Sunteți pe pagina 1din 62

Application guidelines

Inverter scroll compressors


VZH028-035-044
single & manifold
R410A

http://cc.danfoss.com
Application Guidelines Content

VZH028-035-044 - single compressors.............................................................................. 4


VZH035-044 - hybrid manifolding................................................................................... 48

FRCC.PC.034.A3.02 3
Application Guidelines VZH028-035-044 - single compressors

VZH scroll specificities......................................................................................................... 6


Inverter compressors........................................................................................................... 7
Compressor size...........................................................................................................................................................................................7
Frequency converter variants.................................................................................................................................................................7
Compressor and frequency converter combinations....................................................................................................................7

Nomenclature and specifications........................................................................................ 8


Compressor nomenclature......................................................................................................................................................................8
Frequency converter nomenclature.....................................................................................................................................................8
Label.................................................................................................................................................................................................................8
Serial number...............................................................................................................................................................................................8

Technical specifications....................................................................................................... 9
Compressor specifications.......................................................................................................................................................................9
Frequency converter specifications......................................................................................................................................................9
Oil return management............................................................................................................................................................................9
Bearings lubrication...................................................................................................................................................................................9
Capacity Tables.......................................................................................................................................................................................... 10

Dimensions......................................................................................................................... 14
VZH028-035-044G/J single version.................................................................................................................................................... 14
VZH028-035-044G/J manifold version.............................................................................................................................................. 14
Sight glass/oil level switch.................................................................................................................................................................... 15
Schrader....................................................................................................................................................................................................... 15
Oil equalization connection................................................................................................................................................................. 15
Suction & discharge connections....................................................................................................................................................... 15
Frequency converter dimensions....................................................................................................................................................... 15
CDS803 frequency converter............................................................................................................................................................... 16

Electrical data, connections and wiring............................................................................ 17


Supply voltage........................................................................................................................................................................................... 17
Compressor electrical specifications................................................................................................................................................. 17
Terminal cover mounting...................................................................................................................................................................... 17
Terminal cover removal.......................................................................................................................................................................... 17
Fuses.............................................................................................................................................................................................................. 18
Wire sizes..................................................................................................................................................................................................... 19
Wiring & EMC protection....................................................................................................................................................................... 19
EMC correct installation of an IP20 frequency drive CDS803................................................................................................... 20
Wiring diagram.......................................................................................................................................................................................... 20
Wiring connections.................................................................................................................................................................................. 21
Electrical connections............................................................................................................................................................................. 21
Soft-start control....................................................................................................................................................................................... 22
Phase sequency and reverse rotation protection......................................................................................................................... 22
IP rating........................................................................................................................................................................................................ 22
Motor protection...................................................................................................................................................................................... 22
Anti-reverse protection.......................................................................................................................................................................... 22
Temperature protection......................................................................................................................................................................... 23
Voltage imbalance................................................................................................................................................................................... 23

Approvals and certificates................................................................................................. 24


Approvals and certificates..................................................................................................................................................................... 24
Pressure equipment directive 97/23/EC.......................................................................................................................................... 24
Internal free volume................................................................................................................................................................................ 24

4 FRCC.PC.034.A3.02
Application Guidelines VZH028-035-044 - single compressors

Operating conditions......................................................................................................... 25
Application envelopes............................................................................................................................................................................ 25
Short cycle timer function..................................................................................................................................................................... 25
Discharge gas thermostat..................................................................................................................................................................... 26
Oil return management function (single compressor)............................................................................................................... 27
Oil return management in hybrid manifolding............................................................................................................................. 27
High and low pressure protection..................................................................................................................................................... 28

System design recommendations..................................................................................... 29


Essential piping design considerations............................................................................................................................................ 29
Heat exchangers....................................................................................................................................................................................... 30
Refrigerant charge limits....................................................................................................................................................................... 30
Off-cycle migration.................................................................................................................................................................................. 30
Liquid floodback during operation.................................................................................................................................................... 31

Specific application recommendations............................................................................ 32


Low ambient compressor operations............................................................................................................................................... 32
Brazed plate heat exchangers.............................................................................................................................................................. 33
Reversible heat pump systems............................................................................................................................................................ 33

Sound and vibration management................................................................................... 35


Running sound level............................................................................................................................................................................... 35
Sound generation in a refrigeration or air conditioning system............................................................................................. 35
Compressor sound radiation................................................................................................................................................................ 35
Mechanical vibrations............................................................................................................................................................................. 35
Speed by-pass............................................................................................................................................................................................ 35
Gas pulsation............................................................................................................................................................................................. 35

Installation.......................................................................................................................... 36
Compressor handling............................................................................................................................................................................. 36
Mounting..................................................................................................................................................................................................... 36
Removing connections shipping plugs........................................................................................................................................... 36
System cleanliness................................................................................................................................................................................... 37
Tubing........................................................................................................................................................................................................... 37
Filter driers.................................................................................................................................................................................................. 37
Brazing and soldering............................................................................................................................................................................. 37
Compressor connection......................................................................................................................................................................... 37
High voltage test...................................................................................................................................................................................... 38
Leak detection........................................................................................................................................................................................... 39
Vacuum pump down and moisture removal................................................................................................................................. 39
Refrigerant charging............................................................................................................................................................................... 39
Commissioning......................................................................................................................................................................................... 39
Oil level checking and top-up.............................................................................................................................................................. 40

Trouble shooting................................................................................................................ 41
Ordering information and packaging............................................................................... 44
Kit ordering and shipping..................................................................................................................................................................... 44
Packaging.................................................................................................................................................................................................... 44
Ordering information.............................................................................................................................................................................. 44
VZH converter order information....................................................................................................................................................... 45

Accessories.......................................................................................................................... 46
Valves, adapters, connectors & gaskets for use on suction and discharge connections................................................ 46
Crankcase heaters & thermostats....................................................................................................................................................... 46
Lubricant, acoustic hoods and spare parts..................................................................................................................................... 46
Spare parts frequency converter........................................................................................................................................................ 47

FRCC.PC.034.A3.02 5
Application Guidelines VZH scroll specificities Single compressors

Discharge sensor (dome


sensor) for high discharge
temperature/reverse
rotation/loss of charge
monitoring, sensor is
fitted into top bracket.
Discharge sensor is
optional.

Intermediate discharge
valves for better efficiency Scrolls with optimized
at low pressure-ratio volume ratio lead to better
heat pump application

EMC (Electro-Magnetic
Compatibility) bracket
provided allows for
grounding termination
of shielded wire-harness,
which reduces EMC
emissions between drive
and compressor New distributed IPM
motor lead to higher
power factor

PVE 32 lubricant
Linear control oil pump

6 FRCC.PC.034.A3.02
Application Guidelines Inverter compressors Single compressors

Compressor size Inverter technology offers more flexibility 3. Best Seasonal Efficiency Ratio: Select a
in compressor selection than fixed-speed compressor size which achieves the minimum
compressors. Selection of the right inverter system cooling demand at its minimum speed.
compressor size can be made by different Ensure that the compressor is able to cover the
methods: peak load system cooling capacity. This selection
makes the compressor run for a maximum time at
1. Maximum cooling capacity: Select a part load where the system efficiency is highest.
compressor size which achieves the peak load
system cooling capacity demand at its maximum Performance tables at three speeds can be found
speed. in the following pages. Detailed performances
can be found in datasheets and in selection
2. Nominal cooling capacity: Select a compressor programs.
size which achieves the nominal system cooling
capacity at a rotational speed of 3600 - 4500 rpm
(60-75 rps).

Frequency converter Different frequency converter variants are 3. RFI (Radio Frequency Interference) class H4
variants available according to: 4. Printed Circuit Board (PCB) coated
1. Mains supply voltage
2. IP class (CDS803 drives are available in IP20 or
IP21 (requiring additional kit) housings)

Compressor and When the compressor size and mains voltage Note this compressor is equipped with
frequency converter have been defined in the above selection criteria, a four-pole electrical motor so the applied
combinations the code number tables from the “Ordering frequency from the inverter will be 30 Hz
information and packaging” section provides the for 15 rps (900 rpm) up to 200 Hz for 100 rps
appropriate frequency converter sizes and up (6000 rpm).
to eight corresponding code numbers for each
compressor model. Please refer to the table below
min max
rps 15 100
Compressor speed
rpm 900 6000
Drive output frequency Hz 30 200

FRCC.PC.034.A3.02 7
Application Guidelines Nomenclature and specifications Single compressors

Compressor
nomenclature

V Z H 044 C G A N A
Variable speed Evolution index
Motor protection type
Family N: no internal motor protection
VZH scroll (protection by drive)

Lubricant
PVE 32(FVC32D) lubricant, Equipement version
R410A refrigerant A: brazed connections, single version
B: brazed connections, manifold version
Swept volume Oil sight glass Oil level switch
in cm³/rev Single version Threaded None
Manifold version None Threaded

Design pressure ratio Motor voltage code to CDS803 *


C: IDV and IEER G: 380-480V/3~/50 & 60 Hz
optimized J: 200-240V/3~/50 & 60 Hz
* main supply voltage to frequency converter

Frequency converter
nomenclature

CDS 803 P7K5 T4 E20 H4


Dedicated compressor RFI class
drive for VZH scroll

Serie 803 Enclosure protection


IP rating

output power Main supply voltage


in kW T2: 200-240V/3 ph/50-60 Hz
P6K0/P7K5/P10K T4: 380-480V/3 ph/50-60 Hz

Label

Serial number
A B 25 12345678
8 Digit serial number
Year code

Month code

Plant assembly line code

8 FRCC.PC.034.A3.02
Application Guidelines Technical specifications Single compressors

Compressor Displacement
specifications Swept Oil charge Net weight
Compressor model volume 15 rps 50 rps 60 rps 100 rps (Liters) (kg)
(cm³/rev) (m³/h) (m³/h) (m³/h) (m³/h)
VZH028 27.8 1.5 5.0 6.0 10.0 1.1 26
VZH035 34.9 1.9 6.3 7.5 12.6 1.3 27
VZH044 44.5 2.4 8.0 9.6 16.0 1.3 27

Frequency converter
specifications T2: 200 - 240 V +/-10% (3-phase)
Mains supply voltage
T4: 380 - 480 V +/-10% (3-phase)

Supply frequency 50 / 60 Hz

Output voltage 0 - 100 % of supply voltage

Inputs 4 digital (0 - 24 V), 2 analog (0 /±10 V or 4 - 20 mA, scalable)

Programmable outputs 2 digital (0- 24 V), 2 analog (0-24 V), 2 relay

Protection functions Over-current protection, low / high current handling


Pressostat / thermostat function, short cycle protection, oil return
Compressor functions management

Oil return management Oil return management function only works not work even if parameter 28-10 (oil return
under auto mode: After running at low rpm management) is set to on. If compressors run
(less than 40 rps) for 19 minutes, the internal below 40 rps for more than 19 minutes, oil return
lubrication algorithm in the drive will accelerate fault alarm (A208) will report on LCP and stop
the compressor speed to 40 rps or above for the compressor. Please select hands on mode
60 seconds to ensure sufficient lubrication of carefully and only select hands on mode if the
compressor moving parts. OEM has implemented oil return management
in the system controller and qualified oil
Warning: management. Under such conditions, the
This function is enabled by parameter 28-10 as compressor could run below 40 rps continually
default setting. Please notice when hands on and meanwhile disable drive oil return
mode is selected, oil return management will management 28-10.

Bearings lubrication A specific oil pump ensures optimal bearing at low speeds as well as to avoid excessive Oil
lubrication at all compressor speeds. The specific Circulation Ratio (OCR) at high speeds.
oil pump provides sufficient bearing lubrication

FRCC.PC.034.A3.02 9
Application Guidelines Technical specifications Single compressors

Capacity at EN12900 conditions - VZH028CJ-VZH035CJ-VZH044CJ


Models

Te -30 -25 -20 -15 -10 -5 0 5 10 15 20


rpm
rps

Tc Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe

5 - - 1791 0.54 2252 0.519 2798 0.499 3437 0.479 4177 0.46 5027 0.442 - - - - - - - -

25 - - 1460 0.812 1873 0.804 2351 0.79 2905 0.771 3541 0.747 4269 0.717 5096 0.682 6031 0.643 7081 0.599 8257 0.55
1800
30

45 - - - - - - 1805 1.198 2256 1.218 2772 1.227 3359 1.224 4027 1.21 4783 1.185 5636 1.149 6593 1.103

65 - - - - - - - - - - - - - - - - - - - - - -

5 3009 1.04 3787 1.056 4725 1.042 5840 0.984 7151 0.869 8676 0.68 10435 0.403 - - - - - - - -
VZH028CJ

25 2371 1.492 3054 1.527 3863 1.572 4817 1.613 5934 1.634 7232 1.622 8730 1.56 10445 1.436 12396 1.234 14602 0.94 17081 0.539
3600
60

45 - - 2284 2.296 2937 2.292 3702 2.323 4597 2.375 5638 2.431 6845 2.479 8235 2.502 9825 2.487 11634 2.419 13680 2.283

65 - - - - - - - - - - 3761 3.567 4622 3.615 5626 3.68 6789 3.744 8128 3.795 9660 3.818

5 5025 1.96 6302 2.006 7834 1.996 9651 1.917 11784 1.756 14263 1.499 17119 1.131 - - - - - - - -

25 4004 2.64 5147 2.772 6495 2.887 8075 2.972 9920 3.012 12058 2.994 14520 2.905 17336 2.73 20536 2.456 24150 2.068 28209 1.555
6000
100

45 - - 3860 3.845 4978 3.968 6278 4.1 7789 4.225 9540 4.331 11560 4.403 13879 4.429 16527 4.393 19532 4.283 22923 4.084

65 - - - - - - - - - - 6426 6.069 7912 6.187 9633 6.296 11616 6.383 13888 6.433 16477 6.434

5 - - 2268 0.658 2851 0.633 3542 0.608 4350 0.584 5287 0.561 6363 0.539 - - - - - - - -

25 - - 1848 0.99 2370 0.98 2977 0.964 3677 0.94 4483 0.91 5403 0.874 6450 0.832 7634 0.784 8964 0.73 10452 0.67
1800
30

45 - - - - - - 2284 1.461 2856 1.485 3508 1.496 4252 1.492 5098 1.475 6055 1.445 7134 1.401 8346 1.345

65 - - - - - - - - - - - - - - - - - - - - - -

5 3808 1.268 4794 1.287 5981 1.27 7392 1.2 9052 1.059 10983 0.829 13209 0.491 - - - - - - - -
VZH035CJ

25 3002 1.82 3866 1.862 4890 1.917 6098 1.966 7512 1.992 9155 1.977 11050 1.903 13222 1.751 15692 1.505 18484 1.146 21622 0.657
3600
60

45 - - 2891 2.799 3718 2.795 4687 2.833 5819 2.895 7137 2.965 8665 3.022 10424 3.051 12437 3.033 14727 2.95 17316 2.784

65 - - - - - - - - - - 4760 4.349 5851 4.408 7121 4.487 8594 4.566 10289 4.628 12228 4.655

5 6361 2.344 7977 2.398 9916 2.387 12217 2.293 14917 2.1 18055 1.792 21670 1.353 - - - - - - - -

25 5069 3.157 6516 3.314 8221 3.452 10222 3.553 12557 3.601 15263 3.58 18379 3.473 21944 3.264 25994 2.936 30570 2.473 35708 1.859
6000
100

