Project G+1 REINFORCED CONCRETE COUNCIL

1st Slab Made by Date Page


Location Column @ C-2 1
PUNCHING SHEAR to BS8110:1997 INTERNAL COLUMN Checked Revision Job No
Originated from RCC13.xls on CD © 1999 BCA for RCC -

MATERIALS fcu N/mm2 35 STATUS Legend


fyv N/mm2 460 VALID DESIGN
link Ø mm 10

DIMENSIONS A mm 400 E mm 0
B mm 300 F mm 0
G mm 0 H mm 0
Upper Column Weight (KN) 0
LOADIN FROM SAFE (KN) 625
LOADING Vt kN 625 0 0 1600.0
DEAD LOAD = 2.5 LIVE LOAD = 2 Top Mesh T 20 @ 100
ult UDL kN/m2 14.75 X-REINF T 12 @ 150
Y-REINF T 12 @ 150
SLAB h mm 230 dx mm 199 Asx mm2/m 3897
dy mm 187 Asy mm2/m 3897
ave d mm 193 ave As % 2.021

RESULTS Veff = 718.8 kN vc = 1.0726 N/mm2 (Table 3.8)


At col. face, v max = 2.653 N/mm 2 At 1.5d perimeter, v = 0.9818 N/mm2
At 0d perimeter, v = 0.7373 N/mm2

PROVIDE LINKS 0 Links not required

0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0 Plan
0 0 0
Project BUILDING (G+4) REINFORCED CONCRETE COUNCIL

Client SULTAN ALHASAWY Made by Date Page


Location Column @ E-4 M.D. 14.01.2013
PUNCHING SHEAR to BS8110:1997 COLUMN Checked Revision Job No
Originated from RCC13.xls on CD © 1999 BCA for RCC M.D. - 3012

MATERIALS fcu N/mm2 35 STATUS Legend


fyv N/mm2 460 VALID DESIGN
link Ø mm 0

DIMENSIONS A mm 300 E mm 100


B mm 800 F mm -450
D mm 1200 G mm 0
Upper Column Weight (KN) 27.72 H mm 0
LOADIN FROM SAFE (KN) 626

LOADING Vt kN 598.28 0 750


DEAD LOAD = 12.5 LIVE LOAD = 2 Top Mesh T 12 @ 150
ult UDL kN/m2 29.80 X-REINF T 16 @ 150
Y-REINF T 16 @ 150
SLAB h mm 260 dx mm 227 Asx mm2/m 2095
dy mm 211 Asy mm2/m 2095
ave d mm 219 ave As % 0.958

RESULTS Veff = 747.9 kN vc = 0.8103 N/mm2 (Table 3.8)


At col. face, v max = 1.534 N/mm2 At 1.5d perimeter, v = 0.6582 N/mm2
At 0d perimeter, v = 0.4924 N/mm2

PROVIDE LINKS 0 Links not required

0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0 Plan
0 0 0
Project BUILDING (G+4) REINFORCED CONCRETE COUNCIL
Client 1st Slab Made by Date Page
Location COLUMN NO. 4 CORNER M.D. 14.01.2013 3
PUNCHING SHEAR to BS8110:1997 COLUMN Checked Revision Job No
Originated from RCC13.xls on CD © 1999 BCA for RCC M.D. - 3012

MATERIALS fcu N/mm2 40 STATUS Legend


fyv N/mm2 460 VALID DESIGN
link Ø mm 12

DIMENSIONS A mm 200 E mm 0
B mm 600 F mm 0
C mm 400 G mm 0
D mm 400 H mm 0
Upper Column Weight (KN) 13.86
LOADIN FROM ADAPT(KN) 1224

LOADING Vt kN 1210.1 0 0 350


DEAD LOAD = 10 LIVE LOAD = 0 Top Mesh T 16 @ 150
ult UDL kN/m2 40.25 X-REINF T 16 @ 150
Y-REINF T 16 @ 150
SLAB h mm 750 dx mm 717 Asx mm2/m 2682
dy mm 701 Asy mm2/m 2682
ave d mm 709 ave As % 0.378

RESULTS Veff = 1512.7 kN vc = 0.5346 N/mm2 (Table 3.8)


At col. face, v max = 1.328 N/mm2 At 1.5d perimeter, v = 0.5071 N/mm2
At 0d perimeter, v = 0.3610 N/mm2

PROVIDE LINKS 0 Links not required

0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0 Plan
0 0 0
Project G+1 REINFORCED CONCRETE COUNCIL
Client 1st Slab Made by Date Page
Location COLUMN NO. 4 RE-ENTRANT 0 30-Dec-99 4
PUNCHING SHEAR to BS8110:1997 CORNER Checked Revision Job No
Originated from RCC13.xls on CD © 1999 BCA for RCC 0 - 0

MATERIALS fcu N/mm2 50 STATUS Legend


fyv N/mm2 460 VALID DESIGN
link Ø mm 10

DIMENSIONS A mm 1000 E mm 0
B mm 1000 F mm 0
C mm 0 G mm 0
D mm 0 H mm 0
Upper Column Weight (KN) 115.5
LOADIN FROM ADAPT(KN) 1000
LOADING Vt kN 884.5 0 0 591.6
DEAD LOAD = 5 LIVE LOAD = 5 Top Mesh T 12 @ 300
ult UDL kN/m2 23.40 X-REINF T 16 @ 200
Y-REINF T 16 @ 200
SLAB h mm 240 dx mm 207 Asx mm2/m 1383
dy mm 191 Asy mm2/m 1383
ave d mm 199 ave As % 0.696

RESULTS Veff = 1105.6 kN vc = 0.7800 N/mm2 (Table 3.8)


At col. face, v max = 1.352 N/mm2 At 1.5d perimeter, v = 0.9166 N/mm2
At 3d perimeter, v = 0.6833 N/mm2

PROVIDE LINKS (single leg) .

