Documente Academic
Documente Profesional
Documente Cultură
Ventilation
• General ventilation
– Provide heating or cooling
– Provide make-up air
– Provide dilution and reduction of contaminants
such as CO2 and body odor
• Dilution ventilation
– Provide dilution of contaminants to safe levels (<TLV or LEL)
– Constrained by comfort and other factors
– Usually initial cost: DV cost << LEV cost
– Usually for operation: DV cost >> LEV cost
Page 1
Dilution Ventilation - applications
Dilution Ventilation
• The solution to pollution is dilution?
• Do you want to move a lot of air?
• What happens in the winter?
• How do you get a sweeping effect?
• Why bother with local exhaust if there are too many
sources to vent them all?
• To have effective DV we need to:
– Mix contaminated air with large volume of fresh air
– Have sufficient air changes/hour to prevent build-up
– Create air movement and mixing at all required locations
Page 2
“Laminar” Flow Dilution System
Supply Plenum
Exhaust Plenum
10
50
500 200
Page 3
Mixing by entrainment
Vo 22° 0.10 Vo
30 Outlet diameter
40
10
50 350 200
20
Page 4
Effects of Cross-Drafts
and Worker’s Proximity to the Source
40
10
50
350 200
20
POISON POISON
Page 5
Reverse the flow?
POISON POISON
Zones of Ventilation
Supply
Exhaust
General Elevation
Blowing with entrainment produces large scale eddies & mixing
Page 6
Computing Generation Rate
d(Volvapor ) G=
Amount Evaporated
G= t 2 − t1
dt
Page 7
Target Concentration
G
C=
Q
Concentration if not perfect mixing
G
C=
Q/ m
Page 8
Values of mi for each work station
m due to non-uniformity
Ci Supply air mixing
mi =
Cexhaust Contaminant release
Distance from worker
Mixing factors
Ci
mi =
Cexhaust
1 n
Cexhaust n
Cavg = ∑ Citi
8hours i
Cavg =
8hours i
∑ mit i
1 n C 15 min
Mavg = ∑
8hrs i
mit i Mpeak =
Cexhaust
Page 9
Accumulation = Generation – Removal
Q & Cs
G Q&C
dC Q Q
mG
C 2 = C1e -Qt /mR +
Q
+ Cs (1- e-Qt / mR )
V = G + C s − Ct
dt m m
mG
C2 = C1e −Qt / mV + (
+ C s 1 − e −Qt / mV )
Q
ROOM VOLUME
mG
C2 = C1e −Qt / mV + + Cs 1 − e −Qt / mV ( )
Q
Page 10
Application of Equations
mG
C2 = C1e −Qt / mV + (
+ Cs 1 − e −Qt / mV )
Q
C2
mG "Steady"-State
Ct = Generation
Q
t2
Application of Equations
mG
C2 = C1e −Qt / mV + (
+ Cs 1 − e −Qt / mV )
Q
Cmax C1
C2
Buildup Purge
C2
C1 Cs
t2 t2
Page 11
Cyclic operations
• If short cycles, effects “average out”
C2
Cyclic
Generation
t2
mi Gi
+ + Cs i (1 − e i i i )
−Qi t / m iR −Q ∆ t / m R
Ci = Ci −1 e
∆ i
Qi
Page 12
DESIGNING NEW SYSTEM
Page 13
Confined Space Ventilation
Page 14
Example Problem
−2
Rm G + QCs / m – Q Co / m 1000 ft * 3 ln 010
3
Q = ln
= −6
= 599 ft3/min
∆t G + Q Cs / m – Q C2 / m 30 min 025 *10
Summary
• Estimating G and m is difficult
• Reduce G as much as possible
• Reduce greatest contributors to exposure and
perceived exposure first
• Use sweeping, but be realistic about it
• Complement local exhaust systems
• Provide winter and summer
• Purge before and during confined space entry
Page 15