The pop-up Fault Display screen automatically appears when a fault condition
for the Host Drive or any connected peripheral is detected. The pop-up Fault
Display screen flashes to alert that a fault condition exists. This screen displays
the:
• Fault Code number (See Fault and Alarm Display Codes on page 312.)
• Fault description
• Elapsed time (in hh:mm:ss format) from fault detection
Stopped AUTO
0.00 Hz F
– – FAULTED – –
Fault Code 81
Port 1 DPI Loss
Elapsed Time 01:26:37
ESC CLR
Power Layer Interface (PLI) PowerFlex 755 Frame 8 and larger drives utilize a pair of 7-segment displays to
indicate drive status and conditions.
Board 7-Segment Display
Series A Display
Lit Segment Indication Description
Fault Clear Indicates a fault condition has been cleared.
PWM Enable IGBT gating is enabled. When disabled, all IGBT signal inputs to the PLI IGBT
driver chip are low. IGBT gating is enabled by setting bit 0 of the Config Register.
IGBT gating is disabled by clearing bit 0 or by “POE” fault (IOC, Bus Overvoltage,
or Ground Fault).
Fiber Loss Fault Turns on when a Fiber Loss fault occurs. A Fiber Loss fault occurs when the LOS
signal is high or when a valid data packet has not been received for a period of
1024 μs. The fault is latched and is cleared be setting bit 8 of the Config Register.
The Fiber Loss fault inhibits IGBT firing in the same manner as a “POE” fault.
Fiber Loss Pin Indicates the actual state of the LOS pin described in Write Enable.
SAFE Vcc Power On Power is applied to the PLI IGBT driver chip (U14). Delayed for 12 seconds after
power up.
Write Enable Data writes from the Fiber Optic link are enabled to PLI registers. Data writes are
disabled for ten seconds (time required for the Control Board to initialize) after
negation of the LOS pin of the PLI fiber optic transceiver. LOS is driven high when
the optical power into the fiber optic receiver is too low (broken, crimped,
disconnected fiber, or transmitter at opposite end of fiber is not operating.
Series B Display
Lit Segment Indication Description
PWM Enable IGBT gating is enabled. IGBT gating is enabled by setting bit 0 of the Config
Register. IGBT gating is disabled by clearing bit 0 or by fault.
Initialization Done Indicates that the control has initialized the PLI board.
Fiber Loss Actual state of the LOS pin. LOS is driven high when the optical power into the
fiber optic receiver is too low (broken, crimped, disconnected fiber, or
transmitter at opposite end of fiber is not operating.
On Line The PLI is powered.
System Safety Pin 1 of the 541 PLI IGBT driver chip (U14) is low. This pin must be low to fire the
Enable B IGBTs.
Setting Factory Defaults The PowerFlex 20-HIM-A6 / -C6S HIM User Manual, publication 20HIM-
UM001, provides detailed instructions on using Human Interface Module
capabilities including setting PowerFlex 750-Series drive to factory settings.
The following parameters are not reset when Set Defaults “Most” is executed:
P300 [Speed Units], P301 [Access Level], P302 [Language], P305 [Voltage
Class], P306 [Duty Rating], P471 [PredMaint Rst En], and P472 [PredMaint
Reset].
System Resource Allocation Each option installed in the drive requires a percentage of the available system
resources. Some options configurations may exceed the available resources of the
main control board’s processor. If 90% of the available system resources is
reached, an F19 Task Overrun alarm will result indicating that system resource
utilization is excessive.
Hardware Service Manual The PowerFlex 750-Series AC Drive Hardware Service Manual, publication 750-
TG001, provides schematics and detailed instructions on part replacement for
Frame 8 drives and larger.
Integrated Motion When a PowerFlex 755 is used in Integrated Motion on EtherNet/IP mode, the
Logix controller and RSLogix 5000 are the exclusive owners of the drive (same as
Applications Kinetix). A HIM or other drive software tools, such as DriveExplorer and
DriveTools SP, cannot be used to control the drive or change configuration
settings. These tools can only be used for monitoring.
Fault and Alarm Display Event numbers for PowerFlex 750-Series faults and alarms are displayed in one of
three formats.
Codes
• Port 00 (Host Drive) displays the event number only. For example, Fault 3
“Power Loss” is displayed as:
Fault Code 3.
