INSTRUMENTATION LOOP 5284-8550-SP-0001 Rev D4
TEMPLATES
FOSTER WHEELER ENERGY LIMITED
PROJECT SPECIFICATION
1. PURPOSE
This specification, together with the referenced standards and specifications, sets out the requirements to
provide a standard set of project loop type templates that shall be used to populate SmartPlant Instrumentation
for the KNPC Clean Fuels Project.
2. SCOPE
2.1 Project Objectives
The aim of the loop type templates is to provide a method that ensures consistency for SPI data population.
3. DEFINITIONS
Company name abbreviations are used in this procedure as follows:
Term Definition
AV Automation Vendor
CEMS Continuous Emission Monitoring System
An Engineering Company, and their agents, with lump sum turn key responsibility to Engineer,
CONTRACTOR
Procure and Construct a portion of the CFP.
DCS Distributed Control Systems
EPC Engineering, Procurement & Construction
FAR Field Auxiliary Room
FEED Front End Engineering Design
FF Foundation Fieldbus
FGS Fire & Gas System
IMCS Integrated Motor control System
IPS Instrumented Protective System
KNPC Kuwait National Petroleum Company
MAA Mina Al Ahmadi Refinery
MAB Mina Abdullah Refinery
MMS Machinery Monitoring System
OPC Object Linking and Embedding for Process Control communication protocol
SEED files Project ready configuration/reference details
SHU Shuaiba Refinery
SP3D SmartPlant 3D
SPEL SmartPlant Electrical
SPF SmartPlant Foundation
SPI SmartPlant Instrumentation
SPPID SmartPlant P&ID
TGS Tank Gauging System
UDF User Defined Field
UDT User Defined Table
WBS Work Breakdown Structure
4. REFERENCE DOCUMENTS
Conflicts, errors and discrepancies found in this specification and other associated documents shall be brought
to Company/PMC’s attention for resolution.
Company/PMC reserves the right to amend/update this specification and reference documents at any stage of
project and Contractor shall ensure compliance to it.
5. GENERAL NOTES
Alarm identification shown on typical loop templates are for example only and will need to be modified for each
loop as required.
Switch and/or trip identification shown on typical loop templates are for example only and will need to be
modified for each loop as required.
Where the instrument type is listed as undefined, this implies generic instrument types and shall be replaced by
the appropriate instrument type i.e. for a displacer level transmitter, replace level transmitter with level displacer,
etc.
Where the SPI profile default data differs from the loop template tag associated data, the associated tag data in
SPI shall be updated in line with the loop template upon creation of the tag in SPI.
The location of the instrument on the loop template is indicative only and needs to be updated based on the
actual location of the device for each particular loop, e.g. Building number if located inside a building, etc. For
consistency, the following shall be implemented where the devices are field mounted:
- Field: Non Process field mounted instruments such as local indicators and F&G detectors.
- Inline : Direct Mounted In-Line Instrument such as vortex flowmeters, coriolis flowmeters, control valves, VA meters, etc.
- Offline: Process Related Offline Instrument such as flow transmitters, pressure gauges, pressure transmitters
etc.
- On-valve: Valve mounted instruments such as positioners, solenoid valves, proximity switches, etc.
- Equip: Instruments mounted on equipment.
In this case two instruments of the same type (LI’s) are in the same loop. Therefore to ensure they have unique
tag numbers a suffix is used. The control system tag shall follow the associated field device, while the
corresponding duplicated tags shall be suffixed.
UUU-LI-XXXXA
UUU-LI-XXXX
The combined sequence number and suffix making the tag numbers unique.
Alarms to be shown as required.
For each duplicated equipment, the loop number shall be identical with the exception of the suffix, which will be
unique per duplicated equipment.
Example:
For MAB Unit 128 Train 2, the H2 Compression contains 7 identical H2 Compressors. Refer to the table below
for the instrumentation numbering implementation.
Loop Instrument
Equipment No Description
Numbering Numbering
128-LLL- 128-FFFFFF-
128-K-0210 H2 Compressor 1
2XXXA 2XXXAS
128-LLL- 128-FFFFFF-
128-K-0220 H2 Compressor 2
2XXXB 2XXXBS
128-LLL- 128-FFFFFF-
128-K-0230 H2 Compressor 3
2XXXC 2XXXCS
128-LLL- 128-FFFFFF-
128-K-0240 H2 Compressor 4
2XXXD 2XXXDS
128-LLL- 128-FFFFFF-
128-K-0250 H2 Compressor 5
2XXXE 2XXXES
128-LLL- 128-FFFFFF-
128-K-0260 H2 Compressor 6
2XXXF 2XXXFS
128-LLL- 128-FFFFFF-
128-K-0270 H2 Compressor 7
2XXXG 2XXXGS
Where
LLL = Loop Measured Variable
FFFFFF = Instrument Type
XXX = Loop Sequence Number
S = Instrument Suffix where required.
The corresponding tag in the Main FAR shall be suffixed with 'R', depicting it as the remote panel instrument, as
per following examples:-
The following table shows the OFF State and ON State signal description for each instrument type having digital
signals:-
DO Signals
Instrument Type ON OFF
Indicating Lamp Activated Not Activated
Solenoid Valve Energized De-Energized
Motor Start Command Start No Action
Motor Stop Command No Action Stop
Electric Heater ON Command ON No Action
Electric Heater OFF Command No Action OFF
Trip Command Normal Trip
MOV Open Command Open Not Open
MOV Close Command Close Not Close
Permissive Command Permissive No Action
Interface Signals between Systems ON OFF
Alarm Light / Beacon / Horn Activated Not Activated
DI Signals
Instrument Type ON OFF
IPS Hand Signal Normal Activated
FGS Hand Signal Activated Normal
Interface Signals between Systems ON OFF
Limit Switch Open Open Not Fully Open
Not Fully
Limit Switch Closed Closed Closed
Motor Run Status Run Stopped
Motor Auto/Man Status Auto Manual (Local)
Motor Fault Status Normal Alarm
Trip Switch Normal Trip
Alarm Switch Normal Alarm
Enable
MOS Enable Permission Permission Not Permit
Enable
OOS Enable Permission Permission Not Permit
Field Reset Switch Reset No Action
MOV Local / Remote Status Remote Local
Deluge Valve Release Switch Activated Normal
FGS Alarm Switch Alarm Normal
Notes:
2. Where alarms are shown, they are indicative only, refer to PEFS and modify accordingly.
3. I/O type to be defined as applicable, i.e. AI, HART-AI, AO, HART-AO or Fieldbus.
The Emergency Isolation Valve (EV) shall be remotely closed from CCR, Main FAR or locally at a safe distance
from the hazard fire zone, e.g. 15m from pumps. The Emergency Isolation Valve shall only be reset locally at the
pump/compressor RCU, therefore enforcing operator to ensure a safe environment prior to resetting valve to
normal conditions. The Emergency Isolation Valve shall not be operated from the DCS. Valve closed status
indication shall be displayed at the initiating switch in the CCR and Main FAR.
The requirements for limit switches are applicable as per P6000CFP.000.10.30.003 section 7.8.
2) Standby pump auto-start functionality is inhibited if Emergency Isolation Valve close command is given or
Emergency Isolation Valve is not in fully open position.
6. Where instrument type is shown as 'TEMPERATURE ELEMENT', it is because the type of element is not yet
know. Once the element type is known, replace it with the selected type, i.e. RTD or TC.
C CONDUCTIVITY
D DENSITY
J POWER
12 K TIME, SCHEDULE
L LEVEL
14 M MOISTURE
M MOTOR
P PRESSURE
17 P PRESSURE RELIEF
18 Q QUANTITY
R RADIATION
S SPEED, FREQUENCY
T TEMPERATURE
W WEIGHT, FORCE
X UNCLASSIFIED
26
Loop when used in a Safety Instrumented System. Loop to be
YZ EVENT, STATE, PRESENCE (IPS) uniquely identified based on the Measured/Initiating variable
(Y)
APPENDIX 1
ANALYZER (A) Originating
A-001 DCS Analyzer Indication Seed
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
A-106 DCS Analyzer Indication with two Components and Common Fault Alarm
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-A-XXXX Type
TAGS
UUU-AW-XXXX Analyzer Connection / Probe N/A Inline N/A N/A
UUU-AE- XXXX Analyzer Element N/A Offline N/A N/A
UUU-AT- XXXX Analyzer Transmitter N/A Offline N/A N/A
UUU-AY- XXXXA Analyzer Signal HART-AI Analyzer DCS 4-20mA
UUU-AY- XXXXB Analyzer Signal HART-AI Analyzer DCS 4-20mA
UUU-AS- XXXX Analyzer Fault Signal DI Analyzer DCS VFC
UUU-AA- XXXX Analyzer Common Fault Alarm (Soft) SB DCS DCS N/A
UUU-AI- XXXXA Analyzer Indicator (Soft) SB DCS DCS N/A
UUU-AI- XXXXB Analyzer Indicator (Soft) SB DCS DCS N/A
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
A-108 DCS Analyzer Control with Common Fault Alarm to other function
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-A-XXXX Type
TAGS
UUU-AW-XXXX Analyzer Connection / Probe N/A Inline N/A N/A
UUU-AE- XXXX Analyzer Element N/A Offline N/A N/A
UUU-AT- XXXX Analyzer Transmitter HART-AI Analyzer DCS 4-20mA
UUU-AS- XXXX Analyzer Fault Signal DI Analyzer DCS VFC
UUU-AA- XXXX Analyzer Common Fault Alarm (Soft) SB DCS DCS N/A
UUU-AC- XXXX Analyzer Controller (Soft) SB DCS DCS N/A
Note: This is a generic loop template, refer to PEFS for selection of appropriate instrument type.
PEFS
DETAIL
IZ
YYYY
PEFS
HH
AZT ( TYPE OF
XXXX ANALYSIS )
2oo3 A,B,C
DETAIL
APPENDIX 2
FIRE DETECTION (AF) Originating
AF-001 FIRE ALARM BEACONS Seed
AF-002 FIRE ALARM SOUNDER Seed
AF-003 COMMON FIRE ALARM Seed
AF-004 MANUAL CALL POINT Seed
AF-005 FLAME DETECTOR Seed
AF-006 DELUGE VALVES
IZ AFL
YYYY XXXX
FGS
IZ AFA
YYYY XXXX
FGS
IZ AFL
YYYY XXXX
FGS
1) Two non-return valves shall be installed to prevent back flow from the SIA system in the case of loss of Instrument Air
Header pressure.
2) A low pressure alarm shall be provided to indicate low air pressure in the SIA, set at the minimum pressure that is required
for three valve strokes
AFA
XXXX
PEFS / DETAIL
IZ
YYYY
FGS
AFT
XXXX IR
AFA
XXXX
PEFS / DETAIL
IZ
YYYY
FGS
AFT
XXXX HEAT
APPENDIX 3
GAS DETECTION (AG) Originating
AG-001 GAS DETECTOR Seed
AG-002 BEAM GAS DETECTOR Seed
AG-003 GAS ALARM BEACONS Seed
AG-004 GAS ALARM SOUNDER Seed
AG-005 COMMON GAS ALARM Seed
AG-006 COMMON GAS ALARM Seed
IZ
YYYY
FGS
AGT
XXXX
IZ
YYYY
FGS
AGE AGT
XXXX XXXX
IZ AGL
YYYY XXXX
FGS
IZ AGA
YYYY XXXX
FGS
IZ AGL
YYYY XXXX
FGS
IZ AGA
YYYY XXXX
FGS
APPENDIX 4
BURNER (B) Originating
B-001 DCS Burner Indication Seed
B-002 IPS Burner Trip Seed
APPENDIX 5
CONDUCTIVITY Originating
APPENDIX 6
DENSITY Originating
APPENDIX 7
EMERGENCY Originating
E-012 Emergency Isolation Valve Seed
E-002 Emergency Isolation Valve with Limit Switches to IPS Seed
VOLTAGE
E-102 UNDER VOLTAGE TRIP (DCS) PSCJ
E-103 UNDER VOLTAGE TRIP (IPS) PSCJ
Note 1: Remote actuation of Emergency Isolation Valve located at a safe distance in field of at least 15m
away from the anticipated leak point within line of sight of EV and allowing free access in emergency
situations.
Note 2: For Emergency Isolation Valve Operating Philosophy, refer to Section 7, note 5.
Note 3: Hand switch indication (EL) requirements to be determined based on the HFE studies conducted
by ICSS.
Note 1: Only applicable where valve is located inside the fire zone area.
Note 2: For Emergency Isolation Valve Operating Philosophy, refer to Section 7, note 5.
Note 3: Hand switch indication (EL) requirements to be determined based on the HFE studies conducted
by ICSS.
