Documente Academic
Documente Profesional
Documente Cultură
Solutions
No Mark
QUESTION 1
A direct online (DOL) motor starter for three phase AC induction motor.
(a) 1M 1M
1M
1M
Page 3 of 14
Estimate the diversity factors for each type of loads and the maximum
demand. [7 MARKS]
Assumed maximum demand (A.M.D.) using IEE On-Site Guide Table 1B
(small shop premises):
Heaters
2000 7500 75 1M
2 𝑥 2𝑘𝑊 + 3 𝑥 1.5 + 1.0 = + +
230 230 100
= 8.7𝐴 + 24.46𝐴
= 33.16𝐴
Cooker 5kW (cooker unit has socket outlet)
5000 1M
𝐶𝑜𝑜𝑘𝑒𝑟 = = 21.7𝐴
230
Socket at cooker control 5A
(b) i)
Water Heating (thermostatic) 3kW 1M
3000
𝑊𝑎𝑡𝑒𝑟 ℎ𝑒𝑎𝑡𝑒𝑟𝑠 = = 13.04𝐴 (𝑛𝑜 𝑑𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦)
230
Lighting
2500 90
𝐿𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = = 10.9 𝑥 = 9.8 𝐴 1M
230 100
Recommend the rating of the main switch fuse, which can be chosen either
Page 4 of 14
Fault current in relay coil = Primary fault current / CT ratio 1M
50
Plug setting multiplier (P.S.M) = =8 1M
6.25
Page 5 of 14
QUESTION 2
(a) Determine THREE (3) required conditions for selecting insulation of the cable
in electrical wiring circuit
- To deal with the voltage of the system. 1M
- Must not damage by heat produced by the current flow, ambient temp, or
by heat transferred to it by hot objects. 1M
- Protect from environment effect. 1M
(b) List THREE (3) factors that determine the current rating of a cable.
Ambient temperature 1M
(c) A motor which has a full load current of 188 A is fed by a multi-core pvc-
insulated cooper conductor cable installed in trunking at an ambient
temperature of 35oC. This circuit is protected by a MCCB as shown in Figure
XX. Due to the high starting current, the current rating of the MCCB is 350 A.
Determine the size of the cable under the assumptions that:
i) For no overload protection, the minimum tabulated current rating is;
𝐼𝐵
𝐼𝑡,𝑚𝑖𝑛 = 2M
𝐶𝑎 𝑥 𝐶𝑔 𝑥 𝐶𝑖
188
= 200𝐴 2M
0.94 𝑥 1 𝑥 1
From Table 4D2A of IEE Regulations [Ref. 2, P 190], column 5, a 120 2M
mm2/4C cable which has a tabulated current rating of 206 A is selected.
Page 6 of 14
ii) To provide adequate protection against overload,
𝐼𝑁
𝐼𝑡,𝑚𝑖𝑛 = 2M
𝐶𝑎 𝑥 𝐶𝑔 𝑥 𝐶𝑖
350
= 372𝐴 2M
0.94 𝑥 1 𝑥 1
For the same Table 4D2A, column 5, a 400 mm2/4C cable which has a 2M
tabulated current rating of 402 A is selected. The current causing effective
operation of the 350 A MCCB is :
𝐼2 = 1.3 𝑥 350 = 455𝐴 2M
1.45𝐼𝑍 = 1.45 𝑥 402 𝑥 0.94 = 548𝐴 2M
Page 7 of 14
QUESTION 3
(a) Describe the definition and purpose of Circuit Protective Conductor (CPC)
The circuit protective conductor (CPC) is part of the earth fault loop and
connects together all exposed conductive parts to the main terminal. Its
purpose is to convey the earth fault current without damaging the core
insulation. 2M
Regulation 413-02 states that the earth loop impedance value should be such
as to initiate disconnection of the fault within 0.4 to 5.0 seconds for socket
outlets and fixed equipment respectively. 2M
I2 t 5002 0.1 2M
Smin 1.37mm2
k 115
(c) i) The TVDr (mv/A/m) value for 4mm2, 16mm2 and 25mm2 cable in this
circuit.
ii) The cable resistive value, RCPC for 4mm2, 16mm2 and 25mm2 cable for
this circuit.
11 30
R4 0.165 2M
2 1000
2.8 30
R16 0.042 2M
2 1000
1.75 10
R25 0.0088 2M
2 1000
Page 8 of 14
iii) The current causing the automatic operation of protective devices
50
IA 96.9 A 2M
0.5158
Page 9 of 14
QUESTION 4
(a) i) Line interactive system UPS 2M
b) i) Standby Off-Line
Drawbacks
- May not have power conditioning 1M
- Transfers to backup may interrupt load
Benefits 1M
- Lower purchase cost 1M
- Provides basic protection
Page 10 of 14
(c) Figure 5 shows an essential services switchboard supplied (in an
emergency) from a standby alternator. As an electrical engineer, your
responsibility is to define and rectify the short circuit current magnitude at the
terminals of the alternator. Determine
i) The value of 3-phase short circuit current at point A according to the origin of
supply.
𝑆
Short circuit current at point A, 𝐼𝑆𝐶 (3∅) = 2M
√3×400×0.04
630 × 103
= 2M
√3 × 400 × 0.04
= 22.7 𝑘𝐴 1M
The value of 3-phase short circuit current at point A according to the alternator
ii)
supply
𝑆
Short circuit current at point A, 𝐼𝑆𝐶 (3∅) = 2M
√3×400×0.3
400 × 103
= 2M
√3 × 400 × 0.3
= 1.92 𝑘𝐴 1M
Page 11 of 14
QUESTION 5
(a) During an earth fault, the fault current is flowing from the live conductor
through the exposed-conductive-parts to earth. Thus, the metallic parts may
be at a high potential relative to earth. 1M
When high impedance earth fault, the magnitude of earth fault current may
activate the RCCB; 1M
- To open the protected circuit when the residual current exceeds this
reference value. 1M
1) Damage the generator and the prime mover because of mechanical stresses
caused by rapid acceleration or deceleration, bringing the rotating masses
into synchronism (exactly matched speed and rotor angle) with the power
system. 2M
4) Prevent the generator from staying online and picking up load when
protective relay elements interpret the condition as an abnormal operating
condition and trip the generator. 2M
(d) The low voltage is supplied to a double-storey shop lot as shown in Figure 1.
A short circuit occurs inside a final distribution board at the second floor with
the fault current of 500A. Calculate the operating time for:
Page 12 of 14
i) The incoming protective device at the final distribution board if it is in
accordance with theBS EN 60898 standard under type C MCB rated at 63A.
ii) The incoming protective device at the final distribution board when it is IEC
1008 RCCB rated at 63A with a rated residual operating current of 0.1A.
Given line to earth fault happens.
IF 500
The _ residual _ current
I N 0.1
2M
The _ residual _ current 5000 I N
For a RCCB rated at 63A with I N 0.1A; if live-to-earth fault occur, the
operating time of RCCB is 0.04s. 1M
iii) The MCCB rated at 200A at the main switchboard for ambient temperature of
20○C and 40○C.
500 1M
IF
200
I F 2.5I N 1M
The operating time of the 200A MCCB is 50s for ambient temperature
20○C. 1M
Page 13 of 14