• Ports 01 through 09 use the format PEEE, indicating port number (P) and
event number (EEE). For example, Fault 1 “Analog In Loss” on an I/O
module installed in Port 4 is displayed as:
Fault Code 4001.
• Ports 10 through 14 use the format PPEEE, indicating port number (PP)
and event number (EEE). For example, Fault 37 “Net IO Timeout” on
Port 14 is displayed as:
Fault Code 14037.
Parameter Access Level Three parameter access level options are selectable by P301 [Access Level].
• Option 0 “Basic” is the most limited view that only displays commonly
utilized parameters and options.
• Option 1 “Advanced” is an expanded view that may be required to access
more advanced drive features.
• Option 2 “Expert” provides a comprehensive view of the drive’s entire
parameter set.
Drive Fault and Alarm The table below contains a list of drive-specific faults and alarms, the type of fault
or alarm, the action taken when the drive faults, the parameter used to configure
Descriptions the fault or alarm (if applicable), and a description and action (where applicable).
The faults and alarms listed in Table 10 only apply to non Integrated Motion
applications. See Table 14 on page 522 for a list of Integrated Motion faults.
141 Autn Enc Angle Resettable Coast P78 [Encdrlss AngComp] is out of range.
Fault
142 Autn Spd Rstrct Resettable Coast Frequency limit settings are preventing the drive from reaching a
Fault suitable speed during an Inertia Tune test.
143 Autotune CurReg Resettable Coast Calculated values for P96 [VCL Cur Reg Kp] and/or P97 [VCL Cur Reg Ki]
Fault are out of range.
144 Autotune Inertia Resettable Coast Results from the Inertia Tune test out of range for P76 [Total Inertia].
Fault
145 Autotune Travel Resettable Coast When P77 [Inertia Test Lmt] is set, the Inertia Tune test was prevented
Fault from reaching a suitable speed to run the test.
DI Jog 2 Forward
DI Jog 1 Forward
DI Jog 2 Reverse
DI Jog 1 Reverse
DI Fwd Reverse
DI Run Reverse
DI Manual Ctrl
DI Speed Sel 2
DI Speed Sel 1
DI Speed Sel 0
DI Clear Fault
DI Coast Stop
DI HOA Start
DI Aux Fault
DI Decel 2
DI Accel 2
DI Jog 2
DI Jog 1
DI Start
DI Stop
DI Run
DI Stop
DI Coast Stop
DI Cur Lmt Stop
DI Aux Fault • •
DI Clear Fault • •
DI HOA Start • • • • • • • • • •
DI Start • • • • • • • • • •
DI Run • • • • • • • •
DI Run Forward • • • • • •
DI Run Reverse • • • • • •
DI Jog 1 • • • • • •
DI Jog 1 Forward • • • • • •
DI Jog 1 Reverse • • • • • •
DI Jog 2 • • • • • •
DI Jog 2 Forward • • • • • •
DI Jog 2 Reverse • • • • • •
DI Fwd Reverse • • • • • •
DI Accel 2
DI Decel 2
DI Manual Ctrl
DI Speed Sel 0
DI Speed Sel 1
DI Speed Sel 2
DI Stop Mode B
DI Jog 2 Forward
DI Jog 1 Forward
DI Jog 2 Reverse
DI Jog 1 Reverse
DI Fwd Reverse
DI Run Reverse
DI Manual Ctrl
DI Speed Sel 2
DI Speed Sel 1
DI Speed Sel 0
DI Clear Fault
DI Coast Stop
DI HOA Start
DI Aux Fault
DI Decel 2
DI Accel 2
DI Jog 2
DI Jog 1
DI Start
DI Stop
DI Run
DI Stop • • • • • • • • • • • • • • • • • • • •
DI Coast Stop • • • • • • • • • • • • • • • • • • • •
DI Cur Lmt Stop • • • • • • • • • • • • • • • • • • • •
DI Aux Fault • • • • • • • • • • • • • • • • • • • •
DI Clear Fault • • • • • • • • • • • • • • • • • •
DI HOA Start • • • • • • • • • • •
DI Start • • • • • • • • • • •
DI Run • • • • • • • • • • • • • •
DI Run Forward • • • • • • • • • • • • • • • •
DI Run Reverse • • • • • • • • • • • • • • • •
DI Jog 1 • • • • • • • • • • •
DI Jog 1 Forward • • • • • • • • • • • • • • • •
DI Jog 1 Reverse • • • • • • • • • • • • • • • •
DI Jog 2 • • • • • • • • • • •
DI Jog 2 Forward • • • • • • • • • • • • • • • •
DI Jog 2 Reverse • • • • • • • • • • • • • • • •
DI Fwd Reverse • • • • • • • • • • • • • • • •
DI Accel 2 • • • • • • • • • • • • • • • • • • • • •
DI Decel 2 • • • • • • • • • • • • • • • • • • • • •
DI Manual Ctrl • • • • • • • • • • • • • • • • • •
DI Speed Sel 0 • • • • • • • • • • • • • • • • • • • • • •
DI Speed Sel 1 • • • • • • • • • • • • • • • • • • • • • •
DI Speed Sel 2 • • • • • • • • • • • • • • • • • • • • • •
DI Stop Mode B
161 Sleep Config Alarm 2 There is a Sleep/Wake configuration error. With Sleep Wake Mode =
Direct, possible causes include:
Drive is stopped and Wake Level < Sleep Level.
