required by external
conditions), press the Left Arrow button to return to the previous step. Then
repeat the command.

1) Drive Commissioning Wizard


This executes the rule to populate
all torque and current limits
based upon the previous entry.
Calculate Torque Limits

Prev Press ENTER to execute.

1) Drive Commissioning Wizard


This executes the rule to populate
all torque and current limits
based upon the previous entry.
Calculate Torque Limits

Prev <Command Complete> Next

• If a command fails, the wizard fails. To continue the tuneup, correct the
condition causing the failure, then repeat the command.
At this time, push the Right Arrow button (per the Finish prompt) to exit the wizard
and return to the Wizard Menu.

Firmware and Hardware Information


To view the firmware versions for the DSPX board and the keypad:
• From the Main Menu, select General Setup, then select Firmware Version &
Hardware Info.
To view drive hardware information:
• From the Main Menu, select General Setup, then select Display Hardware
Information.

4-14 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


GE Innovation Control

ACDCF-S
DSPX Firmware Version: V02.06.00B
DSPX Boot Monitor Version: V02.02.00C
DDI Firmware Version: V02.00.00B

Press ESC to exit

GE Innovation Control
Hardware Information:
IS200BPIAG1ACB XMT1V
IS215ACLAH1AA 8790040
IS200BICLH1ABB 3340595
IS200DSPXH1AAA 3341057
IS200BAIAH1BCB 3341430 <More ↓>
ESC to exit

Protecting the Keypad


To protect the drive from unauthorized operation or reconfiguration, the keypad
includes two security controls: Password and Privilege Level.
The Password is a 5-digit number that protects the Password and Privilege Level
from being changed by unauthorized personnel. The default Password is 00000.
Privilege Level specifies which operational and configuration functions are disabled
in the keypad. There are three levels:
Read Only disables both the Drive Control and the Configuration functions. An
operator can view but not edit parameters.
Operate & Read Only enables the Drive Control function, but disables
Configuration functions. An operator can view, but not edit parameters.
Configure & Operate enables both the Drive Control and the Configuration
functions. This is the default setting.
If you try to execute a function that is disabled in the active Privilege Level, the
keypad displays an error message.

Function Not Allowed at


present Privilege level!
Press Any Key to Continue

Table 4-5 lists the privilege level for all keypad functions.

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-15


Modifying the Privileges
To modify the Password and Privilege Levels:
1. From the Main Menu, select: General Setup > Keypad > Keypad Security

Press ENTER to accept, ESC to leave

Enter Password: 00000

2. Enter the password as follows:


a. Use the Up and Down Arrow buttons to index through the valid digits (0
through 9).
b. Use the Right and Left Arrow buttons to move the cursor to the digit to edit.
3. Press Enter to accept the Password.
4. If the password that was entered matches the saved Password value, you can
then modify the Privilege Level or Password.
Keypad Security
Keypad privilege =Configure & operate
Keypad password = 00000

If it does not match, the keypad displays an error message.

Incorrect password!
Press Any Key to Continue

5. Use the Up and Down Arrow buttons to select either the Privilege Level or
Password
6. Press Enter to edit the parameter. (See Editing Parameters.)
Note When you modify the keypad password, be sure to select Save Parameters To
Backup. Otherwise, the password stored in the active parameter will not match the
backup parameter set. That causes the Compare Current Parameters to Backup to
identify the Keypad Password parameter as different.

4-16 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Table 4-5 Keypad Function Privileges
Privilege Level
Keypad Function Operate & Configure &
Read Only
Read-Only Read-Only
Drive Control
Stop Button ä ä ä
Start Button ä ä
Reset Faults Button ä ä ä
Change Direction Button ä ä
Remote/Local Button ä ä
Jog Button ä ä
Speed Increment Button ä ä
Speed Decrement Button ä ä
Menu
Navigation Buttons ( Status, Menu, Arrows,
Escape, Enter) ä ä ä
Display Active Faults ä ä ä
Display Fault History ä ä ä
Privilege Level
Keypad Function Operate & Configure &
Read Only
Read-Only Read-Only

Drive Control
View Parameters ä ä ä
Edit Parameters ä
View Variables ä ä ä
Wizards ä
Adjust Screen Contrast ä ä ä
Display Firmware Revision ä ä ä
Display Hardware Information ä ä ä
Save Parameters to Backup ä
Restore Parameters from Backup ä
Compare Current Parameters to Backup ä ä ä
View Overrides ä ä ä

GEH-6131 MV-GP Type H Drives Chapter 4 Drive Diagnostic Interface • 4-17


Notes

4-18 • Chapter 4 Drive Diagnostic Interface GEH-6131 MV-GP Type H Drives


Chapter 5 Preventive Maintenance

Introduction
This chapter defines practices and procedures that help keep the drive in good
running condition. Periodic preventive maintenance extends equipment operating
life and minimizes downtime. This involves specific power-on and more intensive
power-off checks, when permitted. With both checks, necessary repairs should be
undertaken when needed. This information is organized as follows:

Section Page

Schedule, Record, and Materials................................................................................................ 2


Fan and Blower Airflow Check..................................................................................................3
Power-Off Checks......................................................................................................................3
Inspecting Fiber Ends.................................................................................................................5

For liquid cooled drives, refer to GEH-6132.

Only qualified personnel should install, operate,


troubleshoot, and maintain this drive. A qualified
individual is “one familiar with the construction
and operation of the equipment and the hazards
involved.”

Never touch anything within the Innovation Series


Type H drive cabinets until verifying that it is
neither thermally hot nor electrically energized.

Always work with one hand, wear insulated or


rubber safety shoes, and wear safety glasses. Also,
always work with another person present.

Never connect any grounded (i.e., non-isolated)


meters or oscilloscopes to the Innovation Series
Type H drive system.

GEH-6131 MV-GP Type H Drives Chapter 5 Preventive Maintenance • 5-1


Schedule, Record, and Materials
Maintenance Schedule
For maximum benefit, preventive maintenance needs to be performed on six-month
intervals by a qualified technician. The schedule should include an inspection of
wiring and components before re-applying power after an overcurrent trip.

Maintenance Record
GE recommends that the customer keep a detailed record of maintenance (such as a
log book) for every drive. This record serves two purposes:
• Verifies that all equipment is routinely checked
• Aids troubleshooting and prevention of equipment failure by providing a history
of equipment maintenance and problems.

Tools/Materials Needed
The tools and materials listed below may be needed when performing preventive
maintenance on the drive:
• Electrician’s tools, including screwdrivers and pliers.
• Socket set
• Hex wrench
• Torque wrench
• Electrical tape
• Fine file
• Clean dry cloth
• Soft-bristled brush (such as a paintbrush)
• Mild solution of distilled water and household or laboratory detergent
• Isopropyl alcohol
• Insulation resistance tester
• High voltage detector (such as a tic tracer using an insulated pole of appropriate
length)
• Vacuum cleaner with non-metallic nozzle and finely woven, high efficiency
filter
• Fuse puller
• Replacement components, if required, including fuses, wiring, cabling, and door
filters.

5-2 • Chapter 5 Preventive Maintenance GEH-6131 MV-GP Type H Drives


Fan and Blower Airflow Check

Dangerous voltages exist in the equipment


circuitry when power is applied.

Verify proper operation of cooling system by placing a single sheet of standard ply
notebook paper over the cabinet air intakes. The paper should stick to the cabinet.
The following preventive maintenance procedures need to be conducted with power
on within the control cabinet, only.
1. While the equipment is running, open the control cabinet door. The fan is
located underneath the control rack.
2. Without touching any circuitry, look to see that the fan is still running.
3. If it is not, turn off power to the equipment, then replace the fan. (The fan is
held in place by four screws.)

Power-Off Checks
Power-off checks involve cleaning the equipment and checking for wear and damage
through visual inspection and functional tests.

Before Starting Maintenance

Power must be de-energized before performing


any adjustments, servicing, or other act requiring
physical contact with the electrical components or
wiring.

Before starting, the equipment must be prepared as follows:


1. De-energized
2. Tagged and locked out
3. Discharged (the dc link has a minimum discharge time of 5 minutes)
4. Verified that the high-voltage warning LED on every power cell has been
extinguished.
Do not deviate from these conditions. If safety requirements cannot be met
completely, or if you do not understand them, do not work on the equipment.

GEH-6131 MV-GP Type H Drives Chapter 5 Preventive Maintenance • 5-3


Dust Removal
Since the cooling system of the Innovation Series Type H drive draws air through the
power cell heat sinks, dirt will tend to collect at the inputs of the cell heat sinks. If
significant collection is noted, these cells should be removed and cleaned (see
Chapter 7).
Thoroughly clean the inside and outside of all enclosures using a vacuum cleaner
fitted with a plastic nozzle. Keeping the equipment free from dirt and dust allows
proper heat dissipation.

Note Make sure that the air is directed so that dust and foreign matter is removed
rather than relocated.

Inspect the belts and blower motor in the Blower/Transformer Cabinet. Blowers are
located above the transformer. If the Cell Cabinets are fitted with air filters, these
filters can be cleaned and replaced.

Filter must be oriented so that airflow is from


outside to inside of the cabinet.