45 - - 4885 4.597 6301 4.745 7947 4.902 9859 5.052 12076 5.178 14633 5.265 17569 5.295 20920 5.253 24723 5.121 29017 4.883

65 - - - - - - - - - - 8134 7.256 10015 7.397 12193 7.528 14704 7.632 17580 7.692 20857 7.693

5 - - 2916 0.824 3666 0.792 4554 0.76 5594 0.731 6799 0.702 8183 0.675 - - - - - - - -

25 - - 2377 1.239 3048 1.227 3828 1.206 4729 1.176 5765 1.139 6949 1.094 8295 1.041 9817 0.98 11527 0.913 13441 0.839
1800
30

45 - - - - - - 2938 1.828 3673 1.858 4512 1.871 5468 1.867 6556 1.846 7787 1.808 9175 1.753 10733 1.682

65 - - - - - - - - - - - - - - - - - - - - - -

5 4897 1.558 6165 1.581 7691 1.561 9507 1.475 11641 1.301 14124 1.018 16986 0.604 - - - - - - - -
VZH044CJ

25 3860 2.235 4972 2.288 6289 2.355 7842 2.416 9660 2.448 11773 2.429 14211 2.337 17003 2.152 20180 1.849 23770 1.408 27806 0.807
3600
60

45 - - 3718 3.439 4782 3.433 6027 3.48 7483 3.557 9179 3.642 11143 3.713 13405 3.748 15994 3.726 18939 3.624 22269 3.42

65 - - - - - - - - - - 6122 5.343 7524 5.416 9158 5.512 11052 5.609 13232 5.685 15725 5.718

5 8180 2.932 10259 3 12752 2.986 15711 2.868 19183 2.627 23219 2.242 27868 1.692 - - - - - - - -

25 6518 3.949 8379 4.146 10572 4.318 13145 4.445 16148 4.505 19628 4.478 23636 4.345 28220 4.083 33429 3.673 39313 3.094 45920 2.326
6000
100

45 - - 6283 5.751 8103 5.936 10220 6.132 12679 6.32 15529 6.478 18818 6.586 22593 6.624 26903 6.571 31794 6.406 37316 6.109

65 - - - - - - - - - - 10460 9.077 12879 9.254 15681 9.418 18909 9.547 22608 9.623 26823 9.624

To: Evaporating temperature in °C Superheat = 10 K


Tc: Condensing temperature in °C Subcooling = 0 K
Qo: Cooling capacity in W Pe: Power input in kW (with drive loss)

10 FRCC.PC.034.A3.02
Application Guidelines Technical specifications Single compressors

Capacity at ARI conditions - VZH028CJ-VZH035CJ-VZH044CJ


Models

Te -30 -25 -20 -15 -10 -5 0 5 10 15 20


rpm
rps

Tc Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe

5 - - 1894 0.54 2380 0.519 2954 0.499 3626 0.479 4405 0.46 5298 0.442 - - - - - - - -

25 - - 1568 0.812 2009 0.804 2521 0.79 3111 0.771 3790 0.747 4565 0.717 5445 0.682 6440 0.643 7557 0.599 8805 0.55
1800
30

45 - - - - - - 1990 1.198 2484 1.218 3048 1.227 3690 1.224 4418 1.21 5242 1.185 6171 1.149 7212 1.103

65 - - - - - - - - - - - - - - - - - - - - - -

5 3183 1.04 4004 1.056 4992 1.042 6167 0.984 7546 0.869 9150 0.68 10999 0.403 - - - - - - - -
VZH028CJ

25 2550 1.492 3280 1.527 4145 1.572 5164 1.613 6356 1.634 7740 1.622 9336 1.56 11162 1.436 13237 1.234 15582 0.94 18215 0.539
3600
60

45 - - 2526 2.296 3244 2.292 4082 2.323 5062 2.375 6200 2.431 7518 2.479 9034 2.502 10767 2.487 12737 2.419 14963 2.283

65 - - - - - - - - - - 4505 3.567 5520 3.615 6701 3.68 8067 3.744 9637 3.795 11431 3.818

5 5317 1.96 6663 2.006 8277 1.996 10191 1.917 12435 1.756 15043 1.499 18044 1.131 - - - - - - - -

25 4305 2.64 5528 2.772 6969 2.887 8657 2.972 10625 3.012 12905 2.994 15527 2.905 18525 2.73 21928 2.456 25770 2.068 30082 1.555
6000
100

45 - - 4269 3.845 5497 3.968 6922 4.1 8576 4.225 10491 4.331 12697 4.403 15226 4.429 18111 4.393 21383 4.283 25074 4.084

65 - - - - - - - - - - 7698 6.069 9450 6.187 11474 6.296 13802 6.383 16466 6.433 19498 6.434

5 - - 2398 0.658 3012 0.633 3740 0.608 4590 0.584 5576 0.561 6707 0.539 - - - - - - - -

25 - - 1985 0.99 2543 0.98 3191 0.964 3939 0.94 4797 0.91 5778 0.874 6893 0.832 8151 0.784 9565 0.73 11146 0.67
1800
30

45 - - - - - - 2519 1.461 3145 1.485 3858 1.496 4670 1.492 5593 1.475 6636 1.445 7811 1.401 9129 1.345

65 - - - - - - - - - - - - - - - - - - - - - -

5 4029 1.268 5069 1.287 6319 1.27 7806 1.2 9552 1.059 11583 0.829 13922 0.491 - - - - - - - -
VZH035CJ

25 3227 1.82 4152 1.862 5247 1.917 6537 1.966 8046 1.992 9798 1.977 11817 1.903 14129 1.751 16756 1.505 19724 1.146 23057 0.657
3600
60

45 - - 3198 2.799 4106 2.795 5168 2.833 6407 2.895 7849 2.965 9517 3.022 11436 3.051 13630 3.033 16123 2.95 18941 2.784

65 - - - - - - - - - - 5703 4.349 6988 4.408 8483 4.487 10212 4.566 12199 4.628 14469 4.655

5 6730 2.344 8434 2.398 10478 2.387 12900 2.293 15741 2.1 19041 1.792 22841 1.353 - - - - - - - -

25 5449 3.157 6998 3.314 8821 3.452 10958 3.553 13449 3.601 16335 3.58 19655 3.473 23449 3.264 27758 2.936 32621 2.473 38079 1.859
6000
100

45 - - 5403 4.597 6958 4.745 8763 4.902 10856 5.052 13279 5.178 16072 5.265 19274 5.295 22926 5.253 27067 5.121 31739 4.883

65 - - - - - - - - - - 9744 7.256 11962 7.397 14524 7.528 17471 7.632 20844 7.692 24681 7.693

5 - - 3083 0.824 3874 0.792 4809 0.76 5903 0.731 7171 0.702 8625 0.675 - - - - - - - -

25 - - 2553 1.239 3271 1.227 4104 1.206 5065 1.176 6169 1.139 7431 1.094 8864 1.041 10483 0.98 12301 0.913 14333 0.839
1800
30

45 - - - - - - 3239 1.828 4044 1.858 4961 1.871 6006 1.867 7192 1.846 8533 1.808 10045 1.753 11740 1.682

65 - - - - - - - - - - - - - - - - - - - - - -

5 5182 1.558 6518 1.581 8127 1.561 10038 1.475 12284 1.301 14896 1.018 17904 0.604 - - - - - - - -
VZH044CJ

25 4150 2.235 5340 2.288 6748 2.355 8407 2.416 10347 2.448 12600 2.429 15197 2.337 18169 2.152 21548 1.849 25365 1.408 29652 0.807
3600
60

45 - - 4113 3.439 5280 3.433 6646 3.48 8239 3.557 10093 3.642 12238 3.713 14706 3.748 17528 3.726 20734 3.624 24357 3.42

65 - - - - - - - - - - 7334 5.343 8986 5.416 10909 5.512 13132 5.609 15688 5.685 18607 5.718

5 8654 2.932 10846 3 13474 2.986 16589 2.868 20243 2.627 24487 2.242 29373 1.692 - - - - - - - -

25 7008 3.949 9000 4.146 11344 4.318 14092 4.445 17296 4.505 21007 4.478 25276 4.345 30155 4.083 35696 3.673 41950 3.094 48969 2.326
6000
100

45 - - 6949 5.751 8949 5.936 11269 6.132 13961 6.32 17077 6.478 20668 6.586 24786 6.624 29483 6.571 34809 6.406 40816 6.109

65 - - - - - - - - - - 12531 9.077 15383 9.254 18678 9.418 22468 9.547 26805 9.623 31740 9.624

To: Evaporating temperature in °C Superheat = 11.1 K


Tc: Condensing temperature in °C Subcooling = 8.3 K
Qo: Cooling capacity in W Pe: Power input in kW (with drive loss)
Rating point: ARI@60 rps
To/Tc/SH/SC: 7.2°C/54.4°C/11.1K/8.3K@60rps

FRCC.PC.034.A3.02 11
Application Guidelines Technical specifications Single compressors

Capacity at EN12900 conditions - VZH028CG-VZH035CG-VZH044CG


Models

Te -30 -25 -20 -15 -10 -5 0 5 10 15 20


rpm
rps

Tc Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe

5 - - 1791 0.535 2252 0.514 2798 0.494 3437 0.474 4177 0.456 5027 0.438 - - - - - - - -

25 - - 1460 0.804 1873 0.796 2351 0.783 2905 0.763 3541 0.739 4269 0.71 5096 0.676 6031 0.636 7081 0.593 8257 0.544
1800
30

45 - - - - - - 1805 1.186 2256 1.206 2772 1.215 3359 1.212 4027 1.198 4783 1.173 5636 1.138 6593 1.092

65 - - - - - - - - - - - - - - - - - - - - - -

5 3009 1.03 3787 1.045 4725 1.032 5840 0.975 7151 0.86 8676 0.673 10435 0.399 - - - - - - - -
VZH028CG

25 2371 1.478 3054 1.512 3863 1.557 4817 1.597 5934 1.618 7232 1.605 8730 1.545 10445 1.422 12396 1.222 14602 0.931 17081 0.533
3600
60

45 - - 2284 2.273 2937 2.269 3702 2.3 4597 2.351 5638 2.407 6845 2.454 8235 2.478 9825 2.463 11634 2.395 13680 2.261

65 - - - - - - - - - - 3761 3.531 4622 3.58 5626 3.643 6789 3.707 8128 3.758 9660 3.78

5 5025 1.941 6302 1.986 7834 1.976 9651 1.898 11784 1.739 14263 1.484 17119 1.12 - - - - - - - -

25 4004 2.614 5147 2.745 6495 2.859 8075 2.942 9920 2.982 12058 2.964 14520 2.876 17336 2.703 20536 2.431 24150 2.048 28209 1.539
6000
100

45 - - 3860 3.807 4978 3.929 6278 4.059 7789 4.183 9540 4.288 11560 4.36 13879 4.385 16527 4.349 19532 4.24 22923 4.044

65 - - - - - - - - - - 6426 6.009 7912 6.126 9633 6.234 11616 6.32 13888 6.37 16477 6.37

5 - - 2268 0.652 2851 0.627 3542 0.602 4350 0.578 5287 0.555 6363 0.534 - - - - - - - -

25 - - 1848 0.981 2370 0.971 2977 0.954 3677 0.931 4483 0.901 5403 0.866 6450 0.824 7634 0.776 8964 0.723 10452 0.664
1800
30

45 - - - - - - 2284 1.447 2856 1.471 3508 1.481 4252 1.478 5098 1.461 6055 1.431 7134 1.388 8346 1.331

65 - - - - - - - - - - - - - - - - - - - - - -

5 3808 1.256 4794 1.274 5981 1.258 7392 1.188 9052 1.049 10983 0.82 13209 0.486 - - - - - - - -
VZH035CG

25 3002 1.802 3866 1.844 4890 1.898 6098 1.947 7512 1.973 9155 1.958 11050 1.884 13222 1.734 15692 1.49 18484 1.135 21622 0.65
3600
60

45 - - 2891 2.771 3718 2.767 4687 2.805 5819 2.867 7137 2.935 8665 2.993 10424 3.021 12437 3.003 14727 2.921 17316 2.757

65 - - - - - - - - - - 4760 4.306 5851 4.365 7121 4.442 8594 4.52 10289 4.582 12228 4.609

5 6361 2.321 7977 2.374 9916 2.363 12217 2.27 14917 2.079 18055 1.774 21670 1.339 - - - - - - - -

25 5069 3.126 6516 3.282 8221 3.418 10222 3.518 12557 3.565 15263 3.544 18379 3.438 21944 3.231 25994 2.907 30570 2.449 35708 1.841
6000
100

45 - - 4885 4.551 6301 4.698 7947 4.853 9859 5.002 12076 5.127 14633 5.213 17569 5.243 20920 5.2 24723 5.07 29017 4.835

65 - - - - - - - - - - 8134 7.184 10015 7.324 12193 7.454 14704 7.556 17580 7.616 20857 7.617

5 - - 2916 0.815 3666 0.784 4554 0.753 5594 0.723 6799 0.695 8183 0.668 - - - - - - - -

25 - - 2377 1.227 3048 1.214 3828 1.194 4729 1.165 5765 1.128 6949 1.083 8295 1.03 9817 0.971 11527 0.904 13441 0.83
1800
30

45 - - - - - - 2938 1.81 3673 1.84 4512 1.853 5468 1.849 6556 1.828 7787 1.79 9175 1.736 10733 1.666

65 - - - - - - - - - - - - - - - - - - - - - -

5 4897 1.543 6165 1.565 7691 1.545 9507 1.46 11641 1.288 14124 1.008 16986 0.598 - - - - - - - -
VZH044CG

25 3860 2.213 4972 2.265 6289 2.332 7842 2.392 9660 2.423 11773 2.405 14211 2.314 17003 2.13 20180 1.831 23770 1.394 27806 0.799
3600
60

45 - - 3718 3.405 4782 3.399 6027 3.446 7483 3.522 9179 3.606 11143 3.676 13405 3.711 15994 3.689 18939 3.588 22269 3.386

65 - - - - - - - - - - 6122 5.29 7524 5.362 9158 5.457 11052 5.553 13232 5.629 15725 5.662

5 8180 2.903 10259 2.97 12752 2.956 15711 2.84 19183 2.601 23219 2.22 27868 1.675 - - - - - - - -

25 6518 3.91 8379 4.105 10572 4.276 13145 4.401 16148 4.46 19628 4.434 23636 4.302 28220 4.042 33429 3.637 39313 3.063 45920 2.303
6000
100

45 - - 6283 5.694 8103 5.877 10220 6.071 12679 6.257 15529 6.414 18818 6.521 22593 6.559 26903 6.506 31794 6.343 37316 6.049

65 - - - - - - - - - - 10460 8.988 12879 9.162 15681 9.324 18909 9.453 22608 9.528 26823 9.528

To: Evaporating temperature in °C Superheat = 10 K


Tc: Condensing temperature in °C Subcooling = 0 K
Qo: Cooling capacity in W Pe: Power input in kW (with drive loss)

12 FRCC.PC.034.A3.02
Application Guidelines Technical specifications Single compressors

Capacity at ARI conditions - VZH028CG-VZH035CG-VZH044CG


Models

Te -30 -25 -20 -15 -10 -5 0 5 10 15 20


rpm
rps

Tc Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe Qo Pe

5 - - 1894 0.535 2380 0.514 2954 0.494 3626 0.474 4405 0.456 5298 0.438 - - - - - - - -

