Rev

Submitted date
Sec res date
Description SEC comments SSEM Reply TESTING DEP Comments
Not related protection signals and common SOE list shall be
Noted.
submitted for review by concerned department.
380/115/13.8kV SOE Point list In 13.8KV level, 50 OC Y-Phase signals are repeated for
0 15.11.2016 14.12.2016 Complied.
(typical bays) every relay and B-Phase signals are missing, clarify?
In 13.8KV SOE list, bay names are incomplete throughout SOE STD TES-P-108.20
Complied.
the list, shall be updated in the upcoming list. (REV. 0) (REV. 1
Response to SEC comments on DATE 30.10.2017)
1 27.12.2016 04.01.2017 380/115/13.8kV SOE POINT LIST Acceptable
(TYPICAL BAYS)
IFC for 380/115/13.8kV SOE
2 09.04.2017 11.04.2017 IFC Issued
POINT LIST (TYPICAL BAYS)
We have reviewed the above reference and we have the
following notes:
Please, find the SOE point list on a CD (in Excel format)
Re-submit for 380/115/13.8kV for your further action; also note that the subject SOE list PED requested to submitted the
SOE POINT LIST (TYPICAL BAYS) can be modified to include additional signals once required subject SOE list to SEC concern
3 11.02.2018 05.03.2018 SOE List prepared in new format by field. Department ( SCADA ) for review the
with IEC addresses as per SEC BCU and Metering signals shallbe reviewed by concerend submittal so that please find attched
requirement department for your review and approval
Non- related protection signals such as SAS system common
alarms, GIS and switchgear mechanical signals are out of
PED-E scope of work
SCADA Comments
We have reviewed your submittal and please find below our
comments.

in line with SAS Standardization, we


Expect that 380/115/13.8kV BSP SAS Gateway will be only are providing one pair of SCADA
one-please clarify Gateway in Dammam Housing
Project. Hence kindly comply as per
SEC comment on spare addressing.
Re-submit for 380/115/13.8kV
SOE POINT LIST (TYPICAL BAYS) If Gateway is ONE,
4 11.03.2018 09.04.2018 SOE List prepared in new format (a) No need to reserve 100 for each Voltage Level Noted SOE STD TES-P-108.20 (REV.
with IEC addresses as per SEC (b) No need to have separate Transmission / Distrubution 0) (REV. 1 DATE 30.10.2017)
requirement configuration sheets for each Voltage Level BUT FOLLOWED OLD
Alarm code fild is blank for some SOE's Noted REVISION AND 13.8 KV OVER
For the SAS internal equipment SOE's shall start from 001 to CURRENT START SIGNALS
complied MISSING IN APPROVED SOE
till end of the SOE's of SAS Internal equipment
Actual SOE's IOA shall start from 1001 and shall continue till LIST AS PER STD (REV.0)
complied
last SOE
► Contractor is requested to comply all the above
comments and re-submit to GMS SCADA for our review and
approval. complied
► Contractor is requested to submit soft copy by email
(HOB/PMD Cover Letter / All other supporting doucments.
Re-submit for 380/115/13.8kV SCADA Comments
SOE POINT LIST (TYPICAL BAYS) Configuration Sheets for SOE is not provided. Provided
SOE List prepared in new format Color CODE Column is BLANK. Provided
5 18.07.2018 13.08.2018 with IEC addresses as per SEC IFC Group Column are blank. Provided
requirement (to be sub
Network (Block) Diagram is not provided along with the
mitted SCADA Provided
submittal which shall comprises of Distance/Breaker
DEPARTMENTS) Designation / OH or UG / Contract # and other details
Re-submit for 380/115/13.8kV Complied where the first 100 SOE's
SOE POINT LIST (TYPICAL BAYS) First 100 SOE's points shall be reserved for "SAS points reserved for "SAS EQUIPMENT
6 18.09.2018 30.09.2018
SOE List updated to comply with EQUIPMENT ALARMS" ALARMS" as per attached the
SEC requirement. modified SOE HOB point list
Re-submit for 380/115/13.8kV
SOE POINT LIST (TYPICAL BAYS)
7 08.10.2018 15.11.2018 Acceptable
SOE List updated to comply with
SEC requirement.