Stop=CF, Run, Run Fwd, or Run Rev is not configured in Digital Input
functions.
162 Waking Alarm 2 The Wake timer is counting toward a value that will start the drive.
168 HeatSinkUnderTmp Resettable Heatsink temperature sensor is reporting a value below -18.7 °C (-1.66
Fault °F) or the sensor feedback circuit is open.
See P943 [Drive Temp Pct] and/or P944 [Drive Temp C].
169 PWM Freq Reduced Alarm 1 The PWM Frequency has been reduced from the value set in P38 [PWM
Frequency] due to excessive IGBT junction temperatures.
See also P420 [Drive OL Mode].
170 CurLimit Reduced Alarm 1 The current limit value has been reduced from the value set in [Current
Limit n] due to excessive IGBT junction temperatures or P940 [Drive OL
Count] = 95%.
See also P420 [Drive OL Mode].
322 N-1 Operation Alarm 1 20 (Port 10) Drive is operating with fewer inverters than the original parallel
[Recfg Acknowledg] configuration.
21 (Port 10)
[Effctv I Rating]
324 DC Bus Mismatch Non-Reset Coast There is a bus voltage imbalance between parallel inverters that is
Fault greater than 50V DC.
327 HS Temp Imbal U Alarm 1 There is a heatsink temperature imbalance between parallel inverters in
328 HS Temp Imbal V the phase indicated that is greater than 11.5 °C (52.7 °F).
329 HS Temp Imbal W
357 In Vlt Imbal L12 Alarm 1 There is a input line voltage imbalance between parallel converters in
358 In Vlt Imbal L23 the AC lines indicated that is greater than 5% of the converter rated
359 In Vlt Imbal L31 voltage.
360 N-1 See Manual Resettable Coast The number of active inverters has been reduced from the original
Fault parallel configuration.
Refer to N-1 and Re-Rate Functions on page 341.
361 Rerate See Manual Resettable Coast The drive rating has changed from the original parallel configuration.
Fault Refer to N-1 and Re-Rate Functions on page 341.
362 Cnv/Inv Mismatch Alarm 2 There is a voltage class mismatch between the installed parallel
inverters and converters.
363 CBP/Inv Mismatch Alarm 2 There is a voltage class mismatch between the installed parallel
inverters and common DC bus precharge units.
364 CBP Num Mismatch Alarm 2 The number of active inverters and active common DC bus precharge
units does not match.
365 Zero Cnv/Prechrg Alarm 2 No converter or common DC bus precharge unit exists.
366 Cnv Num Mismatch Alarm 2 The number of active inverters and active converters does not match.
371 P1 Comm Loss Resettable Coast A communications fault has occurred between the main control board
372 P2 Comm Loss Fault and the DC precharge control board on the common DC bus precharge
unit n.
380 PWM FPGA Overrun Alarm 1 The time limit on the PWM write to the FPGA was exceeded.
900 900 Resettable Coast Critical input exception.
Fault Cycle power to clear this fault. Contact technical support.
901 Machine Check Resettable Coast Internal error.
Fault Replace the main control board.
902 Data Storage Error Resettable Coast Cache memory corrupt.
Fault Replace the main control board.
