Owner's Manual
Original Instructions
Air Conditioners
Thank you for choosing GREE air conditioners. Please read this
Owner’s Manual carefully before operation and retain it for future
reference.
If you have lost the Owner's Manual,please contact the local agent
or visit www.gree.com or send an email to global@gree.com.cn for
the electronic version.
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
To Users
Thank you for selecting Gree’s product. Please read this instruction manual carefully before installing and using
the product, so as to master and correctly use the product. In order to guide you to correctly install and use our
product and achieve expected operating effect, we hereby instruct as below:
(1) This equipment should be installed, operated or maintained by the qualified servicemen who have had
specific training. During operation, all safety issues covered in the labels, User’s Manual and other
literature should be followed strictly. This appliance can be used by children aged from 8 years and above
and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge
if they have been given supervision or instruction concerning used of this appliance in a safety way
and understand the hazards involved. Children shall not play with the appliances. Cleaning and user
maintenance shall not be made by children without supervision.
(2) This product has gone through strict inspection and operational test before leaving the factory. In order to
avoid damage due to improper disassembly and inspection, which may impact the normal operation of unit,
please do not disassemble the unit by yourself. You can contact with the special maintenance center of our
company if necessary.
(3) For personal injury or property loss and damage caused by improper operation such as improper
installation and debugging, unnecessary maintenance, violation of related national laws and rules and
industrial standard, and violation of this instruction manual, etc., we will bear no liability.
(4) When the product is faulted and cannot be operated, please contact with our maintenance center as soon
as possible by providing the following information.
• Contents of nameplate of product (model, cooling/heating capacity, product No., ex-factory date).
• Malfunction status (specify the situations before and after the error occurs).
(5) All the illustrations and information in the instruction manual are only for reference. In order to make the
product better, we will continuously conduct improvement and innovation. We have the right to make
necessary revision to the product from time to time due to the reason of sales or production, and reserve
the right to revise the contents without further notice.
(6) The final right to interpret for this instruction manual belongs to Gree Electric Appliances Inc. of Zhuhai.
Contents
WARNING: If not abide strictly, it may cause severe damage to the unit or the
people.
NOTE: If not abide strictly, it may cause slight or medium damage to the unit or the
people.
This sign indicates that the operation must be prohibited. Improper operation may
cause severe damage or death to people
This sign indicates that the items must be observed. Improper operation may
cause damage to people or property.
NOTE
After receipt of the unit, check it for appearance, unit model compared with your desire
and attachments.
Design and installation work of the unit must be performed by authorized personnel
according to applicable laws and regulations and this Instruction.
After installation work, the unit cannot be energized unless there is not any problem in
check.
Ensure periodical clean and maintenance of the unit after normal operation of the unit
for longer life and reliable operation.
If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
The appliance shall be installed in accordance with national wiring regulations.
This product is a kind of comfort air conditioning, and is not allowed to be installed
where there are corrosive, explosive and inflammable substances or smog; otherwise
it would lead to operation failure, shortened service life, five hazard or even severe
injuries. Special air conditions are required for where mentioned above.
Correct Disposure
This marking indicates that this product should not be
disposed with other household wastes throughout the EU.To
prevent possible harm to the environment or human health from
uncontrolled waste disposal,recycle it responsibly to promote the
sustainable reuse of material resources. To retuern your used
device,please use the return and collection systems or contact
the retailer where the product was purchased. They can take this
product for environmental safe recycling.
R410A(R32/125:50/50):2087.5
1
Air-to-water Heat Pump Split Versati SPLIT TYPE
WARNING
Once abnormality Don't operate the unit with Before
likeburning smell occurs, wet hand. installation,please see
please cut off the power if the voltage of local
supply immediately and place accords with
then contact with service that on nameplate
center. of unit and capacity
of power supply,
power cord or socket
is suitable for input
power of this unit.
2
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Before cleaning please cut The power supply must User can not change
off the power supply. adopt special circuit with power cord socket
leakage switch and enough without prior consent.
capacity. Wiring working
must be done by
professionals. Ensure
good earthing and
don't change earthing
mode of unit.
3
Air-to-water Heat Pump Split Versati SPLIT TYPE
Don't step on the top of the Never block the air inlet and Keep pressurized
unit or place anything on it. outlet of unit. spray, gas holder and
so on away from the
unit above 1m .
4
SPLIT TYPE
Air-to-water Heat Pump Split Versati
NOTE
Before installation, please check if the adopted power is accordance with that listed on
nameplate, and check the safety of power.
An all-pole disconnection switch having a contact separation of at least 3mm in all
poles should be connected in fixed wiring.
Before using, please check and confirm if wires and water pipes are connected
correctly to avoid water leakage, electric shock or fire etc.
Don’t operate the unit with wet hand, and don’t allow children to operate the unit.
The On/off in the instruction is for the operation to on and off button of PCB for users;
cut off power means to stop supplying power to the unit.
Don’t directly expose the unit under the corrosive ambient with water or dampness.
Don’t operate the unit without water in water tank .The air outlet/inlet of unit cannot be
blocked by other objects.
The water in unit and pipeline should be discharged if the unit is not in use, to prevent
the water tank, pipe line and water pump from frost-cracking.
Never press the button with sharp objects to protect manual controller. Never use
other wires instead of special communication line of the unit to protect control elements.
Never clean the manual controller with benzene, thinner or chemical cloth to avoid
fading of surface and failure of elements. Clean the unit with the cloth soaked in neutral
eradicator. Slightly clean the display screen and connecting parts to avoid fading.
The power cord must be separated with the communication line.
