TEST REPORT

OF MEDIUM VOLTAGE (11kV) SWITCHGEAR

Customer: MAZYOOD GIGA DHA LAHORE EMERALD LIMITED,LAHORE.


Equipment Description 11KV HT Panel (Consumer type) As per WAPDA Specification P-44:96
Panel Serial Nos. 1303631/01
Date of Test 05-July-2019

Tests Verifications performed:

Observation/
Requirements as per Measurements
Serial No. Parameters
P-44:96 during routine
testing
01
Visual Inspection
a) Paint thickness 0.08mm 0.116mm
b) Sheet thickness 2.3mm 2.3mm
c) Dimensions (Height mm, Width mm, depth mm ) (2200, 1800,900) mm (2200,1801,901)
As per approved drawing - mm
d) Insulation barrier sheet 2(100x10)mm 2(100×10)mm
e) Main Bus Bar Size - -
f) Dropper (60×5)mm (60×5)mm
02 Electrical & mechanical operation Tests - OK
03 Ampere Meter FRER (Italy) OK
04 Power Factor Meter FRER (Italy) OK
05 Volt Meter FRER (Italy) OK
06 Energy Meter Blue Star (China) OK
07 Indication Lights GGT (Italy) OK
08 Push Buttons GGT (Italy) OK
09 Over Current & Earth fault relay SEL-551C (0551C0EX533X) SEL (USA) OK
10 DC Supervision Relay (TS 101-110) E-LABS (Pak) OK
11 Sleeve Raychem (Germany) OK
12 Test Block RMS (Australia) OK
13 Post Insulator GG (Malaysia) OK
14 Terminal Block Cabur (Italy) OK
15 MCB’s Schneider (Europe) OK
16 Verification of correct wiring. - OK

Asif Ali Siddiqui Engr. Sumbul Saleem Engr. Rabia Noreen Gul
Sr. Engineer Electrical Asst. Manager (S&R Design) Asst. Manager (S&R Design)
I & QC S/G PEL NTDC Wapda House, Lahore NTDC Wapda House, Lahore
TEST REPORT
OF MEDIUM VOLTAGE (11kV) SWITCHGEAR

Customer: MAZYOOD GIGA DHA LAHORE EMERALD LIMITED,LAHORE.


Equipment Description 11KV HT Panel (Consumer type) As per WAPDA Specification P-44:96
Panel Serial Nos. 1303631/01
Date of Test 05-July-2019

01. (b) POWER FREQUENCY VOLTAGE TEST (MAIN CIRCUIT): As per clause 22.3.1 (i)

R-Phase Y-Phase B-Phase


Voltage Applied: 36kV for one Y.B and Frame R.B and Frame R.Y. and Frame
minute with VCB in Close position Grounded Grounded Grounded
Withstood Withstood Withstood

01. (c) INSULATION TEST OF VCB VACCUM TUBE:

Applied Voltage Results


36kV on Main Bus Bars for One Minute with VCB in Open Position.
Withstood
All Outgoing Terminals are Connected to Ground.

Note: The offered panel qualified the test.

02. POWER FREQUENCY WITHSTAND VOLTAGE TEST (Aux. CIRCUIT): As per clause 22.3.1 (ii)

Applied Voltage Results


2KV for one minute to Auxiliary Circuit Withstood

Circuit and terminals used for performing the test


Applied 2KV on Aux Circuit (Wiring Includes PT.s & CT.S) at Outer Terminal and Short Links Terminal X3 (13 & 5),
X1 (14 & 5)
…………………………………………………………………………………………………………………………….
Note: The offered panel qualified the test.

03. RESISTANCE OF MAIN CIRCUIT As per clause 22.3.1 (iii)

Resistance (µ Ω) at 32 ºC.
Serial No. 1303631/01
R Y B
Circuit With CTs
1- 222 209 200
Circuit Without CTs.
2- 125 114 100

Note: The offered panel qualified the test.

Asif Ali Siddiqui Engr. Sumbul Saleem Engr. Rabia Noreen Gul
Sr. Engineer Electrical Asst. Manager (S&R Design) Asst. Manager (S&R Design)
I & QC S/G PEL NTDC Wapda House, Lahore NTDC Wapda House, Lahore
TEST
OF MEDIUM REPORT
VOLTAGE (11kV) SWITCHGEAR

MAZYOOD GIGA DHA LAHORE EMERALD


Customer:
LIMITED,LAHORE.
Equipment 11KV HT Panel (Consumer type) As per WAPDA Specification P-
Description 44:96
Panel Serial Nos. 1303631/01
Date of Test 05-July-2019

04. VERFICATION OF INTERCHANGINEABILITY OF COMPONENT & MECH. OPERATION TEST:


Rack In/ Rack Out Mechanical Interlocking Interchangeability of Trolleys

OK OK -

Note: The offered panel qualified the test.

05. TRIP CIRCUIT DC SUPERVISION RELAY:

Relay Type/Make Relay Sr. No. Drop Out Drop In Results


(V) (V)
The Relay works satisfactorily by
TS101/110 E-Lab. 680719 82 84
indicating the healthy status.

Note: The offered panel qualified the test.

06. Relay Description: O/C & E/F relay type SEL 551C (Curve: Standard Inverse C1)

CT Set at 200/5A

Over Current & Earth


Relay Elements Pickup Setting Injected I at which trip
Fault Relay
50% (100A) 113A (R-Y)
51 P1
104A (Y-B)
Time Delay Elements of
Relay 46A (Y-G)
51 G1 20% (40A) 45A ( B-G)
46A (R-G)
311A (R-Y)
50 P1 100% (200A)
210A (Y-B)

50 G1 80% (160A) 162A (R-G)


Instantaneous
Element of Relay 113A (R-Y)
50 P1 (Over Current) 50% (100A)
116A (Y-B)

50 G1 (Over Current) 20% (40A) 46A (R-G)

Note: The offered panel qualified the test.

07. Primary injection of current 200A applied to trip the VCB through relay to verify the CT circuit. (OK)

Asif Ali Siddiqui Engr. Sumbul Saleem Engr. Rabia Noreen Gul
Sr. Engineer Electrical Asst. Manager (S&R Design) Asst. Manager (S&R Design)
I & QC S/G PEL NTDC Wapda House, Lahore NTDC Wapda House, Lahore