903 Instruction Storage Error Resettable Coast Cache memory corrupt.
Fault Replace the main control board.
905 Alignment Error Resettable Coast Pointer is pointing to a non-boundary member.
Fault Obtain test points and check grounding.
906 Program Error Resettable Coast Bad memory read.
Fault Check grounding or replace the main control board.
907 Floating Point Unit Not Resettable Coast Firmware issue.
On Fault Obtain test points.
909 Aux Processor Not On Resettable Coast Auxiliary processor interrupt.
Fault Cycle power to clear this fault. Contact technical support.
912 Watchdog Resettable Coast Timer counted down, reached 0, and fault occurred.
Fault Replace the main control board.
913 Data TLB Error Resettable Coast Processor attempted to access non-boundary memory.
Fault Check grounding or replace the main control board.
914 Instruction TLB Error Resettable Coast Processor attempted to access non-boundary memory.
Fault Check grounding or replace the main control board.
IMPORTANT Fault and Alarm event numbers between 3000 and 13999 are generated by a module installed in a port. Refer to Fault and Alarm
Display Codes on page 312 for an explanation. For event numbers that fall between 13000 and 13999, refer to the PowerFlex 755
Drive Embedded EtherNet/IP Adapter User Manual, publication 750COM-UM001 for descriptions.
Inverter (Port 10) Faults and The table below contains a list of Inverter-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
Alarms (Frame 8 and Larger) configure the fault or alarm (if applicable), and a description and action (where
applicable). These faults and alarms only apply to Frame 8 drives and larger.
• Verify that the fiber optic cables are properly connected to the
transceivers.
• Verify that the transceivers are properly seated in the ports.
• Verify that the fiber optic cable is not cracked or broken.
• Verify that power is applied to the fiber optic interface board and
power layer interface board.
10102 I1 Thermal Const Non-Reset Coast The thermal model data sent to the power layer interface board is
10202 I2 Thermal Const Fault incorrect.
10302 I3 Thermal Const • Verify that the inverter is the correct rating for the drive.
• Compare the firmware versions of the power layer interface and
control board for compatibility.
• If necessary, re-flash the application firmware in control board.
10103 I1 HSFan Slow Alarm 1 The inverter heatsink fan is running below normal operating speed.
10203 I2 HSFan Slow • Verify the actual fan speed in [In HSFan Speed] (Port 10).
10303 I3 HSFan Slow • Check for debris in the fan. If necessary, clean the fan and housing.
• Check for noise at the fan, indicating motor bearing failure.
• Verify that the fan power and feedback connections are not loose or
disconnected.
• Replace the fan, if necessary.
Converter (Port 11) Faults The table below contains a list of Converter-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
and Alarms (Frame 8 and configure the fault or alarm (if applicable), and a description and action (where
Larger) applicable). These faults and alarms only apply to Frame 8 drives and larger.
• Verify that the fiber optic cables are properly connected to the
transceivers.
• Verify that the transceivers are properly seated in the ports.
• Verify that the fiber optic cable is not cracked or broken.
• Verify that power is applied to the fiber optic interface board, gate
firing board, and power layer interface board. If necessary, replace
the fiber optic interface, gate firing board, and/or power layer
interface board.
11143 C1 Firmware Flt Non-Reset Coast A firmware fault has occurred.
11243 C2 Firmware Flt Fault • Reset the drive. If this fault persists, replace the converter gate firing
11343 C3 Firmware Flt board.
11144 C1 DC Bus Open Non-Reset Coast The DC bus voltage did not rise above 12V (for 400V class drives) or 20V
11244 C2 DC Bus Open Fault (for 600V class drives) as the SCRs began to ramp on. In this case, the
11344 C3 DC Bus Open converter will try to turn on the SCRs for approximately 10 seconds
before issuing this fault. Event 101/201 “Cn Precharge” is issued
following the first retry.
• Verify that the current transducers have not all failed. If necessary,
replace all three current transducers.
• Verify that the DC link inductor has not failed. If necessary, replace
the DC link choke.
• Verify that the converter line and DC bus wiring is connected.
• Verify that the capacitor bank is properly installed and connected.
11145 C1 DC Bus Short Non-Reset Coast The peak current has exceeded 150% of the converter rating during the
11245 C2 DC Bus Short Fault precharge sequence. Peak charging current is normally limited to 50%
11345 C3 DC Bus Short of the converter rating.
• Check for a DC bus short, internally and externally.