5
Air-to-water Heat Pump Split Versati SPLIT TYPE
6
SPLIT TYPE
Air-to-water Heat Pump Split Versati
6 26 47
9
E
5 4 10 44 46
S D
3
45
C
40 39
11
2 12 18 21
37
49 36
34
38
48 41
16 1 20
13 19 35
14 22
17 50 31
32
15
Liquid Temperature
1 Compressor 18 35 Water Tank
Sensor of the PHE
Discharge Temperature Gas Temperature Sensor of the Leaving Water Temperature
2 19 36
Sensor PHE Sensor of the Solar System
Flow Switch for the Solar
3 High Pressure Switch 20 Plate-type Exchanger 37
System
Leaving Water Temperature Water Pump for the Solar
4 Pressure Sensor 21 38
of the PHE System
Entering Water Temperature
5 4-way Valve 22 39 Solar Panel
of the PHE
Suction Temperature
16 33 Electric 3-way Valve 2 50 Gas Valve Connector
Sensor
Water Tank Temperature
17 Pressure Sensor 34
Sensor 1
7
Air-to-water Heat Pump Split Versati SPLIT TYPE
8
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Emergency mode: this mode is only available for heating and water heating. When the outdoor unit stops due
to malfunction, enter the corresponding emergency mode; as to heating mode, after entering the emergency mode,
heating can only be realized through e-heater of the indoor unit. When the setting outflow temperature or indoor
temperature is reached, the e-heater of indoor unit will stop running; as to water heating mode, the e-heater of
indoor unit stops while the e-heater of water tank runs. When the setting temperature or water tank is reached, the
e-heater will stop running.
Quick water heating: in quick water heating mode, the unit runs according to the water heating control of heat
pump and the e-heater of water tank runs at the same time.
Forced operation mode: this mode is only used for refrigerant recovery and debugging for the unit.
Holiday mode: this mode is only available for heating mode. This mode is set to keep indoor temperature or
leaving water temperature in a certain range, so as to prevent water system of the unit from freezing or protect
certain indoor articles from freezing damage. When the outdoor unit stops due to malfunction, the two e-heaters of
the unit will run.
Disinfection mode: in this mode, the water heating system can be disinfected. When starting up the disinfection
function and setting corresponding time to meet the requirement of disinfection mode, the function will start. After
the setting temperature is reached, this mode will terminate.
Weather-dependent operation: this mode is only available for space heating or space cooling. In Weather-
dependent mode, the setting value (remote room air temperature or leaving water temperature) is detected and
controlled automatically when the outdoor air temperature is changed.
Quiet mode: silent mode is available in cooling, heating and water heating mode. In silent mode, the outdoor
unit will reduce the running noise via automatic control.
Floor commissioning: this function is intended to preheat the floor periodically for the initial use.
Air removal of the water system: this function is intended to replenish water and remove air in the water
system to make the equipment run at the stabilized water pressure.
Solar water heater: when the condition for starting the solar water heater is satisfied, the solar heater will start
to heat the circulation water. Then the heated water will go to the water tank and exchange heat with water in it. At
any condition, the solar water heater will be given priority for startup so as for energy conservation.
Backup heat source: when the outdoor temperature is lower than the set point for starting the backup heat
source and the unit is under the error condition and the compressor has stopped for three minutes, then the backup
heat source will start to supply heat or hot water to the room.
9
Air-to-water Heat Pump Split Versati SPLIT TYPE
3. Nomenclature
G RS - C Q 16 Pd / Na E - M (O)
1 2 3 4 5 6 7 8 9 10
7 Refrigerant Na=R410A
Model Line-Up
Capacity
Model Name Power supply
1
Heating ,kW Cooling2,kW
GRS-CQ8.0Pd/NaE-K 8 7.8
GRS-CQ10Pd/NaE-K 10 8.2
GRS-CQ14Pd/NaE-K 14 13.5
GRS-CQ12Pd/NaE-M 12 13.5
GRS-CQ16Pd/NaE-M 15.5 15
Notes
(a) 1Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 30°C/35°C, Outdoor Air Temperature 7°C DB/6°C WB;
(b) 2Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 23°C/18°C, Outdoor Air Temperature 35°C DB/24°C WB.
Operation Range
Mode Heat Source Side Temperature (°C) User Side Temperature (°C)
10
SPLIT TYPE
Air-to-water Heat Pump Split Versati
4. Installation Example
CASE 1: Connecting Under floor Coil and Fan Coil Unit
Outdoor Indoor
Notes
(a) The two-way valve is very important to prevent dew condensation on the floor and FCU while cooling mode;
(b) Type of thermostat and specification should be complied with installation of this manual;
(c) The bypass valve must be installed to secure enough water flow rate, and should be installed at the
collector.
(d) When the FCU and the underfloor coil are used at the same time, performance of the underfloor coil is
satisfied firstly. When performance of the FCU is required, then “Floor config” should be set to “Without”.
11
Air-to-water Heat Pump Split Versati SPLIT TYPE
CASE 2: Connecting Under floor Coil, Fan Coil Unit and Water Tank
Outdoor Indoor
Notes
(a) The two-way valve is very important to prevent dew condensation on the floor and FCU while cooling mode
(b) In this case, three-way valve should be installed and should be complied with installation of this manual;
(c) When the FCU and the underfloor coil are used at the same time, performance of the underfloor coil is
satisfied firstly. When performance of the FCU is required, then “Floor config” should be set to “Without”.
(d) Anitary water tank should be equipped with internal electric heater to secure enough heat energy in the
very cold days.
12
SPLIT TYPE
Air-to-water Heat Pump Split Versati
CASE 3 : Connecting Under floor Coil, Fan Coil Unit , Water Tank and Solar System
Outdoor Indoor
Notes
(a) The two-way valve is very important to prevent dew condensation on the floor and FCU while cooling mode
(b) In this case, three-way valve should be installed and should be complied with installation of this manual;
(c) Anitary water tank should be equipped with internal electric heater to secure enough heat energy in the
very cold days.