Loose Connections
Vibration during equipment operation can loosen mechanical and electrical
connections and causes intermittent equipment failure. Additionally, dust and
moisture in loose connections can cause loss of low-level signals at terminal boards
and also thermal runaway at bus connections.
The power connections should be re-tightened after the first few days of operation
and checked monthly for tightness during the first few months of operation, then
every 6 months thereafter. Other important procedures include:
• Check all input power and output series connections within the Cell Cabinet (see
system elementary).
• Check all secondary and primary transformer connections within the
Transformer Cabinet (see system elementary).
• Tighten or replace any loosened crimp-style lugs.
• Tighten or replace all loose or missing hardware.
• Inspect printed wiring boards for correct seating, and check that any lugs,
wiring, and bus connectors are tight.

To prevent component damage caused by static


electricity, treat all boards and devices with static-
sensitive handling techniques. Wear a wrist
grounding strap when handling boards or
components, but only after boards or components
have been removed from potentially energized
equipment and are at a normally grounded
workstation.

5-4 • Chapter 5 Preventive Maintenance GEH-6131 MV-GP Type H Drives


Damaged Insulation
Wires and cables with damaged insulation are dangerous when carrying electricity.
They can also intermittently short, causing equipment and functional failure.
• Check all wires and cables for fraying, chipping, nicks, wear, or rodent damage.
• Check all wires and cables for signs of overheating or carbonization.
• Repair minor low voltage insulation damage with a good grade of electrical
tape. If a damaged cable carries high voltage, replace the cable.
• Replace any cables or wires that have more than mild damage.

Inspecting Fiber Ends


Before connecting fiber-optic cable to any equipment, use Table 5-1 to check the
ends for proper termination and damage.

Table 5-1. Procedures for Inspecting Fiber-Optic Cable Ends

Inspection Procedure Appearance of Fiber End Problem How to Correct

1. Check the fiber end for Connector End None. No action required (fiber
pistoning, as follows: has been terminated and
Place a dust cap
Fiber Even With polished to the required
a. Backlight one end of the Connector End on the end until
level).
cable. use.
b. At the other end, use a
magnifier to view the
fiber at an angle.
Pistoning: Reject assembly.
Check the relative position
Fiber not even Re-terminate per section
of the fiber end to the Fiber Below with connector Cable Assembly, then re-
connector end. Connector End end. inspect per
section Inspecting Fiber
Ends.

Fiber Above
Connector End

GEH-6131 MV-GP Type H Drives Chapter 5 Preventive Maintenance • 5-5


Inspection Procedure Appearance of Fiber End Problem How to Correct

2. Check that the fiber end is Connector End None. No action required
polished correctly, as (fiber and connector
Place a dust
follows: Fiber Is Round end have been
cap on the
and Without terminated and
a. Backlight one end of the Scratches end until use.
polished correctly).
cable
b. At the other end, use a
magnifier to view the fiber
end straight on (not at an
angle). Check the appear- Fiber Has a
ance of the fiber surface. Few Light
Scratches

Fiber end Reject assembly.


damaged. Re-terminate then
Fiber Not re-inspect per
Round sections
Cable Assembly and
Inspecting Fiber Ends.
Fiber poorly Re-polish per section
polished. Polishing Fiber Ends,
Fiber Surface then re-inspect per
Cloudy or section Inspecting
Distorted Fiber Ends.
If re-polishing once
does not fix this
problem, then reject
the assembly. Re-
terminate and re-
inspect per sections
Cable Assembly and
Inspecting Fiber Ends.
3. Check that a black band is Black Band None. No action required
clearly visible, as follows: Appears Sharp (black band indicates
Place a dust
and Clear correct termination).
a. Backlight one end of the cap on the
cable. end until use.
b. At the other end, use a
magnifier to view the fiber.
Start viewing straight on Black Band Fiber poorly Re-polish per section
and gradually increase the Appears polished. Polishing Fiber Ends,
angle of tilt. A black band Distorted then re-inspect per
should appear. section Inspecting
Fiber Ends.
If re-polishing once
does not fix this
Surface problem, then reject
Cloudy, Black the assembly. Re-
Band Barely terminate and re-
Visible inspect per sections
Cable Assembly. and
Inspecting Fiber Ends.

5-6 • Chapter 5 Preventive Maintenance GEH-6131 MV-GP Type H Drives


Contactors and Relays
If possible, manually trip the device to ensure that it works properly. Inspect
contacts on open (as opposed to sealed) contactors and relays. Discoloration and
rough contact surfaces are normal.
If beads have formed because of severe arcing:
• Dress the contact faces with a fine file. Do not use emery cloth or sandpaper.
• Identify and correct the cause of arcing.
• Refer to the component’s publication for detailed instructions on maintenance,
repair, and replacement procedures.

Printed Wiring Boards


If boards in a module are dirty:
1. Vacuum to remove dust from around the board connections before and after
unplugging.
2. Remove the boards per the instructions in Chapter 6. Be sure to observe the
personal and equipment safety instructions.
3. Vacuum to remove dust from the board and connections. A soft-bristled brush
may be used to loosen dirt.
4. If excessively dirty, boards may need to be washed, as follows:
• Use a soft-bristled brush to scrub the board in a mild, lukewarm (37.7 °C,
100 °F) solution of distilled water and household or laboratory detergent.
Harsh chemicals and solutions will damage the board. Do not use solvents
containing ammonia, aldehydes, alkalis, aromatic hydrocarbons, or ketones.
• Rinse thoroughly by dipping the board several times in fresh, lukewarm,
distilled water. Do not soak the board.
• Dry the board by shaking off excess water, immersing and agitating the
board isopropyl alcohol, then air drying for a few hours.

Short-Circuit Damage
If a short-circuit occurs, overcurrent protective devices on the circuit should cut off
power to the equipment. This normally prevents electrical damage, except at the
point of the short. However, the heat produced by an electrical arc can carbonize
some organic insulating materials, which then lose insulating qualities.
After repairing the cause of the short and before re-applying power:
1. Inspect the system thoroughly for damage to conductors, insulation, or
equipment. Replace, if found.
2. Check insulation resistance.
3. Inspect the overcurrent protection devices for damage to insulation and contacts
(see previous sections on damaged insulation and contactors). Replace or repair,
as needed.
4. Check and replace any open fuses.

GEH-6131 MV-GP Type H Drives Chapter 5 Preventive Maintenance • 5-7


Notes

5-8 • Chapter 5 Preventive Maintenance GEH-6131 MV-GP Type H Drives


Chapter 6 Component Replacement

Introduction
This chapter of the manual provides guidelines for replacing components during
repair. It is organized as follows:

Section Page

Before Starting ................................................................................................................ ...........2


Replacing Printed Wiring Boards ..............................................................................................2
Removing and Installing Cells .................................................................................................. .4

For liquid cooled drives, refer to GEH-6132.

Always follow the proper lock-out/tag-out


procedures before beginning any maintenance or
troubleshooting work on the drive.

Only qualified personnel should install, operate,


troubleshoot, and maintain this drive. A qualified
individual is “one familiar with the construction
and operation of the equipment and the hazards
involved.”

Never touch anything within the Innovation Series


Type H drive cabinets until verifying that it is
neither thermally hot nor electrically energized.

Always work with one hand, wear insulated or


rubber safety shoes, and wear safety glasses. Also,
always work with another person present.

GEH-6131 eries MV-GP Type H Drives Chapter 6 Component Replacement • 6-1


Never connect any grounded (non-isolated) meters
or oscilloscopes to the Innovation Series Type H
drive system.

Before Starting
Before starting, the equipment must be prepared as follows:
1. De-energized
2. Tagged and locked out
3. Discharged (each cell has a minimum discharge time of 5 minutes after the
removal of input power)
Do not deviate from these conditions. If safety requirements cannot be met
completely, or if you do not understand them, do not work on the equipment.

Replacing Printed Wiring Boards


Because of upgrade, boards of different revision levels may not contain identical
hardware. However, GE ensures backward compatibility of replacement boards.

Handling Precautions

To prevent component damage caused by static


electricity, treat all boards and devices with static-
sensitive handling techniques. Wear a wrist
grounding strap when handling boards or
components, but only after boards or components
have been removed from potentially energized
equipment and are at a normally grounded
workstation.

Printed wiring boards may contain static-sensitive components. Therefore, GE ships


all replacement boards in antistatic bags. Use the following guidelines when
handling boards:
1. Store boards in antistatic bags or boxes.
2. Use a grounding strap when handling boards or board components outside the
enclosure.

6-2 • Chapter 6 Component Replacement GEH-6131 MV-GP Type H Drives


Replacement Procedures

To prevent electric shock, turn off power to the


board, then test to verify that no power exists in
the drive before touching it or any connected
circuits.

To remove a board:
1. Prepare the drive as defined in the first section of this chapter.
2. Open the drive’s cabinet door. Test any electrical circuits before touching
them to ensure that power is off.
3. Carefully disconnect all cables, as follows:
• For a cable with a pull-tab, carefully pull the tab.
• For a screw-terminal connector, loosen the screw at the top of each terminal
and gently pull each wire free.
• For a fiber-optic connector, press and hold the latch on the mating cable
connector while pulling.
4. Carefully remove the board, as follows:
• Some boards are mounted on standoffs with screws. Remove the screws to
release the board, being careful not to drop hardware into the drive.
• For boards mounted within a rack, loosen the screws at the top and bottom
of the board, near the board ejector tabs. (The screws are captive in the
board front and should not be removed.) The board can then be unseated by
raising the ejector tab.
To install a board:
1. On the replacement (new) board, set all jumpers, pots, and switches in the exact
position as those on the board being replaced. If a board revision has added or
eliminated a configurable component, or readjustment is needed, refer to the
individual board publication.
2. If the board contains onboard software, refer to the individual board publication
for instructions.
3. To install a board into a rack:
a. Slide the board into the correct slot in the rack.

