Documente Academic
Documente Profesional
Documente Cultură
Table of Tables
Table 1: Default Idle Time Settings..................................................................2
Table 2: Parameter 37 Settings and Definitions .................................................3
Table 3: Idle Time Abnormal Situation Settings .................................................4
March, 2003 i
MS-ePICAIT-00 / Rev. O
Automatic Idle Time
ii March, 2003
MS-ePICAIT-00 / Rev. O
Automatic Idle Time
This technique is ineffective because the relationship between idle time and run
time does not indicate the same non-linear tendency as the relationship between
fluid production and idle time. Consequently, the idle time determined by this
method is not very accurate and is often too long, causing a corresponding loss of
production.
While this method cannot optimize the idle time applied to a rod pumped well with
the same results that would occur with a closely monitored and hand-tuned
pumping system, it will quickly and reliably stabilize the vast majority of pumping
systems to a very reasonable operating condition. As this method gives a
continuous stabilization of cycle time, it also automatically adjusts for the effects of:
• Power outages
• Production “kicks”
• Pump wear
• Tubing leaks
March, 2003 1
MS-ePICAIT-00 / Rev. O
Automatic Idle Time
2 March, 2003
MS-ePICAIT-00 / Rev. O
Automatic Idle Time
Programming Parameters
P20 (Idle Time) is defined as the minimum idle time. Values from 00:00:01 to
99:59:59 are considered valid. A value of 00:00:00 causes a “PARAMETER 20
MISSING” error message.
P36 (Target Cycle Time) serves as a “long time” parameter. Values ranging from
00:00:00 to 99:59:59 are valid. When set to a non-zero value, the automatic idle
time is activated for operations. A value less than the value in P20 disables the
automatic idle time feature. The factory default value is 00:00:00.
P37 controls the provision for reducing cycle time if the run time percentage is less
than 50%. P37 is a byte parameter. Table 2 describes the values for this
parameter.
The factory default value is set to 0. This instructs the RPC to take no action and
not illuminating the fault lamp.
March, 2003 3
MS-ePICAIT-00 / Rev. O
Automatic Idle Time
As there is no parameter which displays the actual idle time currently in use, it
must be calculated by subtracting the average run time in P205 (P207 if P205 is
zero) from the cycle time in P36. If the average run time is larger than the value of
P36, the value of P20 is the idle time.
4 March, 2003
MS-ePICAIT-00 / Rev. O