• Verify that the wiring harness to P10 on the converter gate firing
board is connected and not damaged. Replace the harness as
necessary.
• Verify that the capacitor bank is properly installed and connected.
• Check for an IGBT short and replace as necessary.
11146 C1 CT Harness Non-Reset Coast A current transducer (CT) wiring harness connection loss has been
11246 C2 CT Harness Fault detected.
11346 C3 CT Harness • Verify that the CT wiring harness is not damaged and is connected to
P6 on the converter gate firing board. Replace the wiring harness if
necessary.
• If this problem persists, replace the converter gate firing board.
11147 C1 LFuse Harness Non-Reset Coast A line fuse wiring harness connection loss has been detected.
11247 C2 LFuse Harness Fault • Verify that the line fuse wiring harness is not damaged and is
11347 C3 LFuse Harness connected to P7 on the converter gate firing board. Replace the
wiring harness if necessary.
• If this problem persists, replace the converter gate firing board.
Precharge (Port 11) Faults The table below contains a list of Precharge-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
and Alarms (Frame 8 and configure the fault or alarm (if applicable), and a description and action (where
Larger) applicable). These faults and alarms only apply to Frame 8 drives and larger.
11133 P1 MCS Closed Resettable Coast The voltage across the molded case switch (MCS) when it was closed
11233 P2 MCS Closed Fault exceeded 10V.
11333 P3 MCS Closed
• Verify that the fiber optic cables are properly connected to the
transceivers.
• Verify that the transceivers are properly seated in the ports.
• Verify that the fiber optic cable is not cracked or broken.
• Verify that power is applied to the fiber optic interface board, gate
firing board, and power layer interface board. If necessary, replace
the fiber optic interface, gate firing board, and/or power layer
interface board.
11143 P1 Firmware Flt Non-Reset Coast A firmware fault has occurred.
11243 P2 Firmware Flt Fault • Reset the drive. If this fault persists, replace the converter gate firing
11343 P3 Firmware Flt board.
11145 P1 DC Bus Short Non-Reset Coast The peak current has exceeded 150% of the converter rating during the
11245 P2 DC Bus Short Fault precharge sequence. Peak charging current is normally limited to 50%
11345 P3 DC Bus Short of the converter rating.
• Check for a DC bus short, internally and externally.
• Verify that the wiring harness to P10 on the converter gate firing
board is connected and not damaged. Replace the harness as
necessary.
• Verify that the capacitor bank is properly installed and connected.
• Check for an IGBT short and replace as necessary.
11157 P1 BFuse Harness Non-Reset Coast A bus fuse wiring harness connection loss has been detected.
11257 P2 BFuse Harness Fault • Check the bus fuse harness and replace if necessary.
11357 P3 BFuse Harness • If this problem persists, replace the converter gate firing board.
N-1 and Re-Rate Functions The N-1 feature is available on Frame 9 and larger drives. This feature allows the
drive to be run at reduced current limits if one of the paralleled inverter/
converter drive assemblies fails.
The letter N represents the number of drive assemblies in the drive. For example,
a frame 9 drive has two drive assemblies, therefore N=2. A Frame 9 drive running
the N-1 feature will be running on one drive assembly, that is, N-1 =1.
The N-1 feature does not change the rating of the drive. It is a way to impose
temporary output restrictions on the drive until the damaged inverter/converter
drive assembly is repaired and re-installed. Some customers may elect to oversize
their drives, in order to have redundant inverter/converter assemblies.
The Re-Rate function allows the rating of the drive to be changed. This
procedure is used when making long-term changes.
This procedure describes how to use the N-1 feature to run the drive at reduced
limits because an inverter/converter assembly has failed.
IMPORTANT You cannot flash update a drive that is using the N-1 feature.
The control pod may need to be moved from the disabled drive assembly
to one of the remaining drive assemblies. Refer to the PowerFlex 750-
Series AC Drives Hardware Service Manual, publication 750-TG001.
3. Energize the drive.
With the drive assembly removed, an F360 “N-1 See Manual” fault is
indicated.
4. Verify the new rating shown in Port 10, P21 [Effctv I Rating].
Alarm 322 “N-1 Operation” is indicated, and persists, while the drive is in
this reconfigured state.
