Submitted date
Sec res date
Description SEC comments SSEM Reply TESTING DEP Comments
Not related protection signals and common SOE list shall be
Noted.
submitted for review by concerned department.
380/115/13.8kV SOE Point list In 13.8KV level, 50 OC Y-Phase signals are repeated for
0 15.11.2016 14.12.2016 Complied.
(typical bays) every relay and B-Phase signals are missing, clarify?
In 13.8KV SOE list, bay names are incomplete throughout SOE STD TES-P-108.20
Complied.
the list, shall be updated in the upcoming list. (REV. 0) (REV. 1
Response to SEC comments on DATE 30.10.2017)
1 27.12.2016 04.01.2017 380/115/13.8kV SOE POINT LIST Acceptable
(TYPICAL BAYS)
IFC for 380/115/13.8kV SOE
2 09.04.2017 11.04.2017 IFC Issued
POINT LIST (TYPICAL BAYS)
We have reviewed the above reference and we have the
following notes:
Please, find the SOE point list on a CD (in Excel format)
Re-submit for 380/115/13.8kV for your further action; also note that the subject SOE list PED requested to submitted the
SOE POINT LIST (TYPICAL BAYS) can be modified to include additional signals once required subject SOE list to SEC concern
3 11.02.2018 05.03.2018 SOE List prepared in new format by field. Department ( SCADA ) for review the
with IEC addresses as per SEC BCU and Metering signals shallbe reviewed by concerend submittal so that please find attched
requirement department for your review and approval
Non- related protection signals such as SAS system common
alarms, GIS and switchgear mechanical signals are out of
PED-E scope of work
SCADA Comments
We have reviewed your submittal and please find below our
comments.