APPENDIX 8
FLOW Originating
F-001 Variable Area Flowmeter Seed
F-002 Restriction Orifice Seed
F-011 DCS Flow Indicator Seed
F-012 DCS Flow Indicator (Foundation Fieldbus) Seed
F-013 DCS Flow Control with Local Indicator Seed
F-014 DCS Flow Control with Local Indicator (Foundation Fieldbus) Seed
F-015 DCS Flow Control and ESD Flow Trip Seed
F-016 IPS Flow Trip Seed
F-017 IPS Flow Trip with 2oo3 Voting Seed
F-018 Mof3 DCS Control Seed
F-019 DCS Flow Split Range Control Seed
F-020 DCS Flow Split Range Control (Foundation Fieldbus) Seed
F-021 Mof3 DCS Control (Foundation Fieldbus)
F-101 DCS Vortex Flow Control with Local Indicator (Foundation Fieldbus) PSCJ
F-102 DCS VA Meter with Transmitter PSCJ
F-103 IPS (1oo1) Flow Trip and DCS Flow Control with Local Indicator (Foundation Fieldbus) PSCJ
F-104 DCS Dual Flow Indication with Local Indicator (Foundation Fieldbus) PSCJ
Vortex Flow Indication (Foundation Fieldbus) with Temperature Compensation with Local
F-105 PSCJ
Indicator
F-106 Ultrasonic Flow Indication (Foundation Fieldbus) with P/T Compensation PSCJ
F-107 Ultrasonic Flow Indication (Foundation Fieldbus) with P/T Compensation from other loops PSCJ
F-108 Flow Ratio Indication PSCJ
F-109 DCS Flow Control (Foundation Fieldbus) PSCJ
F-110 DCS Flow Ratio Control with Local Indicator (Foundation Fieldbus) PSCJ
F-111 DCS Vortex Flow Control with Local Indicator and IPS Flow Trip PSCJ
F-112 Vortex Flow Control with Local Indicator (Foundation Fieldbus) with Temperature Compensation PSCJ
F-113 DCS Vortex Flow Split Range Control with Local Indicator (Foundation Fieldbus) PSCJ
F-114 DCS Utrasonic Flow Control with Local Indicator and IPS Flow Trip PSCJ
F-115 DCS Flow Indication with two Local Indicators (Foundation Fieldbus) PSCJ
F-116 Flow Regulator PSCJ
F-117 DCS Flow Control with Local Indicator (Fieldbus) and IPS Flow Trip with Local Reset PSCJ
F-118 DCS Flow Control (Fieldbus) and IPS Flow Trip with Local Reset PSCJ
F-119 DCS Vortex Flow Control (Fieldbus) and IPS Flow Trip with Local Reset PSCJ
F-120 DCS Vortex Flow Control with Local Indicator (Fieldbus) and IPS Flow Trip with Local Reset PSCJ
F-121 DCS Flow Ratio Control with Local Indicator (Foundation Fieldbus) and Selector Function PSCJ
F-122 Vortex Flow Indication (Foundation Fieldbus) with P/T Compensation PSCJ
F-123 DCS Flow Control with Temperature Compensation (Foundation Fieldbus) PSCJ
F-124 Mof3 DCS Control (Fieldbus) with Local Indicator PSCJ
F-125 Mof3 DCS Function PSCJ
F-126 DCS Flow Indication (Foundation Fieldbus) with P/T Compensation and Local Indicator PSCJ
F-127 DCS Vortex Flow Control with P/T Compensation (Foundation Fieldbus) PSCJ
F-128 DCS Vortex Flow Control (Foundation Fieldbus) PSCJ
IPS (1oo1) Flow Trip and DCS Flow Control with Local Indicator (Foundation Fieldbus) with
F-129 PSCJ
Reset
F-130 DCS Flow Control with Local Indicator and Temperature Compensation (Foundation Fieldbus) PSCJ
F-131 DCS Flow Vortex Indication with Local Indicator (Foundation Fieldbus) PSCJ
F-132 IPS (1oo1) Flow Trip and DCS Flow Control (Foundation Fieldbus) PSCJ
H
FI
XXXX
PEFS
FF
FT
XXXX
H
FI
XXXX
DETAIL
FF
FT FE
XXXX XXXX
FC
XXXX
FI
XXXX
PEFS
FT FV
XXXX XXXX
DETAIL
FC
FF XXXX
FI
XXXX
FF FF
PEFS
FT FV
XXXX XXXX
DETAIL
IZ
YYYY
PEFS
HH
FZT
XXXX
IZ
YYYY
DETAIL
HH
FZT
XXXX
FZE
XXXX
IZ
YYYY
PEFS
HH
FZT
XXXX
2oo3 A,B,C
HH
FZT
XXXX
A
HH
FZT
DETAIL
IZ
XXXX
YYYY
B
HH
FZT
XXXX
C
FZE
XXXX
FC
XXXX
PEFS
FF
B%-100%
FF
0%-A%
FV FV
FF
FT XXXX XXXX
XXXX A B
DETAIL
F-101 DCS Vortex Flow Control with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX Vortex transmitter (Fieldbus) FieldbusFF Inline DCS FIELDBUSFF
UUU-FI-XXXX Flow Indicator (Fieldbus) FieldbusFF Field DCS FIELDBUSFF
UUU-FC-XXXX Flow Controller (Soft) SB DCS DCS N/A
UUU-FY-XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX Control Valve N/A Inline N/A N/A
PEFS
DETAIL
F-103 IPS (1oo1) Flow Trip and DCS Flow Control with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXX Flow Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX Flow Controller (Soft) SB DCS DCS N/A
UUU-FY-XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX Control Valve N/A INLINE N/A N/A
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-FZ-YYYY Type
TAGS:
1
UUU-FZE-YYYY Orifice Plate N/A INLINE N/A N/A
UUU-FZT-YYYY DP Flow transmitter 1 HART-AI Offline IPS 4-20mA
PEFS
DETAIL
F-104 DCS Dual Flow Indication with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX Venturi N/A INLINE N/A N/A
UUU-FT-XXXX DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXXA Flow Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-XXXX Flow Indicator (Soft) SB DCS DCS N/A
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-YYYY Type
TAGS:
UUU-FT-YYYY DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-YYYYA Flow Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-YYYY Flow Indicator (Soft) SB DCS DCS N/A
PEFS
DETAIL
F-107 Ultrasonic Flow Indication (Foundation Fieldbus) with P/T Compensation from other loops
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
FLOW TRANSMITTER ULTRASONIC
UUU-FT-XXXX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FY-XXXX FLOW COMPUTER (SOFT) SB DCS DCS N/A
UUU-FI-XXXX FLOW INDICATOR (SOFT) SB DCS DCS N/A
F-110 DCS Flow Ratio Control with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A Inline N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FFC-XXXX FLOW RATIO CONTROLLER (SOFT) SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-111 DCS Vortex Flow Control with Local Indicator and IPS Flow Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-112 Vortex Flow Control with Local Indicator (Foundation Fieldbus) with Temperature Compensation
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TW-YYYY THERMOWELL N/A INLINE N/A N/A
UUU-TE-YYYY TEMPERATURE ELEMENT 2 N/A OFFLINE N/A N/A
UUU-TT-YYYY TEMPERATURE TRANSMITTER FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TI-YYYY TEMPERATURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-FY-XXXXA FLOW COMPUTER (SOFT) SB DCS DCS N/A
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
Note: Flow, Pressure and Temperature tags may have different sequence numbers but are all
associated to the flow loop.
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
F-113 DCS Vortex Flow Split Range Control with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-XXXXB FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-FY- XXXXA1 DCS FUNCTION SB DCS DCS N/A
UUU-FY- XXXXB1 DCS FUNCTION SB DCS DCS N/A
UUU-FY- XXXXA VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FY- XXXXB VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXXA CONTROL VALVE N/A INLINE N/A N/A
UUU-FV- XXXXB CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
F-114 DCS Utrasonic Flow Control with Local Indicator and IPS Flow Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
FLOW TRANSMITTER ULTRASONIC
UUU-FT-XXXX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-115 DCS Flow Indication with two Local Indicators (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
1
UUU-FE-XXXX Orifice Plate N/A INLINE N/A N/A
UUU-FT-XXXX DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXXA Flow Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-XXXXB Flow Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-XXXX Flow Indicator (Soft) SB DCS DCS N/A
PEFS
DETAIL
F-117 DCS Flow Control with Local Indicator (Fieldbus) and IPS Flow Trip with Local Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A Inline N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-118 DCS Flow Control (Fieldbus) and IPS Flow Trip with Local Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A Inline N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-119 DCS Vortex Flow Control (Fieldbus) and IPS Flow Trip with Local Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-120 DCS Vortex Flow Control with Local Indicator (Fieldbus) and IPS Flow Trip with Local Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-121 DCS Flow Ratio Control with Local Indicator (Foundation Fieldbus) and Selector Function
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A Inline N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FY-XXXXA DCS FUNCTION SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
FY
FF OTHER FUNCTION
XXXX
FI A
XXXX
FF
PEFS
FT FV
XXXX XXXX
FF FY
XXXX OTHER FUNCTION
FI A
XXXX
FF
DETAIL
FF FV FY
FE FT XXXX XXXX
XXXX XXXX
IAS
FC
XXXX
FY TI
XXXX YYYY
PEFS
FF
FF FF FV
FT TT XXXX
XXXX YYYY
(TYPE)
FC
XXXX
FY TI
XXXX YYYY
A
DETAIL
FF
TT
YYYY
FF FF
FV FY
FT FE TE TW XXXX
XXXX
XXXX XXXX YYYY YYYY
(TYPE)
IA
HH FF
Mof3 FC FI
IZ
YYYY ZZZZ ZZZZ
FY-ZZZZA
DETAIL
FF
FY
FV
ZZZZ
ZZZZ
A
IAS
Mof3
IZ OTHER
YYYY FY-ZZZZA FUNCTION
DETAIL
Mof3
IZ OTHER
YYYY FY-ZZZZA FUNCTION
F-126 DCS Flow Indication (Foundation Fieldbus) with P/T Compensation and Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
UUU-FE-XXXX ORIFICE PLATE N/A INLINE N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TW-YYYY THERMOWELL N/A INLINE N/A N/A
2
UUU-TE-YYYY TEMPERATURE ELEMENT N/A OFFLINE N/A N/A
UUU-TT-YYYY TEMPERATURE TRANSMITTER FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TI-YYYY TEMPERATURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-PT-ZZZZ PRESSURE TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PI-ZZZZ PRESSURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-FY-XXXX FLOW COMPUTER (SOFT) SB DCS DCS N/A
UUU-FI-XXXX FLOW INDICATOR (SOFT) SB DCS DCS N/A
Note: Flow, Pressure and Temperature tags may have different sequence numbers but are all
associated to the flow loop.
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
FC
XXXX
PI FY TI
ZZZZ XXXX YYYY
PEFS
FF
FF FF FF FV
PT FT TT XXXX
ZZZZ XXXX YYYY
(TYPE)
FC
XXXX
FY TI
XXXX YYYY
A
DETAIL
FF
TT
YYYY
FF FF
FV FY
FT FE TE TW XXXX
XXXX
XXXX XXXX YYYY YYYY
(TYPE)
IA
F-129 IPS (1oo1) Flow Trip and DCS Flow Control with Local Indicator (Foundation Fieldbus) with Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXX CONTROL VALVE N/A Inline N/A N/A
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-FZ-YYYY Type
UUU-FZE-YYYY ORIFICE PLATE N/A INLINE N/A N/A
UUU-FZT-YYYY DP FLOW TRANSMITTER HART-AI Offline IPS 4-20mA
PEFS
DETAIL
F-130 DCS Flow Control with Local Indicator and Temperature Compensation (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
UUU-FE-XXXX ORIFICE PLATE N/A INLINE N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TW-XXXX THERMOWELL N/A INLINE N/A N/A
UUU-TE-XXXX TEMPERATURE ELEMENT N/A OFFLINE N/A N/A
UUU-TT-XXXX TEMPERATURE TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-TI-YYYY TEMPERATURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-FY-XXXXA FLOW COMPUTATION (SOFT) SB DCS DCS N/A
UUU-FC- XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-FY- XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXX CONTROL VALVE N/A Inline N/A N/A
Note: Flow and Temperature tags may have different sequence numbers but are all associated to the flow loop.
FC
XXXX
FY TI
XXXX YYYY
PEFS
A
FF
FI
XXXX FF
FF FF FV
FT TT XXXX
XXXX YYYY
(TYPE)
FC
XXXX
FY TI
XXXX YYYY
A
DETAIL
FF
FF
FI
XXXX TT
YYYY
FF FF
FV FY
FT FE TE TW XXXX
XXXX
XXXX XXXX YYYY YYYY
(TYPE)
IA
F-131 DCS Flow Vortex Indication with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR (SOFT) SB DCS DCS N/A
PEFS
DETAIL
F-132 IPS (1oo1) Flow Trip and DCS Flow Control (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FC-XXXX Flow Controller (Soft) SB DCS DCS N/A
UUU-FY-XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX Control Valve N/A INLINE N/A N/A
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-FZ-YYYY Type
TAGS:
UUU-FZE-YYYY Orifice Plate 1 N/A INLINE N/A N/A
UUU-FZT-YYYY DP Flow transmitter 1 HART-AI Offline IPS 4-20mA
FC
XXXX
FF
FF
FT
XXXX FV
XXXX
PEFS
HH
FZT
YYYY
IZ
YYYY
FC
XXXX
FF
FT FY FV
XXXX XXXX XXXX
FF
DETAIL
IAS
HH
FZE FZT
YYYY YYYY
IZ
YYYY
FAH
XXXX
PEFS
H
FS
XXXX
FAH
XXXX
DETAIL
H
FS
XXXX
F-135 Vortex Dual Sensor - IPS Trip and DCS Control with Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF Offline DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXX CONTROL VALVE N/A Inline N/A N/A
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-FZ-YYYY Type
UUU-FZE-YYYY VORTEX METER (REMOTE TX) N/A Inline N/A N/A
UUU-FZT-YYYY FLOW TRANSMITTER VORTEX HART-AI Offline IPS 4-20mA
PEFS
DETAIL
F-137 DCs Flow control with local indicator (FF) and selector function
Refer to F-314 & PEFS
F-140 Moo3 temp compensation and DCS control with local indicator
Refer to combination of F-124 & T-017 & PEFS
F-141 Vortex Flow Control with Local Indicator and DCS interlock
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FIELDBUS FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-XY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-FY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
F-142 IPS (1001) flow trip and DCS control with IPS trip with reset
Refer to combination of F-106 & F-118
F-143 DCS vortex flow ratio control with local indicator , IPS trip and reset switch
Refer to as F-117 & PEFS
F-145 DCS flow split range control (FF) with two local indications
Refer to F-113
F-146 IPS Flow Trip (2oo3) and DCS Flow control with Local Indicator (Foundation Fieldbus)
Refer to F-017 & F-014
F-147 IPS Flow Trip (1oo2) and DCS Split Range Flow control with Two Local Indicator (Foundation Fieldbus)
Refer to F022 & F101 & PEFS
F-149 DCS Flow Ratio Control with Local Indicator (Foundation Fieldbus) along with Ratio Alarm Indication
Refer to F-101 & PEFS
F-150 DCS Flow Control with Local Indicator (Foundation Fieldbus) & DCS Flow Trip
Refer to F-141 & PEFS
DCS Flow Control with Local Indicator (Foundation Fieldbus) & Temperature Compensation (Foundation
F-151 Fieldbus) along with inputs & outputs to Other Functions
Refer to PEFS
F-153 DCS Flow Indication with Local Indicator (Foundation Fieldbus) and output to other Function
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A INLINE N/A N/A