Boards that mount in the rack are mechanically


keyed so that they can only be installed into the
correct slot. Do not attempt to defeat or overide
these interlocks. Doing so will damage the
electronics.

b. Begin seating the board by firmly pressing the top and bottom of the board
at the same time with your thumbs.

GEH-6131 eries MV-GP Type H Drives Chapter 6 Component Replacement • 6-3


c. Finish seating the board in the slot by starting and then tightening the
screws at the top and bottom of the board. Tighten the screws evenly to
ensure that the board is seated squarely.
4. To install a board that is seated with standoffs:
a. Place the board onto the standoff in the same orientation as the board that
had been removed.
b. Secure the boards by replacing and tightening the screws that had been
removed.
5. Reconnect all cables, making sure that they are properly seated at both ends.

Removing and Installing Cells


To remove or install a cell, refer to Figure 1-6 and Figure 1-8, then follow the
instructions below.

Hazardous voltages may be present in the cell


cabinet! Verify that the input power is properly
locked in the off position and that the bus LED on
each cell is off. This takes approximately 5
minutes after removal of input power.

1. Disconnect the 3-phase input connections at the bottom of F11, F12, and F13.
These cable connections are factory placed so that the A, B and C phase
connections match the termination designations on the transformer secondary,
however individual cell phase sequence is not important to operation.
2. Disconnect the output connections between adjacent cells on T1 and T2.
3. Disconnect the fiber-optic connection on the cell control board.
4. Each cell can be accessed without removing it from the cabinet by extending the
slide rails. Detent locks on the slides must be pressed in four locations
simultaneously (two on each slide) to remove a cell.

Maintain a two inch bend radius on all fiber-optic


cables.

6-4 • Chapter 6 Component Replacement GEH-6131 MV-GP Type H Drives


Appendix A Warranty and Renewal
Parts

Introduction
When ordering a replacement part for a GE drive, it is important to know:
• GE shop order or requisition number
• Drive serial number and “RSN” number
• How to accurately identify the part
• If the part is under warranty
• How to place the order
This information helps ensure that GE can process the order accurately and as soon
as possible.
To minimize system downtime if repair is needed, GE recommends that the customer
keep a set of spare parts on hand. The Initial Spares Quotation (see section Initial
Spares List) lists recommended spares.
The information in this section is presented as follows:

Section Page

Identifying the Part........................................................................................................... ..........1


Warranty Terms ................................................................................................................. ........4
How to Order Parts ............................................................................................................. .......4

Identifying the Part


A drive component, or part, is identified by its assigned part number and
description. The part number is normally found on a nameplate on the component.
The description is included in the parts tables in Chapter 6 and in the system renewal
parts list.

GEH-6131 MV-GP Type H Drives Appendix A Warranty and Renewal Parts • A-1
Initial Spares List
The Initial Spares Quotation is a separate document that lists the parts of a complete
system. This list applies specifically to the equipment furnished on a customer’s
particular application (requisition) at the time of shipment. It includes:
• Part numbers and descriptions
• Quantity used
• Recommended spares to keep on hand
• Normal delivery cycle for obtaining each part
GE provides the Initial Spares Quotation with the drive’s custom instructions. If this
document is missing, contact the nearest GE sales office or service representative to
obtain a replacement copy. You need to provide the following information (see
Figure A-4) to correctly identify the system:
• GE requisition number
• Material List number or serial number
• Item number

Part Number Structure


A GE part number is structured so that different portions of the number identify the
type of equipment and location of manufacture. A part falls into one of four
categories:
• Order-specific assemblies – Major assemblies or items that make up a specific
drive; constructed from common assemblies
• Common assemblies – Subassemblies used in many GE drive products, not just
a specific drive
• Components – Individual parts that make up assemblies
• Printed wiring boards
These categories and the makeup of their part numbers are defined below.

Order Specific Assemblies


These parts make up the particular drive. Other items obtained specifically for the
order may also use a similar part number structure, which provides information about
the equipment (see Figure A-1).

3V XYZ999 PR 001

Unit identification number


Assembly type 1

Component
Identifies manufacturer as GE Industrial
Control Systems, Salem, VA
1PRfor standard product; LU for lineup;
CAfor case, AM for multi-cabinet assembly
Figure A-1. Sample Part Number for Order-Specific Assembly

A-2 • Appendix A Warranty and Renewal Parts GEH-6131 MV-GP Type H Drives
Common Assemblies
Common assemblies are subassemblies used as components of order-specific
assemblies. Common assemblies are not designed for a particular drive, but provide
a function used in other GE products.
A common assembly part number consists of the number 36 followed by an
alphanumeric character. It may contain up to 14 characters. For example,
36C774524AAG48 is the part number for a drive cable.

Components
Components are the basic parts that make up assemblies. They represent the lowest
discrete level of a system. Component part numbers consist of a combination of
alphanumeric characters that define the class and specific item.

323A 2396 P59

Item or rating (250 V, 4 A, MDL)


Component type (fuse)
Component

Figure A-2. Sample Part Number for Component

Printed Wiring Boards


A printed wiring board is identified by an alphanumeric part (catalog) number
stamped near its edge. Figure A-3 describes the structure of a board’s part number.

Note All digits are important when ordering or replacing any board. The factory
may substitute later versions of boards based on availability and design
enhancements. However, GE Industrial Control Systems ensures compatibility of
replacement boards.

IS 200 DSPX G# A A A

Artwork revision 1

Functional revision 1
Functional revision 2
Group (variation) 3
Functional acronym

Assembly level 4

Manufacturer ( DS & IS for GE in Salem, VA)


1Backward compatible
2Not backward compatible
3G = uncoated, H = conformal coating
4200 indicates a base-level board; 215 indicates a

higher-level assembly or added components (such


as PROM)

Figure A-3. Sample Board Part Number

GEH-6131 MV-GP Type H Drives Appendix A Warranty and Renewal Parts • A-3
Warranty Terms
The GE Terms and Conditions brochure details product warranty information,
including warranty period and parts and service coverage. The brochure is
included with customer documentation. It may be obtained separately from the
nearest GE Sales Office or authorized GE Sales Representative.

How to Order Parts


Parts still under warranty may be obtained directly from the factory:
GE Industrial Systems
Product Service Engineering
1501 Roanoke Blvd.
Salem, VA 24153-6492 USA
Phone: + 1 540 387 7595
Fax: + 1 540 387 8606
(“+” indicates the international access code
required when calling from outside of the USA.)

Renewals (spares or those not under warranty) should be ordered by contacting the
nearest GE Sales or Service Office. Be sure to include:
• Complete part number and description
• Drive serial number and “RSN” number
• Drive Material List number
The serial number, RSN, and material list number may be found on the data
nameplate.

Data Nameplate
The data nameplate is located on the back of the cabinet door. It provides
information needed when ordering parts or contacting GE for assistance (Figure A-
4).

A-4 • Appendix A Warranty and Renewal Parts GEH-6131 MV-GP Type H Drives
DATA NAMEPLATE

REQ# 655-99999 ITEM# HD001


ML# 3VZNX569AM001 SERIAL# NPZNX569AM001001
ACMVACR-G-5B5-4160-4160-NN-BB4000ADAA-BBAYN-AB [AA]
DRAWINGS: ELEM: NA OUTL: NA
LAYO: NA DRWG: NA
DRWG: 459409.ALL DRWG: 459409.ALL
VOLTS 4160 (V) VOLTS 0- 4160 (V)
PWR AMPS 485 (A) PWR AMPS 500 (A)
IN HERTZ 60 (HZ) OUT POWER 5000 HP
PHASE 3 (PH) FREQ 0 TO (60 HZ)
3 PH, ROTATION na
OVRLD CAP: 106%, 0 SEC SERVICE FACTOR: NA
MOTOR FIELD: na VOLTS, na AMPS
MAX SYM S.C.C.: na AMPS AT na VOLTS MAX
NEMA SERVICE CAT: NEMA ENCL. TYPE 12
FREQUENCY- na
VOLTAGE - na RSN#: *******
VOLT. UNBAL.- na

MADE IN NEW KENSINGTON, PA


USA
GE Drive Systems
Figure A-4 Typical Data Nameplate

Each GE lineup, cabinet (panel)/case, and core unit has a unique identifying catalog
number, also called the part or material list (ML) number. This number is
structured to provide information about that equipment (see Figure A-5.) The catalog
number links the equipment to its requisition, drawings, components, materials,
specification item, and shipping documents.
3V AAA 123 XX###
Unit & sequence number of components:
CA## = Case assembly
CD## = Core dc drive controller
CI### = Core ac drive controller
LU### = Lineup, multiple case
assembly
PN## = Panel assembly
RL## = Requisition-level assembly
Sequence/project
Unique
Order month/year/ to req’n
product line
Identifies manufacturer as GE Industrial
Systems, Salem, VA

Figure A-5. Sample Drive ML (Catalog) Number

GEH-6131 MV-GP Type H Drives Appendix A Warranty and Renewal Parts • A-5
Intelligent Part Number
The Intelligent Part Number (IPN) specifies the Innovation Series product and the
basic configuration of the product. The IPN is the catalog number for the Innovation
Series product. It can be found on the inside of the cabinet door.
The IPN for the Innovation Series medium voltage drive with general industrial
application pattern takes the following form:
ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx

Product Field
ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx
AC AC inverter drive
MV Medium voltage
AC AC fed
R Product family of voltage ratings and horsepower ratings

Pattern Field
ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx
G General industrial speed/torque – torque control

Frame Size Field


ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx
The frame size field is called FRM. This field is a combination of the two character
IPN bridge cell type and a single digit IPN cell count per phase. See cell type in
Appendix D. The number of cells per phase ranges from 3 to 6.