25 - - 1568 0.804 2009 0.796 2521 0.783 3111 0.763 3790 0.739 4565 0.71 5445 0.676 6440 0.636 7557 0.593 8805 0.544
1800
30

45 - - - - - - 1990 1.186 2484 1.206 3048 1.215 3690 1.212 4418 1.198 5242 1.173 6171 1.138 7212 1.092

65 - - - - - - - - - - - - - - - - - - - - - -

5 3183 1.03 4004 1.045 4992 1.032 6167 0.975 7546 0.86 9150 0.673 10999 0.399 - - - - - - - -
VZH028CG

25 2550 1.478 3280 1.512 4145 1.557 5164 1.597 6356 1.618 7740 1.605 9336 1.545 11162 1.422 13237 1.222 15582 0.931 18215 0.533
3600
60

45 - - 2526 2.273 3244 2.269 4082 2.3 5062 2.351 6200 2.407 7518 2.454 9034 2.478 10767 2.463 12737 2.395 14963 2.261

65 - - - - - - - - - - 4505 3.531 5520 3.58 6701 3.643 8067 3.707 9637 3.758 11431 3.78

5 5317 1.941 6663 1.986 8277 1.976 10191 1.898 12435 1.739 15043 1.484 18044 1.12 - - - - - - - -

25 4305 2.614 5528 2.745 6969 2.859 8657 2.942 10625 2.982 12905 2.964 15527 2.876 18525 2.703 21928 2.431 25770 2.048 30082 1.539
6000
100

45 - - 4269 3.807 5497 3.929 6922 4.059 8576 4.183 10491 4.288 12697 4.36 15226 4.385 18111 4.349 21383 4.24 25074 4.044

65 - - - - - - - - - - 7698 6.009 9450 6.126 11474 6.234 13802 6.32 16466 6.37 19498 6.37

5 - - 2398 0.652 3012 0.627 3740 0.602 4590 0.578 5576 0.555 6707 0.534 - - - - - - - -

25 - - 1985 0.981 2543 0.971 3191 0.954 3939 0.931 4797 0.901 5778 0.866 6893 0.824 8151 0.776 9565 0.723 11146 0.664
1800
30

45 - - - - - - 2519 1.447 3145 1.471 3858 1.481 4670 1.478 5593 1.461 6636 1.431 7811 1.388 9129 1.331

65 - - - - - - - - - - - - - - - - - - - - - -

5 4029 1.256 5069 1.274 6319 1.258 7806 1.188 9552 1.049 11583 0.82 13922 0.486 - - - - - - - -
VZH035CG

25 3227 1.802 4152 1.844 5247 1.898 6537 1.947 8046 1.973 9798 1.958 11817 1.884 14129 1.734 16756 1.49 19724 1.135 23057 0.65
3600
60

45 - - 3198 2.771 4106 2.767 5168 2.805 6407 2.867 7849 2.935 9517 2.993 11436 3.021 13630 3.003 16123 2.921 18941 2.757

65 - - - - - - - - - - 5703 4.306 6988 4.365 8483 4.442 10212 4.52 12199 4.582 14469 4.609

5 6730 2.321 8434 2.374 10478 2.363 12900 2.27 15741 2.079 19041 1.774 22841 1.339 - - - - - - - -

25 5449 3.126 6998 3.282 8821 3.418 10958 3.518 13449 3.565 16335 3.544 19655 3.438 23449 3.231 27758 2.907 32621 2.449 38079 1.841
6000
100

45 - - 5403 4.551 6958 4.698 8763 4.853 10856 5.002 13279 5.127 16072 5.213 19274 5.243 22926 5.2 27067 5.07 31739 4.835

65 - - - - - - - - - - 9744 7.184 11962 7.324 14524 7.454 17471 7.556 20844 7.616 24681 7.617

5 - - 3083 0.815 3874 0.784 4809 0.753 5903 0.723 7171 0.695 8625 0.668 - - - - - - - -

25 - - 2553 1.227 3271 1.214 4104 1.194 5065 1.165 6169 1.128 7431 1.083 8864 1.03 10483 0.971 12301 0.904 14333 0.83
1800
30

45 - - - - - - 3239 1.81 4044 1.84 4961 1.853 6006 1.849 7192 1.828 8533 1.79 10045 1.736 11740 1.666

65 - - - - - - - - - - - - - - - - - - - - - -

5 5182 1.543 6518 1.565 8127 1.545 10038 1.46 12284 1.288 14896 1.008 17904 0.598 - - - - - - - -
VZH044CG

25 4150 2.213 5340 2.265 6748 2.332 8407 2.392 10347 2.423 12600 2.405 15197 2.314 18169 2.13 21548 1.831 25365 1.394 29652 0.799
3600
60

45 - - 4113 3.405 5280 3.399 6646 3.446 8239 3.522 10093 3.606 12238 3.676 14706 3.711 17528 3.689 20734 3.588 24357 3.386

65 - - - - - - - - - - 7334 5.29 8986 5.362 10909 5.457 13132 5.553 15688 5.629 18607 5.662

5 8654 2.903 10846 2.97 13474 2.956 16589 2.84 20243 2.601 24487 2.22 29373 1.675 - - - - - - - -

25 7008 3.91 9000 4.105 11344 4.276 14092 4.401 17296 4.46 21007 4.434 25276 4.302 30155 4.042 35696 3.637 41950 3.063 48969 2.303
6000
100

45 - - 6949 5.694 8949 5.877 11269 6.071 13961 6.257 17077 6.414 20668 6.521 24786 6.559 29483 6.506 34809 6.343 40816 6.049

65 - - - - - - - - - - 12531 8.988 15383 9.162 18678 9.324 22468 9.453 26805 9.528 31740 9.528

To: Evaporating temperature in °C Superheat = 11.1 K


Tc: Condensing temperature in °C Subcooling = 8.3 K
Qo: Cooling capacity in W Pe: Power input in kW (with drive loss)
Rating point: ARI@60 rps
To/Tc/SH/SC: 7.2°C/54.4°C/11.1K/8.3K@60rps

FRCC.PC.034.A3.02 13
Application Guidelines Dimensions Single compressors

VZH028-035-044G/J VZH028-035-044G/J
single version manifold version

Ø164.5 Overall height:


Top of sensor bracket Top of sensor bracket
Ø164.5

Discharge line
1/2"

Discharge line
1/2"
Suction Suction line
3/4" 3/4"

360.4
404.4
Organ pipe 360.4
404.4
Oil Sight Glass fitting
1 1/8"

Schrader valve Schrader valve 230.5


and cover Oil level sensor and cover
230.5
prism

78.0
78.0
55.0 42.5 55.0

11
11

239
239

190.5 190.5
Ø19.5
Ø19.5
(95.25) 4X
(95.25) 4X

109.7 129.5
129.5 109.7
Suction line

(17°)

111.3 111.3
discharge line
(60°)
14°±2°

(34°) (31°) 14°±2°


70.6 (34°) (31°)
45°±2°
45°±2°

Note: Manifolding drawing is preliminary version

All dimensions in mm

Terminal box (quick connect spade terminals) Mounting Grommet

29.5
Earth grounding

Ø11
EMC bracket to Ø 41
terminations of Recommended torque for
shielded wire mounting bolts: 11 Nm (±1 Nm)

14 FRCC.PC.034.A3.02
Application Guidelines Dimensions Single compressors

Sight glass/oil level VZH compressors single versions come equipped VZH manifold version compressors come
switch with a threaded oil sight glass with 1"1/8 – 18 equipped with a screw-in optical part on oil level
UNEF connection. It can be used for a visual switch port located below the electrical box.
check of oil amount and condition.

Schrader The oil fill connection and gauge port is a 1/4"


male flare connector incorporating a schrader
valve.

Oil equalization VZH manifolding compressors are equipped   Oil equalization


connection with a rotolock oil equalization connection. VZH028-035-044 Rotolock 1"1/8
This connection is used when compressors are
mounted in parallel. Contact Danfoss for further
details and refer to the hybrid manifolding
specific section.

Suction & discharge VZH compressors are all delivered with suction
Suction Discharge
connections and discharge brazed connections only. They are
VZH028-035-044 3/4" 1/2"
copper-plated steel connections.

Rotolock adaptors are available, refer to the


“Accessories” section.

    

Rotolock adaptor set Rotolock adaptor


Compressor models Brazed connection size (adaptor, gasket, sleeve, nut) ( adaptor only)
Rotolock Solder sleeve ODF Code Number Code Number

Suction 3/4" 1-1/4" 3/4" 120Z0366


VZH028-044 120Z0126
Discharge 1/2" 1" 1/2" 120Z0365

Frequency converter Frequency converter dimensions depend


dimensions on supply voltage, IP rating and power. The
Min 100
Clearance above for cooling

table below gives an overview of the overall L


dimensions and different drive enclosures (H3 -
H5). Details for each drive enclosure are on the
following pages.
H

W Min 100
Clearance above for cooling

IP20
Drive power Compressor Compressor Overall drive size
Drive supply voltage Clearance above/
kW voltage code model Overall drive size (H x W x L) mm
Drive enclosure below
(H x W x L) mm incl. decoupling (mm/inch)
plate
6 VZH028 H4 296x135x241 359x135x241 100/4
T2: 200-240/3/50-60 7.5 J VZH035 H4 296x135x241 359x135x241 100/4
10 VZH044 H5 334x150x255 402x150x255 100/4
6 VZH028 H3 255x100x206 329x100x206 100/4
T4: 380-480/3/50-60 7.5 G VZH035 H3 255x100x206 329x100x206 100/4
10 VZH044 H4 296x135x241 359x135x241 100/4

FRCC.PC.034.A3.02 15
Application Guidelines Dimensions Single compressors

CDS803 frequency converter

B e
D
b
C

f
A
a

a
99 99

Decoupling Plate

e Decoupling Plate Illustration

Enclosure Height (mm) Width (mm) Depth (mm) Mounting hole (mm) Max. Weight
Frame IP Class A A1) a B b C d e f kg
H3 IP20 255 329 240 100 74 206 11 5.5 8.1 4.5
H4 IP20 296 359 275 135 105 241 12.6 7 8.4 7.9
H5 IP20 334 402 314 150 120 255 12.6 7 8.5 9.5
A1) Including decoupling plate.

The dimensions are only for the physical units, but when installing in an application it is necessary to add space for free air passage both above and below the units. The amount
of space for free air passage is listed in “frequency converter dimensions - Clearance above/below (mm/inch)”.

16 FRCC.PC.034.A3.02
Application Guidelines Electrical data, connections and wiring Single compressors

Supply voltage Because VZH compressors are powered by a


Voltage code Mains voltage range of drive
frequency converter, the mains frequency, 50 or
60 Hz, is no longer an issue. Only the mains 200-240 V / 3 ph / 50 Hz &
J 200-240 V / 3 ph / 60 Hz (±10%)
voltage is to be taken into account. With 2 motor
380-480 V / 3 ph / 50 Hz &
voltage codes, the most common mains voltages G 380 - 480 V / 3 ph / 60 Hz (±10%)
and frequencies are covered. Never connect the
VZH compressor directly to the mains power
supply in the case motor burns out.

Compressor rated RW(Ω) at 20°C line Max Operating


Compressor electrical Model RLA (A)
voltage (V) to line Current (A)
specifications VZH044CG 15.5 17.8
414 V max. VZH035CG 0.708±7% 12.4 14.3
VZH028CG 10.3 11.8
VZH044CJ 33.3 38.3
210 V max. VZH035CJ 0.185±7% 26.6 30.6
VZH028CJ 22.0 25.3
RW: Winding resistance per winding, measured at motor terminals
RLA: Rated load Amp

RLA (Rated Load Amp) Rated Load Amp value is the current value at at maximum speed and maximum drive input
maximum load, in the operating envelope, and voltage.

Max Operating Current (A) Max operating current is the maximum


continuous current which is 115% of RLA. This
value is printed on compressor nameplate.

Wiring connections VZH scroll compressors will only compress gas


while rotating counter-clockwise (when viewed
from the top of the compressor).
The drawing shows electrical terminal labeling
and should be used as a reference when wiring
the compressor. Earth grounding
U, V & W of the drive and the compressor must be
connected accordingly.
For use of EMC bracket with shielded cable, it is
EMC bracket to
recommended to have a thread cutting screw terminations of
(#10-32) having a torque of 3NM. shielded wire

Terminal cover mounting The terminal cover and gasket should be installed that engage the terminal fence. When installing
prior to operation of the compressor. The terminal the cover, check that it is not pinching the lead
cover has two outside tabs, 180 degrees apart, wires.

Terminal cover removal


push

push

push

FRCC.PC.034.A3.02 17
Application Guidelines Electrical data, connections and wiring Single compressors

Fuses Danfoss recommends using the fuses listed For circuit breakers, Moeller types have been
below to protect service personnel and property tested and are recommended. Other types of
in case of component break-down in the circuit breakers may be used provided they limit
frequency converter. the energy to a level equal to or lower than the
Moeller types.

UL Compliant fuses Recommended circuit breaker


UL Non UL IP20
Bussmann Bussmann Bussmann Bussmann Max fuse
CDS 803 Type RK5 Type RK1 Type J Type T Type G Moeller type
3x200-240 V IP20
4 TR/VZH028 FRS-R-50 KTN-R50 JKS-50 JJN-50 50 PKZM4-50
5 TR/VZH035 FRS-R-50 KTN-R50 JKS-50 JJN-50 50 PKZM4-50
6.5 TR/VZH044 FRS-R-60 KTN-R60 JKS-60 JJN-60 60 PKZM4-63
3x380-480 V IP20
4 TR/VZH028 FRS-R-25 KTS-R25 JKS-25 JJS-25 25 PKZM4-25
5 TR/VZH035 FRS-R-25 KTS-R25 JKS-25 JJS-25 25 PKZM4-25
6.5 TR/VZH044 FRS-R-30 KTS-R30 JKS-30 JJS-30 30 PKZM4-36

18 FRCC.PC.034.A3.02
Application Guidelines Electrical data, connections and wiring Single compressors

Wire sizes Below table lists recommended wiring sizes for the motor compressor power supply cables. These
wiring sizes are valid for a cable length up to 20m.
From network to frequency converter From frequency converter to compressor
Type mm² AWG Type mm² AWG
CDS-6kW(IP20) 6 10 VZH028-J 6 10
200 - 240 V CDS-7.5kW(IP20) 6 10 VZH035-J 6 10
CDS-10kW(IP20) 10 8 VZH044-J 10 8
CDS-6kW(IP20) 4 10 VZH028-G 4 10
380 - 400 V CDS-7.5kW(IP20) 4 10 VZH035-G 4 10
CDS-10kW(IP20) 4 10 VZH044-G 4 10
Note: 1.The wire size here is the guideline but not the actual cable required. The required cable size should be specified by the OEM
depending on the unit design, ambient temperature, the wire material, current, etc.
2.For VZH044-J model could use 6 mm² (10 AWG ) wire but Max operating current percentage need to change to 108% instead of
default 115%, with this change customer could simplify power cable model and save cost.