(d) When the FCU and the underfloor coil are used at the same time, performance of the underfloor coil is
satisfied firstly. When performance of the FCU is required, then “Floor config” should be set to “Without”.
(e) For the solar heating system, only the control port is available and relative accessories are absent.
13
Air-to-water Heat Pump Split Versati SPLIT TYPE
5. Main Components
5.1 Indoor unit
(1) GRS-CQ8.0Pd/NaE-K(I),GRS-CQ10Pd/NaE-K(I)
External
Internal
14
SPLIT TYPE
Air-to-water Heat Pump Split Versati
External
Internal
15
Air-to-water Heat Pump Split Versati SPLIT TYPE
External
Internal
16
SPLIT TYPE
Air-to-water Heat Pump Split Versati
External
Internal
17
Air-to-water Heat Pump Split Versati SPLIT TYPE
External
Internal
18
SPLIT TYPE
Air-to-water Heat Pump Split Versati
427
395
650
980
19
Air-to-water Heat Pump Split Versati SPLIT TYPE
(2) GRS-CQ12Pd/NaE-K(O),GRS-CQ14Pd/NaE-K(O),GRS-CQ16Pd/NaE-K(O),GRS-CQ12Pd/NaE-
M(O),GRS-CQ14Pd/NaE-M(O),GRS-CQ16Pd/NaE-M(O)
1326
1345
900
572
340
412
378
Description:
Unit: inch
No. Name Remarks
20
SPLIT TYPE
Air-to-water Heat Pump Split Versati
>1000
>500
>2000
>500 >500
>500
>2000
21
Air-to-water Heat Pump Split Versati SPLIT TYPE
900
825
Unit outline
22
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Step3: Attaching indoor unit to the wall make use of accessory expansion bolt.
Expansion bolt
Wall
NOTENote
• While lifting the indoor unit, at least two persons should be joined. Weight of the indoor unit is more than 50kg.
• The indoor unit must be installed vertically to the ground and fastened securely.
• Before commissioning, the dust-proof cap of the automatic relief valve must be loosened, other than entirely being
removed away, and it can be tightened in case that it leaks.
23
Air-to-water Heat Pump Split Versati SPLIT TYPE
900
981
324
500
Description:
Unit: inch
No. Name Remarks
250
200 800
1300
Service Space
24
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Note
During operation, the water pump will adjust its output based on the actual load.
2.5
Pre-pressure in expension vessel(Bar)
2.0
1.5
1.0
0.5
0.0
0 50 100 150 200 250 300 350 400
Maximum total water volume(liter)
Notes
(a) The expansion vessel is 10 liter and 1bar pre-pressurized;
(b) Total water volume of 280 liter is default; if total water is changed because of installation condition, the pre-
pressure should be adjusted to secure proper operation. If the indoor unit is located at the highest position,
adjustment is not required;
(c) Minimum total water volume is 20 liter;
(d) To adjust pre-pressure, use nitrogen gas by certificated installer.
25
Air-to-water Heat Pump Split Versati SPLIT TYPE
0 0.00013
4 0
10 0.00027
20 0.00177
30 0.00435
40 0.00782
45 0.0099
50 0.0121
55 0.0145
60 0.0171
65 0.0198
70 0.0227
75 0.0258
80 0.029
85 0.0324
90 0.0359
95 0.0396
100 0.0434
26
SPLIT TYPE
Air-to-water Heat Pump Split Versati
8. Connection of Pipeline
8.1 Connection of outlet pipe for indoor & outdoor unit
(1) Align the expansion end of copper pipe with the center of threaded joint. Tighten the flaring nuts with your
hands.
(2) Tighten the flaring nuts with torque wrench until you hear a “click”.
(3) Bend of fitting pipe shall not be too low; otherwise the fitting pipe might crack. Please use pipe bender when
bending the fitting pipe.
(4) When connecting outdoor and indoor unit, never pull the big and small joint of indoor unit with force, so as
to prevent the tubes of indoor unit from cracking and causing leakage.
(5) Connecting pipe shall be supported by a rack without transmitting its weight to other units.
• Fix the wrapped pipe onto the wall with pipe clamp.
• Do not wrap the protective tape too tightly, as this will decrease the heat insulation performance.
• After completing the protection work and wrapping the pipe properly, close the wall holes with sealing
materials.
No clearance
27
Air-to-water Heat Pump Split Versati SPLIT TYPE
Indoor unit
Outdoor unit
Indoor unit
A
A
Outdoor unit
B B
Outdoor unit
Indoor unit
Oil trap
Pipe size
Length B Elevation A Additional
Model (Diameter:Φ)
refrigerant
gas Liquid Standard Max. Standard Max.
28
SPLIT TYPE
Air-to-water Heat Pump Split Versati
CN15
Remote Air Environment
Temp sensor
AP
2
Electric box
Notes
(a) Distance between the indoor unit and the remote air temperature sensor should be less than 15m due to
length of the connection cable of remote air temperature sensor;
(b) Height from floor is approximately 1.5m;
(c) Remote air temperature sensor cannot be located where the area may be hidden when door is open;
(d) Remote air temperature sensor cannot be located where external thermal influence may be applied;
(e) Remote air temperature sensor should be installed where space heating is mainly applied;
(f) After the remote air temperature sensor is installed, it should be set to “With” through the wired controller so
as to set the remote air temperature to the control point.
29
Air-to-water Heat Pump Split Versati SPLIT TYPE
10. Thermostat
Installation of the thermostat is very similar to that of the remote air temperature sensor.
XT5 XT5 XT6
17 18 19 20 21 22 23 24 33 34
L(220V AC)
24V GND
24V AC
COOL
COOL
HEAT
HEAT
OFF
OFF
N
Thermostat Thermostat
10~30℃ , By means of a large Directly onto the wall or wall-box (mounting screws
Setpoint range Mounting
setpoint dial supplied)
Up to 9 screw-in terminals per unit, capable of
Supply voltage 230V, 50/60Hz Wiring
accepting wires up to 1.5mm2.