Transformer Input Voltage Field


ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx
The transformer IPN Xfmr Input volts field is called TVOLT. This is a four
character field.

System Voltage Field


ACMVACR-G-FRM-TVOLT-SVOLT-xx-xxxxxxx-xxxxx-xx
The IPN system voltage field is called SVOLT and is the maximum AC output
voltage to the load. This is a four character field.

A-6 • Appendix A Warranty and Renewal Parts GEH-6131 MV-GP Type H Drives
Appendix B Drive Parts List

Control Cabinet
Below is a list of the major components included in the control cabinet of the
Innovation Series Type H drive.

Table B-1 Standard Control Parts List

Qty. Description Part no.


1 Innovation Rack 173C8536AL G3
1 Digital Input/Output IS200BAIAH1B
1 Rack Power Supply IS200RAPAG1B
1 Digital Processor IS200DSPXH1B
1 I/O (ATBA) & 115V ETB 173C9226GDG02
1 Fuse, 2A, 250V 323A2396P50
1 Fuse, 4A, 250V 323A2396P59
1 I/O PWA (CTBC) 323A5743AXG03
1 Keypad Assembly 173C9226JBG01
1 Power supply Circuit Board IS200HFPRG1A
1 Bridge Interface Circuit Board IS200BICRH1A
1 Bridge Interconnect Circuit Board IS200BPIRG1A
1 Fiber-Optic Hub Board ISR4600A4.00
1 Master Link Board ISR460K78.01T

GEH-6131 MV-GP Type H Drives Appendix B Drive Parts List • B-1


Notes

B-2 • Appendix B Drive Parts List GEH-6131 MV-GP Type H Drives


Appendix C Cell Specifications

The following tables provide the basic specifications associated with all cell
combinations.

Table C-1 2400 V ac Cell Specifications (9 Cells Total, 3 Cells in Series)


Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
200 44 / 50 20,000 6,500 (4,200) 186 (144) 6,559 (5,456) 00
300 66 / 75 30,000 6,500 (4,200) 186 (144) 6,998 (6,046) 0
400 88 / 100 40,000 6,500 (4,200) 198 (144) 8,035 (6,450) 1
500 110 /150 50,000 6,500 (4,200) 198 (144) 8,307 (7,009) 2
600 131 / 150 60,000 6,500 (4,200) 198 (144) 8,557 (7,259) 2
700 153 / 200 70,000 6,500 222 9,526 3
800 175 / 200 80,000 6,500 222 9,786 3
900 197 / 200 90,000 6,500 222 10,051 3
1,000 220 / 300 100,000 6,500 222 10,481 4
1,250 273 / 300 125,000 6,500 222 11,431 4
1,500 327 / 400 150,000 10,000 282 13,380 5
1,750 382 / 400 175,000 10,000 282 14,305 5

Table C-2 3300 V ac Cell Specifications (12 Cells Total, 4 Cells in Series)
Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
300 49 / 50 30,000 6,500 (4,200) 198 (144) 7,383 (6,097) 00
400 64 / 75 40,000 6,500 (4,200) 198 (144) 7,918 (6,620) 0
500 80 / 100 50,000 6,500 210 8,619 1
600 96 / 100 60,000 6,500 210 8,869 1
700 112 / 100 70,000 6,500 210 9,127 2
800 128 / 150 80,000 6,500 210 9,387 2
900 144 / 150 90,000 6,500 210 9,652 2
1,000 160 / 200 100,000 6,500 246 11,189 3
1,250 199 / 200 125,000 6,500 246 12,139 3
1,500 239 / 300 150,000 10,000 282 14,162 4
1,750 279 / 300 175,000 10,000 282 15,087 4
2,000 319 / 400 200,000 10,000 306 16,954 5
2,250 358 / 400 225,000 10,000 306 17,079 5

GEH-6131 MV-GP Type H Drives Appendix C Cell Specifications • C-1


Table C-3 4160 V ac Cell Specifications (15 Cells Total, 5 Cells in Series)
Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
300 38 / 50 30,000 6,500 (4,200) 198 (144) 7,506 (6,256) 00
500 63 / 75 50,000 6,500 (4,200) 198 (144) 8,253 (6,955) 0
600 75 / 75 60,000 6,500 (4,200) 198 (144) 8,503 (7,205) 0
700 89 / 100 70,000 6,500 222 9,424 1
800 101 / 150 80,000 6,500 222 9,804 2
900 114 / 150 90,000 6,500 222 10,069 2
1,000 126 / 150 100,000 6,500 222 10,319 2
1,250 158 / 200 125,000 6,500 270 12,877 3
1,500 189 / 200 150,000 10,000 306 14,686 3
1,750 221 / 300 175,000 10,000 306 15,911 4
2,000 252 / 300 200,000 10,000 306 16,836 4
2,250 284 / 300 225,000 10,000 306 16,961 4
2,500 315 / 400 250,000 10,000 342 19,223 5
3,000 378 / 400 300,000 13,200 372 21,875 5

Table C-5 4800 V ac Cell Specifications (18 Cells Total, 6 Cells in Series)
Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
400 44 / 50 40,000 6,500 222 8,650 00
500 55 / 75 50,000 6,500 222 8,922 0
600 66 / 75 60,000 6,500 222 9,172 0
700 77 / 100 70,000 6,500 246 10,132 1
800 88 / 100 80,000 6,500 246 10,392 1
900 99 / 100 90,000 6,500 246 10,657 1
1,000 109 / 150 100,000 6,500 246 11,051 2
1,250 137 / 150 125,000 6,500 246 12,001 2
1,500 164 / 200 150,000 10,000 330 15,424 3
1,750 191 / 200 175,000 10,000 330 16,349 3
2,000 218 / 300 200,000 10,000 330 17,634 4
2,250 246 / 300 225,000 10,000 330 17,759 4
2,500 273 / 300 250,000 10,000 330 18,584 4
3,000 327 / 400 300,000 13,200 396 22,799 5
3,500 382 / 400 350,000 13,200 396 24,524 5

Table C-5 6000 V ac Cell Specifications (15 Cells Total, 5 Cells in Series)
Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
500 44 / 100 50,000 6,500 222 9,239 1H
800 70 / 100 80,000 10,000 258 11,423 1H
1000 88 / 100 100,000 10,000 258 12,463 1H
1250 109 / 200 125,000 10,000 316 15,791 3H
1500 131 / 200 150,000 13,200 336 17,738 3H
2000 176 / 200 200,000 13,200 336 19,938 3H
2500 220 / 300 250,000 13,200 372 23,915 4H
3000 264 / 300 300,000 13,200 396 24,465 4H

C-2 • Appendix C Cell Specifications GEH-6131 MV-GP Type H Drives


Table C-6 6600 V ac Cell Specifications (18 Cells Total, 6 Cells in Series)
Hp 3 In 4/Out 5 Amps Losses 6 (BTU/Hr) Req CFM Length 7 (in) Weight 8 (lbs) Cell Size 9
500 40 / 100 50,000 10,000 282 10,705 1H
800 64 / 100 80,000 10,000 282 12,155 1H
1000 80 / 100 100,000 10,000 282 13,195 1H
1250 100 / 100 125,000 10,000 282 14,615 1H
1500 120 / 200 150,000 13,200 360 18,536 3H
2000 160 / 200 200,000 13,200 384 21,286 3H
2500 200 / 200 250,000 13,200 384 23,136 3H
3000 240 / 300 300,000 13,200 420 27,177 4H
3500 284 / 300 350,000 13,200 420 28,477 4H

3
Motor nameplate hp may not exceed the drive rated hp.
4
Drive rated input current is the transformer rated current.
5
Drive rated output current is the maximum cell current.
6
BTU/hr losses are based on a loss of 3 kW per 100 hp.
7
Represents lineup minimum length, subject to change.
8
Represents estimated minimum weight of lineup, subject to change.
9
The cell sizes for each hp rating are based on motors with at least 95% efficiency and at least 85% power factor.

GEH-6131 MV-GP Type H Drives Appendix C Cell Specifications • C-3


Notes

C-4 • Appendix C Cell Specifications GEH-6131 MV-GP Type H Drives


Appendix D Optional Cell Tester

Introduction
General Electric can supply the necessary equipment to perform on-site cell testing
at a customer’s site. This test is essentially a duplication of the cell test done at the
factory prior to installation into the cell cabinet. Since each cell operates
independently within the Type H system, it is possible to fully test the performance
of each cell and thus verify the proper performance of the cell system without having
to actually apply rated voltage to the motor.
This appendix is organized in the following manner:

Section Page

Required Equipment............................................................................................................. ......1


Procedure For Testing an Installed Cell .....................................................................................2
Solid State Variable Voltage Source ..........................................................................................3

Required Equipment
The following equipment is required:
• Portable Innovation Series Cell Tester (PCT, P/N 469939.00)
• IBM compatible computer (286 or greater w/ Centronics port, EGA capability)
• Load Reactor (refer to Table E-1).
• DVM capable of measuring 500 V ac.
• Clamp on ammeter.
• Blower for cooling the cell heat sink
• 480 V ac, 10A Variac (P/N 430278.00 or equal for cell size 0-2), or
480 V ac, 30 A Variac (P/N 430278.01 or equal for cell sizes 3, 4 and 5).