Wiring & EMC protection The motor compressor power supply from Physical installation of the frequency converter
the CDS803 frequency converter to the VZH on the mounting plate must ensure good
compressor must be done with a braided electrical contact between the mounting plate
screened/shielded cable. This cable needs to and the metal chassis of the converter. Use star-
have its screen/shielding conduit connected to washers and galvanically conductive installation
earth on both ends. Avoid terminating this cable plates to secure good electrical connections.
connection with twisting ends (pigtails) because Refer to instructions MG18N102 for tightening
that would result in an antenna phenomenon torques and screw sizes.
and decrease the effectiveness of the cable.
Note that the CDS803 must be mounted on a
Control cables to the CDS803 frequency plain wall to ensure a good air flow through its
converter must use the same installation heat exchanger.
principles as the motor power supply cable.

The motor compressor cable must be installed in


a conduit separated from the control and mains
cables.

FRCC.PC.034.A3.02 19
Application Guidelines Electrical data, connections and wiring Single compressors

EMC correct installation of an IP20 frequency drive CDS803


EMC qualification reports are available upon request to Danfoss technical support.

PLC etc. Panel

Menu Status Quick Main


Menu Menu
Com.

Back
On OK
Warn.
Alarm

Hand Auto
On Reset On

Output
contactor etc.

PLC

Earthing rail

Cable insula-
tion stripped

Min. 16 mm 2
Equalizing cable

All cable entries in


one side of panel
Control cables

Motor cable
Min. 200 mm
between control
Mains-supply cable, mains cable
and between mains
L1 motor cable
L2
L3
PE
Motor, 3 phases and
Reinforced protective earth Protective earth

Wiring diagram
L1 U
L2 V
3 Phase
power L3 W
input
PE PE
Motor

UDC-
Not present on all power sizes

UDC+

50 (+10 V OUT) relay2


+10 V DC
06
0-10 V DC- 53 (A IN) 240 V AC 3 A
0/4-20 mA 05

0-10 V DC- 54 (A IN) 04


0/4-20 mA
55 (COM A IN/OUT) relay1
42 0/4-20 mA A OUT / DIG OUT 03
240 V AC 3 A
45 0/4-20 mA A OUT / DIG OUT 02

Bus ter. 01
12 (+24 V OUT) ON=Terminated
ON
1 2

OFF=Unterminated
18 (DIGI IN)
24 V (NPN)
O V (PNP)
19 (DIGI IN)
24 V (NPN)
20 (COM D IN) O V (PNP)
Bus ter.
27 (DIGI IN)
24 V (NPN) RS-485 (N RS-485) 69
O V (PNP) RS-485
29 (DIGI IN) Interface
24 V (NPN) (P RS-485) 68
O V (PNP) Do not connect shield to 61
(Com RS-485 ) 61

(PNP)-Source
(NPN)-Sink

20 FRCC.PC.034.A3.02
Application Guidelines Electrical data, connections and wiring Single compressors

Wiring connections

L1 91 L1 U 96 T1/U
L2 92 L2 V 97 T2/V
L3 93 L3 W 98 T3/W

95 PE PE 99

45 0/4-20 mA A OUT / DIG OUT


42 0/4-20 mA A OUT / DIG OUT
50 +10 V OUT NC 03

RELAY 1
CDS803
53 A IN NO 02
54 A IN COM 01
55 COM A IN/OUT
NC 06

RELAY 2
NO 05
12 +24 V OUT COM 04
18 DIGI IN
19 DIGI IN
27 DIGI IN
29 DIGI IN
20 COM D IN Legends:
N RS-485 69 A: Analog
P RS-485 68 DIGI: Digital
Com RS-485 61 IN: Input
OUT: Output
COM: Common
NC: Normally-closed
NO: Normally-open

Open loop Process loop


91,92,93 3 phases mains input x x
95 Earth x x
0/4-20 mA Analague Output or Digital
42,45 - -
Output
50 +10V DC Output - -
53 0-10V or 4-20mA Analague Input x -
54 0-10V or 4-20mA Analague Input - x
55 Com Analague In/Out x - The CDS803 frequency converter is factory
12 +24V output - -
18 External On/Off(NO) x x preset with parameters for the open loop control
19 Digital Input - - principle. The process loop control principle can
27 Safety Device e.g.: HP/LP switch x x be selected by changing parameters in the “Quick
29 Digital Input - -
20 Com Digital Input - - menu.”
98 To Compressor T3 x x Open loop: preset on input 53
97 To Compressor T2 x x
0 - 10 V control
96 To Compressor T1 x x
99 Earth x x Frequency converter in slave mode
03,02,01 Relay 1 - - Process loop: preset on input 54
06,05,04 Relay 2 - -
69,68 RS485 Bus - -
4 - 20 mA control
61 RS485 Bus Com - - Frequency converter under own PID controller
-: Optional connection
X: Mandatory connection

Electrical connections VZH028/035/044 scroll compressors are designed


to operate without any assistance.

FRCC.PC.034.A3.02 21
Application Guidelines Electrical data, connections and wiring Single compressors

Soft-start control The CDS803 frequency converter generates by Basically seen from the mains the inrush peak
design a compressor soft start with an default reach a level which is only a few percent more
initial ramp up of 7.5s to 50 rps. than the rated nominal current.

Current inrush will not exceed the frequency


converter maximum current.

Phase sequency and The compressor will only operate properly in a rapidly damaged in these conditions. To protect
reverse rotation single direction. If electrical connections are done compressors from reverse rotation, one of below
protection correctly between the drive and the compressor actions is required:
terminals (compressor and drive terminals U, V & -U
 se pressure sensors to monitor pressure
W matching), the drive will provide correct phase difference between discharge and suction of
supply to the compressor, and reverse rotation the compressor, and for normal operation,
will be not possible: discharge pressure should be at least 1 bar
higher than suction pressure within 30 s
• CDS803 terminal U (96) to VZH terminal T1/U running after compressor starting.
• CDS803 terminal V (97) to VZH terminal T2/V -A
 pply the dome temperature sensor on top of
• CDS803 terminal W (98) to VZH terminal T3/W the compressor upper shell to sense the high
temperature resulted from compressor reverse
If compressor and drive U, V & W terminals are run and trigger the alarm in system controls.
not matching, the compressor can operate in a
reverse rotation. This results in excessive noise, Mains connection to the CDS803 frequency
no pressure differential between suction and converter order has no influence on the output
discharge, and suction line warming rather than phase sequence which is managed by the
immediate cooling. The compressor can be frequency converter.

IP rating The compressor terminal box IP rating according to IEC529 is IP22.


Element Numerals or letters Meaning for the protection of equipment

Against ingress of solid foreign objects

0 (non protected)
1 ≥ 50 mm diameter
First characteristic 2 ≥ 12.6 mm diameter
numeral 3 ≥ 2.5 mm diameter
4 ≥ 1.0 mm diameter
5 dust protected
6 dust tight

Agains ingress of water with harmful effects

0 (non protected
1 vertically dripping
Second 2 dripping (15° tilted)
characteristic 3 spaying
numeral 4 splashing
5 jetting
6 powerful jetting
7 temporary immersion
8 continuous immersion

Motor protection VZH scroll compressors are not equipped with When a warning situation is reached in the
an internal motor protector. Motor protection current control, the CDS803 frequency converter
is provided by the variable speed drive. All will automatically reduce the compressor
parameters are factory preset in order to speed in order to keep the motor current of the
guaranty locked rotor or overload current compressor below the maximum allowed.
protection.

Anti-reverse protection In some cases when compressors stop under of the compressor. The drive shall prevent the
low mass flow low speed condition, discharge compressors scroll set from running the wrong
valve may not seal discharge port fast enough, way during stop with anti reverse protection.
thus compressors may run in a reverse rotation
due to the residual pressure difference and To activate the function, the customer must be
generate a big noise. Running in the wrong able to enable and disable the ANTI-REVERSE
direction will reduce the reliability and lifetime PROTECTION.

22 FRCC.PC.034.A3.02
Application Guidelines Electrical data, connections and wiring Single compressors

Temperature protection If the temperature in the drive is too high, an the reading of the heatsink temperature received
alarm 29 will be seen to trip the drive. When the from the drive to lower the load to avoid a trip-
drive shows a warning 29, it’s suggested that lock. Contact Danfoss for more details.
OEM controller has to be programmed based on

Voltage imbalance The maximum allowable voltage imbalance in 14.12 parameter. It is, by default, factory preset
between each phase is 3%. Voltage imbalance to “[1] Warning”.
causes high amperage over one or several
phases, which in turn leads to overheating and Then the compressor electrical motor is never
possible drive damage. affected by main voltage imbalance situations
which are made completely transparent by the
Mains imbalance function in CDS803 frequency frequency converter.
converter can be set to “[0] Trip” or “[1] Warning”

FRCC.PC.034.A3.02 23
Application Guidelines Approvals and certificates Single compressors

Approvals and VZH compressors comply with the following approvals and certificates.
certificates
CE 0062 or CE 0038 All VZH models
(European Directive)
UL All VZH models
(Underwriters Laboratories)
EMC All VZH models
2004 / 108 / EC
CCC All VZH models

Pressure equipment Products VZH028 VZH035 VZH044


directive 2014/68/EU Fluids Group 2
Category PED I
TS - service temperature LP -35°C < TS < +55°C
PS - service pressure LP 33.3 bar(g)

Internal free volume


Products Internal free volume at LP side without oil (liter)

VZH028 3.2

VZH035 3.2

VZH044 3.2

24 FRCC.PC.034.A3.02
Application Guidelines Operating conditions Single compressors

Application envelopes The operating envelopes for VZH scroll • Minimum suction superheat should be above
compressors are given in the figures below, 5 K and minimum sump superheat should be
where the condensing and evaporating above 6 K due to the risk of liquid flood back.
temperatures represent the range for steady state • Attention to suction line insulation to reduce
operation. Under transient conditions, such as useless superheat.
start-up and defrost, the compressor may operate • Minimum and maximum evaporating and
outside this envelope for short periods. condensing temperatures as per the operating
The figures below show the operating envelopes envelopes.
for VZH compressors with refrigerants R410A. • VZH drive can only protect the compressor from
Due to bearing loads and scroll stability, there over current. Customers need to have a high
will be speed restrictions on the envelops. pressure, low pressure sensor and discharge
The operating limits serve to define the temperature thermostat to fully protect the
envelope within which reliable operation of the envelop. Since out of map running will threaten
compressor is guaranteed: the reliability of compressor, customers must
• Maximum discharge gas temperature: +135°C. qualify map protection under all extreme
conditions.

VZH operating map - R410A (SH 6 K) Voltage: 400-460V/208-230V


-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 °F
70 157
152
65
60-100 rps 40-100 rps 147
142
60
Condensing temperature (°C)

137
55 30-100 rps 132
127
50 122
117
45 112
20-100 rps 107
40 102
97
35
92
30 87
82
25 77

20
15-100 rps 72
67
62
15 57
52
10 47
5 42
37
0 32

°C -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25


Evaporating temperature (°C)

VZH operating map - R410A (SH 6 K) Voltage: 380V


-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 °F
70 157
60-95 rps 152
65
40-95 rps 147
142
60
60-100 rps
Condensing temperature (°C)

137
55 30-100 rps 132
127
50 40-100 rps 122
117
45 112
20-100 rps 107
40 102
97
35
92
30 87
82
25 77

20
15-100 rps 72
67
62
15 57
52
10 47
5 42
37
0 32

°C -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25


Evaporating temperature (°C)

Short cycle timer function Short cycle control is provided directly by the Short cycle settings are accessible in the
CDS803 frequency converter, when parameter parameter 28.0x list, in the “compressor functions”
28-00 is enabled. menu.
The function is factory set to enabled, with If system is fully controlled by an external main
minimum running time to 60 seconds and the controller, it is recommended to limit the start/
interval between starts to 300 seconds. stop frequency to 12 times per hour.

FRCC.PC.034.A3.02 25
Application Guidelines Operating conditions Single compressors

Discharge gas thermostat Discharge gas temperature (DGT) protection which illustrate where DGT protection is required
is required if the high and low pressure switch (Ex. 1) and where it is not (Ex. 2). Please notice the
settings do not protect the compressor against envelope boundaries change based on different
operations beyond its specific application speed limits.
envelope. Please refer to the examples below,
75
70
it
65 lim
T-
60 DG HP1
Example 1

Condensing temperature (°C)


55
HP2
50 Example 2
45

40
35

30
25
R410A
20
15

10
5
LP1 LP2
0
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25
Evaporating temperature (°C)

Example 1 (R410A, SH = 6 K) Example 2 (R410A, SH = 6 K)


LP switch setting: LP switch setting:
LP1 = 3.3 bar (g) (-15.5°C) LP2 = 4.6 bar (g) (-10.5°C)
HP switch setting: HP switch setting:
HP1 = 38 bar (g) (62°C) HP2 = 31 bar (g) (52°C)
Risk of operation beyond the application envelope. No risk of operation beyond the application envelope.
DGT protection required. No DGT protection required.

The discharge gas temperature must not exceed by reverse rotation or loss of charge. A customer
135°C. might select NTC thermistor, 10KOhm@25°C type
from “TOD Company” and this type of sensor
A discharge gas temperature protection device could be fit into VZH top shell directly. However,
must be installed on all heat pumps. In reversible if OEM would like to use their own thermostat,
air-to-air and air-to-water heat pumps, the the thermostat is recommended to install on
discharge temperature must be monitored top of the shell for monitoring high discharge
during development test by the equipment temperature and reverse rotation as well as
manufacturer. loss of charge. The thermostat could also be
attached to the discharge line within 150 mm
The compressor must not be allowed to cycle from the compressor discharge port and must
on the discharge gas thermostat. Continuous be thermally insulated and tightly fixed to the
operations beyond the compressor’s operating pipe. Then another sensor should be installed at
range will cause serious damage to the top of shell to monitor loss of charge and reverse
compressor. rotation.

VZH028-044 can install a discharge sensor/ dome


sensor at the top of shell through a bracket and Bracket at the shell top This side up
the sensor has to been connected and controlled
by OEM controller. By installing it at the top of
shell, the discharge sensor can monitor discharge
temperature and work with OEM controller to
limit discharge temperature within 135°C, also
could observe extreme high temperature caused

26 FRCC.PC.034.A3.02
Application Guidelines Operating conditions Single compressors

Oil return management An insufficient oil level can be the result of oil Oil return function: To double ensure well
function (single depositing itself in pipes and heat exchangers lubrication, compressor speed will boost to 40
compressor) or low velocity of compressors. The oil return rps (minimum ORM Boost Speed, 28-17) at a fixed
management could be achieved by increasing time intervals (as programmed in parameter 28-
velocity for short periods, at regular time 12, default 24 hrs) any way. OEM could set 28-17
intervals. to a higher speed, such as 70 rps to secure oil
management
CDS803 integrates oil return management
function together with compressor internal According to different application requirements,
lubrication protection. OEM can either add oil separator (including to
add more oil in the system) or adjust oil return
Internal lubrication protection: If compressor parameters or might need both actions to keep
runs below 40 rps (ORM Min Speed Limit, 28-15) oil safety for compressor.
for more than 19 minutes (low speed running
time, 28-11), then CDS803 internal lubrication Oil management related parameters, 28-11, 28-
function will accelerate compressor speed to 12, 28-13,28-15, 28-17 could also be programmed
40 rps (minimum ORM Boost Speed, 28-17) for by OEM.
1 minute (minimum duration, includes ramp
up time, 28-13) to guarantee compressor inner Considering oil return risk, a split system
parts get lubricated. In case slow acceleration with more than 10 m piping length requires
condition, please make sure compressor maintain mandatory application approval by Danfoss
minimum speed 40 rps (80Hz) for at least 1 application specialists.
minute running.