UUU-FT-XXXX DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
PEFS
DETAIL
IPS (1oo1) Flow Trip and DCS Flow Control along with Temperature Compensation Input from Other Function
F-154 with Local Indicator (Foundation Fieldbus)
Refer to F-103 & PEFS
F-155 DCS Flow Control with local Indicator (Foundation Fieldbus) along with Input from Other Function
Refer to F-110 & PEFS
F-156 DCS Vortex Flow Indication with Local Indicator (Foundation Fieldbus) and output to other function
Refer to F-153
F-157 Anti Surge Flow Control with Local Indicator and IPS Flow Trip with Local Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
F-158 DCS Vortex Dual Flow Control with Local Indicator (Foundation Fieldbus), with facility for Manual set point
control
Refer to PEFS
F-159 DCS Flow control with Local Indicator (Foundation Fieldbus) and DCS Indication with Temperature
Compensation (Foundation Fieldbus)
Refer to F-112 & PEFS
F-160 DCS Vortex Flow Control with Local Indicator (Foundation Fieldbus) and DCS Indication with Temperature
Compensation (Foundation Fieldbus)
Refer to F-112 & PEFS
F-161 DCS Coriolis Flow control with local Indicator (Foundation Fieldbus) & IPS Trip along with Other Function
with local Reset
Refer to F-117 & P-310
F-162 DCS Vortex Flow Control with Local Indicator (Foundation Fieldbus) with Inputs from other functions
Refer to F-101 & PEFS
F-164 DCS VORTEX FLOW CONTROL WITH IPS TRIP USING DUAL SOV, LOCAL INDICATION (FOUNDATION
FIELDBUS)
PEFS
F-166 DCS Ultrasonic Flow Indication (Foundation Fieldbus) with P/T Compensation
Refer to F-106
F-168 DCS Flow Control with local Indicator (Fieldbus) along with Input from Flow Ratio Controller having steam
Ratio Set Point
Refer to F-110 & PEFS
F-169 DCS Dual DP type Flow Transmitter Flow control with local indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A INLINE N/A N/A
UUU-FT-XXXXA DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FT-XXXXB DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FY-XXXXA DCS FUNCTION SB DCS DCS N/A
UUU-FY-XXXXB DCS FUNCTION SB DCS DCS N/A
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
PEFS
DETAIL
F-170 DCS Vortex flow control & IPS trip along with Pressure/temp compensation input and DCS Indication and
output to raito control in DCS
Refer to F-016 & F-106 & PEFS
F-172 DCS Flow Compensation with P/T Compensation (FF) with Pressure Local Indicator (FF)
Refer to F-107 & T-016 & P-300 & PEFS
F-174 IPS (2oo1) Vortex Flow Trip and DCS vortex flow control (FF) with Local Indicator (FF)
Refer to F-103
F-175 DCS flow control & IPS trip with temperature compensation (FF)
Refer to F-117 & T-017 & PEFS
F-176 IPS Dual Transmitter (1oo2) flow trip & DCS flow control (FF) with local indicator (FF)
Refer to F-014 & F-022
F-177 DCS Vortex Flow Indication (FF) with flow totalizing indicator in DCS
Refer to F-012 & PEFS
F-178 DCS Dual DP type flow control with IPS trip (1oo1) with local indicator (FF)
Refer to F-016 & F-179
F-179 DCS dual DP type flow transmitter control with local indicator (FF)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE-XXXX ORIFICE PLATE N/A INLINE N/A N/A
UUU-FT-XXXXA DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FT-XXXXB DP FLOW TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-FY-XXXXA DCS FUNCTION SB DCS DCS N/A
UUU-FY-XXXXB DCS FUNCTION SB DCS DCS N/A
UUU-FI-XXXXA FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
PEFS
DETAIL
F-180 IPS Flow Trip (1oo3) and DCS Split Range Flow control with Two Local Indicator (Foundation Fieldbus)
Refer to F-017 & F-101 & PEFS
F-185 IPS (2oo3) TRIP AND DCS FLOW CONTROL WITH LOCAL INDICATOR FF
Refer to F-014
F-187 DCS FLOW SPLIT RANGE CONTROL WITH LOCAL INDICATOR (FF) WITH IPS TRIP
Refer to F-113 & PEFS
F-188 Anti-surge control valve with position transmitter , IPS TRIP , LIM SW TO IPS
Refer to F-022 & Z-101
F-202 IPS Low Low Flow Alarm with Start-up Bypass switch
Loop Instrument Type I/O Location System
UUU-F-XXXX Description Type Type
TAGS
UUU-FT-XXXX Flow Transmitter (Pneumatic) In-Line
UUU-FSLL-XXXX Flow Switch DI Off-Line IPS
UUU-FALL-XXXX Low Low Flow Alarm (Soft) SB IPS DCS
UUU-HS-YYYY Selector Switch DI HWC LCR IPS
F-206 DCS Flow Control with Local Indicator and IPS Trip
Loop Instrument Type I/O Location System
UUU-F-XXXX Description Type Type
TAGS
UUU-FE-XXXX Orifice plate Inline
UUU-FT-XXXX DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXX Flow Indicator (Hard) Field
UUU-FC-XXXX Flow Control (Soft) SB DCS DCS
UUU-FY-XXXXB Solenoid Valve DO On-Valve IPS
UUU-FY-XXXXA I/P Converter AO On-Valve DCS
UUU-FV-XXXX Control Valve Inline
F-207 DCS Flow Indicator with Two inputs One Local Indicator
Loop Instrument Type I/O Location System
UUU-F-XXXX Description Type Type
TAGS
UUU-FE-XXXX Orifice plate Inline
UUU-FT-XXXX DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXXB Flow Indicator (Hard) Field
UUU-FI-XXXX Flow Indicator (Soft) SB DCS DCS
UUU-FE-XXXXA Orifice plate Inline
UUU-FT-XXXXA DP Flow Transmitter AI Off-line DCS
F-209 DCS Flow Control with Two DP Transmittters Two Local Indicators
Loop Instrument Type I/O Location System
UUU-F-XXXX Description Type Type
TAGS
UUU-FE-XXXX Orifice plate Inline
UUU-FT-XXXXA DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXXA Flow Indicator (Hard) Field
UUU-FT-XXXXB DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXXB Flow Indicator (Hard) Field
UUU-FC-XXXX Flow Controller (Soft) SB DCS DCS
UUU-FY-XXXX I/P Converter AO On Valve DCS
UUU-FV-XXXX Control Valve In-Line
F-210 DCS Flow Indicator with Two DP Transmittters Two Local Indicators
Loop Instrument Type I/O Location System
UUU-F-XXXX Description Type Type
TAGS
UUU-FE-XXXX Orifice plate Inline
UUU-FT-XXXXA DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXXA Flow Indicator (Hard) Field
UUU-FT-XXXXB DP Flow Transmitter AI Off-line DCS
UUU-FI-XXXXB Flow Indicator (Hard) Field
UUU-FI-XXXX Flow Indicator (Soft) SB DCS DCS
F-315 DCS Flow Split Range Control with Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
TAGS:
UUU-FE- XXXX Orifice Plate 1 N/A Inline N/A N/A
UUU-FT- XXXX DP Flow transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-FI- XXXX Flow Indicator - Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-FC- XXXX Flow Controller (Soft) SB DCS DCS N/A
UUU-FY- XXXXA1 DCS Function (Soft) SB DCS DCS N/A
UUU-FY- XXXXB1 DCS Function (Soft) SB DCS DCS N/A
UUU-FY- XXXXA Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-FY- XXXXB Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXXA Control Valve N/A Inline N/A N/A
UUU-FV- XXXXB Control Valve N/A Inline N/A N/A
PEFS
DETAIL
F-392 Vortex Flow Control (Foundation Fieldbus) with P/T Compensation with Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-F-XXXX Type
UUU-FT-XXXX FLOW TRANSMITTER VORTEX FieldbusFF INLINE DCS FIELDBUSFF
UUU-FI-XXXX FLOW INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-TW-YYYY THERMOWELL N/A INLINE N/A N/A
UUU-TE-YYYY TEMPERATURE ELEMENT 2 N/A OFFLINE N/A N/A
UUU-TT-YYYY TEMPERATURE TRANSMITTER FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-TI-YYYY TEMPERATURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-PT-ZZZZ PRESSURE TRANSMITTER FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PI-ZZZZ PRESSURE INDICATOR (SOFT) SB DCS DCS N/A
UUU-FY-XXXXA FLOW COMPUTER (SOFT) SB DCS DCS N/A
UUU-FC-XXXX FLOW CONTROLLER (SOFT) SB DCS DCS N/A
UUU-FY- XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-FV- XXXX CONTROL VALVE N/A INLINE N/A N/A
Note: Flow, Pressure and Temperature tags may have different sequence numbers but are all
associated to the flow loop.
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
PLC
PEFS
FT
XXXX
FI
XXXX
PLC
DETAIL
FT FE
XXXX XXXX
APPENDIX 9
HAND (H) Originating
H-001 DCS Hand Control Seed
H-002 DCS Hand Control (Foundation Fieldbus) Seed
H-003 IPS trip from Local Panel PSCJ
H-004 IPS trip from CCR or MFAR PSCJ
H-005 Field Pushbutton via DCS Interlock PSCJ
H-102 DCS Hand Control (Foundation Fieldbus) and IPS Trip PSCJ
H-104 DCS Hand Control and IPS Trip PSCJ
H-105 Heater Damper Control and IPS Trip with Position Indication PSCJ
H-106 DCS Hand Control (Foundation Fieldbus) and IPS Trip and Field Reset PSCJ
H-107 DCS hand control (FF) & DCS interlock PSCJ
H-108 IPS push button (CCR & Main FAR) PSCJ
H-109 On-off valve control pushbutton via DCS interlock PSCJ
H-110 Trip Switch to IPS (Local Panel) PSCJ
H-111 Hand Switch to DCS (Local Panel) PSCJ
H-112 Reset Switch to IPS (Local Panel) PSCJ
H-113 DCS and Field Hand control (combined) FF PSCJ
H-114 IPS Functional Block Reset from DCS, with Pump Shutdown Switches in CCR & FAR with Light PSCJ
H-115 IPS Functional Block Reset from DCS, with Pump Shutdown Switches located in CCR & FAR PSCJ
H-116 IPS Functional Block Reset from DCS, CCR & FAR PSCJ
H-117 IPS Pump Shutdown Switches located in CCR & FAR with two Positions PSCJ
H-118 Reset Switch located in Field PSCJ
H-119 Trip Switch located in Field PSCJ
H-120 IPS Functional Block Trip from CCR, FAR & Field PSCJ
H-121 Manitainance Overide Switch (MOS) located in FAR & CCR for FGS System PSCJ
H-122 Manitainance Overide Switch (MOS) located in FAR & CCR for IPS System PSCJ
H-123 FGS & PEAS Console Silence/All Clear Push Buttons PSCJ
H-124 DCS HAND SWITCH LOCATED IN CCR PSCJ
H-125 Heater trip by trip switches in field through IPS Function Block PSCJ
H-126 Compressor emergency trip by trip switches in field through the common IPS function block PSCJ
H-127 Compressor emergency trip by trip switches in field, CCR & FAR through the common IPS PSCJ
H-128 Pump Stoke control (Foundation Fieldbus) PSCJ
H-129 IPS functional block trip from field PSCJ
H-130 MOV WTH LOCAL OPERATION SWITCH PSCJ
H-131 HAND SWITCH TO IPS PSCJ
H-134 FGS MOS WITH LAMP PSCJ
H-136 3 POS SELECTOR SWITCH TO IPS AT CCR AND MAIN FAR PSCJ
H-137 HS WITH TWO CONTACTS TO IPS AT CCR AND MAIN FAR PSCJ
H-138 HEATER DAMPER CONTROL WITH IPS TRIP WITH POSTION INDICATOR , POS TO IPS PSCJ
H-139 DCS HARDWIRED CONSOLE @ CCB & MAIN FAR PSCJ
H-140 SRS Pump to AH PSCJ
H-141 HAND SWTICH TO FGS PSCJ
H-142 RESET SWITCH TO FGS PSCJ
HC
XXXX
PEFS
FF
HV
XXXX
HC
XXXX
DETAIL
FF
HV HY
XXXX XXXX
IAS
H-105 Heater Damper Control and IPS Trip with Position Indication
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-H-XXXX Type
TAGS:
UUU-HC-XXXXA Hand Controller (Soft) SB DCS DCS N/A
UUU-HC-XXXXB Hand Controller AI LP DCS 4-20mA
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XZY-YYYY Solenoid Valve DO On-Valve IPS 24VDC
UUU-ZT-XXXX Position Transmitter FieldbusFF On-Valve DCS FIELDBUSFF
UUU-ZI-XXXX Position Indication (Soft) SB DCS DCS N/A
UUU-ZI-XXXX Position Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-HY-XXXX Valve Positioner Fieldbus FieldbusFF On-Valve DCS FIELDBUSFF
UUU-HV-XXXX Control Damper N/A Equip N/A N/A
PEFS
DETAIL
H-106 DCS Hand Control (Foundation Fieldbus) and IPS Trip and Field Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-H-XXXX Type
TAGS:
UUU-HC-XXXX Hand Controller (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XZY-YYYY Solenoid Valve DO On-Valve IPS 24VDC
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed SB DCS DCS N/A
UUU-HY-XXXX Valve Positioner Fieldbus FieldbusFF On-Valve DCS FIELDBUSFF
UUU-HV-XXXX Hand Control Valve N/A Inline N/A N/A
PEFS
DETAIL
H-114 IPS Functional Block Reset from DCS, with Pump Shutdown Switches in CCR & FAR with Light
Refer to H-004 & X-058 & PEFS
IPS Functional Block Reset from DCS, with Pump Shutdown Switches located in CCR & FAR with System
H-115 selector Configuration
Refer to H-004 & PEFS
H-116 IPS Functional Block Reset from DCS, CCR & FAR
Refer to H-004 & PEFS
H-117 IPS Pump Shutdown Switches located in CCR & FAR with two Positions
Refer to H-004 & PEFS
H-120 IPS Functional Block Trip from CCR, FAR & Field
Refer to H-003 & H-004 & PEFS
H-121 Manitainance Overide Switch (MOS) located in FAR & CCR for FGS System
Refer to H-004 & X-058 & PEFS
H-122 Manitainance Overide Switch (MOS) located in FAR & CCR for IPS System
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-H-XXXX Type
TAGS:
UUU-HS-XXXXB HAND SWITCH DI CCB IPS VFC
UUU-HS-XXXXC HAND SWITCH DI FAR IPS VFC
UUU-XL-XXXXB LAMP DO CCB IPS 24VDC
UUU-XL-XXXXC LAMP DO FAR IPS 24VDC
UUU-HL-XXXXB LAMP DO CCB IPS 24VDC
UUU-HL-XXXXB LAMP DO FAR IPS 24VDC
PEFS
DETAIL
H-123
FGS & PEAS Console Silence/All Clear Push Buttons
(HOLD)
H-125 Heater trip by trip switches in field through IPS Function Block
Refer to H-003 & PEFS
H-126 Compressor emergency trip by trip switches in field through the common IPS function block
Refer to H-003 & PEFS
H-127 Compressor emergency trip by trip switches in field, CCR & FAR through the common IPS function block
Refer to H-003 & H-004 & PEFS
H-138 HEATER DAMPER CONTROL WITH IPS TRIP WITH POSTION INDICATOR , POS TO IPS AND RESET
Refer to H-105 & PEFS
APPENDIX 10
CURRENT (I) Originating
I-001 DCS Current Indicator
APPENDIX 11
Power (J) Originating
APPENDIX 12
Time/Schedule (K) Originating
APPENDIX 13
LEVEL Originating
L-001 Level Gauge Seed
L-011 DCS Level Indicator Seed
L-012 DCS Level Indicator (Foundation Fieldbus) Seed
L-013 DCS Level Indicator Seed
L-014 DCS Level Indicator (Foundation Fieldbus) Seed
L-015 DCS Level Control Seed
L-016 DCS Level Control (Foundation Fieldbus) Seed
LZ-017 IPS Level Trip Seed
L-018 DCS Split Level Control Seed
L-019 DCS Split Level Control Foundation Fieldbus Seed
L-020 DCS Level Indicator (Foundation Fieldbus) with DCS Interlock FDH
L-201 L-201 DCS Level Controller with local indicator FDH (CSR)
L-202H IPS High Level Alarm FDH (CSR)
L-202HH IPS High High Level Alarm FDH (CSR)
L-202L IPS Low Level Alarm FDH (CSR)
L-202LL IPS Low Low Level Alarm FDH (CSR)
L-203H IPS High Level Alarm FDH (CSR)
L-203HH IPS High High Level Alarm FDH (CSR)
L-203L IPS Low Level Alarm FDH (CSR)
L-203LL IPS Low LowLevel Alarm FDH (CSR)
L-204 DCS Level Control with local indicator FDH (CSR)