Note For more information on the solid state variac, refer to section Solid-state
Variac Option.

GEH-6131 MV-GP Type H Drives Appendix D Optional Cell Tester • D-1


Table D-1 Load Reactor Information

Cell Size Rated Current Reactor Part Number Weight


00 50 161661.09 250 Lb
0 75 161661.11 340 Lb
1 100 161661.12 420 Lb
2 150 161661.14 530 Lb
1
3 200 161664.16 540 Lb
1
4 300 161664.18 675 Lb
1
5 400 161664.20 Consult Factory
1
6 500 2x161664.18 Future Use
7 800 2x161664.20 1 Future Use
1
- Requires small cooling fans that are not included.

The PCT comes equipped with cables and software required to interface the PCT
with the cell’s optical communications port and the PC. The individual tests are
menu driven with Go and No Go features.
The load reactors will allow each cell to attain full rated current with a minimal input
service requirement to the variacs.
The clamp-on ammeters and voltmeters will allow evaluation of the proper output
voltages and cell currents during the test.

Procedure For Testing an Installed Cell


1. If possible, switch off the source of the medium voltage power at the switchgear.
Make sure the drive's medium voltage input switch is open, and lock it out.
Rack out any output contactors in the system and lock them out. Take any other
necessary steps to release the interlock key that allows access to the cell cabinet.
Keep the transformer cabinet and input switch cabinet closed and locked.
2. Isolate the cell to be tested by removing the series links from the output at T1
and T2 (see illustrations in Chapter 1).
3. Unplug the fiber-optic cable from this cell at the Master Link Board and plug it
into the PCT (see illustrations in Chapter 1). Connect the PCT to the parallel
printer port of the computer. Turn on the power to the portable cell tester.
4. Disconnect the 3-phase input from the cell and connect the 3-phase output of the
variable voltage source to the input of the cell (see illustrations in Chapter 1).
Connect the input of the voltage source to the load side of the 460 V ac control
breaker (CB1).
5. Execute the 1CELL.EXE program on the computer. From the Main Menu
choose #1. The preliminary test will go through a step-by-step go/no go
procedure. This will verify that the communications are working and the
transistors are blocking (not shorted).

D-2 • Appendix D Optional Cell Tester GEH-6131 MV-GP Type H Drives


Note At this point of the test, the functionality of the IGBTs has been determined.
When prompted to use a resistor, the operator should cancel the program by
following the instructions on the screen.

6. Turn off the variable voltage source. Connect the load reactor to output
connections T1 and T2 of the cell (see illustrations in Chapter 1). When running
with the cell mounted in the Cell Cabinet, be sure that the cell is fully receded to
allow proper cooling from the blower. If the cell is operated externally to the
cabinet, a separate blower or fan may be required.
7. From the Main Menu choose #2 Burn-in Test Menu. Make sure the pot on the
tester is turned fully in the counter-clockwise direction. From the burn-in test
menu start the burn-in. The bottom of the screen will indicate that the cell is
running. Q1-Q4 LEDs on the cell should be on. This verifies that all four
transistors are firing. Connect an ammeter to T1 or T2. Turn the pot on the
tester clockwise and note that the output current increases. Continue until
output current reaches the rated current of the cell. Run the cell for 1 hour.
Turn the pot fully in the counter-clockwise direction. Stop the burn-in test and
exit to the Main Menu.
8. Enter #4 (the diagnostic display). This screen verifies which faults are occurring
and whether they are able to be reset. For more information on cell faults, refer
to Chapter 7 Cell Faults and Troubleshooting
This completes the field cell test procedure.

Note Spare parts are available through the General Electric Customer Service
which can be reached by calling 1-540-387-7595.

Solid State Variable Voltage Source

Introduction
Two versions of the Solid State Variable Voltage Source are available: 480 V ac, 25
A (P/N 430278.00), and 480 V ac, 50 A (P/N 430278.01). This product is an option
when a GP Type H drive is purchased.
The solid-state variable voltage source is a light-weight way of supplying a variable
voltage source for back-feeding the drive. It can also be used for supplying power to
an individual cell being tested.

Use of this supply for back-feeding systems is


reserved for General Electric qualified service
personnel.

GEH-6131 MV-GP Type H Drives Appendix D Optional Cell Tester • D-3


Protective Circuits
The solid-state source contains built-in current limiting circuitry and input power
fuses for protection. It contains solid-state current limit control that limits the
source’s output to the maximum rated output current. In addition, input power fuses
are supplied to protect the supply from internal short circuits.

Potentially hazardous voltages are present when


this equipment is in normal use. Only qualified
personnel should operate and maintain this
equipment.

Before connecting the solid-state variable voltage


source to a drive (or other device), be sure that all
power to the drive (or device) is turned off at the
source. Be sure to follow proper lock-out/tag-out
instructions.

Operation
Use the connection diagram shown in Figure E-1when connecting the solid-state
variable voltage source to a cell for testing. Follow the steps outlined below.
• After the unit is connected, check that the voltage adjust potentiometer is fully
rotated to the counter-clockwise (CCW) position, and the On/Off switch is in the
“off” position. Refer to Figure E-1.

An SCR does not completely isolate the load when


switched to the “off” position. Before voltage is
supplied to the variable voltage source, be sure the
load is ready for voltage.

• Set the On/Off switch to the “on” position.


• Adjust the voltage as needed by the cell test procedure.

460 V ac Input 0-460 V ac Output

L1
Solid-state Cell
L2 Variable Voltage Source Being
Tested
L3

Figure E-1 Cell Test Connection Diagram

D-4 • Appendix D Optional Cell Tester GEH-6131 MV-GP Type H Drives


Analog Voltage
Display Meter

Voltage On/Off
Adjustment Pot Control Switch

DANGER
480 VAC

Figure D-2 Variable Voltage Source Controls

Troubleshooting

Table D-2 Common Troubleshooting Issues


Problem Possible Cause Possible Solution
No output voltage Is the unit switched “on” Switch unit to “on” position.
Pot not properly adjusted Adjust voltage adjustment potentiometer clock-wise
(CW).
Input voltage is incorrect Correct the input source according to the specifications
in Table E-3.
Blown power fuse(s) Replace blown power fuse(s). Also, do a power bridge
test to check for shorted SCRs.
Defective control circuit Replace control cards.
Full output voltage Load is not connected If the variable voltage source has input voltage with no
load connected, full voltage will appear on the output.
This is due to the inherent leakage from the SCRs.
Defective control circuit Replace control cards.

SCR Power Bridge


The solid-state variable voltage source uses three sets of back-to-back SCRs. A
VOM (volt/Ohm meter) can be used to test the resistance across the SCR switch. A
zero Ohm reading (0 Ω) indicates a defective SCR. To test, connect one lead to L1
and the other to T1. Repeat the test for L2 to T2 and L3 to T3. Replace any SCRs that
are shorted. The VOM test meter should be set to the Ohm scale (R×1).

GEH-6131 MV-GP Type H Drives Appendix D Optional Cell Tester • D-5


Meter indication is
high resistance
(SCR not shorted)

Meter indication is low


resistance (SCR is
shorted)

Figure D-3. Sample Power Bridge Test Results

Follow the instructions listed below for proper power fuse replacement.
1. Disconnect the input voltage to the variable voltage source.
2. Fuse access is provided via the back panel of the variable voltage source. Refer
to Figure D-4.

Input Power
Output Terminal Block
Fuses

Figure D-4. Solid-state Variable Voltage Source (Rear View)

D-6 • Appendix D Optional Cell Tester GEH-6131 MV-GP Type H Drives


Specifications
Specifications for the solid-state variable voltage source are outlined in Table D-3.

Table D-3 Solid State Variable Voltage Source Specifications


Item Description (P/N 430278.00) Description (P/N 430278.01)
Input Voltage 460 V ac +10% to -5%, 460 V ac +10% to -5%,
3-phase, 60 Hz 3-phase, 60 Hz
Input Current 25 Amps AC (max) 50 Amps AC (max)
Output Voltage 0-460 V ac phase angle output 0-460 V ac phase angle output
Output Current 25 Amps AC (max) 50 Amps AC (max)
Ambient Temperature 0-40° C 0-40° C
Humidity 95% non-condensing 95% non-condensing
Altitude Maximum 3,300 ft (MSL) Maximum 3,300 ft (MSL)

GEH-6131 MV-GP Type H Drives Appendix D Optional Cell Tester • D-7


Notes

D-8 • Appendix D Optional Cell Tester GEH-6131 MV-GP Type H Drives


Glossary of Terms

ACL_ board
IS215ACL_Application Control Layer board. This board contains the ACL
controller functions for the drive. Located in the drive control rack.

ACL controller
Application Control Layer controller. A form of the Innovation Series controller
hosted in the Innovation Series drive rack that performs job specific, outer layer,
drive control loops, and sequencing.

application software
Job-specific software resident in the drive, designed specifically for the customer’s
application.