6. Run the reconfigured drive with reduced current and power limits.
This procedure describes how to use the Re-Rate feature to run the drive at a
reduced rating because a drive assembly has been removed.
1. Save the drive’s current parameter settings using the Human Interface
Module (HIM), DriveExecutive, or DriveExplorer.
2. Remove all incoming power to the drive.
3. Disconnect all fiber-optic cables from the fiber interface board, including
the connections to the drive assemblies that will not be removed.
4. Remove the selected drive assembly from the cabinet.
5. Energize the drive.
With all the fiber-optic cables disconnected, “No Inverters” and “No
Converters” port verification errors are indicated.
6. On the HIM, press FIX to acknowledge the error then Enter to confirm.
7. Remove all incoming power to the drive. Verify that the bus capacitors
have discharged before continuing.
8. Reconnect the fiber-optic cables to the fiber interface board.
9. Energize the drive.
With the drive assembly removed, a “One Inverter” port verification error
is indicated.
10. On the HIM, press FIX to acknowledge the error then Enter to confirm.
An F361 “Rerate See Manual” fault is indicated.
11. Verify the new rating shown in Port 10, P21 [Effctv I Rating].
Set Port 10, P20 [Recfg Acknowledg] to 1 “Acknowledge” to accept the
reconfiguration.
IMPORTANT Drive parameters are set to factory defaults when the new rating is
acknowledged. If a condition exists that does not allow the drive
parameters to be set to factory defaults, setting P20 to 1
“Acknowledge” will not be accepted. Such conditions include the drive
is currently running, DeviceLogix is currently running, or the drive is
communicating with a PLC.
12. Press the Stop key on the HIM to clear the fault.
P20 [Recfg Acknowledg] automatically returns to 0 “Ready.”
13. Use the HIM download function, DriveExecutive download function, or
DriveExplorer download function to download the parameter settings
saved in Step1.
IMPORTANT Do not use the Compare Screen Copy function in DriveExecutive or the
Error Check Download function in DriveExplorer to perform this step.
14. Run the reconfigured drive at the reduced rating and power limits.
This procedure describes how to use the Re-Rate feature to increase the drive
rating because a drive assembly has been added. For example, a drive assembly has
been repaired and is being reinstalled. Because the drive was Re-Rated when the
drive assembly was removed it needs to be re-rated again to run at full rating and
power limits.
1. Save the drive’s current parameter settings using the Human Interface
Module (HIM), DriveExecutive, or DriveExplorer.
2. Remove all incoming power to the drive.
3. Add the drive assembly to the drive and connect it to the fiber interface
board in consecutive order.
IMPORTANT Do not use the Compare Screen Copy function in DriveExecutive or the
Error Check Download function in DriveExplorer to perform this step.
9. Run the drive at the full rating and full power limits.
Embedded EtherNet/IP (Port The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry consisting of the
13) Events event’s numeric code and a timestamp is put into the event queue. You can view
the event queue using the PowerFlex 20-HIM-A6/-C6S HIM, DriveExplorer
software (version 6.01 or later), DriveExecutive software (version 5.01 or later) or
other clients using the DPI Fault object. For details on viewing and clearing
events using the HIM, see the PowerFlex 20-HIM-A6/-C6S HIM (Human
Interface Module) User Manual, publication 20HIM-UM001.
Many events in the event queue occur under normal operation. If you encounter
unexpected communications problems, the events may help you or Rockwell
Automation personnel troubleshoot the problem. The following events may
appear in the event queue.
I/O Faults and Alarms The table below contains a list of I/O-specific faults and alarms, the type of fault
or alarm, the action taken when the drive faults, the parameter used to configure
the fault or alarm (if applicable), and a description and action (where applicable).
Safe Torque Off Fault The table below lists the safe torque off-specific fault, the action taken when the
drive faults, and its description.
Table 19 - Safe Torque Fault and Alarm Types, Descriptions and Actions
Event Fault/Alarm Text Type Fault Configuration Auto Description/Action(s)
No. (1) Action Parameter Reset
xx000 No Entry
xx058 Module Defaulted Fault Coast Module was commanded to write default values.
(1) xx indicates the port number. Refer to Fault and Alarm Display Codes on page 312 for an explanation.