ID Name Factory setup Unit


2810 Oil return management ON
2811 Low speed running time 19 min
2812 Fixed boost interval 24 h
2813 Boost duration 60 s
2815 ORM min speed limit 80 Hz
2817 ORM boost speed (Hz) 80 Hz

Oil return management Use the “oil level switch” accessory with the fitting preassembled and refer to the “VZH hybrid
in hybrid manifolding appropriate compressor housing having the manifolding” section at the end of this document.

FRCC.PC.034.A3.02 27
Application Guidelines Operating conditions Single compressors

High and low pressure


protection

High pressure According to EN378-2, a high-pressure (HP) safety Please note port 27 is not UL certificated and
switch is required to shut down the compressor. when connected with high pressure switch, no
The high-pressure switch can be set to lower delay is permitted. OEM need to set port 27 to
values depending on the application and “coast reverse/coast and reset inverse” to get rid
ambient conditions. The HP switch must either be of minimum running time restriction.
placed in a lockout circuit or consist of a manual
reset device to prevent cycling around the high-
pressure limit. If a discharge valve is used, the HP
switch must be connected to the service valve
gauge port, which must not be isolated. The HP
switch can be connected to the CDS803 input
27 or an external contactor which could be set
before or after the drive.

Low pressure A low-pressure (LP) safety switch must be operations of the compressor. LP switch settings
used. Deep vacuum operations of a scroll for pump-down cycles with automatic reset are
compressor can cause internal electrical arcing also listed in the table below. The lock-out circuit
and scroll instability. VZH compressors exhibit or LP switch or series with other safety devices
high volumetric efficiency and may draw very could be connected to CDS803 input 27. The low
low vacuum levels, which could induce such pressure switch must have the highest priority
a problem. The minimum low-pressure safety that shall not be by passed. It means when
switch (loss-of-charge safety switch) setting is low pressure switch is activated, compressor
given in the following table. For systems without minimum running time should not work. OEM
pump-down, the LP safety switch must either be need to set port 27 to “coast reverse/coast and
a manual lockout device or an automatic switch reset inverse” to get rid of minimum running time
wired into an electrical lockout circuit. The LP restriction.
switch tolerance must not allow for vacuum

Pressure settings
Pressure settings R410A
Working pressure range high side bar (g) 8.3 - 41.1 bar
Working pressure range low side bar (g) 1.5-13.9 bar
Maximum high pressure safety switch setting bar (g) 43.75
Minimum low pressure safety switch setting * bar (g) 1.0
Minimum low pressure pump-down switch setting ** bar (g) 1.18
* LP safety switch shall never be bypassed.
** Recommended pump-down switch settings: 2.2 bar below nominal evaporating temperature with minimum of 1.18

Electronic expansion valve With variable capacity systems, an electronic compressor. The EXV can also be opened, up
expansion valve (EXV) is the strongly to a certain degree, before the start up of the
recommended solution to handle refrigerant compressor.
mass flow variations. Danfoss recommends the
use of ETS products. Ramp-up and ramp-down Ramp-down of the EXV must be longer than the
settings, of both EXV and compressor, must be ramp-down of the compressor, also to avoid low
done with great care. pressure operation (except with pump-down).

Ramp-up of the EXV must be shorter than EXV should be closed, and remain closed,
the ramp-up of the compressor, to avoid any when the compressor is off, to avoid any liquid
low pressure operation on suction side of the refrigerant entering the compressor.

Crankcase heating function There is no crankcase heating function in be preferred. Refer to accessory list for code
CDS803. An external crankcase heater is numbers.
required, and surface sump heater type should

28 FRCC.PC.034.A3.02
Application Guidelines System design recommendations Single compressors

Essential piping design The working pressure in systems with R410A is the refrigerant piping must be reduced in size
considerations about 60% higher than in systems with R22 or compared to R22 / R407C systems. Take care
R407C. Consequently, all system components and also to not create overly high pressure drops
piping must be designed for this higher pressure as in R410A systems the negative impact of
level. high pressure drops on the system efficiency is
Proper piping practices should be employed to stronger than in R22/R407C systems.
ensure adequate oil return, even under minimum The design in this guideline is for short circuit
load conditions with special consideration given application. However, for long circuit and split
to the size and slope of the tubing coming system application, an oil separator and an
from the evaporator. Tubing returns from the external non-return valve are recommended for
evaporator should be designed so as not to trap use based on system qualification status.
oil and to prevent oil and refrigerant migration CDS803 frequency converter integrates a special
back to the compressor during off-cycles. feature in the compressor functions in order
In systems with R410A, the refrigerant mass to improve and secure the oil recovery from
flow will be lower compared to R22/R407C the system. Refer to “Oil Return Management”
systems. To maintain acceptable pressure section.
drops and acceptable minimum gas velocities,

Piping should be designed with adequate from abrasion. Aside from tubing and connection
three-dimensional flexibility. It should not be in damage, excess vibration may also transmitted
contact with the surrounding structure, unless to the surrounding structure and generate an
a proper tubing mount has been installed. unacceptable noise level within that structure.
This protection proves necessary to avoid For more information on noise and vibration, see
excess vibration, which can ultimately result in “Sound and Vibration Management” section.
connection or tube failure due to fatigue or wear

Suction lines If the evaporator lies above the compressor, as


To condenser
is often the case in split or remote condenser
HP
systems, the addition of a pump-down cycle
U-trap
is strongly recommended. If a pump-down
cycle were to be omitted, the suction line must 0.5% slope LP
4 m/s or more
have a loop at the evaporator outlet to prevent
refrigerant from draining into the compressor max. 4 m

during off-cycles. U-trap, as short as possible


If the evaporator were situated below the
8 to 12 m/s
compressor, the suction riser must be trapped so max. 4 m
as to prevent liquid refrigerant from collecting at Evaporator
0.5% slope
the outlet of the evaporator while the system is
4m/s or more
idle, which would mislead the expansion valve’s
U trap, as short as possible
sensor (thermal bulb) at start-up.

Discharge lines When the condenser is mounted at a higher must be applied between discharge U-trap and
position than the compressor, a suitably sized upper U-trap where the condenser is above the
U-shaped trap close to the compressor is compressor unit.
necessary to prevent oil leaving the compressor We also recommend installing one check valve
from draining back to the discharge side of the on the discharge line to the condenser next to
compressor during off cycle. The upper loop also the condenser to avoid the possibility of having
helps avoid condensed liquid refrigerant from the discharge tube full of liquid during off cycles;
draining back to the compressor when stopped. discharge lines flooded by liquid which may
For inverter applications with long lines we create start-up issues by drive over-torque or HP
recommend the use of an oil separator even if it switch trip.
is only the condenser which is far away from the Upper loop

unit.
Piping must also be designed with care in order
to make sure the remaining oil not trapped by HP
the oil separator is properly carried over the U Trap Condenser
system.
Basic principal is shown here. Note that for the LP
3D flexibility
discharge line, following the same principle
as for the suction line with a U-trap every 4 m

FRCC.PC.034.A3.02 29
Application Guidelines System design recommendations Single compressors

Heat exchangers To obtain optimum efficiency of the complete A sub-cooler circuit in the condenser that creates
refrigerant system, optimized R410A heat high sub-cooling will increase efficiency at
exchangers must be used. R410A refrigerant has high condensing pressure. In R410A systems
good heat transfer properties: it is worthwhile the positive effect of sub-cooling on system
designing specific heat exchangers to gain in size efficiency will be significantly larger than in R22/
and efficiency. R407C systems.

An evaporator with an optimized R410A Furthermore, for good operation of the


distributor and circuit will give correct superheat expansion device and to maintain good
at outlet and optimal use of the exchange efficiency in the evaporator it is important to
surface. This is critical for plate evaporators that have an adequate liquid sub-cooling. Without
generally have a shorter circuit and a lower adequate sub-cooling, flash gas will be formed at
volume than shell & tubes and air cooled coils. the expansion device resulting in a high degree
of vapor at the evaporator inlet leading to low
For all evaporator types, special care is required efficiency.
for superheat control leaving the evaporator and
oil return.

Refrigerant charge limits VZH compressors can tolerate liquid refrigerant If the refrigerant charge exceeds the values
up to a certain extend without major problems. in table below, a suction line accumulator is
However, excessive liquid refrigerant in the strongly recommended.
compressor is always unfavorable for service life.
Besides, the installation cooling capacity may Model Refrigerant charge limit (kg)
be reduced because of the evaporation taking VZH028-044 3.6
place in the compressor and/or the suction line
instead of the evaporator. System design must be More detailed information can be found in the
such that the amount of liquid refrigerant in the paragraphs hereafter. Please contact Danfoss
compressor is limited. In this respect, follow the technical support for any deviation from these
guidelines given in the section: “Essential piping guidelines.
design recommendations” as a priority.

Off-cycle migration Liquid refrigerant can find its way into the elements), which must be avoided as it causes
compressor by means of off-cycle migration or irreversible damage to the compressor.
liquid floodback during operation.
The presence of liquid in the crankcase can be
Off-cycle refrigerant migration is likely to occur easily detected by checking the sump level
when the compressor is located at the coldest through the oil sight glass. Foam in the oil sump
part of the installation, when the system uses indicates a flooded start.
a bleed-type expansion device, or if liquid is
allowed to migrate from the evaporator into VZH scroll compressors can tolerate occasional
the compressor sump by gravity. If too much flooded starts as long as the total system charge
liquid refrigerant accumulates in the sump it does not exceed the maximum compressor
will saturate the oil and lead to a flooded start: refrigerant charge limit.
when the compressor starts running again, the
refrigerant evaporates abruptly under the sudden Off-cycle migration can be prevented by
decrease of the bottom shell pressure, causing implementing a crankcase heating or adding a
the oil to foam. In extreme situations, this might pump-down cycle to the operation cycle and a
result in liquid slugging (liquid entering the scroll liquid line solenoid valve.

30 FRCC.PC.034.A3.02
Application Guidelines System design recommendations Single compressors

Crankcase heater / sump heater: When the temperature of the refrigerant on the low-
compressor is idle, the oil temperature in the pressure side. This requirement ensures that
sump of the compressor must be maintained the liquid refrigerant is not accumulating in the
at no lower than 6 K above the saturation sump. Refer to the flood back test criteria.

Floodback Requirement
22

20

18

16
ACCEPTABLE

Sump Superheat
14

12

10

4
UNACCEPTABLE
2

0
-30 -25 -20 -15 -10 -5 0 5 10 15 20
°C
Saturated Suction

A crankcase heater is only effective if capable of Provide separate electrical supply for the
sustaining this level of temperature difference. heaters so that they remain energized even
Tests must be conducted to ensure that the when the machine is out of service (eg. seasonal
appropriate oil temperature is maintained under shut-down).
all ambient conditions (temperature and wind).
Refer to section “Crankcase heating function” for
details and settings of crankcase heating function
integrated in the drive.

Liquid line solenoid valve (LLSV): An LLSV EXV also ensures this function. The quantity of
may be used to isolate the liquid charge on the refrigerant on the low-pressure side of the system
condenser side, thereby preventing against can be further reduced by using a pump-down
charge transfer or excessive migration to the cycle in association with the LLSV.
compressor during off-cycles. When installed,

Pump-down cycle: A pump-down cycle low side in order to prevent off-cycle migration.
represents one of the most effective ways to The recommended low-pressure pump-down
protect against the off-cycle migration of liquid switch setting is 1.5 bar below the nominal
refrigerant. Once the system has reached its set evaporating pressure. It shall not be set lower
point and is about to shut off, the LLSV on the than 2.3 bar.
condenser outlet closes. The compressor then
pumps the majority of the refrigerant charge into An external non return valve is recommended to
the condenser and receiver before the system avoid liquid flood back from the high-pressure
stops on the low pressure pump-down switch. side.
This step reduces the amount of charge on the

Liquid receiver: Refrigerant charge optimization The receiver shall be large enough to contain part
varies with compressor speed. To avoid flash of the system refrigerant charge, but shall not
gas at low speed, a receiver may be necessary. be too large, to avoid refrigerant overcharging
Receiver dimensioning requires special attention. during maintenance operations.

Liquid floodback during Danfoss recommends the use of an electronic conditions, and it protects the compressors from
operation expansion valve for all air conditioning flood back during adverse running conditions.
applications with VZH028-044 compressors. An Exceptions to the use of EXV’s with Danfoss
EXV has two key benefits: it provides modulating variable speed compressors must be approved by
control of the system under varying load Danfoss application engineering.

FRCC.PC.034.A3.02 31
Application Guidelines Specific application recommendations Single compressors

Low ambient compressor


operations

Low ambient start-up Under cold ambient conditions, upon start-up the table section “Pressure settings” in order to
the pressure in the condenser may be so low prevent this from happening.
that a sufficient pressure differential across
the expansion device cannot be developed to Low pressure differentials can also cause the
properly feed the evaporator. As a result, the expansion device to “hunt” erratically, which
compressor may go into abnormal low suction might cause surging conditions within the
pressure, which can lead to compressor failure. evaporator, with liquid spillover into the
Under no circumstances should the compressor compressor. This effect is most pronounced
be allowed to operate under vacuum. The low- during low load conditions, which frequently
pressure control must be set in accordance with occur during low ambient conditions.

Head pressure control under Several possible solutions are available to prevent Under very low ambient conditions, in which
low ambient conditions the compressor from drawing down to a vacuum testing has revealed that the above procedures
upon start-up under low ambient conditions. might not ensure satisfactory condensing and
In air-cooled machines, cycling the fans with suction pressures, the use of a liquid receiver
a head pressure controller will ensure that the with condenser and receiver pressure regulators
fans remain off until the condensing pressure would be possible.
has reached a satisfactory level. In water-cooled
units, the same can be performed using a water Condensing pressure control is also strongly
regulator valve that is also operated by head recommended to improve any system efficiency.
pressure, thereby ensuring that the water valve The most accurate value is to control the
does not open until the condensing pressure condensing temperature at 12 K above the
reaches a satisfactory level. ambient temperature for air cooled condensers.

Note: The minimum condensing pressure must For further information, please contact Danfoss
be set at the minimum saturated condensing Technical support.
temperature shown in the application envelopes.

Crankcase heaters A crankcase heating will minimize refrigerant Belt type crankcase heaters can be used, see
migration caused by the large temperature section "Accessory". They can be connected to
gradient between the compressor and the CDS803 relay 1 or 2.
remainder of the system.

Low load operations It is recommended that the unit is tested and • The superheat setting of the expansion
monitored at minimum load and, if possible, device should be sufficient to ensure proper
during low ambient conditions as well. During superheat levels during low loading periods. 5
conditions of low load on the system, the to 6 K stable superheat is required. In addition,
following considerations should be taken into the refrigerant charge should be sufficient
account to ensure proper system operating to ensure proper sub-cooling within the
characteristics. condenser so as to avoid the risk of flashing in
the liquid line before the expansion device. The
expansion device should be sized to ensure
proper control of the refrigerant flow into the
evaporator.

32 FRCC.PC.034.A3.02
Application Guidelines Specific application recommendations Single compressors

An oversized valve may result in erratic control. • The compressors should be run for a
This can lead to liquid refrigerant entering the minimum period in order to ensure that the
compressor if the expansion valve does not oil has sufficient time to properly return to
provide stable refrigerant super-heat control the compressor sump and that the motor has
under varying loads. sufficient time to cool under conditions of
• Condenser fans should be cycled in such a lowest refrigerant mass flows.
way that the minimum pressure differential is
maintained between the suction and discharge Refer to section “Oil return management
pressures. Inverter fans can also be used to function”.
control the amount of heat to be removed from
the condenser.