ACOM
Analog common. Used to supply power and signals to all analog devices and
components fed by +50 and -50 V power supplies.

armor
The overall protective covering for the insulated cable. Same as sheath.

ATBA
IS200ATBA Application Terminal Board, used for customer and power I/O. Located
in the drive’s control cabinet.

AWG
American Wire Gage (or Gauge). Standard measurement for the thickness of
electrical wires. Ranges are based on the wire’s diameter. As the thickness increases,
the AWG number decreases.

b
Alphabetic symbol for bit. Used in measurement (for example, kb for kilobits.)

B
Alphabetic symbol for byte. Used in measurement (for example, kB for kilobytes.)

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-1


BAIA
IS200BAIA Basic I/O board, which provides for custom and application I/O.
Located in the drive’s control cabinet.

baud
A measure of data transmission speed, representing the number of signal-state
changes per second. Named after French engineer B.M.E. Baudot.

BICR
IS200BICR Bridge Interface board. Located in the drive control rack.

blocks (software)
Standard modules (blocks) of microprocessor code that perform specific software
functions (for example, a speed regulator). Blocks are configured into the application
program.

board
Printed wiring board.

BPIR
IS200BPIR Control interface to the Fiber Optic Hub Board. Located in the drive
control rack.

bps
Abbreviation for bits-per-second, the standard measure of data transmission speed.

bus
An electrical path for transmitting and receiving data.

cable
A standard single conductor or a combination of conductors insulated from each
other.

cableway
See raceway.

CABP
IS200CABP Control Rack Backplane board. Located in the drive’s control cabinet.

Category 5
Cabling standard specified by EIA/TIA for use with data transmission speeds up to
100 Mbps. Category 5 cable is made up of eight color-coded, twisted copper wires
encased in a sheath. Similar to standard telephone wire.

Cat 5
Category 5 (cable).

CCB
Cell Control Board

GL-2 • Glossary of Terms Innovation Series MV-GP Type H Drives


Cell
Also Power Cell. Component of drive responsible for rectification and inversion of
power.

CE
Conformité Européene. The CE mark signifies that a product meets specific
conformity assessment requirements of the European Union (EU), a European trade
organization. The mark does not endorse the quality or durability of a product, but
only that it satisfies mandatory technical requirements.

coaxial cable
A type of wire cable with a solid metal core surrounded by an insulator, a
combination shield and ground wire, and an outer protective jacket.

COM port
Serial controller communication ports (two). COM1 is reserved for diagnostic
information and the Serial Loader. COM2 is used for I/O communication

commissioning
Putting into service.

configure
To select specific options, either by setting the location of hardware jumpers or
loading software parameters into memory.

conduit
A tubular device for holding wires or cables.

connector
A device, either a plug or receptacle, used to terminate or connect cables.

control system
A means of governing the starting, stopping, direction of motion, acceleration, speed,
and retardation of the moving member of any electric apparatus, machine, or system.

control system toolbox


A Windows-based software package used to configure and perform diagnostics on
controllers and drives.

CSA
Canadian Standards Association. An independent, nonprofit product standards and
certification organization in Canada.

CT
Line current transformer.

CTBC
IS200CTBC Core Terminal Board, used for customer and power I/O. Located in the
drive’s control cabinet.

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-3


DCOM
Digital common. Used to supply power and signals to all digital devices fed by +5,
+12, and -12 V power supplies. Sometimes, this is also fed by the +28 V power
supply.

DDI
See Drive Diagnostic Interface.

drive
The equipment used for converting available power into mechanical power suitable
for operation of a machine. (See control system.)

Drive Diagnostic Interface


The operator interface module located on the front door of the drive’s control cabinet
Also called DDI or the keypad.

device
A configurable component of a process control system.

diagnostics
Software that checks drive hardware or software, providing error indications that
identify the type or location of malfunction.

DSPX
IS200DSPX Digital Signal Processor board. Is the primary controller for the bridge
and motor regulator and gating functions for Innovation SeriesTM drives. Located in
the drive’s control cabinet.

duplex cable
A dual-stranded fiber-optic cable.

EEPROM
Electrically erasable programmable read-only memory, also called EE or E 2 (E
squared). Contains the drive parameters.

EIA
Electronics Industry Association (EIA), a trade organization representing the U.S.A.
high technology community. The EIA establishes Recommended Standards (RS) for
hardware devices and their interfaces.

electromagnetic
Of or pertaining to magnetism produced by or associated with electricity.

electromagnetic interference
See EMI.

elementary diagram
Also called elementary. A schematic drawing that represents the electrical wiring
and electrical connections of a device.

GL-4 • Glossary of Terms Innovation Series MV-GP Type H Drives


EMI
Electromagnetic interference. Any electromagnetic disturbance that interrupts,
obstructs, or otherwise degrades or limits the effective performance of
electronics/electrical equipment.

EPROM
Erasable programmable read-only memory.

equipment grounding conductor


Also called safety ground. The conductor used to connect the noncurrent carrying
parts of conduits, cableways, and equipment enclosures to the grounding electrode at
the service equipment (main panel) or secondary of a separately derived system
(such as an isolation transformer).

Ethernet
LAN with a 10/100 MB baud collision avoidance/collision detection system used to
link one or more computers together. Basis for TCP/IP and I/O services layers that
conforms to the IEEE 802.3 standard, developed by Xerox, Digital, and Intel.

exothermically weld
The process of exothermic welding is a method of making electrical connections of
copper to copper or copper to steel in which no outside source of heat or power is
required.

fault code
A number that represents a drive malfunction, such a warning or failure. The drive
controller automatically sends this code to the operator interface, such as the DDI
(keypad). Also see warning, failure, DDI.

fiber-optic cable
A type of high speed cable that contains glass or plastic thread as its signal conductor
surrounded by cushioning and insulation.

Finder
A subsystem of the GE Control System Toolbox for searching and determining the
usage of a particular item in a configuration.

firmware
The set of executable software that is stored in memory chips that hold their content
without electrical power, such as EEPROM.

FOHB
IS200FOHB Fiber Optic Hub Board

Genius bus
GE Fanuc’s distributed network of intelligent I/O blocks.
ground
An electrical path designed to disperse high-voltage electrical spikes, usually by
routing them to the earth.

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-5


grounding electrode
A conductor or group of conductors in intimate contact with the earth for the purpose
of providing a connection with ground.

jacket
The outermost layer of insulating material of a cable or conductor.

hardware (hard) reset


Reset generated by a hardware device, rather than by a software reset. Used to reset
the drive boards, clear some faults, and allow certain parameter changes. Activated
by pressing the SDCC’s RESET button or by connecting NTB/3TB terminal board
point 3TB-58 or STBA terminal board point STBF-38 to +5 or +24 V dc.

health
A term that defines whether the drive is functioning as expected.

heartbeat
Also know as SQE (signal quality error), a test between the transceiver and data
terminal equipment to check that the transceiver is still functioning.

HFPR
IS200HFPR Power Supply board. Located in the drive’s control cabinet.

IEC
International Electrotechnical Commission. An organization that cooperates with the
ISO for technology standards.

IEEE
Institute of Electrical and Electronic Engineers. A United States-based society that
develops for electrical and electronic standards.

IEEE 802.3
The IEEE standard that defines Ethernet conventions.

IGBT
Insulated-gate bipolar transistor.

initialize
To set values (addresses, counters, registers, and such) to a beginning value before
the rest of the processing.

I/O
Input/output. Data flow into and out of a device, or the term for input/output
interfaces.

IPN
Intelligent Part Number.

GL-6 • Glossary of Terms Innovation Series MV-GP Type H Drives


ISBus
A synchronous bus, serial communications system developed by GE for the
Innovation Series drive system LAN. Uses RJ-45 connectors and Category 5 cabling
with data transmission rate up to 5 Mbps.

ISO
International Standards Organization. An organization that promotes the
development of standards for computers.

k
Kilo. Alphabetic symbol for 1 thousand.

keypad
See Drive Diagnostic Interface.

LAN
Local area network. A communications link that enables attached devices to
communicate with each other over a limited geographical area. A typical LAN
consists of peripheral devices and controllers contained in the same building, and
often on the same floor.

layout drawing
A diagram showing the components of a panel (see definition), and their location and
connections.

LED
Light-emitting diode. Used as a visual indicator for a board or drive function.

LEM
Trademark of LEM Inc. – current sensor.

m
Milli. Alphabetic symbol for 1 thousandth.

M
Mega. Alphabetic symbol for 1million.

menu
A list of available software functions for selection of an operator, displayed on the
computer screen after a software program has been entered or a software selection is
made.

MLB
Master Link Board.

module
(Hardware) An electronic assembly of boards, components, or a combination of
these, that together perform a specific function.
(Software) A collection of tasks that have a defined scheduling period.

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-7


NEC
National Electrical Code. Electrical safety guidelines developed by the National
Fire Protection Association and adopted as a standard by the American National
Standards Institute (ANSI).