Thermostat switch S.P. D.T. Enclosure Plastic 2-piece housing
Typical differential 1℃ (heating
Dimensions 85*130*40mm(W*H*D)
Performance & cooling) at 20 at 50% load with
Protection class IP30
anticipator connected
4(2)A, 230V, Typical loads
are fans, zone valves, relays,
compressors. Compressors of Environmental
Electric ratings Operating temperature range 0 to 40℃ . S
greater than 0.5kW capacity requirements
should be switched via a
contactor.
Greater than 100000 cycles (all
The XE70 range is CE, RoHs and WEEE
loads) for thermostat contacts
compliant. For regulatory information, DoC/CoC
Operational life at 230V; greater than 6000 Approvals
D0045 is available on request. Product must be
operations for all manually
wired as shown for CE compliance.
operated swtiches
30
SPLIT TYPE
Air-to-water Heat Pump Split Versati
NOTE
• Never use 230V AC and 24V AC thermostat at the same time, otherwise, it will cause short circuit and power cut-off
by the circuit breaker;
• Setting temperature by the thermostat(heating or cooling) should be within the temperature range of the product;
• For other constrains, please refer to previous pages about the remote air temperature sensor;
• Do not connect external electric loads. Wire 230V AC(24V AC) and 230V GND(24V GND) should be used only for the
electric thermostat;
• Never connect external electric loads such as valves, fan coil units, etc. If connected, the mainboard of the unit can be
seriously damaged;
• Installation of the thermostat is very similar to that of the remote air temperature sensor.
• “OFF” interfaces can be kept vacant and no adverse effect will be produced for nomrla operation. When signals for
both heating and cooling are not detected, it can be considered the thermostat is “OFF”.
XT2 4 5 6
L2(ON)
L1(OFF)
2-Way Valve 1
WARNING
• Normal Open type should be connected to wire (ON) and wire (N) for valve closing in cooling mode.
• Normal Closed type should be connected to wire (OFF) and wire (N) for valve closing in cooling mode.
• (ON) : Line signal (for Normal Open type) from PCB to 2-way valve
• (OFF) : Line signal (for Normal Closed type) from PCB to 2-way valve
• (N) : Neutral signal from PCB to 2-way valve
31
Air-to-water Heat Pump Split Versati SPLIT TYPE
(1) SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow B), and Neutral (for
common).
(2) Flow A means 'water flow from the indoor unit to under floor water circuit'.
(3) Flow B means 'water flow from the indoor unit to sanitary water tank'.
Follow steps below to wire the 3-way valve:
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the unit and open the control box.
Step 2. Find terminal block and connect wires as below.
XT2 1 2 3
L2(ON)
L1(OFF)
3-Way Valve 2
WARNING
• The 3-way valve should select water tank loop when electric power is supplied to wire (OFF) and wire (N).
• The 3-way valve should select under floor loop when electric power is supplied to wire (ON) and wire (N).
• (ON): Line signal (Water tank heating) from the main board to the 3-way valve
• (OFF): Line signal (Under floor heating) from the main board to the 3-way valve
• (N): Neutral signal from the main board to the 3-way valve
XT2 7 8
Other Thermal
14. Gate-controller
If there is gate control function, installation guide follow as:
(1) GRS-CQ8.0Pd/NaE-K,GRS-CQ10Pd/NaE-K, GRS-CQ12Pd/NaE-K, GRS-CQ14Pd/NaE-K,GRS-CQ16Pd/
NaE-K
XT4 3 4
Gate-Controller
32
SPLIT TYPE
Air-to-water Heat Pump Split Versati
(2) GRS-CQ12Pd/NaE-M,GRS-CQ14Pd/NaE-M,GRS-CQ16Pd/NaE-M
XT4 25 26
Gate-Controller
“Lo”knob “HI”knob
Liquid valve
Vacuum pump
Connection pipe
Gas valve
(4) After confirming that there is no leakage from the system, when the compressor is not in operation, charge
additional R410A working fluid with specified amount to the unit through the filling opening of the liquid pipe
valve of the outdoor unit.
• Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe. Since this
refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to change,
preventing normal operation.
• Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not.
WARNING
• When charging is interrupted or finished, reinspect the unit but do not let the compressor run into operation.
NOTE
• Do not use mixture of refrigerant vapor and air or oxygen for pressurizing for fear of explosion.
33
Air-to-water Heat Pump Split Versati SPLIT TYPE
(6) Fully close the ball valve on the gas pipe side of the outdoor unit when the pressure gauge on the gauge
manifold shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner. Then
press UP key or Down key or ON/OFF key can exit pump down mode.
(7) Turn off the power supply (circuit breaker), remove the gauge manifold, and then disconnect the refrigerant
pipes.
WARNING
• When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the
pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, personal
injury, etc.
34
SPLIT TYPE
Air-to-water Heat Pump Split Versati
35
Air-to-water Heat Pump Split Versati SPLIT TYPE
Fix
With
Bolts
Installed on the ground
and never suspended
The minimum clearance from the water tank to combustible surface must be 500mm.
There should be water pipe, hot water joint and floor drain near the water tank in favor of water replenishment,
hot water supply and drainage of water tank.
Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit (with the arrow on it
pointing at the water tank) with the water inlet of water tank with PPR pipe according to the following figure, sealing
with unsintered tape. The other end of the safety check valve should connect with tap water joint. Connect the hot
water pipe and water outlet of water tank with PPR pipe.
Note
(a) For safe use of water, water outlet/inlet of water tank must connect with a certain length of PPR pipe ,L
≥70×R2(cm, R is inside radius of the pipe). Moreover, heat preservation should be conducted and metal pipe
cannot be used. For the first use, water tank must be full of water before the power is on.