Brazed plate heat A brazed plate heat exchanger needs very little The suction line running from the heat exchanger
exchangers internal volume to satisfy the set of heat transfer to the compressor must be trapped to avoid
requirements. Consequently, the heat exchanger refrigerant migration to the compressor.
offers very little internal volume for the
compressor to draw vapor from on the suction When using a brazed plate condenser heat
side. The compressor can then quickly enter into exchanger, a sufficient free volume for the
a vacuum condition. It is therefore important discharge gas to accumulate is required in order
that the expansion device be sized correctly to avoid excess pressure build-up. At least 1
and that a sufficient pressure differential across meter of discharge line is necessary to generate
the expansion device be available to ensure this volume. To help reduce the gas volume
adequate refrigerant feed into the evaporator. immediately after start-up even further, the
This aspect is of special concern when operating supply of cooling water to the heat exchanger
the unit under low ambient and load conditions. may be opened before the compressor starts
For further information on these conditions, up so as to remove superheat and condense the
please refer to the previous sections. incoming discharge gas more quickly.

Due to the small volume of the brazed plate heat Because of the large compressor capacity
exchanger, no pump-down cycle is normally variation and VZH capability to run at low
required. condensing temperature an EXV (electronic
expansion valve) is mandatory.

Reversible heat pump Transients are likely to occur in reversible heat 1 minute at 50 rps each time after reverse.
systems pump systems, i.e. a changeover cycle from Regardless of the refrigerant charge in the
cooling to heating, defrost or low-load short system, specific tests for repetitive flood-back
cycles. These transient modes of operation are required to confirm whether or not a suction
may lead to liquid refrigerant carry-over (or accumulator needs to be installed. The following
flood-back) or excessively wet refrigerant return considerations cover the most important issues
conditions. As such, reversible cycle applications when dealing with common applications.
require specific precautions in order to ensure a Each application design however should
long compressor life and satisfactory operational be thoroughly tested to ensure acceptable
function. Compressors need to run at least operating characteristics.

Discharge temperature Heat pumps frequently utilize high condensing from excessive temperatures. Operating the
monitoring temperatures in order to achieve a sufficient compressor at too high discharge temperatures
temperature rise in the medium being heated. can result in mechanical damage to the
At the same time, they often require low compressor as well as thermal degradation of the
evaporating pressures to obtain sufficient compressor lubricating oil and a lack of sufficient
temperature differentials between the evaporator lubrication.
and the outside temperature. This situation
may result in high discharge temperature; as Refer to the “Discharge gas thermostat” section
such, it is mandatory that a discharge gas safety for frequency converter settings and accessories
control is included to protect the compressor availability.

FRCC.PC.034.A3.02 33
Application Guidelines Specific application recommendations Single compressors

Discharge line and reversing The VZH scroll compressor is a high volumetric gas to collect and to reduce the pressure peak
valve machine and, as such, can rapidly build up during the time it takes for the valve to change
pressure in the discharge line if gas in the line position. At the same time, it is important that
becomes obstructed even for a very short period the selection and sizing of the reversing or 4-way
of time which situation may occur with slow- valve ensure that the valve switches quickly
acting, reversing valves in heat pumps. Discharge enough to prevent against too high discharge
pressures exceeding the operating envelope may pressure and nuisance high-pressure cutouts.
result in nuisance high-pressure switch cutouts
and can generate excessive load on bearings and Check with the valve manufacturer for optimal
motor. sizing and recommended mounting positions.

To prevent such occurrences, it is important that It is strongly recommended to reduce the


a 1-meter minimum discharge line length be compressor speed to 25/30 rps before the 4-way
allowed between the compressor discharge port valve is moved from a position to another.
and the reversing valve or any other restriction.
This gives sufficient free volume for the discharge Refer also to high and low pressure protection.

Defrost and reverse cycle After the 4-way valve is moved to defrost When the compressor is started again each time,
position, and in order to shorten the defrost compressor will run at 50 rps for at least 1 minute.
period, the compressor speed can be maintained Thus to avoid excessive liquid refrigerant to come
at 70 rps or higher speed during the defrost back to the compressor sump.
period.

Suction line accumulator The use of a suction line accumulator is strongly the cycle switches back to a defrost cycle or to
recommended in reversible-cycle applications. normal cooling operations.
This because of the possibility of a substantial
quantity of liquid refrigerant remaining in the Sustained and repeated liquid slugging and
evaporator, which acts as a condenser during the floodback can seriously impair the oil’s ability to
heating cycle. lubricate the compressor bearings. This situation
can be observed in wet climates where it is
This liquid refrigerant can then return to the necessary to frequently defrost the outdoor
compressor, either flooding the sump with coil in an air source heat pump. In such cases a
refrigerant or as a dynamic liquid slug when suction accumulator becomes mandatory.

Water utilizing systems Apart from residual moisture in the system Corrosion: Materials in the system shall be safe to
after commissioning, water could also enter the use with water and protected against corrosion.
refrigeration circuit during operation. Water in
the system should always be avoided. Not only Freezing: When water freezes into ice its volume
because it can quickly lead to electrical failure, expands which can damage heat exchanger
sludge in sump and corrosion but in particular walls and cause leaks. During off periods water
because it can cause serious safety risks. inside heat exchangers could start freezing when
ambient temperature is lower than 0°C. During
Common causes for water leaks are corrosion and on periods ice banking could occur when the
freezing. circuit is running continuously at too low load.
Both situations should be avoided by connecting
a pressure and thermostat switch in the safety
line.

34 FRCC.PC.034.A3.02
Application Guidelines Sound and vibration management Single compressors

Running sound level For all VZH models, noise level given in table does not include bottom hood attenuation.
200 V 400 V
Model Frequency RPS Without accoustic hood With accoustic hood Without accoustic hood With accoustic hood
(dBA) (dBA) (dBA) (dBA)
60 77 70 77 70
VZH028-044
100 86 79 86 79
Average sound power for reference at ARI A/C conditions measured in free space.
Please notice below two phenomenon is also normal for variable speed compressor:
1. At light load and low speed condition the compressor may produce certain discharge pulsation.
2. In some situations when the compressor stops working, there may still be some noise which lasts around 2 seconds. The electromagnetic noise is caused by drive anti-reverse
protection.

Sound generation in a Typical sound and vibration in refrigeration and Mechanical vibrations: These generally extend
refrigeration or air air conditioning systems encountered by design along the parts of the unit and structure.
conditioning system and service engineers may be broken down into Gas pulsation: This tends to travel through the
the following three source categories. cooling medium, i.e. the refrigerant.
Sound radiation: This generally takes an
airborne path. The following sections focus on the causes and
methods of mitigation for each of the above
sources.

Compressor sound For sound radiating from the compressor, the outside. Ensure that no components capable
radiation emission path is airborne and the sound waves of transmitting sound/vibration within the unit
travel directly from the machine in all directions. come into direct contact with any non insulated
parts on the walls of the unit.
The VZH scroll compressor is designed to be
quiet and the frequency of the sound generated Because of the VZH unique design of a full-
is pushed into the higher ranges, which not only suction gas-cooled motor, compressor body
are easier to reduce but also do not generate the insulation across its entire operating range is
penetrating power of lower-frequency sound. possible. Acoustic hoods are available from
Danfoss as accessories. These hoods are quick
Use of sound-insulation materials on the inside of and easy to install and do not increase the overall
unit panels is an effective means of substantially size of the compressors to a great extent.
reducing the sound being transmitted to the

Mechanical vibrations Vibration isolation constitutes the primary plate to the unit are held to a strict minimum.
method for controlling structural vibration. VZH In addition, it is extremely important that the
scroll compressors are designed to produce frame supporting the mounted compressor be of
minimal vibration during operations. The use of sufficient mass and stiffness to help dampen any
rubber isolators on the compressor base plate or residual vibration potentially transmitted to the
on the frame of a manifolded unit is very effective frame.
in reducing vibration being transmitted from
the compressor(s) to the unit. Once the supplied For further information on mounting
rubber grommets have been properly mounted, requirements, please refer to the section on
vibrations transmitted from the compressor base mounting assembly.

Speed by-pass If vibrations occurs at some typical frequencies vibration levels, speed by-pass is adjustable
of the VZH variable speed compressor system, in the frequency converter, in order to avoid
design must be checked: frame, piping, some frequency ranges. Four by-pass ranges
pipes using cushioned clamps. But if some are adjustable, and settings can be made in
frequencies continue to produce unacceptable parameter group 4-6.

Gas pulsation The VZH scroll compressor has been designed conditions and operating configurations to
and tested to ensure that gas pulsation has been ensure that minimum gas pulsation is present. If
optimized for the most commonly encountered an unacceptable level is identified, a discharge
air conditioning pressure ratios. On heat pump muffler with the appropriate resonant volume
installations and other installations where the and mass should be installed. This information
pressure ratio lies beyond the typical range, can be obtained from the component
testing should be conducted under all expected manufacturer.

FRCC.PC.034.A3.02 35
Application Guidelines Installation Single compressors

Each compressor is shipped with printed http://instructions.cc.danfoss.com


instructions for installation. These instructions
can also be downloaded from:

Compressor handling Each VZH scroll compressor is equipped with or that the compressor could separate from the
one lift ring on the top shell. Always use the base frame with extensive damage and possible
ring when lifting the compressor. Use lifting personal injury as a result.
equipment rated and certified for the weight
of the compressor. A spreader bar rated for the Never apply force to the terminal box with the
weight of the compressor is highly recommended intention of moving the compressor, as the
to ensure a better load distribution. The use force placed upon the terminal box can cause
of lifting hooks closed with a clasp certified to
lift the weight of the compressor is also highly
recommended. Always respect the appropriate
HEAVY
rules concerning lifting objects of the type and
weight of these compressors. Maintain the
compressor in an upright position during all
handling operations.
do not lift
When the compressor is mounted as part of manually
an installation, never use the lift rings on the
compressor to lift the installation. The risk is that extensive damage to both the box and the
the lugs could separate from the compressor components contained inside.

Mounting Maximum inclination from the vertical plane,


while operating must not exceed 7 degrees.
All compressors are delivered with four rubber
grommets and metal sleeves. Compressors
29.5
must always be mounted with these grommets.
Recommended torque for mounting bolts: 11 Nm
(±1 Nm).
Ø11
Ø 41
Recommended torque for
mounting bolts: 11 Nm (±1 Nm)

Removing connections Before the suction and discharge plugs are the compressor to the installation in order to
shipping plugs removed, the nitrogen holding charge must be avoid moisture from entering the compressor.
released via the suction schrader valve to avoid When the plugs are removed, it is essential to
an oil mist blowout. Remove the suction plug keep the compressor in an upright position so as
first and the discharge plug afterwards. The plugs to avoid oil spillage.
should be removed only just before connecting

36 FRCC.PC.034.A3.02
Application Guidelines Installation Single compressors

System cleanliness The refrigerant compression system, regardless operation. The presence of non-condensable
of the type of compressor used, will only provide substances and system contaminants such as
high efficiency and good reliability, along with metal shavings, solder and flux, have a negative
a long operating life, if the system contains impact on compressor service life. Many of these
solely the refrigerant and oil it was designed contaminants are small enough to pass through a
for. Any other substances within the system mesh screen and can cause considerable damage
will not improve performance and, in most within a bearing assembly.
cases, will be highly detrimental to a system’s

The use of highly hygroscopic polyolester oil • Brazing and welding oxides,
in R410A compressors requires that the oil be • Filings and particles from the removal of burrs in
exposed to the atmosphere as little as possible. pipe-work,
System contamination is one of main factors • Brazing flux,
affecting equipment reliability and compressor • Moisture and air.
service life. It is important therefore to take
system cleanliness into account when assembling Consequently, when building equipment
a refrigeration system. During the manufacturing and assemblies, the precautions listed in the
process, circuit contamination may be caused by: following paragraphs must be taken.

Tubing Only use clean and dehydrated refrigeration both a design and size to allow for a minimum
grade copper tubing. Tube-cutting must be pressure drop through the completed assembly.
carried out so as not to deform the tubing Follow the brazing instructions bellow. Never drill
roundness and to ensure that no foreign debris holes into parts of the pipe-work where filings
remains within the tubing. Only refrigerant grade and particles can not be removed.
fittings should be used and these must be of

Filter driers For new installations with VZH compressors with The drier is to be oversized rather than
polyolester oil, Danfoss recommends using the undersized. When selecting a drier, always take
Danfoss DML 100% molecular sieve, solid core into account its capacity (water content capacity),
filter drier. Molecular sieve filter driers with loose the system refrigeration capacity and the system
beads from third party suppliers shall be avoided. refrigerant charge.
For servicing of existing installations where acid
formation is present the Danfoss DCL solid core
filter driers containing activated alumina are
recommended.

Brazing and soldering

Copper to copper When brazing copper-to-copper connections, temperature of below 800°C is recommended. No
connections the use of copper/phosphorus brazing alloy flux is required during brazing.
containing 5% silver or higher with a melting

Dissimilar metals When manipulating dissimilar metals such as


connections copper and brass or steel, the use of silver solder
and anti-oxidant flux is required.

Compressor connection When brazing the compressor fittings, do not


heat shield
overheat the compressor shell, which could
severely damage certain internal components
due to excessive heating. Use of a heat shield C
B
and/or a heat-absorbent compound is highly A

recommended. Due to the relatively sizable


tubing and fitting diameters a double-tipped
torch using acetylene is recommended for
brazing operation on VZH compressors.

FRCC.PC.034.A3.02 37
Application Guidelines Installation Single compressors

For brazing the suction and discharge • Remove all remaining flux “once the joint has
connections, the following procedure is advised: been soldered” with a wire brush or a wet cloth.
• Make sure that no electrical wiring is connected Remaining flux would cause corrosion of the
to the compressor. tubing.
• Protect painted surfaces on the terminal box
and compressor from torch heat damage (see Ensure that no flux is allowed to enter into the
diagram). tubing or compressor. Flux is acidic and can cause
• Remove the Teflon gaskets when brazing substantial damage to the internal parts of the
rotolock connectors with solder sleeves. system and compressor.
• Use only clean, refrigeration-grade copper
tubing and clean all connections. The polyolester oil used in VZH compressors
• Use brazing material with a minimum of 5% is highly hygroscopic and will rapidly absorb
silver content. moisture from the air. The compressor must
• Purge nitrogen or CO2 through the compressor therefore not be left open to the atmosphere
in order to prevent against oxidation and for a long period of time. The compressor fitting
flammable conditions. The compressor should plugs shall be removed just before brazing the
not be exposed to the open air for extended compressor. The compressor should always be
periods. the last component brazed into the system
• Use of a double-tipped torch is recommended.
• Apply heat evenly to area A until the brazing Before eventual unbrazing the compressor or
temperature is reached. Move the torch to any system component, the refrigerant charge
area B and apply heat evenly until the brazing must be removed from both the high- and
temperature has been reached there as well, low-pressure sides. Failure to do so may result in
and then begin adding the brazing material. serious personal injury. Pressure gauges must be
Move the torch evenly around the joint, in used to ensure all pressures are at atmospheric
applying only enough brazing material to flow level.
the full circumference of the joint.
• Move the torch to area C only long enough to For more detailed information on the appropriate
draw the brazing material into the joint, but not materials required for brazing or soldering, please
into the compressor. contact the product manufacturer or distributor.
For specific applications not covered herein,
please contact Danfoss for further information.