NEMA
National Electrical Manufacturers Association. An organization that develops
standards for the electrical manufacturing industry.

network
A data communication system that links two or more computers and peripheral
devices.

node
Any device that is connected to a network.

noise
Electrical surges, spikes, or transients on transmission lines. Noise can cause slow or
immediate damage to sensitive electronic equipment.

non-regenerative
Opposite of regenerative. See regenerative.

outline drawing
A drawing or diagram that shows the dimensions and non-detailed layout of a device
or equipment.

panel
The side or front of a piece of equipment on which terminations and termination
assemblies are mounted.

panel layout drawing


See layout drawing.

parameters
Adjustable software settings used to program and tune the drive.

plug connector
An electrical fitting or termination assembly with contacts constructed to be
electrically connected to a receptacle connector by being inserted into the receptacle
connector. Also known as male connector.

power cell
Component of drive responsible for rectification and inversion of power. Also Cell.

pu
Per unit

PWM
Pulse Width Modulated.

GL-8 • Glossary of Terms Innovation Series MV-GP Type H Drives


raceway
Any channel for enclosing and loosely holding wires, cables, or busbars in interior
work that is designed and used solely for this purpose. Also called cableway.

radio frequency interference (RFI)


See RFI.

RAM
Random access memory. Memory that can be both read from and written to.

reboot
See hardware reset and software reset.

receptacle connector
An electrical fitting or termination assembly with contacts constructed to be
connected electrically to a cable by the insertion of the cable’s plug connector into
the receptacle connector. Also known as female connector.

regenerative
Ability of a drive to return power from the motor to the ac line. Creates a braking
effect on the motor.

RFI
Electromagnetic radiation in the radio frequency (RF) spectrum from 15 kHz to 100
GHz. The best shielding material against RFI are copper and aluminum alloys.

signal reference structure (SRS)


A system of conductive paths among interconnected equipment that reduces noise-
induced voltages to levels that minimize improper operation. Common
configurations include grids and planes.

simplex cable
A single-stranded fiber-optic cable.

skin effect
The tendency for current to crowd to the surface.

RAPA
IS200RAPA Control Rack Power Supply board. Located in the drive’s control
cabinet.

RJ-45
Registered jack-45. A serial connector, typically used in LANs to connect computer-
based devices using Category 5 cable. Similar to a telephone jack, but with 8 wires.

RS-232C
An EIA Recommended Standard (RS) for the serial link communications interface
for interconnecting data terminal equipment, such as printers, computer monitors, or
computers to data communications equipment, such as modems, for transmission

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-9


over a telephone line or network. RS-232C uses an unbalanced or single-ended
voltage interface. (Also see EIA.)

RS-422
An EIA Recommended Standard (RS) that defines electrical characteristics of a
serial link communications interface. The standard permits greater distances between
equipment and faster data transfer than RS-232C. RS-422 is characterized by a
balanced or differential voltage interface. (Also see EIA.)

safety ground
See equipment grounding conductor.

shield
A conductive sheath (usually metallic) applied over the insulation of a conductor or
conductors. See shielding.

shielded cable
Cable surrounded by a separate conductor (the shield) intended to minimize the noise
effects of internal or external electrical circuits.

shielding
Use of a conducting barrier between a potentially disturbing noise source and
sensitive circuitry. Shields are used to protect cables (data and power) and electronic
circuits. They may be in the form of metal barriers, enclosures, or wrappings around
source circuits and receiving circuits.

software (soft) reset


Reset initiated by software input, rather than by a hardware device. Activated by a
serial input, or by pressing the DDI’s RESET key.

terminal board
A type of I/O connector in which individual wires from external components are
inserted into a connector point and are fastened by turning a screw on the connector.

terminator
A resistor that reflects cable signals. On coaxial cable bus networks, a terminator is
installed at each end of the cable, with one end requiring ground connection.

toolbox
See control system toolbox.

twisted-pair cable
Cable consisting of pairs of copper wire, surrounded by an insulator, and twisted
together in a manner that reduces capacitance.

UL
Underwriters Laboratories. An independent, nonprofit organization that publishes
standards for public safety. These standards are generally recognized by inspection
authorities in the USA.

GL-10 • Glossary of Terms Innovation Series MV-GP Type H Drives


VFD
Variable Frequency Drive.

VME controller
A form of the Innovation SeriesTM controller that is hosted in a Versa Module
Eurocard (VME) rack.

Innovation Series MV-GP Type H Drives Glossary of Terms • GL-11


blower transformer cabinet 5-4
breakers 1-12
BTU per hour losses C-1, C-2, C-3
BTU/hr losses C-3
burn-in test D-3

Index burn-in test menu D-3


Burn-In Test Menu D-3
bus LED 6-4
bypass contactor cabinet 1-4, 1-5
bypass SCR driver board 2-14

C
cabinet 1-5, 1-11, 1-12, 6-4
600 hp and below 1-5
clearances 1-6
2 line-up 1-4
cabinet louvers 5-3
286 PC D-1
cable connections 6-4
cables D-2
3 capacitor bank 2-3
Capacitors 2-2
3-phase diode rectifier 2-3
carrier signals 2-5
3-phase input D-2
carrier waves 2-9
3-phase output D-2
CB1 D-2
3-phase secondary connections 1-9
Cell 1-5, 1-9
cell A1 2-5
4 cell boards
460 VAC D-2 control power 2-14
480 VAC D-1 cell cabinet 1-4, D-1, D-2, D-3
Cell Cabinet 1-5, 5-4, D-1, D-2
cell control board 1-9
5 fiber-optic connection 6-4
5 KV class isolation 2-3 switch mode power supply 2-14
Cell Control Board 1-10
cell current C-3
A cell currents D-2
acoustic noise 2-2 cell fault condition 2-14
air duct cover 1-6 cell heat sinks 5-4
air filters 5-4 cell optical communications port D-2
air flow 5-4 cell phase sequence 6-4
altitude 2-18 cell section 1-4
ambient temperature 2-18 cell size 1-9
ammeter D-3 cell sizes 0 and 00 1-5
Arrow keys 4-3, 4-8, 4-9, 4-11, 4-12, 4-13, 4-14, 4-16 cell specifications C-1, C-2, C-3
cell test D-1, D-3
cells
B combining to achieve medium voltage levels 2-2
bar graph 4-3, 4-7 commands from controller 2-3
belts 5-4 communications 2-14
blower D-3 comparison to a static power converter 2-3
Blower 1-5 comparison to standard PWM drives 2-2
blower cabinet 1-4 fiber-optic cables 2-3
blower motor 5-4 floating neutral 2-2
blower power 1-11 input current specifications C-1, C-2, C-3
blower section 1-4 output current specifications C-1, C-2, C-3

GEH-6131 MV-GP Type H Drives Index • I-1


power supplied to 2-3 Drive Health 4-3, 4-4, 4-5, 4-6
powering 2-2 duct cover 1-6
removal and cleaning 5-4 duplex fiber-optic cables 2-9
resident bypass SCR driver boards 2-14 dust contamination 2-18
series connection 2-2 DVM D-1
sizes C-1, C-2, C-3, D-2
used to drive a motor phase 2-2 E
cells in series, number of 1-9
Centronics port D-1 efficiency C-3
circuit breakers 1-12 EGA capability D-1
clamp on ammeter D-1 electrical components 2-11
clamp-on ammeters D-2 electrical connections, tightness 5-4
clearance 1-6 electrically alive 5-1, 6-1
communication channels 2-9 electronic power conversion process 2-2
communication circuits 2-9 enclosure 2-18
communications port D-2 enclosures
computer D-1, D-2 cleaning and maintaining 5-4
control boards 1-5, 1-9 Enter 4-8, 4-9, 4-11, 4-12, 4-13, 4-16, 4-17, D-3
control breaker (CB1) D-2 equipment damage 1-12
control cabinet 1-4, 2-14 errors
Control Cabinet 1-9 link faults 2-9
Control Cards Escape 4-7, 4-8, 4-9, 4-11, 4-12, 4-13, 4-17
IS200ATBA Application I/O TB 2-16 exposed connections 1-11
IS200BAIA Basic I/O 2-16
IS200BICR Bridge Interface 2-9, 2-16, 2-17 F
IS200BPIR Bridge Interface 2-9, 2-16, 2-17
IS200CABP Control Rack Backplane 2-9, 2-16, 2-17 fan D-3
IS200CTBC Drive I/O TB 2-16 fan “tub” assembly 1-6
IS200DSPX Motor Control 2-9, 2-16, 4-14 fan servicing
IS200HFPR Control power supply 2-16 vertical clearance 1-6
IS200RAPA Rack Power Supply 2-16 fault condition 2-14
control circuits 2-9 faults D-3
control power 2-14 Faults
control section 1-4, 1-10 Reverse rotation 4-6
Control Section 1-9 Faults History 4-10, 4-17
cooling D-1, D-3 Faults List 4-9, 4-10
cooling blowers 1-5 fiber-optic 6-4
cooling cell heat sink D-1 fiber-optic cable D-2
cooling requirements C-1, C-2, C-3 fiber-optic cables 1-5, 2-3, 2-9
cooling system 5-4 5 Megabaud communication 2-9
notebook paper test 5-3 fiber-optic communications link 1-10
proper opertion of 5-3 Fiber-Optic Hub Board 2-9
cooling to the drive 1-11 fiber-optic link 1-9
crystal oscillator 2-9 fiber-optic links 2-14
Customer Service Center D-3 filters 5-4
firmware 4-14
Firmware 4-1, 4-14, 4-17
D flammable material 1-11
DC capacitor bank 2-3 floating neutral 2-2, 2-5
DDI 4-1 fork truck tines 1-11
detent lock 6-4 fork trucks 1-11
Diagnostic Display D-3 frequency 2-5, 2-6
diagnostics 2-9 full load 2-8
digital registers 2-9 full rated current D-2
dimensions C-1, C-2, C-3 full voltage bypass operation 1-5
disconnect switch 1-5 full-load operation 2-7