L-205 DCS Level Control with Local Indicator One output Two Valves FDH (CSR)
L-206 DCS Level Control with Local Indicator Two outputs FDH (CSR)
L-207L IPS Low Level Alarm with Output to Local Panel FDH (CSR)
L-207LL IPS Low Low Level Alarm with Output to Local Panel FDH (CSR)
L-207H IPS High Level Alarm with Output to Local Panel FDH (CSR)
L-207HH IPS High High Level Alarm with Output to Local Panel FDH (CSR)
L-208 DCS Level Control with Two Local Indicator One output Two Valves FDH (CSR)
L-209H IPS High Level Alarm with Local Pneumatic level control FDH (CSR)
L-210 DCS Level Indicator with IPS Alarm to LP FDH (CSR)
FF
PEFS
LT LI
XXXX XXXX
(TYPE)
FF
DETAIL
LT LI
XXXX XXXX
(TYPE)
PIPING INST
LI
XXXX
FF
LT
XXXX
PEFS
(TYPE)
LI
XXXX
FF
LE
DETAIL
LT
XXXX XXXX
(TYPE)
LT LC
XXXX XXXX
DETAIL
(TYPE)
LY LV
XXXX XXXX
PIPING INST
IAS
FF
LT LC
XXXX XXXX
PEFS
(TYPE)
FF
LV
XXXX
FF
LT LC
XXXX XXXX
DETAIL
(TYPE)
FF
LY LV
XXXX XXXX
PIPING INST
IAS
HH
PEFS
LZT IZ
XXXX YYYY
(TYPE) LL
HH
DETAIL
LZT IZ
XXXX YYYY
(TYPE)
LL
PIPING INST
LY
XXXX
B1
LT LC LY
XXXX XXXX XXXX
A1
(TYPE)
PEFS
LV
XXXX
A
LV
XXXX
B
LY
XXXX
B1
LT LC LY
XXXX XXXX XXXX
(TYPE) A1
DETAIL
LV LY
XXXX XXXX
PIPING INST A A
IA LV
LY XXXX
XXXX B
A
IA
L-103 DCS Split Level Control with two Local Indicators Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP Level transmitter Fieldbus FieldbusFF Equip DCS FIELDBUSFF
UUU-LC- XXXX Level Controller (Soft) SB DCS DCS N/A
UUU-LI-XXXXA Level Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-LI-XXXXB Level Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-LY- XXXX A1 DCS Function SB DCS DCS N/A
UUU-LY- XXXX B1 DCS Function SB DCS DCS N/A
UUU-LY- XXXX A Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-LY- XXXX B Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-LV- XXXX A Control Valve N/A Inline N/A N/A
UUU-LV- XXXX B Control Valve N/A Inline N/A N/A
PEFS
DETAIL
L-105 DCS Cascade Level Control (Foundation Fieldbus) with Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP Level Transmitter Fieldbus FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXX Level Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX Level Controller (Soft) SB DCS DCS N/A
PEFS
DETAIL
L-106 DCS Cascade Level Control (Foundation Fieldbus) with two Local Indicators
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP Level Transmitter Fieldbus FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXXA Level Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-LI-XXXXB Level Indicator Fieldbus FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX Level Controller (Soft) SB DCS DCS N/A
PEFS
DETAIL
L-108 IPS Level Trip with 2oo3 Voting with Local Indicators (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-LZ-XXXX Type
TAGS:
UUU-LZT-XXXXA DP Level Transmitter HART-AI EQUIP IPS 4-20mA
UUU-LZT-XXXXB DP Level Transmitter HART-AI EQUIP IPS 4-20mA
UUU-LZT-XXXXC DP Level Transmitter HART-AI EQUIP IPS 4-20mA
UUU-LI-XXXXA Level Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-LI-XXXXB Level Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-LI-XXXXC Level Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
PEFS
DETAIL
Note: Local indicators signal is generated from DCS, shown above from transmitter signal to indicate its association.
L-110 DCS Level Control and IPS Trip and Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP LEVEL TRANSMITTER FIELDBUS FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXXA LEVEL INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX LEVEL CONTROLLER (SOFT) SB DCS DCS N/A
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-LY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-Valve DCS FIELDBUSFF
UUU-LV-XXXX CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
L-111 DCS GWR Level Control and DCS Interlock and Local Indicator (Foundation Fieldbus)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX GUIDED WAVE RADAR FIELDBUS FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXXA LEVEL INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX LEVEL CONTROLLER (SOFT) SB DCS DCS N/A
UUU-XY-YYYY SOLENOID VALVE DO On-Valve DCS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-LY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-Valve DCS FIELDBUSFF
UUU-LV-XXXX CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
L-114 DCS GWR Level Control and IPS Trip and Local Indicator (Foundation Fieldbus) with Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX GUIDED WAVE RADAR FIELDBUS FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXXA LEVEL INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX LEVEL CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-LY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-Valve DCS FIELDBUSFF
UUU-LV-XXXX CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
L-114 DCS DP Level Control and IPS Trip and Local Indicator (Foundation Fieldbus) with Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP LEVEL TRANSMITTER FIELDBUS FieldbusFF EQUIP DCS FIELDBUSFF
UUU-LI-XXXXA LEVEL INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-LC-XXXX LEVEL CONTROLLER (SOFT) SB DCS DCS N/A
UUU-HS-XXXXB RESET SWITCH DI FIELD IPS VFC
UUU-XZY-YYYY SOLENOID VALVE DO On-Valve IPS 24VDC
UUU-ZSH-XXXX POSITION SWITCH OPEN DI On-Valve DCS PROX
UUU-ZSL-XXXX POSITION SWITCH CLOSED DI On-Valve DCS PROX
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB DCS DCS N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB DCS DCS N/A
UUU-LY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-Valve DCS FIELDBUSFF
UUU-LV-XXXX CONTROL VALVE N/A INLINE N/A N/A
FF
LI
XXXX
FF
H
LT LC ZL
XXXX XXXX XXXX
L
DP
XZY
PEFS
YYYY
HS
IZ
XXXX
YYYY FF
B H
LV ZS
RESET XXXX XXXX
L
RESET
HS
XXXX
FF
B
LI
XXXX
FF
ZLL ZLH IZ LC LT
XXXX XXXX YYYY XXXX XXXX
DP
XZY
DETAIL
YYYY
FF
ZSL ZSH LY INST PIPING
XXXX XXXX XXXX
IAS
LV
XXXX
L-118 DCS Level Control with Outputs for Split Range Control to Other Functions
Refer to L-104 & PEFS
L-119 DCS Level Control with a Local Indicator (Foundation Fieldbus) with Dual Control Valve
Refer to L-103 & PEFS
L-120 DCS Dual Level Control with a Local Indicator (Foundationn Fieldbus) with single Control Valve
Refer to L-016 & L-104 & PEFS
L-121 DCS Dual Level Control with Two Local Indicator (Foundationn Fieldbus) with two Control Valve
Refer to L-103 & PEFS
L-122 DCS Level Control (Foundation Fieldbus) with Two Position Selection
Refer to L-104 & PEFS
L-123 DCS Level Split Range Control (Divided in 3 Part control) Foundation Fieldbus, with 3 Local Indicators
Refer to L-103 & PEFS
L-124 DCS Dual Level measurement with Split Range Control (3 Parts) Foundation Fieldbus with three Local
Refer to PEFS
L-125 DCS Level Control (Foundation Fieldbus) with Two Position Selection soft Switch
Refer to L-104 & PEFS
L-126 DCS Level Control (Foundation Fieldbus) with Two Position Selection soft Switch for control output to Pump
Refer to PEFS
L-128 DCS Level Control with two Position Selection Switch Soft for Pump Stroking (FF) signal
Refer to PEFS
L-130 DCS level control with local indication (FF) and output to other function
Refer to L-105 & PEFS
FF
H
LT LC ZL
XXXX XXXX XXXX
L
DP
PEFS
XZY
YYYY
HS
IZ
XXXX
YYYY
B FF H
LV ZS
RESET XXXX XXXX
L
RESET
HS
XXXX
B
FF
ZLL ZLH IZ LC LT
XXXX XXXX YYYY XXXX XXXX
DP
XZY
YYYY
DETAIL
FF
ZSL ZSH LY INST PIPING
XXXX XXXX XXXX
IAS
LV
XXXX
L-205 DCS Level Control with Local Indicator One output Two Valves
Loop Instrument Type I/O Location System
UUU-L-XXXX Description Type Type
TAGS
UUU-LT-XXXX DP Level Transmitter AI Off-line DCS
UUU-LI-XXXX Level Indicator FIELD
UUU-LC-XXXX Level Control (Soft) SB DCS DCS
UUU-LY-XXXXA I/P Converter AO On-Valve DCS
UUU-LV-XXXXA Control Valve Inline
UUU-LV-XXXXB Control Valve Inline
L-207LL IPS Low Low Level Alarm with Output to Local Panel
Loop Instrument Type I/O Location System
UUU-L-XXXX Description Type Type
TAGS
UUU-LSLL-XXXX LOW LOW LEVEL SWITCH DI On-line IPS
UUU-LALL-XXXX LOW LOW LEVEL ALARM (SOFT) SB DCS IPS
UUU-LAL-XXXX LOW LOW LEVEL INDICATION (HARD) DO LP IPS
L-207HH IPS High High Level Alarm with Output to Local Panel
Loop Instrument Type I/O Location System
UUU-L-XXXX Description Type Type
TAGS
UUU-LSHH-XXXX HIGH HIGH LEVEL SWITCH DI On-line IPS
UUU-LAHH-XXXX HIGH HIGH LEVEL ALARM (SOFT) SB DCS IPS
UUU-LAHH-XXXX HIGH HIGH LEVEL INDICATION (HARD) DO LP IPS
L-208 DCS Level Control with Two Local Indicator One output Two Valves
Loop Instrument Type I/O Location System
UUU-L-XXXX Description Type Type
TAGS
UUU-LT-XXXX DP Level Transmitter AI Off-line DCS
UUU-LI-XXXXA Level Indicator FIELD
UUU-LI-XXXXB Level Indicator FIELD
UUU-LC-XXXX Level Control (Soft) SB DCS DCS
UUU-LY-XXXX I/P Converter AO On-Valve DCS
UUU-LV-XXXXA Control Valve Inline
UUU-LV-XXXXB Control Valve Inline
L-209H IPS High Level Alarm with Local Pneumatic level control
Loop Instrument Type I/O Location System
UUU-L-XXXX Description Type Type
TAGS
UUU-LSH-XXXX HIGH LEVEL SWITCH DI Off-line IPS
UUU-LAH-XXXX HIGH LEVEL ALARM (SOFT) SB IPS DCS
UUU-LT-XXXX Level Transmiter (Pnuematic) Field
UUU-LC-XXXX Level Controller (Pnuematic) Field
UUU-LV-XXXX Control Valve Inline
L-302 DCS Level Control and IPS Trip with Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-L-XXXX Type
TAGS:
UUU-LT-XXXX DP Level Transmitter 1 HART-AI EQUIP DCS 4-20mA
UUU-LI-XXXX Level Indicator (Hard) AO FIELD DCS 4-20mA
UUU-LC-XXXX Level Controller (Soft) SB DCS DCS N/A
UUU-XZY-YYYY Solenoid Valve DO Field IPS 24VDC
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open (Soft) SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed (Soft) SB DCS DCS N/A
UUU-LY-XXXX Valve Positioner HART-AO On-Valve DCS 4-20mA
UUU-LV-XXXX Control Valve N/A Inline N/A N/A
PEFS
DETAIL
APPENDIX 14
MOISTURE (M) Originating
APPENDIX 15
MOTOR (M) /MOV Originating
M-001 LV Motor with Standard Link and IPS Trip Seed
M-002 LV Motor with Standard Link, IPS Trip and DCS Auto Start Seed
M-040 LV Motor with Standard Link Seed
M-004 LV Motor with Standard Link and DCS Auto Start Seed
M-005 LV Motor with Standard Link, DCS Auto Start, DCS Auto Stop and DCS Start / Stop FDH
M-006 LV Motor with Standard Link, DCS Auto Start, DCS Auto Stop and DCS Stop FDH
M-007 LV Motor with Standard Link, DCS Auto Stop and DCS Stop FDH
M-008 LV Motor with Standard Link, DCS Auto Start and DCS Stop FDH
M-009 LV Motor with Standard Link, DCS Auto Start/Stop, DCS Stop and Motor Auto Stroke FDH
M-010 LV Motor with Standard Link, IPS Trip DCS Auto Start and DCS Start /Stop FDH
M-011 LV Motor with Standard Link and DCS Start/Stop FDH
M-012 LV Motor with Standard Link, DCS Auto Stop and DCS Start /Stop FDH
M-043 HV Motor with Standard Link, DCS AutoStart, DCS Stop and IPS Trip FDH
M-044 HV Motor with Standard Link and DCS AutoStop/Stop FDH
M-045 HV Motor with Standard Link, DCS Auto Stop and DCS Start/Stop FDH
M-046 HV Motor with Standard Link and DCS Auto Stop, DCS Stop and IPS Trip FDH
M-047 LV Motor with Hard DCS Auto Start/Stop PSCJ
M-048 HV Motor with Standard Link and DCS Auto Start, DCS Stop and IPS Trip PSCJ
MOV-201 PLC Controlled MOV in On-Off service (Two Wire Communication Network) FDH
M-002 LV Motor with Standard Link, IPS Trip and DCS Auto Start
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-005 LV Motor with Standard Link, DCS Auto Start, DCS Auto Stop and DCS Start / Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXC MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-006 LV Motor with Standard Link, DCS Auto Start, DCS Auto Stop and DCS Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-007 LV Motor with Standard Link, DCS Auto Stop and DCS Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-008 LV Motor with Standard Link, DCS Auto Start and DCS Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-009 LV Motor with Standard Link, DCS Auto Start/Stop, DCS Stop and Motor Auto Stroke
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
UUU-MY-XXXX MOTOR AUTO STROKE AO EQUIP DCS 4-20mA
PEFS
DETAIL
M-010 LV Motor with Standard Link, IPS Trip DCS Auto Start and DCS Start /Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXC MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-012 LV Motor with Standard Link, DCS Auto Stop and DCS Start /Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXC MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-014 HV Motor with Standard Link, IPS Trip and DCS Auto Start
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START HARD DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-017 HV Motor with Standard Link, IPS Trip, DCS Auto Start / Auto Stop and DCS Start / Stop
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START HARD DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXXC MOTOR START HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-018 HV Motor with Standard Link, DCS Auto Start / Auto Stop and DCS Start / Stop
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-M-XXXX Type Type
TAGS:
UUU-HS-XXXXA MOTOR AUTO START HARD DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXXC MOTOR START HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-019 LV Motor with VSDS, PLC Start, PLC Stop and IPS Trip
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXAA MOTOR START SOFT SID DCS PLC SL
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXXBB MOTOR STOP SOFT SID DCS PLC SL
UUU-SC-XXXX SPEED CONTROL (SOFT) SB DCS DCS N/A
UUU-SC-XXXXA SPEED CONTROL (SOFT) SIA DCS PLC SL
UUU-SY-XXXX SPEED CONTROL SIGNAL AO MCC PLC 4-20mA
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXAA MOTOR STATUS SOFT (RUN) SID DCS PLC SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXBB MOTOR STATUS SOFT (AVAILABLE) SID DCS PLC SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
UUU-ML-XXXXCC MOTOR STATUS SOFT (FAULT) SID DCS PLC SL
UUU-SI-XXXX SPEED INDICATOR (SOFT) SIA MCC DCS SL
UUU-SI-XXXXA SPEED INDICATOR (SOFT) SIA DCS PLC SL
Note1: DCS Start if indicated in PEFS.
