Sunteți pe pagina 1din 5

Settings Guide

Type MOPN

Introduction Typical motor parameters

The MOPN 01, 02 is a The following motor parameters will


comprehensive microprocessor based be used to help illustrate how to
motor protection relay. It is designed determine the most common MOPN
for use as main protection for settings.
asynchronous medium voltage motors Voltage 11kV
or large synchronous low voltage
Full load current 239A
motors.
Starting current 470%
In order to perform this task the
MOPN has a number of protective Starting time 10s
features for which careful Heating time constant 20m
consideration to the setting of each
Cooling time constant 100m
must be given. This setting guide and
application example are intended to Hot locked rotor
be used in conjunction with withstand time 20s
publications R6121 and R8121 to Cold locked rotor
assist in the selection of the most withstand time 30s
common settings on the MOPN. CT Ratio 300/1
However, it must be remembered that
motor protection relay settings are
application specific and therefore can
vary considerably from one motor to
the next depending on the system
conditions and application in
question. With this in mind, we must
stress that the following settings are
only intended to be used as a guide.
If further assistance is required, please
contact GEC ALSTHOM T&D
Protection & Control Limited.

2
Useful information Heating and cooling time constants cyclically operated. If this is the case,
HS refers to disable in the menu (Te1,Te2 & Tr) having a cooling time constant setting
system. The relay heating and cooling time less than the motor cooling time
constants are set in accordance with constant would result in a premature
the motor thermal heating and cooling successive start and possible damage
Iθ Thermal setting
time constants. The relay heating time to the motor.
The I θ setting chosen will depend on
constant (Te1) should be set equal to
the type of motor being protected;
the motor heating thermal time IL Threshold limit
nowadays most machines are termed
constant. However, it is good practice In certain applications the relay
CMR (continuous maximum rating)
to set Te1 slightly less than the motor thermal curve may cut the starting
motors. These motors are designed to
heating thermal time constant to allow characteristic thus resulting in a
carry the name plate value or full load
for relay tolerances. Te2 is thermal trip during starting. Instead of
current continuously. A CMR motor is
automatically applied above 2 Iθ and altering the thermal time constant, IL
usually run at some value less than its
is used to modify the relay thermal can be used to increase the operating
CMR and set to trip at its CMR. If the
curve under certain applications, for time of the thermal characteristic
machine is not a CMR motor then the
example when a more sensitive setting during starting. After the start time has
I θ setting will need to take into
is required under starting conditions. elapsed, the characteristic will resume
account the amount of overload which
For most applications (DOL starting) its original path.
can be tolerated without thermal
Te2 should be set equal to Te1,
damage resulting. To determine if this setting is required
resulting in one continuous thermal
For this application we have assumed plot the thermal and starting
curve. For the motor parameters
that the machine is a CMR motor and characteristics to see if a conflict
given:
therefore Iθ setting is calculated as: exists. For this particular application
Set Te1 = 20m or 19m to allow for example this feature is not required
Iθ = ICMR x (1/CT ratio) tolerances and has therefore been disabled:
where I CMR = Continuous Motor Set Te2 = Te1 Set IL = HS
Rating
In certain applications the thermal
Therefore: time constants are unknown but a Starting inhibit threshold E1
1 thermal withstand curve is given.
Iθ = 293 x 130 E1 is expressed as a percentage of
For this application a heating time the thermal state of the motor.
= 0.976In constant must be chosen which will A contact associated with this setting
Therefore: give a thermal curve that fits just is designed to open when the thermal
below the cold thermal withstand state of the machine reaches the E1
set I θ = 0.98In
curve of the motor. For applications setting and close again when the
where neither the thermal time thermal state drops below the E1
constants or the thermal withstand setting. If this contact is wired into the
curve are available, settings Te1 and starting circuitry it can be used to
Te2 should be chosen such that the inhibit a hot restart until the motor has
resulting thermal curve when plotted, cooled to the E1 setting. There is no
on time current graph, lies above the definite setting for E1 since it is based
start time but less than the stall on the motors capability to withstand
withstand time. a hot restart. It is usually set to the
Tr is the cooling time constant. This is minimum, which is 40%, and
set as a multiple of Te1 and should be increased if desired.
set to the nearest value above the Set E1 = 40%
motor cooling time constant.
With Te1 = 20m:
Overheat alarm threshold E2
Set Tr to 5 x Te1 = 100m.
E2 is expressed as a percentage of
It is not uncommon for motors to have the thermal state of the machine and
a considerably long cooling time is used to give an alarm when the
constant. If this is the case then it may thermal state reaches a predetermined
not be possible to achieve the desired value, say 90%.
setting on the MOPN and therefore Tr
Set E2 = 90%
must be set to maximum. However, it
must now be remembered that during
cooling the thermal replica in the
relay does not follow the cooling
curve of the motor. This is not usually
a problem unless the motor is being