I-2 • Index GEH-6131 MV-GP Type H Drives


Functions input power cabinet 1-4, 1-5
Cell Faults D-3 input power factor 2-18
Intelligent Part Number (IPN) A-5 input switch D-2
Local Speed Reference 4-4 input switch cabinet D-2
fuse block 6-4 input terminals 1-5
fuses 1-5 input transformer 2-7
input voltage 2-7, 2-8
G tolerance 2-18
input/output options 1-5
gas contamination 2-18 input/output section 1-4
gate driver board 2-14 Inputs
Go and No Go features D-2 Digital 4-8
install 5-1, 6-1
H installation D-1
integral isolation transformer 2-2
handling 1-5 secondaries, number of 2-2
Hardware Information 4-1, 4-14, 4-17 interlock key D-2
harmonic cancellation 2-8 isolated 1-9, 5-1, 6-2
harmonic currents isolation transformer 2-2
cenceling 2-3
harmonic distortion 2-2
Harmonics 2-2, 2-18
J
H-bridge of IGBTs 2-3 Jog 4-4, 4-6, 4-17
Heartbeat 4-6
heat dissipation 5-4
K
heat sinks 1-11
high voltage cells 1-9 keypad 2-2, 2-16, 4-1, 4-2, 4-4, 4-6, 4-7, 4-8, 4-9, 4-10,
high voltage sign 1-12 4-13, 4-14, 4-15, 4-16, 4-17
horizontal cell voltages 1-5
hp range 2-18 L
HP ranges C-1, C-2, C-3
Hub Board 2-9 LED 6-4
digital registers 2-9 LEDs D-3
multiplexing scheme 2-9 length C-3
humidity 2-18 lethal voltages 1-11
lifting bolts 1-5
lifting tubes 1-5, 1-11
I
line-to-neutral VAC maximums 2-3
IBM compatible computer D-1 line-to-neutral voltage levels 2-4
IGBT gate driver board 2-14 link fault 2-9
IGBT power switches 2-14 load reactor D-1, D-2, D-3
IGBTs 2-3 load reactor part numbers D-2
incoming message 2-9 load reactors D-2
individual output cells 1-9 lock-out/tag-out procedures
induction motors following 6-1
derating 2-2 losses C-1, C-2, C-3
heating 2-2
thermal limitations 2-2 M
initiate a transmission 2-9
input circuit breaker 1-12 main menu D-2, D-3
input connections 6-4 main power 1-11
input current 2-8, C-3 maintain 5-1, 6-1
input current ratings 1-9 master control boards 2-14
input current specifications C-1, C-2, C-3 master link board D-2
input phase shifting transformer 1-5 master link boards 2-14
input power 1-5, 6-4 Master Link Boards 2-9

GEH-6131 MV-GP Type H Drives Index • I-3


maximum cell current C-3 output/control cabinet 1-4
maximum output 2-3 Output/Control Cabinet 1-5
mechanical resonances 2-2 overheat 1-11
medium voltage input switch D-2 overload capability 2-18
medium-voltage power D-2
menu 4-2, 4-3, 4-7, 4-9, 4-12, D-2, D-3 P
Menu 4-3, 4-4, 4-5, 4-6, 4-7, 4-8, 4-9, 4-11, 4-12, 4-13,
4-14, 4-16, 4-17, D-2, D-3 parallel printer port D-2
metal mesh filters 5-4 Parameters
Meter 4-7, 4-8, D-5 Comparing 4-12
meter options 1-5 IPN bridge cell type A-5
meters 1-12, 5-1, 6-2 IPN cell count A-5
microprocessor 2-9 IPN system voltage A-5
modular construction 2-2 IPN Xfmr Input volts A-5
motherboard 2-9 Numeric 4-3, 4-10, 4-11
motor insulation 2-2 Option 4-3, 4-10, 4-11
Motor nameplate C-3 Restoring 4-12
motor neutral 2-5, 2-7 Saving 4-11
motor voltage and current waveforms 2-7 parity 2-9
multiplexing scheme 2-9 Password 4-15, 4-16
PCT D-2
permanent positioning 1-11
N
personal injury 1-12
Navigation 4-2, 4-3, 4-4, 4-9, 4-17 phase angle 2-3
NEMA 1 specifications 2-18 phase displacement 2-9
neutral 2-4, 2-5, 2-6, 2-7 phase shifting transformer 1-5, 1-10
non-operating fault condition 2-14 phase shifts of carriers 2-5
notebook paper test 5-3 plenum/duct connections 1-6
portable cell tester D-2
O portable Harmony cell tester D-1
pot D-3
on-site cell testing D-1 power bridge test D-6
operate 5-1, 6-1 power cell 2-9
option cabinet 1-4, 1-5 power cells 2-4, 2-9
oscilloscopes 5-1, 6-2 combining 2-2
output see also cells 2-3
maximums based on number of cells 2-3 series connection 2-2
output cell 1-10, 2-14 used to drive a motor phase 2-2
output cells 1-5, 1-9, 1-10, 2-11 power circuit
output current C-3, D-3 topology 2-2
output current ratings 1-9 power conversion process 2-2
output current specifications C-1, C-2, C-3 power factor 2-2, 2-8, C-3
output harmonics 2-2 at full load 2-3
output link 6-4 power factor capacitors 2-2
output link connections 1-5 power filters 2-2
output operating voltage 2-11 power switches 2-14
output operating voltages 1-9 primary and secondary transformer connections 5-4
output phase 1-5, 2-3 primary currents 2-3
small difference in phase angle 2-3 printed circuit (PC) boards 1-10
output phase voltage 1-5 printed circuit boards 1-12
output torque 2-18 Privilege 4-15, 4-16, 4-17
output voltage level 2-14 pulsations 2-2
output voltages 2-5, 2-6, D-2 PWM control signals for the power cells 2-9
output voltages of cells
3 possible 2-4
output waveform 2-5

I-4 • Index GEH-6131 MV-GP Type H Drives


Q operational range 1-9
switchgear D-2
Q1 2-4, 2-5
Q1 - Q4 D-3
Q2 2-4, 2-5 T
Q3 2-4, 2-5 T1 2-4, D-2, D-3
Q4 2-4, 2-5 T1 and T2 connections
qualified individuals 5-1, 6-1 disconnecting 6-4
T2 2-4, D-2, D-3
R tap board 1-5
termination designations 6-4
rated current D-2, D-3 THD 2-7, 2-8
rated HP C-3 thermal limitations of the motor 2-2
rated voltage D-1 thermally hot 5-1, 6-1
reference signal 2-5 thermally hot components 1-11
reference signals 2-9 three possible output voltages 2-4
removal of input power 6-4 timing signals 2-9
remove or install a cell 6-4 Tools 5-2
required CFM for cooling C-1, C-2, C-3 torque pulsations 2-2
reset D-3 total harmonic distortion 2-7
resonance 2-2 transformer 1-5, 1-9, 1-10, 6-4, C-3
rubber safety shoes 5-1, 6-1 transformer cabinet 1-4, 5-4, D-2
Transformer Cabinet 1-5, 1-11, 5-4, D-2
S transformer secondaries 2-3
Transformer/Blower Cabinet 1-5
safety 1-11 transistors are firing D-3
safety glasses 5-1, 6-1 transmitted message 2-9
safety precautions 1-12 data bits 2-9
safety shields 1-12 start bits 2-9
secondary and primary transformer connections 5-4 stop bits 2-9
secondary tap board 1-5 troubleshoot 5-1, 6-1
secondary winding, isolated 2-2
troubleshooting
secondary windings 1-5 variac D-5
serial communication 2-9
series links D-2
seven basic cell sizes 1-9 U
shields 1-12 unloading 1-11
short-circuit 5-7
sine wave 2-7
single-phase H-bridge of IGBTs 2-3 V
sinusoidal 2-4 Vacuum 5-2, 5-7
sinusoidal primary currents 2-3 variable speed operation 2-2
sizes of cells C-1, C-2, C-3 Variables
slaves 2-9 Motor current 4-8
slide rails 6-4 Motor power 4-8
solid-state variac D-6 Motor voltage 4-8
spare cells 2-9 Run command 4-4
specifications Speed feedback 4-8
variac D-7 variac D-2, D-3, D-6
speed range 2-18 specifications D-7
stage number 2-9 variacs D-2
static electricity 5-4, 6-2 ventilation losses C-1, C-2, C-3
Status screen 4-5 vertical clearance 1-6
Status Screen 4-1, 4-3, 4-4, 4-7, 4-8 Vibration 5-4
surge suppression 1-5 voltmeter D-2
switch mode power supply 1-9, 2-14

GEH-6131 MV-GP Type H Drives Index • I-5


W
warnings 1-12
weight of lineup C-3
wye connected power cells 2-2
wye-connected primary 2-7

I-6 • Index GEH-6131 MV-GP Type H Drives



*(,QGXVWULDO6\VWHPV
*HQHUDO(OHFWULF&RPSDQ\
 5RDQRNH%OYG
ZZZJHFRP 6DOHP9$86$

S-ar putea să vă placă și