Note 2 : Permissive Start and Stop interlock from PLC if required.
PEFS
DETAIL
M-021 LV Motor with VSDS, DCS Start, DCS Stop and IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-SC-XXXX SPEED CONTROL (SOFT) SB DCS DCS N/A
UUU-SY-XXXX SPEED CONTROL AO MCC DCS 4-20mA
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
UUU-SI-XXXX SPEED INDICATOR SOFT (SOFT) SIA MCC DCS SL
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-022 LV Motor with standard link, IPS Trip and Run Feedback to IPS
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-MZL-XXXX MOTOR STATUS HARD (RUN) DI MCC IPS VFC
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-023 LV Motor with standard link, IPS Trip and Run/Current Feedback to IPS
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-MZL-XXXX MOTOR STATUS HARD (RUN) DI MCC IPS VFC
UUU-MZI-XXXX MOTOR STATUS HARD (CURRENT) AI MCC IPS 4-20mA
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-024 LV Motor with Standard Link, IPS Trip, DCS Auto Start, DCS Auto Stop and DCS Start / Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXC MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-025 HV Motor with VSDS, PLC Start, PLC Stop and IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR START SOFT SID PLC DCS SL
UUU-HS-XXXXAA MOTOR START HARD DO MCC PLC 24VDC
UUU-HS-XXXXB MOTOR STOP SOFT SID PLC DCS SL
UUU-HS-XXXXBB MOTOR STOP HARD DO MCC PLC 24VDC
UUU-SC-XXXX SPEED CONTROL (SOFT) SB DCS DCS N/A
UUU-SC-XXXXA SPEED CONTROL (SOFT) SIA DCS PLC SL
UUU-SY-XXXX SPEED CONTROL AO MCC PLC 4-20mA
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID PLC DCS SL
UUU-ML-XXXXAA MOTOR STATUS HARD (RUN) DI MCC PLC VFC
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID PLC DCS SL
UUU-ML-XXXXBB MOTOR STATUS HARD (AVAILABLE) DI MCC PLC VFC
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID PLC DCS SL
UUU-ML-XXXXCC MOTOR STATUS HARD (FAULT) DI MCC PLC VFC
UUU-SI-XXXX SPEED INDICATOR (SOFT) SIA PLC DCS SL
UUU-SI-XXXXA SPEED INDICATOR AI MCC PLC 4-20mA
Note1: DCS Start if indicated in PEFS.
Note 2 : Permissive Start and Stop interlock from PLC if required.
PEFS
DETAIL
M-027 HV Motor with VSDS, DCS Start, DCS Stop and IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR START HARD DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR STOP HARD DO MCC DCS 24VDC
UUU-SC-XXXX SPEED CONTROL (SOFT) SB DCS DCS N/A
UUU-SY-XXXX SPEED CONTROL SIGNAL AO MCC DCS 4-20mA
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
UUU-SI-XXXX SPEED INDICATOR AI MCC DCS 4-20mA
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-028 HV Motor with standard link, IPS Trip and Run Feedback to IPS
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXB MOTOR STOP HARD DO MCC DCS 24VDC
UUU-MZL-XXXXA MOTOR STATUS HARD (RUN) DI MCC IPS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-029 HV Motor with standard link, IPS Trip, Run and Current Feedback to IPS
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXB MOTOR STOP HARD DO MCC DCS 24VDC
UUU-MZL-XXXXA MOTOR STATUS HARD (RUN) DI MCC IPS VFC
UUU-MZI-XXXXA MOTOR STATUS HARD (CURRENT) AI MCC IPS 4-20mA
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-030 LV Motor with Standard Link, IPS Trip and DCS Auto Start
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
Note: DCS Start if indicated in PEFS.
PEFS
DETAIL
M-032 LV Motor with PLC Start, PLC Stop and IPS Trip
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXAA MOTOR START SOFT SID DCS PLC SL
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXXBB MOTOR STOP SOFT SID DCS PLC SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXAA MOTOR STATUS SOFT (RUN) SID DCS PLC SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXBB MOTOR STATUS SOFT (AVAILABLE) SID DCS PLC SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
UUU-ML-XXXXCC MOTOR STATUS SOFT (FAULT) SID DCS PLC SL
PEFS
DETAIL
M-034 LV Motor with Hard Link, DCS Auto Start, Run Feedback, DCS Stop and Standard Link
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-M-XXXX Type Type
TAGS:
UUU-HS-XXXXA MOTOR AUTO START SOFT SID MCC DCS SL
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-XS-XXXX MOTOR START PERMISSIVE DO MCC DCS 24VDC
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
I
YYYY
PEFS
HS
M XXXX
I
YYYY
HS HS HS ML ML ML
XXXX XXXX XXXX XXXX XXXX XXXX
A B A B C
AUTO START
MCC
M-035 HV Motor with Standard Link, IPS Trip and Start Permissive
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-XS-XXXX MOTOR START PERMISSIVE DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR STOP HARD DO MCC DCS 24VDC
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-043 HV Motor with Standard Link, DCS AutoStart, DCS Stop and IPS Trip
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-045 HV Motor with Standard Link, DCS Auto Stop and DCS Start/Stop
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-M-XXXX Type Type
TAGS:
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXXC MOTOR START HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-046 HV Motor with Standard Link and DCS Auto Stop, DCS Stop and IPS Trip
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-MZ-XXXX Type Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO IPS IPS 24VDC
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
M-048 HV Motor with Standard Link, DCS AutoStart, DCS Stop and IPS Trip
Refer to M-043
IZ
YYYY
PEFS
HS
M XXXX
STOP - XXXXB
IZ HS ML ML ML
YYYY XXXX XXXX XXXX XXXX
B A B C
MZS-XXXX
DETAIL
MCC
M-103 LV Motor with Standard Link, Motor Auto Stroke and IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-M-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXB MOTOR STOP SOFT SID MCC DCS SL
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
UUU-MY-XXXX MOTOR AUTO STROKE FIELDBUSFF EQUIP DCS FIELDBUSFF
PEFS
DETAIL
M-104 LV Motor with Standard Link, DCS Auto Stop and DCS Start /Stop and IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-HS-XXXXB MOTOR AUTO STOP SOFT SID MCC DCS SL
UUU-HS-XXXXC MOTOR START SOFT SID MCC DCS SL
UUU-HS-XXXXD MOTOR STOP SOFT SID MCC DCS SL
UUU-ML-XXXXA MOTOR STATUS SOFT (RUN) SID MCC DCS SL
UUU-ML-XXXXB MOTOR STATUS SOFT (AVAILABLE) SID MCC DCS SL
UUU-ML-XXXXC MOTOR STATUS SOFT (FAULT) SID MCC DCS SL
PEFS
DETAIL
M-105 HV Motor with Standard Link, IPS Trip, DCS Auto Start / Auto Stop and DCS Stop
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-MZ-XXXX Type
TAGS:
UUU-MZS-XXXX MOTOR TRIP DO MCC IPS 24VDC
UUU-HS-XXXXA MOTOR AUTO START HARD DO MCC DCS 24VDC
UUU-HS-XXXXB MOTOR AUTO STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXXC MOTOR START HARD DO MCC DCS 24VDC
UUU-HS-XXXXD MOTOR STOP HARD DO MCC DCS 24VDC
UUU-HS-XXXX SELECTOR SWITCH SOFT SB DCS DCS N/A
UUU-ML-XXXXA MOTOR STATUS HARD (RUN) DI MCC DCS VFC
UUU-ML-XXXXB MOTOR STATUS HARD (AVAILABLE) DI MCC DCS VFC
UUU-ML-XXXXC MOTOR STATUS HARD (FAULT) DI MCC DCS VFC
PEFS
DETAIL
H
HS ZL
XXXX XXXX
L
PEFS
H
MOV ZS
XXXX XXXX
M L
NOT IN
OPEN CLOSE REMOTE
HS HS HL ZLH ZLL
XXXX XXXX XXXX XXXX XXXX
A B
DETAIL
HS IZ
XXXX YYYY
PEFS
H
MOV ZZS
XXXX XXXX
M L
NOT IN
OPEN CLOSE REMOTE
HS HS ML IZ ZZLH
XXXX XXXX XXXX YYYY XXXX
A B
DETAIL
ZZLL
XXXX
MOV ZZSL ZZSH
XXXX XXXX XXXX
M
HS
XXXX
FF
PEFS
MOV
XXXX
M
HS HS HS HS ZLH ZLL XR XL XA
XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX XXXX
A B C D
DETAIL
FF
MOV
XXXX
M
MOV-201 PLC Controlled MOV in On-Off service (Two Wire Communication Network)
LOOP: System Signal
Instrument Type Description I/O Type Location
UUU-M-XXXX Type Type
TAGS:
UUU-HS-XXXXA HAND SWITCH OPEN SB PC-1 PLC N/A
UUU-HS-XXXXB HAND SWITCH CLOSE SB PC-1 PLC N/A
UUU-ML-XXXX NOT IN REMOTE STATUS SB MOV PLC N/A
UUU-ZSH-XXXX POSITION SWITCH OPEN SB MOV PLC N/A
UUU-ZSL-XXXX POSITION SWITCH CLOSED SB MOV PLC N/A
UUU-ZLH-XXXX VALVE STATUS INDICATOR OPEN SB PC-1 PLC N/A
UUU-ZLL-XXXX VALVE STATUS INDICATOR CLOSED SB PC-1 PLC N/A
UUU-MOV-XXXX MOTOR OPERATED VALVE N/A INLINE N/A N/A
NOTE: HARDWARE INTERFACE UNIT IS LOCATED IN BETWEEN MOV & PLC
PEFS
DETAIL
APPENDIX 16
7.16 PRESSURE (P) Originating
P-001 Pressure Gauge Seed
P-011 DCS Pressure Indication Seed
P-012 DCS Differential Pressure Indication Seed
P-013 DCS Pressure Control Seed
P-014 DCS Differential Pressure Control Seed
P-016 DCS Pressure Split Range Control Seed
P-017 IPS Pressure Trip Seed
P-018 IPS Pressure Trip with 2oo3 Voting Seed
P-019 DCS Pressure Control with IPS trip Seed
P-020 DCS Pressure Indication Foundation Fieldbus Seed
P-021 DCS Differential Pressure Indication Foundation Fieldbus Seed
P-022 DCS Pressure Control Foundation Fieldbus Seed
P-023 DCS Differential Pressure Control Foundation Fieldbus Seed
P-024 P-024 DCS Pressure Split Range Control Foundation Fieldbus Seed
P-025 IPS Low Pressure Trip FDH
P-026 IPS High Low Pressure Trip FDH
PC
XXXX
DETAIL
PT
XXXX
PY PV
XXXX XXXX
INST
PIPING
IA
PDT
XXXX
PDC
DETAIL
XXXX
IA
PC PY PY
XXXX XXXX XXXX
A1 B1
PEFS
PV PV
PT XXXX XXXX
XXXX A B
PY PC PY
XXXX XXXX XXXX
B1 A1
DETAIL
PV PY PY PV
PT
XXXX XXXX XXXX XXXX
XXXX
B B A A
INST
PIPING
IZ
YYYY
PEFS
HH
PZT
XXXX
IZ
YYYY
DETAIL
HH
PZT
XXXX
INST
PIPING
IZ
YYYY
PEFS
HH
PZT
XXXX
2oo3 A,B,C
IZ
YYYY
DETAIL
HH
HH HH
PZT PZT PZT
XXXXA XXXXB XXXXC
H
PC ZL
XXXX XXXX
L
PEFS
IZ
YYYY
H
PT PV ZS
XXXX XXXX XXXX
L
DETAIL
PI
XXXX
PEFS
FF
PT
XXXX
PI
XXXX
DETAIL
FF
PT
XXXX
INST
PIPING
PDI
XXXX
FF
PEFS
PDT
XXXX
PDI
XXXX
DETAIL
FF
PDT
XXXX
INST
PIPING
FF
PDT
XXXX
PDC
PEFS
XXXX
FF
PDV
XXXX
FF
PDT
XXXX
PDC
DETAIL
XXXX
FF
INST PDY PDV INST
XXXX XXXX
PIPING PIPING
IA
P-113 DCS Pressure Split Range Control with Two Local Indicators Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-P-XXXX Type
TAGS:
UUU-PT-XXXX PRESSURE TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PI-XXXXA PRESSURE INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-PI-XXXXB PRESSURE INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-PC-XXXX PRESSURE CONTROLLER (SOFT) SB DCS DCS N/A
UUU-PY-XXXXA VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-PY-XXXXB VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-PY-XXXXA1 DCS FUNCTION SB DCS DCS N/A
UUU-PY-XXXXB1 DCS FUNCTION SB DCS DCS N/A
UUU-PV-XXXXA CONTROL VALVE N/A INLINE N/A N/A
UUU-PV-XXXXB CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
P-114 DCS Pressure Split Range Control with Local Indicator Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-P-XXXX Type
TAGS:
UUU-PT-XXXX PRESSURE TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PI-XXXX PRESSURE INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-PC-XXXX PRESSURE CONTROLLER (SOFT) SB DCS DCS N/A
UUU-PY-XXXXA VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-PY-XXXXB VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-PY-XXXXA1 DCS FUNCTION SB DCS DCS N/A
UUU-PY-XXXXB1 DCS FUNCTION SB DCS DCS N/A
UUU-PV-XXXXA CONTROL VALVE N/A INLINE N/A N/A
UUU-PV-XXXXB CONTROL VALVE N/A INLINE N/A N/A
PEFS
DETAIL
P-115 DCS Differential Pressure Indication with Local Indicator Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-PD-XXXX Type
TAGS:
UUU-PDT-XXXX PRESSURE DIFF. TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PDI-XXXXA DIFF. PRESSURE INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
DIFFERENTIAL PRESSURE INDICATOR
UUU-PDI-XXXX SB DCS DCS N/A
(SOFT)
PEFS
DETAIL
PP
PEFS
PP
DETAIL
INST
PIPING
Note: Tag number shall not be assigned to "PP" bubble as it is not a instrument tag number.