36
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Gross weight kg 77 80 92 97
37
Air-to-water Heat Pump Split Versati SPLIT TYPE
Joints Dimension
Indoor Unit
Water Tank
Other
Thermal
System
Temp Sensor 1
Safety check
valv e Filter
Tap water
Cool Water Temp sensor 2
Inlet
Blow-off Outlet
Power cord of booster heater Cut-off valve
38
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Notes
(a) Distance between indoor unit and water tank should not exceed 5m levelly and 3m vertically. If higher,
please contact with us. Water tank on lower and main unit on higher side is recommended.
(b) Prepare the materials according to the above joints dimension. If cut-off valve is installed outside the room,
PPR pipe is recommended to avoid freeze damage.
(c) Waterway pipelines can’t be installed until water heater unit is fixed. Do not let dust and other sundries
enter into pipeline system during installation of connection pipes.
(d) After connection of all waterway pipelines, perform leakage test firstly. After that, perform heat preservation
of waterway system; meanwhile, pay more attention to valves and pipe joints. Ensure enough thickness of
insulated cotton. If necessary, install heating device for pipeline to prevent the pipeline from freezing.
(e) Hot water supplied from insulated water tank depends on pressure of water tap, so there must be supply of
tap water.
(f) During using, the cut-off valve of cooling water inlet of water tank should be kept normally on.
39
Air-to-water Heat Pump Split Versati SPLIT TYPE
40
SPLIT TYPE
Air-to-water Heat Pump Split Versati
H-PRESS
CN8
COM-ESPE2
CN7
PWR1 HPP
DC-MOTOR0
T-SENSOR3
4V 4-way valve
FA To EXV1,pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V;
H-PRESS Signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V;
To the wired controller, communication cable: 1 pin earthed, 2 pin B, 3 pin A, 4 pin+12power
CN8
supply;
CN7 Communication between AP1 and AP2;communication cable 2 pin B, 3 pinA
41
Air-to-water Heat Pump Split Versati SPLIT TYPE
AC-L N ERR RUN WT_HEAT HEAT1 BAN_HEAT PUMP2 2V1_ON 2V2_ON 3V1_ON 3V2_ON
PUMP1
N1
OTHER_HETA_DCIN
X23
CN33
OTHER_HETA_DCIN
CN31
CN31 COM-OUT
TR-IN
CN8 INDOOR_PUMP
TR-
CN8
TR-
POOL_PUMP
T-SEN13
SW_IN
SOLAR_PUMP
SW_SO
T-SEN12
SW_PO
N1 N1 Reserved
42
SPLIT TYPE
Air-to-water Heat Pump Split Versati
HEAT_M2
COOL_M2
CN31 Power supply interface and control signal of the thermostat (24V)
24VAC
OFF2
OFF1
COOL_M1
BAN_HEAT X3 Reserved
PUMP1 X5 Reserved
PUMP2 X9 Reserved
43
Air-to-water Heat Pump Split Versati SPLIT TYPE
INDOOR_PUMP CN4 Control of the water pump for the main unit
44
SPLIT TYPE
Air-to-water Heat Pump Split Versati
PWR
L2-2 N
Silk Screen Introduction
U To compressor phase U
V To compressor phase V
W To compressor phase W
DC-BUS1 Pin for electric discharge of the high-voltage bar during test.
P-OUT Reserved
G-OUT Reserved
45
Air-to-water Heat Pump Split Versati SPLIT TYPE
11
1
No Silk Screen Introduction
46
SPLIT TYPE
Air-to-water Heat Pump Split Versati
14
13
12
3
4
8 7 6
11 10 9
3 X1 Connector to filter R
4 X2 Connector to filter S
5 X3 Connector to filter T
47
Air-to-water Heat Pump Split Versati SPLIT TYPE
N-OUT
L-OUT
E1
Silk Screen Introduction
AC-N Neutral line of the power supply for the main unit
AC-L Live line of the power supply for the main unit
Neutral line output of the filter board (to the drive board)
N-OUT
Neutral line output of the filter board (to the main board )
L-OUT Live line output of the filter board (to the drive and main boards)
N-OUT
AC-N
L-OUT
AC-L
Neutral line output of the filter board (to the drive board)
N-OUT
Neutral line output of the filter board (to the main board )
L-OUT Live line output of the filter board (to the drive and main boards)
48
SPLIT TYPE
Air-to-water Heat Pump Split Versati
X4
X7 X3
X6 X2
X5 X1
7 X7 W line output of the filter board (to the drive and main boards)
49
Air-to-water Heat Pump Split Versati SPLIT TYPE
A PE PE A
XT1
CODE NAME
Power
1 20K RT1 AP Main Board Only For RT6
L AC-L
6 XT2