3
Isc Short circuit setting Earthfault time delay TØ In order for these protective functions
The short circuit protection is designed A time delay of 0.3s shall be set, this to be used, a start condition must be
to provide very fast operation for has two function: detected by the relay. This condition is
heavy faults at the motor terminals. obtained by the current reaching
To provide stability under motor
It is usually set to 1.2 X Maximum 0.9Is and a dc input applied to
starting conditions where asymmetric
starting current. terminal 42 on the relay within a
CT saturation may occur.
200ms time window. For further
Set to 1.2 x 4.7 x 239A = 1348A To allow the protection to be used information refer to publication
1 where the motor is controlled by fused R6121.
Isc = 1348 x 130 = 4.5In
contactors.
In this application start/stall protection
Set to zero if stabilising resistor is should be used since the thermal
Earth fault current setting I∅
used. withstand curve of the machine is
Set to give an earth fault sensitivity greater than the stall withstand time.
within 10% to 25% of the minimum I2 Phase unbalance protection The following settings are
earth fault level, or within 10% to recommended:
Small values of negative phase
60% of the motor continuous rated
sequence current due to an unbalance Set Is < motor start up current
current, whichever is the lowest.
on the system will be accounted for in Set Td – 1s to 2s above the motor
For earth fault settings <20% of the the thermal curve calculation, resulting start up time
motor continuous rated current, a core in an accelerated thermal trip.
balance CT should be utilised. Set Tb – If the motor stall withstand
However, for large values of negative
time > motor start time, set
Where residually connected CTs are sequence current resulting for example
Tb1 < motor stall withstand
used, spill current may flow in the from loss of one phase during starting
time. If the stall withstand
residual circuit under motor starting the I2 setting is used.
time < motor start time, in
conditions. To ensure relay stability Recommended setting I2 < Ist/6 order to provide adequate
for these conditions, a stabilising
where Ist = starting current. stall and start protection a
resistor is required to be connected in
This setting is adopted since loss of scheme consisting of a timer
series with the earth fault element.
a phase during starting will cause relay plus a speed sensing
The value of the stabilising resistor switch connected in series
I2 = 0.5 x Ist. Setting the element to
can be calculated using the following will be required. For the
a third of this value ensures correct
formula: latter application, if the
operation.
Rstab = motor fails to start, the speed
I2 < (4.7 x 239)/6 = 187A
Ist Relay Burden at In switch will not operate,
R + N.R1 + ---- (a) I2 < 187/300 = 0.62In thereby allowing the timer
Io ct In2
Set I2 = 0.6In relay to time out and operate
where I o = earth fault setting in amps the circuit breaker (scheme
Ist = motor starting current referred to Excessive start time and rotor stalling diagram is available upon
CT secondary request). Typically the time
If the thermal curve is greater than the delay relay will be set to 1s
Rct = dc resistance of CT secondary start time and less than the stall for a starting time of 5s.
N = 1 for 4 wire CT connection (star withstand time then stall protection
point at CTs) 2 for 6 wire CT can be provided by the thermal curve. For this application:
connection (both star points If this is not the case then additional Set Is = 3 x Iθ = 717A
formed at relay panel). stall protection will be required. Set Td = 12s
R1 = resistance of single lead from The MOPN utilises internal Set Tb = 6s
relay to CT overcurrent detectors and timers to
For further information refer to the provide excessive start time protection
MOPN Service Manual R8121. (stalling under starting) and rotor stall
protection. When the machine is run
up, the relay will detect a start
condition and trip if the current is still
above the Is setting after a time Td.
With the machine running, the relay
will detect a stall condition if the
current increases above the Is setting
and is not accompanied by a
re-acceleration input (positive
auxiliary supply on terminal 44), the
relay will then trip after a time Tb1.

4
Minimum current IMIN and timer Plotting the relay characteristic
TMIN When the various settings have been
This function allows a trip when the calculated it is good practice to plot
current being drawn by the motor falls out the thermal curves and start/stall
below a selected threshold. It can be information in order to see if there is
used, for example, to protect electric any conflict.
pumps against becoming unprimed or It is possible to plot the cold thermal
to stop a motor in the event of a curve in one of two ways; firstly using
failure in the mechanical transmission. the following equation and secondly
The trip occurs: using the thermal curves at the back of
1. At the end of the normal start-up the service manual:
time Td, if the current remains Cold curve operating time
below the selected setting. (K2)
2. After an adjustable delay, TMIN, = Te1 Ln
(K2 – 1)
if the current drops below the
Where K = Ie/Iθ
preset value once Td has elapsed.
Ie = Equivalent current flowing into
Number of starts limitation the relay = I1 + 3I2
It is possible to limit the frequency of I1 = Positive sequence current
motor restarts. This is done by I2 = Negative sequence current
selecting the maximum number of
K is therefore a multiple of setting
starts using the ST.Nb.(Tref) setting
and if a CMR machine is used
over a specified period given by the
Iθ = 100% full load current and
Tref TIME Setting. Exceeding this
therefore K is a multiple of full load
number during Tref will cause the
current. For example in this
relay to operate the same output that
application the starting current
is used to inhibit the motor when the
= 4.7 x full load current, hence at
overload percentage E1 is exceeded.
start K=4.7.
This contact will then remain open for
a time given by FORBID TIME. This would result in the following
operating time at start:
It is important to note that there is no
restriction on the time between starts Cold curve operating time
during the time period Tref TIME.
(4.72)
= 20 x 60 x Ln = 56s
(4.72 – 1)
External trip timer TBV
It is possible to trip the relay by Using the thermal curves, proceed
applying a signal from an external along the x axis to K = 4.7 then
under voltage or under frequency project up to the 0% thermal state
relay. An adjustable time delay, TBV, curve and read off the corresponding
is provided within the relay. During t/Te1 value, which in this case is:
this time the relay allows the motor to t/Te1 = 0.045, therefore the
draw starting current ie. re-accelerate operating time in seconds
without tripping. For a detailed = 0.047 x 60 x 20 = 56.4s
explanation on this feature refer to It is recommended that at least three
publication R6121. points are calculated in order to get a
true representation of the curve.
This curve along with the stall
withstand times and starting
characteristic should be plotted to
verify that no conflict exists (ie. the
thermal curve does not intersect the
starting characteristic).

5
Example setting

1000

Thermal overload Te1

100

Excessive start time

Cold stall

10

Hot stall
Operating time in seconds

Starting chr. Locked rotor Short circuit

0.1

Is

0.01
1 10
K = Ie/Iθ

S-ar putea să vă placă și