P-125 DCS Differential Pressure Control Foundation Fieldbus with Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-PD-XXXX Type
TAGS:
UUU-PDT-XXXX PRESSURE DIFF. TRANSMITTER FIELDBUS FieldbusFF OFFLINE DCS FIELDBUSFF
UUU-PDI-XXXX PRESSURE DIFF. INDICATOR FIELDBUS FieldbusFF FIELD DCS FIELDBUSFF
UUU-PDC-XXXX DIFF. PRESSURE CONTROLLER (SOFT) SB DCS DCS N/A
UUU-PDY-XXXX VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
UUU-PDV-XXXX CONTROL VALVE N/A Inline N/A N/A
PEFS
DETAIL
2oo3
PDZT IZ
XXXX YYYY
A/B/C
DETAIL
PIPING INST
P-128 DCS Pressure Control (Foundation Fieldbus) with Local Indicator and Outputs to Other Function
Refer to P-113 & PEFS
P-129 DCS Pressure Control with IPS Trip with Position Feedback of Damper to DCS
Refer to P-025 & Z-103
P-131 DCS Pressure Control with two Pressure Inputs and a single Local Indicator (Foundation Fieldbus)
Refer to P-022 & P-112 & PEFS
P-132 DCS PRESSURE CONTROL USING DAMPER, WITH IPS TRIP, AND POSTION FEEDBACK
Refer to P-119 & Z-102 & PEFS
P-134 DCS DIFFERENTIAL PRESSURE CONTROL WITH LOCAL INDICATOR (FOUNDATION FIELDBUS), IPS TRIP
Refer to P-026 & PEFS
P-135 DCS Differential Pressure (Foundation Fieldbus) Split Range Control with two local indicators (Foundation
Refer to P-117 & P-027 & PEFS
P-136 DCS DIFFERENTIAL PRESSURE SPLIT RANGE CONTROL WITH TWO LOCAL INDICATORS (FOUNDATION
Refer to P-024 & PEFS
DCS DIFFERENTIAL PRESSURE SPLIT RANGE CONTROL WITH THREE LOCAL INDICATORS (FOUNDATION
P-137 FIELDBUS)
Refer to P-027 & PEFS
P-139 DCS pressure control (FF) with local indicator (FF) with IPS trip
Refer to P-111
P-140 DCS pressure control (FF) with output to other functions and IPS trip
Refer to P-119 & PEFS
P-141 DCS pressure control with local indicator (FF) having input selection for set point in DCS
Refer to P-028 & PEFS
P-142 DCS Cascade Pressure Control Foundation Fieldbus with two local indicator (FF)
Refer to P-029 & PEFS
P-208L IPS Low Pressure Alarm with Two Outputs (Auto Starts)
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PSL-XXXX LOW PRESSURE SWITCH DI On-line IPS
UUU-PAL-XXXX LOW PRESSURE ALARM (SOFT) SB IPS DCS
<free format>STR HS DO MCC IPS
<free format>STR HS DO MCC IPS
IPS Low Pressure Alarm with Three Outputs (1 Solenoid valves One Autostart) Hand/Auto Start
P-210L Input
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PSL-XXXX LOW PRESSURE SWITCH DI On-line IPS
UUU-PAL-XXXX LOW PRESSURE ALARM (SOFT) SB IPS DCS
UUU-PY-XXXX Solenoid Valve DO On-Valve IPS
UUU-PV-XXXX Control Valve Inline
UUU-ZSH-YYYY Position Switch High DI On-Valve DCS
UUU-ZAH-YYYY Position Indication High (Soft) SB DCS DCS
UUU-PHS-XXX HS Hand/Auto Field
UUU-HS-XXXXHND HS DI HS IPS
UUU-HS-XXXXAUT HS DI HS IPS
<free format> HS START Field
<free format>STR HS DI HS IPS
<free format>STR HS DO MCC IPS
IPS Low Pressure Alarm with Three Outputs (2 Solenoid valves One Autostart) Hand/Auto Start
P-211L Input
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PSL-XXXX LOW PRESSURE SWITCH DI On-line IPS
UUU-PAL-XXXX LOW PRESSURE ALARM (SOFT) SB IPS DCS
UUU-PY-XXXXA Solenoid Valve DO On-Valve IPS
UUU-PY-XXXXB Solenoid Valve DO On-Valve IPS
UUU-PV-XXXX Control Valve Inline
UUU-ZSH-YYYY Position Switch High DI On-Valve DCS
UUU-ZAH-YYYY Position Indication High (Soft) SB DCS DCS
UUU-PHS-XXX HS Hand/Auto Field
UUU-HS-XXXXHND HS DI HS IPS
UUU-HS-XXXXAUT HS DI HS IPS
<free format> HS START Field
<free format>STR HS DI HS IPS
<free format>STR HS DO MCC IPS
P-213 DCS Pressure Control with 1 Local Indicator Two valves One Output
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PT-XXXX Pressure Transmitter AI Off-line DCS
UUU-PI-XXXX Pressure Indicator Field
UUU-PC-XXXX Pressure Control (soft) DCS DCS
UUU-PY-XXXX I/P Converter AO On-Valve DCS
UUU-PV-XXXXA Control Valve Inline
UUU-PV-XXXXB Control Valve Inline
P-215L IPS Low Pressure Differential Alarm with Local Pneumatic Control
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PDSL-XXXX LOW PRESSURE DIFFERENTIAL SWITCH DI On-line IPS
UUU-PDL-XXXX LOW PRESSURE DIFFERENTIAL ALARM SB(SOFT) IPS DCS
UUU-PDt-XXXX PRESSURE DIFFERENTIAL TRANSMITTER (PNEUMATIC0 Field
UUU-PDIC-XXXX PRESSURE DIFFERENTIAL CONTROLLER (PNEUMATIC) Field
UUU-PV-XXXX Control Valve Inline
P-216H IPS High Pressure Alarm with Output to Solenoid and Local PIC (Pneumatic)
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PSH-XXXX HIGH PRESSURE SWITCH DI Off-line IPS
UUU-PA-XXXX HIGH PRESSURE ALARM (SOFT) SB IPS DCS
UUU-PY-XXXX Solenoid Valve DO On-Valve IPS
UUU-PIC-XXXX PRESSURE CONTROLLER Off-line
UUU-PV-XXXX Control Valve Inline
P-221LL IPS Low Pressure Alarm with Two Outputs (Indication Lamp and Permissive)
Loop Instrument Type I/O Location System
UUU-P-XXXX Description Type Type
TAGS
UUU-PSLL-XXXX LOW LOW PRESSURE SWITCH DI On-line IPS
UUU-PALL-XXXX LOW LOW PRESSURE ALARM (SOFT) SB IPS DCS
UUU-CTA-XXXX SWITCH DI LP DCS
UUU-CTA-XXXX DCS ALARM (Soft) SB DCS DCS
<free format>PER HS DO MCC IPS
PC
XXXX
PI
PEFS
XXXX
PT PV
XXXX XXXX
DETAIL
APPENDIX 17
PRESSURE RELIEF (P) Originating
PSV-001 Pressure Relief Valve Seed
PVV-002 Breather Valve
APPENDIX 18
QUANTITY (Q) Originating
APPENDIX 19
RADIATION (R) Originating
APPENDIX 20
SPEED (S) Originating
S-001 DCS SPEED CONTROL PSCJ
S-002 PLC SPEED SENSOR (2OO3) PSCJ
S-003 PLC SPEED SENSOR PSCJ
S-004 SPEED ALARM PSCJ
S-005 MMS SPEED PSCJ
APPENDIX 21
TEMPERATURE (T) Originating
T-001 Temperature Gauge Seed
T-011 DCS Temperature Indication Seed
T-012 DCS Temperature Control Seed
T-013 DCS Temperature Split Range Control Seed
T-014 DCS Motor Temperature Indication Seed
T-015 IPS Temperature Trip Seed
T-016 8 Point Temperature Multiplexer Seed
T-017 DCS Temperature Indication Foundation Fieldbus Seed
T-018 DCS Temperature Control Foundation Fieldbus Seed
T-019 DCS Temperature Split Range Control Foundation Fieldbus Seed
T-020 DCS Motor Temperature Indication Foundation Fieldbus Seed
T-021 8 Point Temperature Multiplexer Foundation Fieldbus Seed
T-022 4 Point Temperature Multiplexer Foundation Fieldbus PSCJ
T-023 5 Point Temperature Multiplexer Foundation Fieldbus PSCJ
T-024 6 Point Temperature Multiplexer Foundation Fieldbus PSCJ
T-308 Differential Temperature Control (Foundation Fieldbus) with Local Indicator FDH
TT TC
XXXX XXXX
DETAIL
(TYPE)
TW TE TY TV
XXXX XXXX XXXX XXXX
IA
TC TY TY
XXXX XXXX XXXX
A1 B1
PEFS
TV TV
TT XXXX XXXX
XXXX A B
TY TC TY
XXXX XXXX XXXX
B1 A1
DETAIL
TT
XXXX
TV TY (TYPE) TY TV
TW TE
XXXX XXXX XXXX XXXX
XXXX XXXX
B B A A
IZ
YYYY
PEFS
HH
TZT
XXXX
IZ
YYYY
HH
DETAIL
TZT
XXXX
(TYPE)
TW TZE
XXXX XXXX
TI
XXXX
PEFS
(A-H)
TT
XXXX
(TYPE)
TI
XXXX
DETAIL
TT
XXXX
(A-H) (A-H)
TW TE
XXXX XXXX
(TYPE)
HH
TI
XXXX
PEFS
FF
TT
XXXX
(TYPE)
HH
TI
XXXX
FF
DETAIL
TT
XXXX
TW TE
XXXX XXXX
(TYPE)
TC
XXXX
PEFS
FF
FF
TT
XXXX TV
XXXX
(TYPE)
TC
XXXX
FF
TT
DETAIL
XXXX
FF
TW TE (TYPE) TY TV
XXXX XXXX XXXX XXXX
IAS
HH
TI
XXXX
FF
PEFS
TT
XXXX
(TYPE)
TI
XXXX
FF
TT
XXXX
DETAIL
TE
XXXX
(TYPE)
HH
TI
XXXX
PEFS
(A-H) FF
TT
XXXX
(TYPE)
HH
TI
XXXX
FF
DETAIL
TT
XXXX
(A-H)
(A-H) TW TE
XXXX XXXX
(TYPE)
T-105 DCS Temperature Indication with Two Local Indicators Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXXA Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TI- XXXXB Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TI- XXXX Temperature Indicator (Soft) SB DCS DCS N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
T-107 DCS Cascade Temperature Control Foundation Fieldbus with Local Indicator
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TC- XXXX Temperature Controller(Soft) SB DCS DCS N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
T-110 DCS Temperature Split Range Control with two Indicators Foundation Fieldbus
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXXA Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TI- XXXXB Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-TY- XXXXA1 DCS Function SB DCS DCS N/A
UUU-TY- XXXXB1 DCS Function SB DCS DCS N/A
UUU-TY- XXXXA Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TY- XXXXB Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV-XXXXA Control Valve N/A Inline N/A N/A
UUU-TV-XXXXB Control Valve N/A Inline N/A N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
T-111 DCS Temperature Control with Local Indicator (Foundation Fieldbus) with IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-XZY- YYYY Solenoid Valve DO On-valve IPS 24VDC
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed SB DCS DCS N/A
UUU-TY- XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV- XXXX Control Valve N/A Inline N/A N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
T-113 DCS MultiTemperature Control with Local Indicator (Foundation Fieldbus) with IPS Trip
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Temperture Probe N/A EQUIP N/A N/A
UUU-TE- XXXX (A-J) Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX (A-J) Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX (A-J) Temperatue Indicator (Soft) SB DCS DCS N/A
UUU-XZY- YYYY Solenoid Valve DO On-valve IPS 24VDC
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed SB DCS DCS N/A
UUU-TY- XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV- XXXX Control Valve N/A Inline N/A N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
FF
TT TI TY
XXXX XXXX XXXX
(A-J) (A-J)
H
TC ZL
XXXX XXXX
XZY L
PEFS
YYYY
IZ
YYYY
FF H
TV ZS
XXXX XXXX
L
ZLL ZLH IZ TC TY TI
XXXX XXXX YYYY XXXX XXXX XXXX
(A-J)
XZY
YYYY
FF
ZSL ZSH TY
XXXX XXXX FF
XXXX
DETAIL
TT
XXXX
(A-J)
IAS
(TYPE)
TE
XXXX
(A-J)
TV
XXXX
TW
XXXX
IZ Mof3 TC
YYYY TY-ZZZZA ZZZZ
FF
PEFS
TV
ZZZZ
IZ Mof3 TC
YYYY TY-ZZZZA ZZZZ
DETAIL
FF
TY TV
ZZZZ ZZZZ
IAS
T-115 DCS Temperature Control with Local Indicator (Foundation Fieldbus) with IPS Trip with Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XZY- YYYY Solenoid Valve DO On-valve IPS 24VDC
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed SB DCS DCS N/A
UUU-TY- XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV- XXXX Control Valve N/A Inline N/A N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
PEFS
DETAIL
FF
TT TI
XXXX XXXX
PEFS
TC (A-B) (A-B)
FF
DETAIL
TE TT TI
XXXX XXXX XXXX
TC (A-B) (A-B)
(A-B)
TC SP TO OTHER
XXXX CONTROLLER
PEFS
FF
TT
XXXX
TC SP TO OTHER
XXXX CONTROLLER
FF
DETAIL
TT
XXXX
TW TE (TYPE)
XXXX XXXX
T-119 Air Fin Cooler Temperature Control Foundation Fieldbus (A-Z Bays) with VSDS
S System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TC- XXXX Temperature Controller(Soft) SB DCS DCS N/A
UUU-TY- XXXX (A-Z) DCS Function 3 SB DCS DCS N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
Note 3: SP to each speed controller for each bay as applicable.