4 8 2 L1(OFF) 36 20K RT3
N 2 1 X11 HL1 Running indicating lamp
electric heater
valve2
27 37
3-way
KM3 L2(ON)
2 X12
7 8 9 10
N
3
HL2 Error indicating lamp
L1(OFF) 38
PE PE 4 X8
HT1 Temperature limiter 1
valve1
28
2-way
L2(ON) 39 20K RT8
5 X7
Consumer Connection
N
6 20K
HT2 Temperature limiter 2
40 CN13 RT9
7 X6
KM1 Auxiliary electric heater 1 AC contactor
thermal
29
N
Other
8
2
B
B KM2 KM1
KM2 Auxiliary electric heater 2 AC contactor
XT3
HL1
9
41 50K RT4 KM3 Water tank Auxiliary electric heater AC contactor
8
N 30 CN11
cating lamp
WH RD
10 42 M2 Indoor unit pump
BK BU HL2
Error indi- 11 31 X19
78 50K
N RT5
17 家研
cating lamp
12 CN12 79
RT1 Water-out temp sensor of the whole unit
201 家用 HT1 RT2 Water-in temp sensor of the whole unit
15K RT7
202 试制 CN14 RT3 Liquid line temp sensor
22 质控
24 采购 Gate-controller
XT4
50K
RT4 Water-tank temp sensor1
49 RT11
3 50 CN24 RT5 Water-tank temp sensor2
29 出口 220VAC
4
CN23
50 控制 PE PE 18 X17 KM1 1 3
62 0 1 2
51 空四
Electrical heater Electrical box 24VACGND
19 CN31 18 RT13 Solar Board temp sensor
Earthing Earthing 24VAC 63 19
20 X18
0 KM2 1 SW1 Solar waterflow switch
55 管二 OFF 64
21 11
62 重庆
OFF 57 CN26 12
KM1-6 SW3 Indoor units waterflow switch
79 小家电 22
HEAT
23
58
CN33 TC Transformer
61 巴西 COOL 59 13
24 KM2-6 XT1 Terminal block(L,N,1,2)
Thermostat
CN27 14
Specification: 15
XT2 Terminal block(1~8)
XT6 KM3-6
N
33
55 CN28 16 XT3 Terminal block(9~16)
1. The wires in the imaninal frames L(220VAC)
34
56 CN18
21 20
XT3 XT4 Terminal block(1~6) D
D are connected by the consumer. Solar-pump
70
X16
0
KM3 1 12
XT5 Terminal block(17~24)
35 71
是否属于客 control signal 36 72 SW3 XT6 Terminal block(33~40)
户化物料 CN7 CN25
是
2. power supply for Thermostat: If it Solar-pump fault
feedback signal
37 73
38
否
is 24V AC, Please connect Terminal 2
15K RT6
74 CN15
block(XT5) 17.18.19.20.21; If it is Pump Control
signal (OUT)
39 75 CN8 Electric component position map
使用范围 40 CN1 AP
220V AC, please connect Terminal
通用 TC
block(XT5) 22.23.24 and connect
KM3
4 Display
出口 CN6
XT3
XT6
Terminal block(XT6) 33.34. board
XT1
内销 Communication Line
KM2
AP2 3 AP1
CN7 CN5
BK/BN
XT4
M2 KM1-4
XT2
XT5
CN4 BU KM1
KM1-2
OUTDOOR
UNIT CN1 CN2 CN3 YE/GN HT2
地点 状态 PE PE E
E
是否需
管一
要加工 3L PE
1L
是否需 3N
管二
要加工 2L
借通用登记 1N
TC 2N
物料状态
钣金
喷塑 印刷线路图技术要求:
GRS-CQ12Pd/NaE-M(I), GRS-CQ14Pd/NaE-M(I),GRS-CQ16Pd/NaE-M(I)
两器
管路 1.严格按图幅比例,图文正确,画面优美;
机加件 1 2.图幅为白底黑字; 2 3 4 5 6 D 换版 许海强 7
170913 材料:光白PET 8
采购 C 2 许海强 161011 F
注塑
3.用湿布擦15秒,再用浸汽油布擦15秒,图文仍清晰明了; B 换版 许海强 160125
F 喷涂 4.材料为光白PET; 标记 处数分区 更改文件号 签名 年月日 产品型号:
GRS-CQ16Pd/NaE-K(I)
丝印 线路图
控制
5.印刷线路图尺寸为:外框300X200(宽X高),内框296X196(宽X高), 设计 许海强 151215 标准化
图样标记 重量 比例
预装 Power XT1
外框圆角半径为R4,内框圆角半径为R2,尺寸公差为±1。 审核 数据审核
A W15 RT1 20K S 物料编码: 600007000179
下料 L1
6.其余应符合 L1
QJ/GD 41.12.001的要求。 AC-L 工艺 审定 A
会签 CODE
批准 共 1张
NAME 第 1张 GRSCQ16PdNaEKI.XL
L2 L2 RT2
1 2 3 4 5 620K 7 8
CN10 AP Main Board Only For RT6
L3 L3
AP1 Main PCB
W14 RT3 20K
N N N EH1 Auxiliary electric heater
HL1 Running indicating lamp
PE PE XT2 RT8 20K HL2 Error indicating lamp
W8 W9 W10 L1(OFF) W48
W45
3-way L2(ON) 1 W49 X11 CN13 HT1 Thermostat (WP95A-R)
XT4 KM2 valve2 2 X12 RT9
N
3
20K HT2 Thermostat (WP75A-R)
W16 2 1 W5 L1(OFF) W52
29 2-way L2(ON) 4 W50 W53 X8 KM1 Auxiliary electric heater AC contactor
5
Water tank Auxiliary
W17 4 3 W6 valve1 N
X7 RT4
30 6
50K KM2 Water tank Auxiliary electric heater AC contactor
Other
W55 CN11 B
B 7 X6
electric heater
W18 W7 N W51
31 KM1 thermal 8 W41 RT5 50K
RT1 Water-out temp sensor of the whole unit
CN12 W42
2
6
2
W77
X16 2 XT4 Terminal block(25~32)
A1 A2
connected by the consumer. Solar-pump 35 W78 XT5 Terminal block(17~24)
control signal 36 W79 CN7 CN1
Solar-pump fault 37 1L 1N XT6 Terminal block(33~40)
W80
2. power supply for Thermostat: If it is 24V AC, feedback signal 38 TC D
D
XT7 Terminal block(1,2)
Please connect Terminal block(XT5) Pump Control 39
W81 3L 3N 2L 2N
是否属于客 W82 CN8 CN2
户化物料
17.18.19.20.21; If it is 220V AC, please signal (OUT)
40
是 connect Terminal block(XT5) 22.23.24 and
CN3
否 connect Terminal block(XT6) 33.34.