High voltage test Carry out a high voltage test by short-circuiting motor compressor test can be conducted
terminals U, V, W, L1, L2 and L3. Energize by max. together. When conducting a high voltage test
1920 V DC for code G compressors and 1460 V DC make sure the system is not under vacuum: this
for code J compressors for one second between may cause electrical motor compressor failure.
this short-circuit and the chassis. When running Please note, it is note recommended that a high-
high voltage tests of the entire installation, voltage test be carried out too often as it may
frequency converter and compressor electrical damage the motor.

38 FRCC.PC.034.A3.02
Application Guidelines Installation Single compressors

Leak detection Leak detection must be carried out using a


Leak detection Leak detection
mixture of nitrogen and refrigerant or nitrogen with refrigerant with a mass spectrometer
and helium, as indicated in the table below.
Never use other gasses such as oxygen, dry air Nitrogen & R410A Nitrogen & Helium
or acetylene as these may form an inflammable
mixture.

Pressurize the system on HP side first then LP


side.

Vacuum pump down and Moisture obstructs the proper functioning these phenomena may cause both mechanical
moisture removal of both the compressor and the refrigeration and electrical compressor failures. The typical
system. Air and moisture reduce service life and method for avoiding such problems is a vacuum
increase condensation pressure, which causes pump-down executed with a vacuum pump, thus
abnormally high discharge temperatures that creating a minimum vacuum of 500 microns (0.67
are then capable of degrading the lubricating mbar). Please refer to News bulletin
properties of the oil. The risk of acid formation Tl1-026-0302 “Vacuum pump down and
is also increased by air and moisture, and this dehydration procedure”.
condition can also lead to copper plating. All

Refrigerant charging For the initial charge, the compressor must not in liquid phase: slowly throttling liquid in on the
run and eventual service valves must be closed. low pressure side as far away as possible from the
Charge refrigerant as close as possible to the compressor suction connection. The refrigerant
nominal system charge before starting the charge quantity must be suitable for both
compressor. This initial charging operation must summer and winter operations.
be done in liquid phase as far away as possible
from the compressor. The best location is on the Refer to news bulletin FRCC.EN.050 “Danfoss
liquid line between the condenser outlet and the Commercial Compressors recommended
filter drier. Then during commissioning, when refrigerant system charging practice” for more
needed, a complement of charge can be done details.

Commissioning The system must be monitored after initial A short cycling protection is provided in the
startup for a minimum of 60 minutes to ensure CDS803 frequency converter. It is factory preset
proper operating characteristics such as: “enabled” with the following parameters in:
• Proper metering device operation and desired 28.01 - interval between 2 starts: 300 secondes
superheat readings 28.02 - minimum run time: 60 seconds.
• Suction and discharge pressure are within
acceptable levels This minimum run time is set to guaranty long
• Correct oil level in compressor sump indicating enough running time at start up in order to
proper oil return create enough refrigerant flow velocity in the
• Low foaming in sight glass and compressor system to recover the oil to the compressor
sump temperature 10K above saturation sump.
temperature to show that there is no refrigerant • Current draw of compressor within acceptable
migration taking place values (RLA ratings)
• Acceptable cycling rate of compressors, • No abnormal vibrations and noise.
including duration of run times.

Note this compressor is equipped with 15 rps(900 rpm) up to 200 Hz for 100 rps (6000
a four-pole electrical motor so the applied rpm).
frequency from the inverter will be 30 Hz for

FRCC.PC.034.A3.02 39
Application Guidelines Installation Single compressors

Oil level checking and In installations with good oil return and line The oil level can also be checked a few minutes
top-up runs up to 15 m, no additional oil is required. If after the compressor stops, the level must be
installation lines exceed 15 m, additional oil may between ¼ and ¾ of sight glass.
be needed. 1 or 2% of the total system refrigerant
charge (in kg) can be used to roughly define the When the compressor is off, the level in the
required oil top-up quantity (in liters) but in any sight glass can be influenced by the presence of
case the oil charge has to be adjusted based on refrigerant in the oil.
the oil level in the compressor sight glass.
Always use original Danfoss PVE Oil from new
When the compressor is running under stabilized cans.
conditions, the oil level must be visible in the
sight glass. Top-up the oil while the compressor is idle. Use
the schrader connector or any other accessible
The presence of foam filling in the sight glass connector on the compressor suction line and
indicates large concentration of refrigerant in the a suitable pump. See news bulletin “Lubricants
oil and / or presence of liquid returning to the filling in instructions for Danfoss Commercial
compressor. Compressors.”

40 FRCC.PC.034.A3.02
Application Guidelines Trouble shooting Single compressors

c


  
 





a
 

 




&  
 s & w


 c
  w

ms

s 


06/03/2015 page 1




   


f  
o 
O 

 Check HP/LP e


 switch

c

Reset & start 



 
b
s
Smains a



l



06/03/2015 page 2

FRCC.PC.034.A3.02 41
Application Guidelines Trouble shooting Single compressors




 
 
heating overheating


t 




 



o



m 


r

06/03/2015 page 3

06/03/2015 page 4

42 FRCC.PC.034.A3.02
Application Guidelines Trouble shooting Single compressors




 

 


   
 

    


   

 
   





06/03/2015 page 5

FRCC.PC.034.A3.02 43
Application Guidelines Ordering information and packaging Single compressors

Kit ordering and shipping The tables on the following pages give code compressor and CDS803 frequency converter kit
numbers for ordering purposes for the VZH packed and shipped separately.

Packaging

Compressor single pack


Height Width Depth Weight
Compressor model (mm) (mm) (mm) (kg)

VZH028/035/044 464 292 286 30

Frequency converter single IP20


pack Drive supply Compressor Drive
voltage enclosure Width Depth Weight
CD803 packaging Height (mm) (mm) (mm) (kg)
VZH028/035 H4 380 250 375 7.9
T2: Code J
VZH044 H5 420 290 375 9.5
Height

Depth VZH028/035 H3 255 100 206 4.5


T4: Code G
Width VZH044 H4 380 250 375 7.9

Ordering information VZH scroll compressors and drive can be ordered


in single packs. Please use the code numbers
from below tables for ordering.

Compressors
G J
Equipment 380-480V/3ph/50&60Hz 200-240V/3ph/50&60Hz
Compressor model
version
Compressor Name Code NO Compressor Name Code NO

VZH028 Single VZH028CGANA 120G0061 VZH028CJANA 120G0064


Single VZH035CGANA 120G0060 VZH035CJANA 120G0063
VZH035
Manifold VZH035CGBNA 120G0073 VZH035CJBNA 120G0076
Single VZH044CGANA 120G0059 VZH044CJANA 120G0062
VZH044
Manifold VZH044CGBNA 120G0072 VZH044CJBNA 120G0075

44 FRCC.PC.034.A3.02
Application Guidelines Ordering information and packaging Single compressors

VZH converter order information

CDS803 drive

Voltage Compressor Description Code NO

VZH028 CDS803P6K0T2E20H4 134N4260


T2 VZH035 CDS803P7K5T2E20H4 134N4261
200-240V/3ph/50&60Hz
VZH044 CDS803P10KT2E20H4 134L9470
VZH028 CDS803P6K0T4E20H4 134N4262
T4 VZH035 CDS803P7K5T4E20H4 134N4263
380-480V/3ph/50&60Hz
VZH044 CDS803P10KT4E20H4 134L9473

LCP: user interface 120Z0581 (accessory)

FRCC.PC.034.A3.02 45
Application Guidelines Accessories Single compressors

Rotolock adaptor

Type Code n° Description Application Packaging Pack size


VZH028-044
120Z0366 Rotolock adaptor (1-1/4" ~ 3/4") Multipack 10
suction
VZH028-044
120Z0365 Rotolock adaptor (1" ~ 1/2") Multipack 10
discharge

Valves, adapters, connectors & gaskets for use on suction and discharge connections
Solder sleeve adapter sets
Type Code n° Description Application Packaging Pack size
Solder sleeve adapter set (1"1/4 Rotolock, 3/4" ODF),
120Z0126 VZH028-044 Multipack 6
(1" Rotolock, 1/2" ODF)

Crankcase heaters & thermostats


Crankcase heaters
Type Code n° Description Application Packaging Pack size
120Z5040 Belt type crankcase heater,65W,230V,CE mark,UL(wire length: 1270mm) Multipack 4
VZH028-044
120Z5041 Belt type crankcase heater,55/70W,400/460V,CE mark,UL(wire length: 1270mm) Multipack 4

Lubricant, acoustic hoods and spare parts


Acoustic hoods
Type Code n° Description Application Packaging Pack size
120Z5043 Acoustic hood VZH028-044 Single pack 1

46 FRCC.PC.034.A3.02
Application Guidelines Accessories Single compressors

Mounting kits

Type Code n° Description Application Packaging Pack size


Mounting kit for 1 scroll compressor including 4
120Z0622 grommets, 4 sleeves, 4 bolts, 4 washers, 2 grounding VZH028-044 Single pack 1
screws

Terminal boxes, covers & T-block connectors

Type Code n° Description Application Packaging Pack size


120Z5015 Terminal box cover VZH028-044 Multipack 10

Oil level switch

Type Code  n° Description Application Packaging Pack size


120Z0560 Oil level switch screw in- mechanical part all models Single pack 1
120Z0561 Oil level switch - electrical part (24V AC/DC) all models Single pack 1
120Z0562 Oil level switch - electrical part (230V AC) all models Single pack 1

Spare parts frequency converter

LCP’s

Type Code n° Description Application Packaging Pack size


120Z0581 LCP Frequency converter / all models Single pack 1
120Z0617 LCP kit for remote mounting Frequency converter / all models Single pack 1

Decoupling Plate

Compressor
Frame Decoupling plate Packaging Pack size
200-240V 380-480V
H3 - VZH028/035 120Z0582 Single pack 1
H4 VZH028/035 VZH044 120Z0583 Single pack 1
H5 VZH044 - 120Z0583 Single pack 1
Note: use the decoupling plate for EMC correct installation

FRCC.PC.034.A3.02 47
Application Guidelines VZH035-044 - hybrid manifolding

General overview................................................................................................................ 49
Scope............................................................................................................................................................................................................ 49
Benefits........................................................................................................................................................................................................ 49
Application envelops.............................................................................................................................................................................. 50

Oil management concept................................................................................................... 51


Systems........................................................................................................................................................................................................ 51
Approved hybrid tandem configurations and capacity range................................................................................................ 52

System design recommendation....................................................................................... 53


Electronic expansion valve................................................................................................................................................................... 53
Pressure switch settings......................................................................................................................................................................... 53
Essential piping design considerations............................................................................................................................................ 53
Cycle rate limit of H compressors....................................................................................................................................................... 54
Short cycle timer function of VZH compressors............................................................................................................................ 54

Installation and service...................................................................................................... 55


Handling...................................................................................................................................................................................................... 55
Compressor mounting........................................................................................................................................................................... 55
Tightening torques.................................................................................................................................................................................. 55
Tandem piping design............................................................................................................................................................................ 56
Wiring and rotation direction.............................................................................................................................................................. 56
Failure analysis........................................................................................................................................................................................... 56
Oil equalisation connection................................................................................................................................................................. 56

Ordering information......................................................................................................... 57
VZH035-VZH044................................................................................................................. 58
Compressor mounting........................................................................................................................................................................... 59
Oil equalization connection................................................................................................................................................................. 59
Restrictor..................................................................................................................................................................................................... 60

48 FRCC.PC.034.A3.02
Application Guidelines General overview Manifold compressors

Scope The application guideline describes the operating • It is essential to respect all instructions given
characteristics, design features and application in these guidelines, the instruction leaflet
requirements for hybrid manifolding of the delivered with each compressor and the
Danfoss HLH061- HLJ072 fixed speed compressor Application Guidelines for single compressors.
and VZH035-044 inverter compressor in air • For additional system components related to
conditioning and heat pump applications. specific application requirements, the supplier
recommendations must always be respected.
To ensure proper parallel installation and running
conditions, the following recommendations must
be followed:

Benefits A parallel compressor installation refers to a The main reason is reduced operating cost
system of interconnected compressors with a through greater control of capacity and power
common suction line and common discharge consumption. This is achieved by both staggering
line. The technique of mounting compressors compressor switch-on sequences and regulating
in parallel is also called manifolding. The hybrid speed of inverter compressor that allow the
manifolding in this application guideline refers to parallel system to continuously match its power
manifolding of Danfoss inverter compressor (VZH with the capacity needed.
035-044) and fixed speed compressor (HLH061-
HLJ072), which has several benefits.
Capacity

Compressor n°1
VZH 15-100 Rps

Compressor n°2
Compressor n°1
fixed speed HLH061-HLJ072
VZH 15-100 Rps

A second reason for manifolding of inverter methods and manifolding of fixed speed
compressor and fixed speed compressor is compressors impose a serious penalty for part
improved part load efficiency. In the variable load efficiency, mainly at low load operation.
speed+fixed speed parallel installation, the
system can run either only inverter compressor Third, the capacity of hybrid manifolding
at lower load or both inverter and fixed speed system can be widely regulated ex. 8% to 100%.
compressors at higher load with fixed speed The continuous capacity regulation allows for
compressor operating at 100% load. Therefore accurate temperature control and comfort indoor
the higher part load efficiency can be achieved. environment.
Conventional fixed speed compressor unloading

Preliminary data FRCC.PC.034.A3.02 49


Application Guidelines General overview Manifold compressors

Application envelops VZH hybrid tandem operating envelops are Since out of map running will threaten the
given in the figures below, where the condensing reliability of compressors, customers must qualify
and evaporating temperatures represent the map protection under all extreme conditions.
range of steady state operation. Under transient
conditions, such as start-up and defrost,
compressors may operate outside this envelop
for short periods.

Manifolding operating map - R410A (SH 11K) Voltage: 400-460V/208-230V


-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 °F
70 157
152
65
147
40-100 rps 142
60
Condensing temperature (°C)

137
30-100 rps
55 132
127
50 122
117
45 112
20-100 rps 107
40 102
97
35
92
30 87
82
25
15-100 rps 77
72
20 67
62
15 57
52
10 47
5 42
37
0 32

°C -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25


Evaporating temperature (°C)

Manifold operating map - R410A (SH 11K) Voltage: 380V


-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 °F
70
157
152
65
40-95 rps 147
142
60
Condensing temperature (°C)

137
55 60-100 rps 30-100 rps 132
127
50 122
117
45
20-100 rps 112
107
40 102
97
35
92
30 87
15-100 rps 82
25 77
72
20 67
62
15 57
52
10 47
5 42
37
0 32

°C -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25


Evaporating temperature (°C)

50 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines Oil management concept Manifold compressors

ModBus

OEM main controller

Power supply

VZH HLH/HLJ

Optical oil
level sensor

Systems The oil management system architecture is The patented 2 pieces of organ pipes fitting are
described as below. Compressor sumps and pre-installed at standard oil equalization port.
low pressure shells are interconnected. An The patented organ pipe design allows for better
interconnecting pipe, on the lower part of the separation of oil and gas in the oil equalization
compressor (below the oil level), ensures oil line and facilitate the balance of oil level and low
balancing. To ensure a pressure drop balancing side pressure between compressors.
and equal distribution of oil returning from
the system when all compressors are running, Considering oil return risk, split system
the manifolding of VZH and H compressors by with more than 10m piping length need
Danfoss is designed in an innovative way which is mandatory application approval by Danfoss
robust with any kind of upstream piping. application specialists.