SP to SC-XXXX
TC
(A-Z)
XXXX
(Bay A-Z)
TY-XXXX (A-Z)
PEFS
FF
TT
XXXX
SP to SC-XXXX
TC
(A-Z)
XXXX
TY-XXXX (A-Z) (Bay A-Z)
FF
DETAIL
TT
XXXX
TW TE (TYPE)
XXXX XXXX
T-120 Air Fin Cooler Temperature Control with Local Indicator Foundation Fieldbus with VSDS (Multi Bays)
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Thermowell N/A Inline N/A N/A
UUU-TE- XXXX Temperature Element 2 N/A Offline N/A N/A
UUU-TT- XXXX Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX Temperature Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-TY-XXXX(A-Z) DCS Function 3 SB DCS DCS N/A
UUU-TY- XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV- XXXX Control Valve N/A Inline N/A N/A
Note 2: Temperature element shown is generic, to be replaced with selected type, i.e. RTD or TC.
Note 3: Suffices I, O and Q shall not be used. Siffix will be changeable according to the number of bays.
PEFS
DETAIL
T-122 DCS MultiTemperature Control with Local Indicator (Foundation Fieldbus) with IPS Trip with Reset
LOOP: System
Instrument Type Description I/O Type Location Signal Type
UUU-T-XXXX Type
TAGS:
UUU-TW-XXXX Temperture Probe N/A EQUIP N/A N/A
UUU-TE- XXXX (A-J) Multi TC N/A Offline N/A N/A
UUU-TT- XXXX (A-J) Temperature Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-TI- XXXX (A-J) Temperatue Indicator (Soft) SB DCS DCS N/A
UUU-TI- XXXX Temperatue Indicator Fieldbus FieldbusFF Field DCS FIELDBUSFF
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XZY- YYYY Solenoid Valve DO On-valve IPS 24VDC
UUU-TC- XXXX Temperature Controller (Soft) SB DCS DCS N/A
UUU-TY- XXXXA DCS Function SB DCS DCS N/A
UUU-ZSH-XXXX Position Switch Open DI On-Valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-Valve DCS PROX
UUU-ZLH-XXXX Valve Status Indicator Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indicator Closed SB DCS DCS N/A
UUU-TY- XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUSFF
UUU-TV- XXXX Control Valve N/A Inline N/A N/A
FF FF
TT TI TY TI
XXXX XXXX XXXX XXXX
(A-J) (A-J) A
H
TC ZL
XXXX XXXX
XZY L
PEFS
YYYY
HS
XXXX IZ
B YYYY
FF H
TV ZS
RESET
XXXX XXXX
L
HS TY TI
ZLL ZLH IZ TC
XXXX XXXX XXXX
XXXX XXXX YYYY XXXX
B A (A-J)
RESET XZY
YYYY
FF
ZSL ZSH TY
XXXX XXXX FF FF
XXXX
TI TT
XXXX XXXX
DETAIL
(A-J)
IAS
(TYPE)
TE
XXXX
(A-J)
TV
XXXX
TW
XXXX
T-129 DCS Cascade Temperature Control with local indicator (Foundation Fieldbus) and input from other
Function
Refer to T-112 & PEFS
T-130 DCS Temperature Control (Foundation Fieldbus) with outputs to Other Function
Refer to T-118 & PEFS
T-131
DCS Temperature Control with Local Indicator (Foundation Fieldbus) having multiple temperature Inputs
Refer to T-120 & PEFS
T-133 3 Point IPS Multipoint Indication/Input and Rate of Change of Temperature Indication to DCS
Refer to T-015 & PEFS
T-134 24 Point IPS Multipoint Indication/Input and Rate of Change of Temperature Indication to DCS
Refer to T-015 & PEFS
T-135 2 Point IPS Multipoint Indication/Input and Rate of Change of Temperature Indication to DCS
Refer to T-015 & PEFS
T-136 IPS Multipoint Indication/Input and Rate of Change of Temperature Indication to DCS
Refer to T-015 & PEFS
T-141 6 POINT TEMPERATURE MULTIPLEXER (FOUNDATION FIELDBUS), AND IPS TEMPERATURE TRIP
Refer to T-015 & T-017 & PEFS
T-156 MULTI-TE (10 TC) TEMP IND VIA 8 PPOINT TEMP MUX
Refer to T-155 & PEFS
APPENDIX 22
MULTIVARIABLE (U) Originating
APPENDIX 23
VIBRATION (V) Originating
Note: Software tags shown within the dotted-dashed line will not be populated in SPI but they shall be defined in
ICSS typical configuration document and they shall be made available within the ICSS.
PEFS
DETAIL
Note: Software tags shown within the dotted-dashed line will not be populated in SPI but they shall be defined in
ICSS typical configuration document and they shall be made available within the ICSS.
PEFS
DETAIL
Note: Software tags shown within the dotted-dashed line will not be populated in SPI but they shall be defined in
ICSS typical configuration document and they shall be made available within the ICSS.
PEFS
DETAIL
TAGS
Note: Software tags shown within the dotted-dashed line will not be populated in SPI but they shall be defined in
ICSS typical configuration document and they shall be made available within the ICSS.
PEFS
DETAIL
APPENDIX 24
WEIGHT, FORCE Originating
W-001 IPS Weight Trip FDH
APPENDIX 25
ON/OFF - TRIP VALVES - MISCELLANEOUS (X) Originating
XZ-001 On/Off Valve with IPS Trip Seed
XZ-016 On/Off Valve with IPS Trip and Partial Stroke Testing Seed
XZ-003 On/Off Valve with IPS Trip and Partial Stroke Testing (Foundation Fieldbus) Seed
XZ-004 On/Off Valve with IPS Trip with Position to IPS Seed
X-005 On/Off Valve activated from DCS Logic Seed
X-006 Solenoid Valve activated from DCS Logic FDH
X-017 On/Off Valve activated from DCS Logic/Manually Seed
X-007 On/Off Valve activated from DCS Manually Seed
On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing (Foundation Fieldbus) with
XZ-018 Seed
Reset from CCR, FAR and Field
XZ-009 DELETED - REFER TO XZ-003 Seed
XZ-010 DELETED - REFER TO XZ-018 Seed
On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing (Foundation Fieldbus) with
XZ-011 Seed
Reset from Field
H
HS IZ ZL
XXXX YYYY XXXX
B L
RESET
XZY
XXXX
PEFS
IA H
ZS
XXXX
L
XZV
XXXX
HS IZ ZLH ZLL
XXXX YYYY XXXX XXXX
B
RESET
XZY
XXXX
DETAIL
XZ-016 On/Off Valve with IPS Trip and Partial Stroke Testing
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-XZ-XXXX Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY-XXXX Solenoid Valve DO On-valve IPS 24VDC
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XY-XXXX Smart Positioner HART-AO On-valve DCS 4-20mA
UUU-ZSH-XXXX Position Switch Open DI On-valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-valve DCS PROX
UUU-ZLH-XXXX Valve Status Indication Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indication Closed SB DCS DCS N/A
H
HS IZ ZL
XXXX YYYY XXXX
B L
XZY
XXXX
H
PEFS
HS XZV ZS
XXXX IA XXXX
XXXX
A L
HS HS IZ ZLH ZLL
XXXX XXXX YYYY XXXX XXXX
A B
RESET
XZY
XXXX
DETAIL
XZ-003 On/Off Valve with IPS Trip and Partial Stroke Testing (Foundation Fieldbus)
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-XZ-XXXX Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY-XXXX Solenoid Valve DO On-valve IPS 24VDC
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI FIELD IPS VFC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS FieldbusFF
UUU-ZSH- XXXX Position Switch Open DI On-valve DCS PROX
UUU-ZSL- XXXX Position Switch Closed DI On-valve DCS PROX
UUU-ZLH- XXXX Valve Status Indication Open SB DCS DCS N/A
UUU-ZLL- XXXX Valve Status Indication Closed SB DCS DCS N/A
H
HS IZ ZL
XXXX YYYY XXXX
B L
XZY
XXXX
H
PEFS
HS XZV ZS
XXXX IA XXXX
XXXX
A L
HS HS IZ ZLH ZLL
XXXX XXXX YYYY XXXX XXXX
A B
RESET
XZY
XXXX
DETAIL
FF
XY XZV ZSH ZSL
XXXX XXXX IA XXXX XXXX
Note: Generally, the tag number sequence for all components of the loop shall follow the loop, but in
cases where the sequence number has already been used as part of a H-loop or Z-loop, alternative
sequencing numbers will have to be used and all components are associated to the XZ loop.
ZZLL HS
XXXX XXXX
ZZLH IZ
XXXX YYYY
DETAIL
XZY
XXXX
H
I ZL
YYYY XXXX
L
XY
XXXX
PEFS
H
XV ZS
IA XXXX
XXXX
L
I ZLH ZLL
YYYY XXXX XXXX
XY
DETAIL
XXXX
XV ZSH ZSL
XXXX IA XXXX XXXX
O H
HS I ZL
XXXX YYYY XXXX
C L
XY
PEFS
XXXX
H
XV ZS
IA XXXX
XXXX
L
O
HS I ZLH ZLL
XXXX YYYY XXXX XXXX
C
DETAIL
XY
XXXX
XV ZSH ZSL
XXXX IA XXXX XXXX
O H
HS ZL
XXXX XXXX
C L
XY
XXXX
PEFS
H
XV ZS
IA XXXX
XXXX
L
O
ZLH ZLL
HS
XXXX XXXX
XXXX
C
DETAIL
XY
XXXX
XV ZSH ZSL
XXXX IA XXXX XXXX
On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing (Foundation Fieldbus) with Reset from
XZ-018
Field
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-XZ-XXXX Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY- XXXXA Solenoid Valve DO On-valve IPS 24VDC
UUU-XZY- XXXXB Solenoid Valve DO On-valve IPS 24VDC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS FieldbusFF
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-ZZSH- XXXX Position Switch Open DI On-valve IPS PROX
UUU-ZZSL- XXXX Position Switch Closed DI On-valve IPS PROX
UUU-ZZLH- XXXX Valve Status Indication Open SID IPS DCS N/A
UUU-ZZLL- XXXX Valve Status Indication Closed SID IPS DCS N/A
HS IZ
XXXX YYYY
B
RESET
XZY XZY
XXXX XXXX
A B
PEFS
FF H
HS XZV ZS
XXXX IA
XXXX XXXX
A L
ZZLH ZZLL
XXXX XXXX
RESET
HS IZ
XXXX YYYY
B
HS IZ
XXXX YYYY
A
DETAIL
XZY XZY
XXXX
XXXX
A
B
FF
XY XZV ZZSH ZZSL
XXXX XXXX IA
XXXX XXXX
On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing (Foundation Fieldbus) with Reset from
XZ-011 Field
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-XZ-XXXX Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY- XXXXA Solenoid Valve DO On-valve IPS 24VDC
UUU-XZY- XXXXB Solenoid Valve DO On-valve IPS 24VDC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS Fieldbus
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-ZSH- XXXX Position Switch Open DI On-valve IPS PROX
UUU-ZSL- XXXX Position Switch Closed DI On-valve IPS PROX
UUU-ZLH- XXXX Valve Status Indication Open SB DCS DCS N/A
UUU-ZLL- XXXX Valve Status Indication Closed SB DCS DCS N/A
HS IZ
XXXX YYYY
B H
ZL
XXXX
L
XZY XZY
XXXX XXXX
PEFS
A B
FF H
HS XZV ZS
XXXX XXXX IA XXXX
A L
DETAIL
On/Off Valve with Dual SOV IPS & DCS Activated and Partial Stroke Testing (Foundation Fieldbus) with
XZ-012 Reset from Field
Loop: System
Instrument Type Description I/O Type Location Signal Type
UUU-XZ-XXXX Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY- YYYY Solenoid Valve DO On-valve IPS 24VDC
UUU-XY- ZZZZ Solenoid Valve DO On-valve DCS 24VDC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS Fieldbus
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-ZSH- XXXX Position Switch Open DI On-valve IPS PROX
UUU-ZSL- XXXX Position Switch Closed DI On-valve IPS PROX
UUU-ZLH- XXXX Valve Status Indication Open SB DCS DCS N/A
UUU-ZLL- XXXX Valve Status Indication Closed SB DCS DCS N/A
PEFS
DETAIL
NOTE: HCP depicts Heater Control Panel and HCP panel number to be entered in service/equipment.
ON ON
IZ TC HS XL AVAILABLE
YYYY YYYY XXXX XXXX FAULT
OFF OFF
TY-YYYY
XZS-XXXX
PEFS
THYRISTOR/ HEATER CP
IZ HS HS XL XL XL XL TC
YYYY XXXX XXXX XXXX XXXX XXXX XXXX YYYY
A B A B C D
TY-YYYY
XZS-XXXX
DETAIL
THYRISTOR/ HEATER CP
NOTE: HCP depicts Heater Control Panel and HCP panel number to be entered in service/equipment.
