T& D Division – Commissioning Department

HVAC SYSTEM - Site Test Report


MAIN
CONTRACTOR
ABB CONTRACT NO. RFX2131400086-B1
CLIENT DEWA S/S .NAME 132/11KV MAADEN S/S
HVAC
UNIVERSAL VOLTAS LLC. DATE 17-05-2018
CONTRACTOR
MANUFACTURER M/s. FAWAS KUWAIT EQUIPMENT DUCT HEATER
TEST : ELECTRIC DUCT HEATER

DESCRIPTION RESULT CHECK REMARKS

MANUFACTURER FAWAZ , KUWAIT OK

MODEL NUMBER FL-20 / 3/415 / 24-OP


OK
OK
CAPACITY KW 20 KW

VOLTAGE / PHASE / Hz 415 / 3 / 50HZ


OK
OK
NO. OF STAGES 3
R Y B
RUNNING CURRENT AMPS AS PER STAGE
ST-1 9.55 9.59 9.88

ST-2 9.36 8.39 9.50 OK


ST-3 8.03 8.93 8.28

OK
TOTAL CURRENT R- 26.94 Y- 26.91 B – 27.66
STAGE 1,2,& 3 OK OK OK OK

COMMON FAULT OK OK

INTERLOCKED WITH AC UNIT( SYSTEM-1) OK OK

TESTED WITNESSED BY WITNESSED BY APPROVED BY


UNIVERSAL VOLTAS ABB DEWA DEWA
Signature

Name

PAGE- 36
T& D Division – Commissioning Department
HVAC SYSTEM - Site Test Report
MAIN
CONTRACTOR
ABB CONTRACT NO. RFX2131400086-B1
CLIENT DEWA S/S .NAME 132/11KV MAADEN S/S
HVAC
UNIVERSAL VOLTAS LLC. DATE 17-05-2018
CONTRACTOR
MANUFACTURER M/s. FAWAS KUWAIT EQUIPMENT DUCT HEATER
TEST : ELECTRIC DUCT HEATER

TESTED WITNESSED BY WITNESSED BY APPROVED BY


UNIVERSAL VOLTAS ABB DEWA DEWA
Signature

Name

PAGE- 36