Damper
Discharge line VZH HLH/HLJ

Suction line
Restrictor inside fixed
speed compressor
Oil equalization line Oil level sensor

Grommet

Organ pipe fitting Rigid spacer Rail

Preliminary data FRCC.PC.034.A3.02 51


Application Guidelines Oil management concept Manifold compressors

A restrictor is used in suction line of fixed speed When the oil is below required minimum level, fix
to well balance the low side pressure between speed compressor should stop for variable speed
inverter and fixed speed compressors. compressor oil recovery.

230VAC model An TEKLAB LC-XT optical-electrical level sensor


L1
L2
is fixed on the inverter compressor. The oil
L3
N level sensor monitors the compressor oil level
and sends oil level signal to an external relay
1 2
(provided by OEM ).
Sensor 3

If OEM main controller receives “ON” signal, the


External
Load / Relay oil level stays above required minimum level.
ON the contrary, signal OFF indicates oil below
24V AC/DC model minimum required level and will trigger OEM
24VAC main controller to activate oil management
0VAC action (refer to document “oil management
specification for hybrid manifolding system”
1 2
3
to get details). Regarding this oil level signal, a
Sensor
5±2 seconds delay is recommended to be used
to consider the oil level fluctuation which may
External
Load / Relay trigger false alarms.

For customers who needs UL certificates, please


order 24V AC/DC sensor.

Approved hybrid tandem Different configuration of hybrid tandems are possible, all VZH models (different voltage) could be
configurations and manifold with fix speed compressors.
capacity range
Danfoss VSD : VZH compressor DriveTM 380-480 Volt

50Hz (both FS &VS) 60Hz (both FS &VS)


Model Description
kW TR kW TR
VZH096 VZH035+HLH061 24.3 6.9 29.0 8.2
VZH105 VZH044+HLH061 26.9 7.6 32.1 9.1
VZH116 VZH044+HLJ072 29.5 8.4 35.3 10.0

ARI conditions: 7.2/54.4/11.18.3


G motor code: 380-480V/3ph/50-60Hz The kit available for these tandems are tested with Danfoss recommended piping design. If the piping
Please note capacity here is preliminary is customized by the customer, additional test to check oil balancing must be performed.
data.
Please contact your Danfoss Application Specialist for support.

52 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines System design recommendation Manifold compressors

Electronic expansion With variable capacity systems, an electronic when the compressor is off, to avoid any liquid
valve expansion valve (EXV) is the mandatory solution refrigerant entering the compressor.
to handle refrigerant mass flow variations. Ramp
up and ramp-down settings, of both EXV and The expansion device should be sized to ensure
compressor, must be done with great care. Ramp- proper control of the refrigerant flow into the
up of the EXV must be shorter than the ramp-up evaporator. An oversized valve may result in
of the compressor, to avoid any low pressure erratic control. This consideration is especially
operation on suction side of the compressor. important in variable speed+fixed speed
The EXV can also be opened, up to a certain manifolded units where low load conditions
degree, before the start up of the compressor. may require low speed running of inverter
Ramp-down of the EXV must be longer than the compressor. This can lead to liquid refrigerant
ramp-down of the compressor, also to avoid low entering the compressor if the expansion valve
pressure operation (except with pump-down). does not provide stable refrigerant superheat
EXV should be closed, and remained closed, control under varying loads.

Pressure switch settings The pump down pressure switch must have a set compressors. Please refer to Danfoss H and VZH
point slightly higher than the lowest compressor scroll compressors single application guidelines
safety pressure switch set point. The high- reference FRCC.PC.012. for recommended
pressure safety pressure switch shall stop all settings.

Essential piping design Proper piping practices should be employed to or maintained in a defined time period. In oil
considerations ensure adequate oil return, even under minimum boost mode, the inverter compressor will be
load conditions with special consideration given increased to a certain level and meanwhile the
to the size and slope of the tubing coming fixed speed compressor keeps running regardless
from the evaporator. Tubing returns from the of oil level. In addition to oil boost operation,
evaporator should be designed so as to not trap hybrid tandems also need to balance oil between
oil and to prevent oil and refrigerant migration compressors when both compressors are running
back to the compressor during off cycles. The to maintain proper oil levels. Oil balancing
additional capacity range of Hybrid tandems in variable speed hybrids relies on the oil
makes oil return even more important due to equalization line, suction restrictors, organ pipe
the lower velocities with respect to system pipe and oil level switch to balance oil between the
size. Oil boost function shall be written in OEM two compressors. Please refer to oil management
main controller to return oil from system pipes specification for hybrid manifolding system for
to compressor when oil balance can’t be reached more details.

HP
0.5% >
>4 m/s

LP max. 4 m Condenser

U-trap
HP
8 to 12 m/s
max. 4 m LP
0.5%<
>4m/s
Evaporator

fig 1 fig 2

If the evaporator lies above the compressor, as omitted, the suction line should have a loop at
is often the case in split or remote condenser the evaporator outlet to prevent refrigerant from
systems, the addition of a pump-down cycle is draining into the compressor during off-cycles.
strongly recommended. If a pump-down cycle is

Preliminary data FRCC.PC.034.A3.02 53


Application Guidelines System design recommendation Manifold compressors

If the evaporator was situated below the can ultimately result in connection or tube failure
compressors, the suction riser must be trapped due to fatigue or wear from abrasion. Aside from
so as to prevent liquid refrigerant from collecting tubing and connection damage, excess vibration
at the thermal bulb location (see fig 1). may be transmitted to the surrounding structure
and generate an unacceptable noise level within
When the condenser is mounted at a higher that structure as well (for more information on
position than the compressors, a suitably sized noise and vibration, see section "Sound and
“U”-shaped trap close to the compressors is vibration management" in Danfoss H scroll
necessary to prevent oil leaving the compressor compressors application guidelines).
from draining back to the discharge side of the
compressors during off cycle. The upper loop also The design in this guideline is for short circuit
helps avoid liquid refrigerant from draining back application. But for long circuit and split system
to the compressor when stopped (see fig 2). application, oil separator is recommended to use
based on system qualification status.
Piping should be designed with adequate three-
dimensional flexibility. It should not be in contact Besides, in order to reduce the piping vibration,
with the surrounding structure, unless a proper customers need to add support specified for their
tubing mount has been installed. This protection own design.
proves necessary to avoid excess vibration, which

Cycle rate limit of H The system must be designed in a way that it depends upon system design. There must
compressors guarantees a minimum compressor running be no more than 12 starts per hour; a number
time of 2 minutes so as to provide for sufficient higher than 12 reduces the service life of the
motor cooling after start-up along with proper motor compressor unit. A 4-minute timeout is
oil return. Note that the oil return may vary since recommended.

Short cycle timer function Short cycle control is directly provided by the and interval between starts 300 seconds. Short
of VZH compressors CDS803 frequency converter, when parameter cycle settings are accessible in parameter 28.0x
28.0x is enabled. The function is factory set to list, in the compressor functions” menu.
enabled, with minimum running time 60 seconds

54 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines Installation and service Manifold compressors

Installation and service procedures for a parallel common rules. Please refer to the Application
system are similar to basic system installations. Guidelines for Danfoss H scroll compressors
The selection of additional system components (FRCC.PC.012) for detailed installation and service
for parallel installations follows the basic system procedures.

Handling Danfoss Commercial Compressors recommends


using the lift and handling devices, as shown in Spreader block Spreader bar
picture beside, and that the following procedure
be used to prevent damage.
• One lift ring is provided on each compressor.
Use all two rings.
• Maximum loads authorized per sling and for the Slings
hoist hook must not be lower than the weight
of the assembly.
• The minimum spreader bar length must be at
least equal to the centre distance between the
two compressors to prevent bending the frame.
• When lifting, use a spreader block between the
compressors to prevent any unit frame damage.
• When the tandem unit is already mounted
into an installation, never lift the complete Frame
installation by using the lift rings on the
compressors.

Compressor mounting A common base frame, rigid enough to support common frame using flexible tubing. Suction
the weight of the compressors, must be used for and discharge lines must have adequate three
installation. The common frame must always be dimensional flexibility. For parallel systems the
mounted on grommets to reduce transmission of simplest means of acquiring this is by the use of
vibration to the floor. It is recommended to install vibration absorbers. For details see compressors
all control and safety devices on an independent mounting for each tandem arrangement.
frame. These devices should be connected to the

Tightening torques

Tightening Torque Tightening Torque


15Nm 15Nm

Tightening Tightening
Torque 15Nm Torque 15Nm

VZH035-044 HLH061-HLJ072

Preliminary data FRCC.PC.034.A3.02 55


Application Guidelines Installation and service Manifold compressors

Tandem piping design For each tandem configuration specific outline No changes shall be made to the indicated
drawings are available as indicated on the tubing diameter and fitting types. The oil
following pages. These drawings must always be equalisation line shall be made of copper tube
respected. and assembled in such a way that it does not
extend above the connection height and must be
horizontal so as not to trap oil.

Wiring and rotation All compressors in a tandem unit must be Compressors should run with the correct rotation
direction electrically wired individually. direction. This can be achieved by having the
correct phase sequence on each compressor
motor terminal (L1-T1, L2-T2, L3-T3).

Failure analysis When one compressor in a parallel system fails, failure analysis must be done quickly to insure
the chance of foreign particles entering other further proper running conditions for the overall
compressors is greatly increased. Therefore a installation (i.e. : oil analysis).

Oil equalisation Danfoss Commercial Compressors has developed rotolock connections and patented design organ
connection specially adapted oil equalisation systems pipes:
(VZH+H) which ensure proper oil balancing
between the compressors. Hence, Danfoss hybrid • HLH061-HLJ072: 1-1/8" oil equalisation line.
manifolding compressors are equipped with • VZH035-044: 1-1/8" oil equalisation line.

56 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines Ordering information Manifold compressors

Ordering information To build a complete tandem, one must order the Danfoss H scroll compressors can be ordered in
2 compressors and the tandem kit. For example : either industrial packs or in single packs, please
refer to below table.
Tandem VZH035+HLH061,400V
• Compressor 1 : VZH035 Code number 120G0073 Please note for VZH hybrid tandem: HLH061 and
• Compressor 2 : HLH061 Code number 121L3167 HLJ072 will be with oil equalization ports which
• Tandem kit 120Z**** according to the are different from standard H models, please refer
compressor models and voltage type of oil level to single application guideline or table below for
switch electrical part. ordering:

H series compressors Model number(on compressor Code number for single pack Code number for industrial pack
nameplate)
HLH061T4LCT 121L3167 121L3166
HLH061T2LCT 121L3169 121L3168
HLJ072T4LCT 121L3171 121L3170
HLJ072T2LCT 121L3173 121L3172

Code Number
Manifolding kit 24V Type 24VAC/VDC type
120Z0618 120Z0619

No Description VZH044+HLJ072 VZH044+HLH061/VZH035+HLH061

1 Oil level monitor-Electrical part 1 1


2 Sleeve 1 1/8" 2 2
3 Teflon gasket 1 1/8" 2 2
4 Restrictor VZH044+HLJ072 1
Restrictor VZH035+HLH061 /
5 1
VZH044+HLH061
6 Rigid spacer thickness 7mm 4 4
7 Flat washer Thickness 4mm 8 8
8 Rigid spacer Thickness 14mm 8 8
9 Bolt 8 8

Code Number
Manifolding kit 230V Type 24VAC/VDC type
120Z0620 120Z0621

No Description VZH044+HLJ072 VZH044+HLH061/VZH035+HLH061

1 Oil level monitor-Electrical part 1 1


2 Sleeve 1 1/8" 2 2
3 Teflon gasket 1 1/8" 2 2
4 Restrictor VZH044+HLJ072 1
Restrictor VZH035+HLH061 /
5 1
VZH044+HLH061
6 Rigid spacer thickness 7mm 4 4
7 Flat washer Thickness 4mm 8 8
8 Rigid spacer Thickness 14mm 8 8
9 Bolt 8 8

Preliminary data FRCC.PC.034.A3.02 57


Application Guidelines VZH035-VZH044 Manifold compressors

Composition of VZH035-044
tandem Composition
Tandem model
Variable speed Fixed speed
VZH035+HLH061 VZH035 HLH061
VZH044+HLH061 VZH044 HLH061
VZH044+HLJ072 VZH044 HLJ072

1/2"

3/4"

3/4"
1"1/4

7/8"

Oil equalization line 1"1/8

58 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines VZH035-VZH044 Manifold compressors

Compressor mounting The tandem is fixed on the frame using the Because VZH is 7 mm smaller than H compressor
flexible grommets supplied with the compressor. and in order to have the oil equalization
connection at the same level for both
The compressors are fixed on the rails (not compressors, an additional 7mm rigid spacer
included) using the flat washers , 14 mm rigid  must be added under the VZH feet only for
spacer , included in the “tandem kit” reference composition of VZH hybrid tandem.
120Z**** (to be ordered with the compressors).

 

 

 S


VZH035-044 HLH061-HLJ072

S Supplied in single compressor

Oil equalization The level of oil is naturally balanced by a 1"1/8 oil The organ pipe is preinstalled on oil equalization
connection equalization line. port.

The kit 120Zxxxx includes a 1"3/4 to 1"1/8


adaptor sleeve  & a teflon seal  to connect the
oil line to the compressor 1"3/4 oil equalization
port.

Organ pipe  

Preliminary data FRCC.PC.034.A3.02 59


Application Guidelines VZH035-VZH044 Manifold compressors

Restrictor Due to the difference of capacities of the


compressors, it is essential to equalise the
pressure of the sump. A restrictor is used in
suction line of fixed speed to well balance the or
low side pressure between inverter and fixed
speed compressors. The oil protection for
variable speed is achieved by oil level sensor.

60 FRCC.PC.034.A3.02 Preliminary data


Application Guidelines Updates

Previous Version Current Version

• Page 8: Nomenclature & label • Page 8: Updated Motor protection type in


nomenclature & new label is placed.
• Page 47: Added oil level switch accessories.
• Page 48-60: Added VZH035-044 - hybrid
manifolding.

FRCC.PC.034.A3.02 61
Danfoss Commercial Compressors
is a worldwide manufacturer of compressors and condensing units for refrigeration and HVAC applications. With a wide range
of high quality and innovative products we help your company to find the best possible energy efficient solution that respects
the environment and reduces total life cycle costs.

We have 40 years of experience within the development of hermetic compressors which has brought us amongst the global
leaders in our business, and positioned us as distinct variable speed technology specialists. Today we operate from engineering
and manufacturing facilities spanning across three continents.

Danfoss Turbocor Compressors

Danfoss Inverter Scrolls

Danfoss Scrolls

Danfoss Optyma Condensing Units

Danfoss Maneurop Reciprocating Compressors

Secop Compressors for Danfoss

Our products can be found in a variety of applications such as rooftops, chillers, residential air conditioners,
heatpumps, coldrooms, supermarkets, milk tank cooling and industrial cooling processes.

http://cc.danfoss.com

Danfoss Commercial Compressors, BP 331, 01603 Trévoux Cedex, France | +334 74 00 28 29

FRCC.PC.034.A3.02 © Danfoss | DCS (CC) | 2015.06

S-ar putea să vă placă și