PEFS
DETAIL
XZ-103 Electrical Heater and Thyristor Control Panel with UV Trip (Under Voltage)
Refer to E-102 & X-102
X-104 On-off valve with dual SOV (IPS activated, DCS activated) and PST with reset in field
Refer to X-012
X-105 On-off valve with dual SOV (2oo2), IPS activated with reset in field and SIA (without PST)
Refer to XZ-018 (without PST)
XZ-111 On/Off Valve with Dual SOV IPS actuated with Reset form Field
Refer to X-105
XZ-112 On/Off Valve with IPS Trip and Partial Stroke Testing (Foundation Fieldbus) with Position to IPS
Loop: System Signal
Instrument Type Description I/O Type Location
UUU-XZ-XXXX Type Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY- XXXX Solenoid Valve DO On-valve IPS 24VDC
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS FieldbusFF
UUU-ZZSH- XXXX Position Switch Open DI On-valve IPS PROX
UUU-ZZSL- XXXX Position Switch Closed DI On-valve IPS PROX
UUU-ZZLH- XXXX Valve Status Indication Open SID IPS DCS N/A
UUU-ZZLL- XXXX Valve Status Indication Closed SID IPS DCS N/A
PEFS
DETAIL
XZ-113 On/Off Valve with IPS Trip with Position to IPS, and with OPEN & CLOSE Hand Switches
Loop: System Signal
Instrument Type Description I/O Type Location
UUU-XZ-XXXX Type Type
TAGS
UUU-XZV-XXXX ON/OFF VALVE N/A INLINE N/A N/A
UUU-XZY- XXXX SOLENOID VALVE DO ON-VALVE IPS 24VDC
UUU-HS-XXXXB HAND SWITCH OPEN HARD DI FIELD IPS VFC
UUU-HS-XXXXC HAND SWITCH OPEN HARD DI FIELD IPS VFC
UUU-ZZSH- XXXX POSITION SWITCH OPEN DI ON-VALVE IPS PROX
UUU-ZZSL- XXXX POSITION SWITCH CLOSED DI ON-VALVE IPS PROX
UUU-ZZLH- XXXX VALVE STATUS INDICATION OPEN SID IPS DCS N/A
UUU-ZZLL- XXXX VALVE STATUS INDICATION CLOSED SID IPS DCS N/A
PEFS
DETAIL
X-121 On-Off valve with Dual SOV with limit Switch feedback to DCS
Refer to X-011 & PEFS (No PST)
X-123 Hardwired Signal from DCS to Other Systems with Soft Alarm
Refer to X-052 & PEFS
X-124 Hardwired Signal from Other Systems to DCS with Soft Alarm
Refer to X-055 & PEFS
XZ-130 ON/OFF VALVE WITH IPS TRIP WITH POSTION TO IPS WITHOUT RESET
Refer to XZ-004 (No field reset)
XZ-134 On/Off Valve with 2OO3 SOV configuration, IPS Activated and Partial Stroke Testing (Foundation Fieldbus) with Reset from Field
Refer to Z-103
APPENDIX 26
EVENT (Y) Originating
APPENDIX 27
POSITION (Z) Originating
Z-101 DCS Position Indication with Local Indicator PSCJ
Z-103 Position Switch PSCJ
Z-103 Turbine Trip Valve Close Position to DCS PSCJ
Z-201 IPS Output (Solenoid Valve Limit Switch Low input IPS) FDH (CSR)
Z-202 IPS Output (Solenoid Valve Limit Switch High and Low input IPS) FDH (CSR)
Z-203 MOV with Limit Switch High and Low input IPS and HS in Operator Shelter FDH (CSR)
Z-204 DCS Run Status Indication FDH (CSR)
Z-205 MOV with Limit Switch High and Low input IPS and HS local and on MOV and Indication in LP FDH (CSR)
Z-206 HV with Limit Switch High input IPS and HS local and Solenoid Valve IPS FDH (CSR)
XV with Limit Switch High and Low input IPS Solenoid Valve IPS Open Close Indication Lamps
Z-208 FDH (CSR)
on LP
Z-209 IPS Open Switch LP and Open indication in LP FDH (CSR)
Z-210 IPS 2 x Open Switch LP one Input and Open indication in LP FDH (CSR)
Z-211 LIMIT SWITCH HIGH AND LOW INPUT TO DCS INDICATION FDH
Z-212 LIMIT SWITCH HIGH INPUT TO DCS INDICATION FDH
Z-213 LIMIT SWITCH LOW INPUT TO DCS INDICATION FDH
Z-214 LIMIT SWITCH LOW INPUT TO IPS FDH
Z-215 LIMIT SWITCH HIGH INPUT TO IPS FDH
Z-201 IPS Output (Solenoid Valve Limit Switch Low input IPS)
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-XY-XXXX Solenoid Valve DO On-Valve IPS
UUU-XV-XXXX Control Valve Inline
UUU-ZSL-XXXX Position Switch Low DI On-Valve IPS
UUU-ZAL-XXXX Position Indication Low (Soft) SID IPS DCS
Z-202 IPS Output (Solenoid Valve Limit Switch High and Low input IPS)
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-XY-XXXX Solenoid Valve DO On-Valve IPS
UUU-XV-XXXX Control Valve Inline
UUU-ZSH-YYYY Position Switch High DI On-Valve IPS
UUU-ZAH-YYYY Position Indication High (Soft) SID IPS DCS
UUU-ZSL-XXXX Position Switch Low DI On-Valve IPS
UUU-ZAL-YYYY Position Indication Low (Soft) SID IPS DCS
Z-203 MOV with Limit Switch High and Low input IPS and HS in Operator Shelter
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-HS-ZZZZ Hans Switch LP
UUU-MOV-ZZZZ Motor Operated Valve Inline
UUU-ZSH-YYYY Position Switch High DI On-Valve IPS
UUU-ZAH-YYYY Position Indication High (Soft) SID IPS DCS
UUU-ZSL-XXXX Position Switch Low DI On-Valve IPS
UUU-ZAL-XXXX Position Indication Low (Soft) SID IPS DCS
Z-205 MOV with Limit Switch High and Low input IPS and HS local and on MOV and Indication in LP
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-HS-AAAA Hans Switch Field
UUU-HS-ZZZZ Hans Switch DI On-Valve IPS
UUU-HA-ZZZZB Hans Switch Alarm (Soft) DI On-Valve IPS
UUU-MOV-ZZZZ Motor Operated Valve DO Inline IPS
UUU-ZSH-YYYY Position Switch High DI On-Valve IPS
UUU-ZHL-YYYY Position Indication High (Soft) SID IPS DCS
UUU-ZAH-YYYY Position Indication High (Hard) DO LP IPS
UUU-ZL-YYYY Position Indication High (Hard) DO LP IPS
UUU-ZSL-XXXX Position Switch Low DI On-Valve IPS
UUU-ZHL-XXXX Position Indication Low (Soft) SID IPS DCS
UUU-ZL-XXXX Position Indication Low (Hard) DO LP IPS
Z-206 HV with Limit Switch High input IPS and HS local and Solenoid Valve IPS
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-HS-YYYY-C Hans Switch (Close) DI Field IPS
UUU-HS-YYYY-C Hans Switch (Open) DI LP IPS
UUU-HV-YYYY Hand Operated Valve Inline
UUU-HY-YYYY Solenoid Valve DO On-Valve IPS
UUU-ZSH-XXXX Position Switch High DI On-Valve IPS
UUU-ZAH-XXXX Position Indication High (Soft) SID IPS DCS
Z-208 XV with Limit Switch High and Low input IPS Solenoid Valve IPS Open Close Indication Lamps on LP
Loop Instrument Type I/O Location System
UUU-Z-XXXX Description Type Type
TAGS
UUU-XV-ZZZZA Motor Operated Valve Inline
UUU-XY-ZZZZ Solenoid Valve DO On-Valve IPS
UUU-ZSH-YYYY Position Switch High DI On-Valve IPS
UUU-ZAH-YYYY Position Indication High (Soft) SID IPS DCS
UUU-ZL-YYYY Position Indication Open (Hard) DO LP IPS
UUU-ZSL-XXXX Position Switch Low DI On-Valve IPS
UUU-ZAL-XXXX Position Indication Low (Soft) SID IPS DCS
UUU-ZL-XXXX Position Indication Closed (Hard) DO LP IPS
APPENDIX 28
TYPICALS
ZLH ZLL HS HS IZ
XXXX XXXX XXXX XXXX YYYY
A B
RESET
XZY PSV
XXXX CCCC
FF
ZSH ZSL XY XZV
XXXX XXXX XXXX XXXX
DETAIL
PG
FF BBBB
PI PT
AAAA AAAA
L
NOTE 2 IA
NOTE 1
1) Two non-return valves shall be installed to prevent back flow from the SIA system in the case of loss of Instrument Air Header
pressure.
2) A low pressure alarm shall be provided to indicate low air pressure in the SIA, set at the minimum pressure that is required for three
valve strokes
Typical Detail of Secured Air System for On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing
Typical 2 (Foundation Fieldbus)
Loop: (XZ-018) System
Instrument Type Description I/O Type Location
UUU-XZ-XXXX Type Signal Type
TAGS
UUU-XZV-XXXX On/Off Valve N/A Inline N/A N/A
UUU-XZY- XXXXA Solenoid Valve DO On-valve IPS 24VDC
UUU-XZY- XXXXB Solenoid Valve DO On-valve IPS 24VDC
UUU-XY-XXXX Smart Positioner Fieldbus FieldbusFF On-valve DCS FieldbusFF
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HS-XXXXB Reset Switch DI Field IPS VFC
UUU-ZZSH- XXXX Position Switch Open DI On-valve IPS PROX
UUU-ZZSL- XXXX Position Switch Closed DI On-valve IPS PROX
UUU-ZZLH- XXXX Valve Status Indication Open SID IPS DCS N/A
UUU-ZZLL- XXXX Valve Status Indication Closed SID IPS DCS N/A
LOOP: (P-020) System
Instrument Type Description I/O Type Location
UUU-P-AAAA Type Signal Type
TAGS:
UUU-PT-AAAA Pressure Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-PI-AAAA Pressure Indication (Soft) SB DCS DCS N/A
LOOP: (P-001) System
Instrument Type Description I/O Type Location
N/A Type Signal Type
TAGS:
UUU-PG-BBBB Pressure Gauge N/A Offline N/A N/A
LOOP: (PSV-001) System
Instrument Type Description I/O Type Location
N/A Type Signal Type
TAGS:
UUU-PSV-CCCC Pressure Relief Valve N/A Inline N/A N/A
PEFS
Typical Detail of Secured Air System for On/Off Valve with Dual SOV IPS Activated and Partial Stroke Testing
Typical 2
(Foundation Fieldbus) (Continued)
ZLH ZLL HS HS IZ
XXXX XXXX XXXX XXXX YYYY
A B
RESET
XZY XZY PSV
XXXX XXXX CCCC
A B
FF
ZSH ZSL XY XZV
XXXX XXXX XXXX XXXX
DETAIL
PG
FF BBBB
PI PT
AAAA AAAA
L
NOTE 2 IA
NOTE 1
1) Two non-return valves shall be installed to prevent back flow from the SIA system in the case of loss of Instrument Air Header
pressure.
2) A low pressure alarm shall be provided to indicate low air pressure in the SIA, set at the minimum pressure that is required for three
valve strokes
Typical 3 Typical Detail of Secured Air System for Emergency On/Off Valve
Loop: (E-012) System
Instrument Type Description I/O Type Location
UUU-E-XXXX Type
TAGS
UUU-EY-XXXX Solenoid Valve DO On-valve IPS 24VDC
UUU-HS-XXXXA Hand Switch Partial Stroke Test (Soft) SB DCS DCS N/A
UUU-HZS-XXXXB TRIP SWITCH DI CCR IPS VFC
UUU-HZS-XXXXC TRIP SWITCH DI FAR IPS VFC
UUU-HS-XXXXD Reset Switch DI Field IPS VFC
UUU-HZS-XXXXD TRIP SWITCH DI Field IPS VFC
UUU-EL-XXXXB Emergency Light DO CCR DCS 24VDC
UUU-EL-XXXXC Emergency Light DO FAR DCS 24VDC
UUU-XY-XXXX Valve Positioner Fieldbus FieldbusFF On-valve DCS FIELDBUS
UUU-ZSH-XXXX Position Switch Open DI On-valve DCS PROX
UUU-ZSL-XXXX Position Switch Closed DI On-valve DCS PROX
UUU-ZLH-XXXX Valve Status Indication Open SB DCS DCS N/A
UUU-ZLL-XXXX Valve Status Indication Closed SB DCS DCS N/A
UUU-EV-XXXX Emergency Isolation Valve N/A Inline N/A N/A
LOOP: (P-020) System
Instrument Type Description I/O Type Location
UUU-P-AAAA Type Signal Type
TAGS:
UUU-PT-AAAA Pressure Transmitter Fieldbus FieldbusFF Offline DCS FIELDBUSFF
UUU-PI-AAAA Pressure Indication (Soft) SB DCS DCS N/A
LOOP: (P-001) System
Instrument Type Description I/O Type Location
N/A Type Signal Type
TAGS:
UUU-PG-BBBB Pressure Gauge N/A Offline N/A N/A
LOOP: (PSV-001) System
Instrument Type Description I/O Type Location
N/A Type Signal Type
TAGS:
UUU-PSV-CCCC Pressure Relief Valve N/A Inline N/A N/A
Typical 3 Typical Detail of Secured Air System for Emergency On/Off Valve (Continued)
PEFS
DETAIL
1) Two non-return valves shall be installed to prevent back flow from the SIA system in the case of loss of Instrument Air Header
pressure.
2) A low pressure alarm shall be provided to indicate low air pressure in the SIA, set at the minimum pressure that is required for three
valve strokes
3) For notes relevant to the E-012 template, refer to the loop template.
APPENDIX 28
APPLICATION EXAMPLES
7.29.1 IPS Flow Trip with 2oo3 Voting and Mof3 Control
LOOP: System
Instrument Type Description I/O Type Location Signal Type
119-IZ-1030 Type
119-IZ-1030 IPS Function Block N/A IPS N/A N/A
LOOP:
Instrument Type Description I/O Type Location System TypeSignal Type
119-FZ-1043
TAGS:
119-FZE- 1043 Orifice Plate N/A Inline N/A N/A
119-FZT- 1043A DP Flow transmitter HART-AI Offline IPS 4-20mA
119-FZT- 1043B DP Flow transmitter HART-AI Offline IPS 4-20mA
119-FZT- 1043C DP Flow transmitter HART-AI Offline IPS 4-20mA
LOOP:
Instrument Type Description I/O Type Location System TypeSignal Type
119-XZ-1031
TAGS:
119-XZV-1031 On/Off Valve N/A Inline N/A N/A
119-XZY- 1031 Solenoid Valve DO On-valve IPS 24VDC
LOOP:
Instrument Type Description I/O Type Location System Type
Signal Type
119-XZ-1032
TAGS:
119-XZV-1032 On/Off Valve N/A Inline N/A N/A
119-XZY- 1032 Solenoid Valve DO On-valve IPS 24VDC
7.29.3 IPS Flow Trip with 2oo3 Voting and Mof3 Control (Foundation Fieldbus)
IZ
1030
XZY XZY
1031 1032
HH
FZT
1043
2oo3 A,B,C
7.29.4 IPS Level Trip with 2oo3 Voting and Mof3 Control (Foundation Fieldbus)
LOOP:
System
119-LZ-1043 Instrument Type Description I/O Type Location Signal Type
Type
Refer to L-102
TAGS: N/A
119-LZT- 1043A DP LEVEL TRANSMITTER HART-AI Offline IPS 4-20mA
119-LZT- 1043B DP LEVEL TRANSMITTER HART-AI Offline IPS 4-20mA
119-LZT- 1043C DP LEVEL TRANSMITTER HART-AI Offline IPS 4-20mA
LOOP:
System
119-LZ-1044 Instrument Type Description I/O Type Location Signal Type
Type
Refer to L-109
TAGS:
119-LY-1044A Mof3 SELECTOR SAO IPS DCS SL
119-LC-1044 LEVEL CONTROLLER (SOFT) SB DCS DCS N/A
119-LY-1044 VALVE POSITIONER FIELDBUS FieldbusFF On-valve DCS FIELDBUSFF
119-LV-1044 CONTROL VALVE N/A Inline N/A N/A