ATEX Faults The table below lists the ATEX-specific fault, the action taken when the drive
faults, and its description.
Single Incremental Encoder The table below contains a list of encoder-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
Faults and Alarms configure the fault or alarm (if applicable), and a description and action (where
applicable).
Table 21 - Single Incremental Encoder Fault and Alarm Types, Descriptions and Actions
Event Fault/Alarm Text Type Fault Configuration Auto Description/Action(s)
No. (1) Action Parameter Reset
xx000 Open Wire Configurable P3 The encoder module has detected an input signal (A, B, or Z) in the same
[Fdbk Loss Cfg] state as its complement (A Not, B Not, or Z Not). For open wire detection
to work, the encoder signals must be differential (not single ended). The
Z channel is only checked when enabled. See P1 [Encoder Cfg].
xx001 Phase Loss Configurable P3 More than 30 phase loss (open wire) events have occurred over an 8
[Fdbk Loss Cfg] millisecond time period. The same restrictions as for Open Wire
detection apply.
xx002 Quadrature Loss Configurable P3 Quadrature loss events occur when simultaneous edge transitions occur
[Fdbk Loss Cfg] on both the A and B encoder channels. This fault will occur when more
than 10 quad loss events over a 10 millisecond time period are detected.
Only valid when both A and B channels are used (not Bit 1 “A Chan
Only”) in P1 [Encoder Cfg].
xx058 Module Defaulted Fault Coast Module was commanded to write default values.
(1) xx indicates the port number. Refer to Fault and Alarm Display Codes on page 312 for an explanation.
Dual Incremental Encoder The table below contains a list of encoder-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
Faults and Alarms configure the fault or alarm (if applicable), and a description and action (where
applicable).
Table 22 - Dual Incremental Encoder Fault and Alarm Types, Descriptions and Actions
Event Fault/Alarm Text Type Fault Configuration Auto Description/Action(s)
No. (1) Action Parameter Reset
xx000 Enc0 Open Wire Configurable P3 The dual encoder module has detected an encoder 0 input signal (A, B,
[Enc 0 FB Lss Cfg] or Z) in the same state as its complement (A Not, B Not, or Z Not). For
open wire detection to work, the encoder signals must be differential
(not single ended). The Z channel is only checked when enabled. See P1
[Enc 0 Cfg].
xx001 Enc0 Phase Loss Configurable P3 More than 30 encoder 0 phase loss (open wire) events have occurred
[Enc 0 FB Lss Cfg] over an 8 millisecond time period. The same restrictions as for Enc0
Open Wire detection apply.
xx002 Enc0 Quad Loss Configurable P3 Encoder 0 Quadrature loss events occur when simultaneous edge
[Enc 0 FB Lss Cfg] transitions occur on both the A and B channels of encoder 0. This fault
will occur when more than 10 quad loss events over a 10 millisecond
time period are detected. Only valid when both A and B channels are
used (not Bit 1 “A Chan Only”) in P1 [Enc 0 Cfg].
xx030 Enc1 Open Wire Configurable P13 The dual encoder module has detected an encoder 1 input signal (A, B,
[Enc 1 FB Lss Cfg] or Z) in the same state as its complement (A Not, B Not, or Z Not). For
open wire detection to work, the encoder signals must be differential
(not single ended). The Z channel is only checked when enabled. See
P11 [Enc 1 Cfg].
xx031 Enc1 Phase Loss Configurable P13 More than 30 encoder 1 phase loss (open wire) events have occurred
[Enc 1 FB Lss Cfg] over an 8 millisecond time period. The same restrictions as for Enc1
Open Wire detection apply.
xx032 Enc1 Quad Loss Configurable P13 Encoder 1 Quadrature loss events occur when simultaneous edge
[Enc 1 FB Lss Cfg] transitions occur on both the A and B channels of encoder 1. This fault
will occur when more than 10 quad loss events over a 10 millisecond
time period are detected. Only valid when both A and B channels are
used (not Bit 1 “A Chan Only”) in P11 [Enc 1 Cfg].
xx058 Module Defaulted Fault Coast Module was commanded to write default values.
(1) xx indicates the port number. Refer to Fault and Alarm Display Codes on page 312 for an explanation.
Universal Feedback Faults The table below contains a list of universal feedback-specific faults and alarms,
the type of fault or alarm, the action taken when the drive faults, the parameter
and Alarms used to configure the fault or alarm (if applicable), and a description and action
(where applicable).
