TCD - 054 Over current error in motor


Point of Application ● DI120~150
detection ● Speed CPU ● DI180~420
[Meaning] In case that high current that over 1.3 times than motor standard current is [Action to take]
detected over 40seconds under inspection or normal operation. 1. Check if the motor code of address 0001 by A51E is match
to motor model name plate on motor.
[Explanation]
22kW:EMV-30HU1S, 30HU1 Motor Code $15
20msec Routine
30kW:EMV-40HU1S, 40HU1 Motor Code $16
Start 45kW:EMV-60HU1G, Motor Code $17
43kW:EMV-60HU1, (LG GL motor) Motor Code $21
It reads current of motor in 3 phase
50kW:TGLV-HM(LEORY SOMER Motor) Motor Code $22
76kW:EMH-101HU1,2,3 Motor Code $23
Is it over 1.3 times No
than motor standard 2. Check if the TR/MC code of address 0002 by A52E is match
current? to real applied motor.
Yes
Counter reset 3. Check if the CT turn code of address 000A by A51E is match
Increase Counter to real applied turn number.
4. Check if the CT code of address 000B by A51E is match to
Counter >=200? real Hall CT type.
Yes No Code Capacity
TCD occurs $01 100A/4V
$02 150A/4V
Yes
$03 200A/4V
$04 400A/4V

End 5. Check load that car real load and added 50% load of car
capacity is balanced with Counter weight.
6. Motor connection of each phase (U-V-W, U-W-V)
check A,B phase of R.E
7. Try to replace DPC-1XX,300 PCB
8. Try to replace R.E