COMPUTATION IN ELECTRICAL PLAN

(FINAL PROJECT)

SIZES OF WIRINGS
FOR 1: AIRCON CIRCUIT BREAKER
(BEDROOM 1) FOR 1: AIRCON CIRCUIT BREAKER
970 WATTS (BEDROOM 1)
970 WATTS/220 V= 4.41 A AT 30A
USE 10A CKT BREAKER FROM TABLE 4.2
 THE USE OF 6A FOR AN A/C IS GOOD IF ONLY THE THHN 90 C
WATTAGE IS CLEARLY SPECIFIED
AT 30A 3.50 mm2 (2 mm)
 THE LARGEST HP FOR A WINDOW TYPE AC IS 3HP
 3HP * 746= 2238 WATTS
 2238 WATTS/220 VOLTS = 10.17 A
FROM NEC, A SINGLE, MOTOR EQUIPMENT OR APPLIANCES SHALL FOR 2: AIRCON CIRCUIT BREAKER
BE INCREASED BY 250% IN RATING (LIVING ROOM)
10.17A (2.5) = 25.43 A AT 30A
*USE 30A CKT BKR FROM TABLE 4.2
THHN 90 C
FOR 2: AIRCON CIRCUIT BREAKER AT 30A 3.50 mm2 (2 mm)
(LIVING ROOM)
970 WATTS
970 WATTS/220 V= 4.41 A FOR 3: KITCHEN AND DINING CO BREKER
USE 10A CKT BREAKER AT 6A
 THE USE OF 6A FOR AN A/C IS GOOD IF ONLY THE FROM TABLE 4.2
WATTAGE IS CLEARLY SPECIFIED THHN 90 C
 THE LARGEST HP FOR A WINDOW TYPE AC IS 3HP AT 25A 2 mm2 (1.6 mm)
 3HP * 746= 2238 WATTS
 2238 WATTS/220 VOLTS = 10.17 A
FROM NEC, A SINGLE, MOTOR EQUIPMENT OR APPLIANCES SHALL FOR 4: LIVING ROOM CO BREAKER CO BREAKER
BE INCREASED BY 250% IN RATING AT 6A
10.17A (2.5) =25.43 A
FROM TABLE 4.2
*USE 30A CKT BKR
THHN 90 C
FOR 3: KITCHEN AND DINING CO BREAKER (2 GANG OUTLET) AT 25A 2 mm2 (1.6 mm)
Since there is 2-2gang outlet
4*180 WATTS= 720 WATTS
720 WATTS/.8 = 900 WATTS FOR 5: LIVING ROOM CO BREAKER CO BREAKER
900 WATTS/220 V= 4.10 A AT 10A
*USE 6A CKT BREAKER FROM TABLE 4.2
THHN 90 C
FOR 4: LIVING ROOM CO BREAKER (2 GANG OUTLET) AT 25A 2 mm2 (1.6 mm)
Since there is 2-2gang convenience outlet
4*180 WATTS= 720 WATTS
720 WATTS/.8 = 900 WATTS FOR 6: REFRIGIRATOR
900 WATTS/220 V= 4.09 A AT 10A
*USE 6A CKT BREAKER FROM TABLE 4.2
THHN 90 C
FOR 5: FOR 2ND FLOOR CO BREAKER (2 GANG OUTLET) AT 25A 2 mm2 (1.6 mm)
Since there is 4-2gang outlet
8*180 WATTS= 1440 WATTS
1440 WATTS/.8 = 1800 WATTS FOR 7: LIVING ROOM LIGHTS
1800 WATTS/220 V= 6.14 A AT 6A
*USE 10A CKT BREAKER
FROM TABLE 4.2
THHN 90 C
FOR 6: REFRIGERATOR
1000 WATTS AT 25A 2 mm2 (1.6 mm)
1000 WATTS/.8 = 1250 WATTS
1250 WATTS/230 V= 5.43 A
*USE 10A CKT BREAKER FOR 8: LAUNDRY, KITCHEN AND B&T LIGHTS
AT 6A
FOR 7: LIVING ROOM LIGHTS FROM TABLE 4.2
Since there is 6 light fixtures THHN 90 C
6*100 WATTS= 600 WATTS AT 25A 2 mm2 (1.6 mm)
600 WATTS/.8 = 750 WATTS
750 WATTS/220 V= 3.41 A
*USE 6A CKT BREAKER FOR 9: 2ND FLOOR LIGHTS
AT 6A
FOR 8: LAUNDRY, KITCHEN AND B&T LIGHTS FROM TABLE 4.2
Since there is 3 light fixtures THHN 90 C
3*100 WATTS= 300 WATTS AT 25A 2 mm2 (1.6 mm)
300 WATTS/.8 = 375 WATTS
375 WATTS/220 V= 1.70 A SIZE OF CONDUIT (ELECTRICAL PVC)
*USE 6A CKT BREAKER
 FOR THE 3.5 mm^2 WIRE
FOR 9: 2ND FLOOR LIGHTS FROM TABLE 4-1A
Since there is 8 light fixtures 15 mm  PVC PIPE  MAX OF 7- 3.5 mm2 TTHN WIRE
8*100 WATTS = 800 WATTS  MAX OF 9- 2.0 mm2 TTHN WIRE
800 WATTS/.8 = 1000 WATTS 20 mm  PVC PIPE  MAX OF 15- 2 mm2 TTHN WIRE
1000 WATTS/220 V = 4.54 A  MAX OF 9- 3.5 mm2 TTHN WIRE
*USE 6A CKT BREAKER *ONLY 2 WIRES ARE IN A CONDUIT FOR ORDINARY CONST.
25 mm  PVC PIPE  MAX OF 25- 2 mm2 TTHN WIRE
 MAX OF 19- 3.5 mm2 TTHN WIRE
 MAX OF 15- 5.5 mm2 TTHN WIRE