Table 23 - Universal Feedback Fault and Alarm Types, Descriptions and Actions
Event Fault/Alarm Text Type Fault Configuration Param Auto Description
No. (1) Action Reset
xx000 LightSrc Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Light source failure
xx001 Ch0 SigAmp Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] -Signal amplitude error
xx002 Ch0 PsnVal Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Position value error
xx003 Ch0 OverVolt Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Overvoltage error
xx004 Ch0 UndVolt Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Undervoltage error
xx005 Ch0 OverCur Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Overcurrent error
xx006 Ch0 Battery Err Configurable P9 Error reported by Heidenhain Encoder on Channel 0 with EnDat Interface
[FB0 Loss Cfg] - Battery empty
xx009 Ch0 AnalSig Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Analog signals outside specification
xx010 Ch0 IntOfst Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Faulty internal angular offset
xx011 Ch0 DataTabl Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Data field partitioning table damaged
xx012 Ch0 AnalLim Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Analog limit values not available
xx013 Ch0 Int I2C Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Internal I2C bus not operational
xx014 Ch0 IntChksm Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Internal checksum error
xx015 Ch0 PrgmResetErr Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Encoder reset occurred as a result of program monitoring
xx016 Ch0 CntOvrflwErr Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Counter overflow
xx017 Ch0 Parity Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Parity error
xx018 Ch0 Chksum Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Checksum of the data transmitted is incorrect
xx019 Ch0 InvCmd Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Unknown command code
xx020 Ch0 SendSize Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Number of data transmitted is incorrect
xx021 Ch0 CmdArgmt Err Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - Command argument transmitted is not allowed
xx022 Ch0 InvWrtAdrErr Configurable P9 Error reported by Stegmann Encoder on Channel 0 with Hiperface
[FB0 Loss Cfg] Interface - The selected data field must not be written to (invalid write
address)
Port Verification When connecting to select devices, such as PowerFlex 750-Series drives, the Port
Verification dialog box will display if device conflicts are found during the
connection process. These conflicts typically require resolution prior to
establishing the connection to the device.
The information and options available in this dialog box are detailed below:
Item Description
Previous Setup The device previously installed at the port identified.
Current Setup The device currently installed at the port identified (if applicable).
(Device Not Found) A message identifying the conflict at the identified port.
Changed Indicates that the device previously installed at the port identified has been
removed or changed to a different device.
Not supported - Must remove device Indicates that the device currently installed at the port identified has a
before connection firmware revision that is not compatible with the drive. The drive must be flash
updated to be able to use this device or the device must be removed from the
port before a connection can be made.
Not functioning - Must remove Indicates that the device currently installed at the port identified is not
device before connection functioning. The device must be removed from the port before a connection can
be made.
Invalid Duplicate - Must remove Indicates that the device currently installed at the port identified is already
device before connection installed at another port for the device to which you are attempting to connect
and the device cannot support the number of devices installed. The duplicate
device must be removed from the port before a connection can be made.
Requires Configuration Indicates that the device installed at the port identified requires configuration
before a connection can be made.
Accept All Accepts all configuration changes and continues the device connection process.
Cancel Cancels the device connection process.
Common Symptoms and Drive does not Start from Start or Run Inputs wired to the terminal block.
Corrective Actions Cause(s) Indication Corrective Action
Drive is Faulted Flashing red Clear fault.
status light • Press Stop
• Cycle power
• “Clear Faults” on the HIM Diagnostic
menu.
Incorrect input wiring. See Installation Instructions, None Wire inputs correctly.
publication 750-IN001, for wiring examples.
• 2 wire control requires Run, Run Forward, Run
Reverse or Jog input.
• 3 wire control requires Start and Stop inputs.
• Verify 24 Volt Common is connected to Digital
Input Common.
Incorrect digital input programming. None Configure input function.
• Mutually exclusive choices have been made (i.e.,
Jog and Jog Forward). Flashing yellow Resolve input function conflicts.
• 2 wire and 3 wire programming may be status light and
conflicting. “DigIn Cnfg B”
• Start configured without a Stop configured. or
“DigIn Cnfg C”
indication on LCD
HIM.
P936 [Drive Status
2] shows type 2
alarm(s).
Terminal block does not have control. None Check P324 [Logic Mask].