使用范围 XT4 2 15K RT6
Gate controller W102 CN15
通用 25
220VAC W103 CN23
26 CN1 AP
出口
内销
Electric component position map SW1
27
W104
W105 CN16
28 4 Display
CN6
board
XT1
KM2
XT6
XT3
TC AP1 3 CN4 M3
BU
1 W114
XT1-L1
管一
是否需 CN7 CN5 2 XT1-N
要加工
YE/GN
XT2
XT5
是否需 OUTDOOR
XT7
管二
要加工 KM1 UNIT AP2
HT2
借通用登记 PE
物料状态
钣金
喷塑 印刷线路图技术要求:
两器 1.严格按图幅比例,图文正确,画面优美;
管路
机加件 2.图幅为白底黑字; 材料:光白PET
采购 3.用湿布擦15秒,再用浸汽油布擦15秒,图文仍清晰明了; F
注塑 F 换版 许海强 170913
F 喷涂 4.材料为光白PET; 标记 处数分区 更改文件号 签名 年月日 产品型号:
GRS-CQ16Pd/NaE-M(I)
丝印 5.印刷线路图尺寸为:外框300X200(宽X高),内框296X196(宽X高), 线路图
50
设计 许海强 160105 标准化 重量
控制 图样标记 比例
预装 外框圆角半径为R4,内框圆角半径为R2.尺寸公差为±1; 审核 数据审核
下料 6.其余应符合 QJ/GD 41.12.001的要求。 工艺 审定 S 物料编码: 600007000180
会签 批准 共 1张 第 1张 GRSCQ16PdNaEMI.XL
1 2 3 4 5 6 7 8
SPLIT TYPE
Air-to-water Heat Pump Split Versati
2 3 4 5 6 7 8
Power XT1
L4
L
24
AC-L CODE NAME
E1
25 AP3 AP2 Outdoor unit Main Board
N AC-N
26
L5
L-OUT N-OUT
80 AP3 Filter Board
AP4 Drive Board
COMP Compressor
PE 84 83 85 PE
EH4 Compressor band heater
EH5 Bottom band heater
L2 L6 L3
20K RT14 82
AC-L
X2 X1
EKV1 Electronic expansion valve coil1
15K RT15
AC-N
81 HP High pressure switch
T-SENSOR2
50K RT16 86 L1 Electrical Inductance 1
CN5
87
PWR
AC-L N L2 Electrical Inductance 2
88
20K RT17 L3~L7 Magnetic ring
T-SENSOR3 LP low pressure switch
89
PE AP4 M1 DC motor
HP p 76 90
77 HPP COM-ESPE2 91 COMM RT14 Defrosting temp sensor
92 U V W
L2-1 L1-1 L1-2 L2-2
RT15 Outdoor temp sensor
LP p 79 RT16 Discharged temp sensor
78 CN4
93 94 95
YE BN WH BU
RT17 Suction temp sensor
5
4 SP1 High pressure sensor
SP1 FA
3
EKV1 L7 XT1 Terminal block(3 BIT)
2
H-PRESS
1 YV4 4-way valve coil
SP AP2 U V W
COMP
3~
L1
PE
YV4 96 Electric component position map
4V
EH4
HEAT PE L1 AP2
AP4
EH5 DC-MOTOR1
VA-1 AP3
1
3
4
5
6
Communication Line
M1 XT1
AP1 3 L2
CN5
CN7
INDOOR
UNIT PE PE PE
Earthing wire is available for iron-clad motor,
while unavailable for plastic-clad motor.
2 3 4 5 6 7 8
SP
AP2 5
16 17 18
YE BN WH BU
S H-PRESS FA
4
EKV
Electric component position map
3
P 2
L10 L10
AP3
1
L13 L13 L13 L11 L11
L1
AP4
DC-MOTOR1
4V YV1 U V W L12 L12 L2
EH1 COMP
M1 AP2
HEAT 3~
PE
EH2 L1
VA-1
19 XT1
DC-MOTOR0
Communication Line PE
3 AP1 M2
1
3
4
5
6
3
4
5
6
CN7 CN5
M1 M2
INDOOR
PE PE UNIT
PE PE
印刷线路图技术要求:
1.严格按图幅比例,图文正确,画面优美;
2.图幅为白底黑字;
3.用湿布擦15秒,再用浸汽油布擦15秒,图文仍清晰明了; 51 材料:光白PET
4.材料为光白PET; C 换版 许海强 160224
5.印刷线路图尺寸为:外框200X150(宽X高),内框196X146(宽X高), B 换版 许海强 151215
GRS-CQ16Pd/NaE-K(O)
标记 处数分区 更改文件号 签名 年月日 产品型号:
外框圆角半径为R4,内框圆角半径为R2.尺寸公差为±1 线路图
设计 许海强 150801 标准化
6.其余应符合 QJ/GD 41.12.001的要求 图样标记 重量 比例
审核 数据审核
Air-to-water Heat Pump Split Versati SPLIT TYPE
1 2 3 4 5 6 7 8
CODE NAME
Power XT1
AP2 Outdoor unit Main Board
L4 L5 L6
1
L1 X1(AC-L1)
L4 L5 L6 AP3 Filter Board
2
L2 X2(AC-L2)
AP4 Drive Board
3
L4 L5 L6 AP3 X9
L3 X3(AC-L3)
EH1 Compressor band heater
L4 L5 L6
4
N X4 6
EH2 Bottom band heater
L7
5 X11(AC-L1) X8(N-F) X5(L1-F) X6(L2-F) X7(L3-F)
EKV Electronic expansion valve coil
RD HP High pressure switch
10 7 8 9
PE PE L Electrical Inductance
L8 L8 L8 L8 L1-L3 Inductor
20K RT1
AC-L LP High pressure switch
家研 L
家用
15K RT2
AC-N
BK M1 UP DC Motor
T-SENSOR2
试制 50K RT3 M2 Down DC Motor
质控
采购 11
L9
X1(R) X2(S) X3(T) RT1 Defrosting temp sensor
20K RT4
出口
T-SENSOR3
PWR1
12
L9 PWR RT2 Outdoor temp sensor
商工
钣金 HP p 27 13 RT3 Discharged temp sensor
喷塑
两器
28 HPP
COM-ESPE2
14
15 COMM AP4 RT4 Suction temp sensor
16
管一 LP p SP High pressure sensor
29
模具 30 LPP U V W X7 X8 X9 X6 X5 X4 XT1 Terminal block(5 BIT)
筛选 (X501) (X502) (X503) (R-2) (S-2) (T-2) (T-1) (S-1) (R-1)
EH1
U V W
HEAT
COMP L1 L2 L3 AP3
EH2
3~ M1 L
于客 VA-1 PE
DC-MOTOR0 AP2
物料 26
3
4
5
6
3
4
5
6
CN7 CN5
M1 M2 M2
INDOOR
PE PE UNIT
PE PE
否需
加工
19.2.3 印刷线路图技术要求:
Terminal Board
登记
状态
1.严格按图幅比例,图文正确,画面优美;
(1) 2.图幅为白底黑字;
GRS-CQ8.0Pd/NaE-K(I),GRS-CQ10Pd/NaE-K(I),GRS-CQ12Pd/NaE-K(I),GRS-CQ14Pd/NaE-K(I), GRS-
金
塑
器 3.用湿布擦15秒,再用浸汽油布擦15秒,图文仍清晰明了;
路
4.材料为光白PET;
加件
购
塑
CQ16Pd/NaE-K(I)
5.印刷线路图尺寸为:外框200X150(宽X高),内框196X146(宽X高),
B 换版 许海强 160120
材料:光白PET
会签 批准 共 1张 第 1张 GRSCQ16PdNaEMO.XL
1 2 3 4 5 6 7 8
52
SPLIT TYPE
Air-to-water Heat Pump Split Versati
(2) GRS-CQ12Pd/NaE-M(I),GRS-CQ14Pd/NaE-M(I),GRS-CQ16Pd/NaE-M(I)
20. Commissioning
20.1 Check before startup
For safety of users and unit, the unit must be started up for check before debugging. The procedures are as
below:
2 Is there written notice in which amendment items are shown in respect of unqualified installation? □
No. Pre-check √
1 Is appearance of the unit and internal pipeline system ok during conveying, carrying or installation? □
2 Check the accessories attached with the unit for quantity, package and so on. □
3 Make sure there is drawings in terms of electricity, control, design of pipeline and so on. □
4 Check if installation of the unit is stable enough and there is enough space for operation and repair. □
5 Completely test refrigerant pressure of each unit and perform leakage detection of the unit. □
6 Is the water tank installed stably and are supports secure when the water tank is full? □
7 Are heat insulating measures for the water tank, outlet/inlet pipes and water replenishing pipe proper? □
53
Air-to-water Heat Pump Split Versati SPLIT TYPE
Are the nilometer of water tank, water temperature indicator, controller, manometer, pressure relief valve and
8 □
automatic discharge valve etc. installed and operated properly?
9 Does power supply accord with the nameplate? Do power cords conform to applicable requirements? □
Is power supply and control wiring connected properly according to wiring diagram? Is earthing safe? Is each
10 □
terminal stable?
11 Are connection pipe, water pump, manometer, thermometer, valve etc. are installed properly? □
NOTE: If there is any item marked with ×, please notify the contractor. Items listed above are just for reference.
Judge the following items (if there is not any filling, qualification will be regarded.)
Confirmed Items after pre-checking
Normal debugging work can’t be performed unless all installation items are qualified. If there is any problem,
it must be solved firstly. The installer will be responsible for all costs for delay of debugging and re-debugging
incurred by any problem which is not solved immediately.
Is the written amending report which should be signed after communication provided to installer?
Yes ( ) No ( )
The following procedure should be executed by experience and qualified maintenance men.
NOTE: heat the lubricating oil at least 8h in advance to prevent refrigerant from mixing with the lubricating oil, which
may cause damage to the compressor when starting up the unit.
Check whether the oil temperature of the compressor is obviously higher than the outdoor ambient
2
temperature.
NOTE: if the oil temperature of the compressor is obviously higher than the outdoor ambient temperature, it means
that the heating tape of compressor is damaged. In that case, the compressor will be damaged easily. Therefore, repair
the heating tape before using the unit.
Check whether the phase sequence of the main power supply is correct. If not, correct the phase sequence
3
firstly.
NOTE: recheck the phase sequence before start-up to avoid reverse rotation of the compressor which may damage
the unit.
Apply the universal electric meter to measure the insulation resistance between each outdoor phase and earth
4
as well as between phases.
NOTE: defective earthing may cause electric shock.
No. Ready to start
54
SPLIT TYPE
Air-to-water Heat Pump Split Versati
Cut off all temporary power supply, resume all the insurance and check the electricity for the last time.
1
Check the power supply and voltage of the control circuit; _____V must be ±10% within the range of rated
operating power.
No. Start up the unit
1 Check all the conditions needed to start up the unit: oil temperature, mode, required load etc.
Start up the unit, and observe the operation of compressor, electric expanding valve, fan motor and water
pump etc.
2
Note: the unit will be damaged under abnormal running state. Do not operate the unit in states of high
pressure and high current.
Others:
55
Air-to-water Heat Pump Split Versati SPLIT TYPE
① Liquid slugging happens when liquid ① Check if expansion valve is failure and
Heavy noise of
refrigerant enters into compressor. temp. sensor is loose. If that, repair it.
compressor ② Internal parts in compressor are broken. ② Replace compressor.
The unit does not heat ① Repair by leakage detection and add
① Leakage of refrigerant.
although compressor refrigerant.
② Malfunction of compressor.
is running ② Replace compressor.
56