Perimeter 1 11 T10 @ 285 99 from col face


Perimeter 2 14 T10 @ 290 249 from col face
Perimeter 3 17 T10 @ 290 398 from col face
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0 Plan
0 0 0
Project BUILDING (G+4)

Location Column @ C-2 INTERNAL COLUMN


PUNCHING SHEAR to BS8110:1997 Made by Job No
Originated from RCC13.xls on CD © 1999 BCA for RCC Date 30-Dec-99

DETAILED CALCULATIONS
Veff/Vt 1.1500 (enhancement factor) link leg area 78.5
Hole deduction ? NO
CRITICAL PERIMETERS ENCLOSED AREAS
Per No a Internal deduct Final m Per No Internal
1 289.5 3716 0 3716 1 0.861
2 434.25 4874 0 4874 2 1.482
3 579 6032 0 6032 3 2.272
4 723.75 7190 0 7190 4 3.229
5 868.5 8348 0 8348 5 4.353
6 1013.25 9506 0 9506 6 5.645
7 1158 10664 0 10664 7 7.105
8 1302.75 11822 0 11822 8 8.732
Hole face 0 1400 0 1400 Hole face 0.120
Col face 0 1400 0 1400 Col face 0.120

LINK REQUIREMENTS within


Per No v Asv Total No Location Band?
1 0.9818 655 0.00 0.00 d 0
2 0.7373 859 0.00 0.00 d 0
3 0.5843 1063 0.00 0.00 d 0
4 0.4785 1267 0.00 0.00 d 0
5 0.4003 1471 0.00 0.00 d 0
6 0.3396 1675 0.00 0.00 d 0
7 0.2907 1879 0.00 0.00 d 0
8 0.2501 2083 0.00 0.00 d 0
Hole face 2.6525
Col face 2.6525

LINK PERIMETERS 0
Per No a Internal deduct Final m No Spacing
1 96.5 2172 0 2172 10 270
2 241.25 3330 0 3330 14 275
3 386 4488 0 4488 18 280
4 530.75 5646 0 5646 22 280
5 675.5 6804 0 6804 26 280
6 820.25 7962 0 7962 30 280
7 965 9120 0 9120 34 285
8 1109.75 10278 0 10278 38 285
9 1254.5 11436 0 11436 42 285
Project BUILDING (G+4)

Location Column @ E-4 COLUMN


PUNCHING SHEAR to BS8110:1997 Made by M.D. Job No 3012
Originated from RCC13.xls on CD © 1999 BCA for RCC Date 14.01.2013

DETAILED CALCULATIONS
Veff/Vt 1.2500 (enhancement factor) link leg area 0.0
Hole deduction ? NO
CRITICAL PERIMETERS ENCLOSED AREAS
Per No a Internal Choose m deduct Final m Per No Edge D
1 328.5 4828 4828 0 4828 1 1.394
2 492.75 6142 6142 0 6142 2 2.295
3 657 7456 6928 0 6928 3 3.412
4 821.25 8770 7585 0 7585 4 4.745
5 985.5 10084 8242 0 8242 5 6.293
6 1149.75 11398 8899 0 8899 6 8.057
7 1314 12712 9556 0 9556 7 9.703
8 1478.25 14026 10213 0 10213 8 11.327
Hole face 0 2200 2200 0 2200 Hole face 0.240
Col face 0 2200 0 2200 Col face 0.240

LINK REQUIREMENTS within


Per No v Asv Total No Location Band?
1 0.6582 965 0.00 0.00 d 0
2 0.4924 1228 0.00 0.00 d 0
3 0.4091 1385 0.00 0.00 d 0
4 0.3438 1517 0.00 0.00 d 0
5 0.2845 1648 0.00 0.00 d 0
6 0.2297 1779 0.00 0.00 d 0
7 0.1846 1911 0.00 0.00 d 0
8 0.1457 2042 0.00 0.00 d 0
Hole face 1.5336
Col face 1.5336

LINK PERIMETERS 0
Per No a Internal Choose m deduct Final m No Spacing
1 109.5 3076 3076 0 3076 12 305
2 273.75 4390 4390 0 4390 16 310
3 438 5704 5704 0 5704 20 315
4 602.25 7018 6709 0 6709 23 315
5 766.5 8332 7366 0 7366 25 320
6 930.75 9646 8023 0 8023 27 320
7 1095 10960 8680 0 8680 29 320
8 1259.25 12274 9337 0 9337 31 320
9 1423.5 13588 9994 0 9994 33 320
Project BUILDING (G+4)

Location COLUMN NO. 4 CORNER COLUMN


PUNCHING SHEAR to BS8110:1997 Made by M.D. Job No 3012
Originated from RCC13.xls on CD © 1999 BCA for RCC Date 14.01.2013

DETAILED CALCULATIONS
Veff/Vt 1.2500 (enhancement factor) link leg area 113.1
Hole deduction ? NO
CRITICAL PERIMETERS
Per No a Internal Edge C Edge D Corner Choose m deduct Final m
1 1063.5 10108 6054 6454 3727 3727 0 3727
2 1595.25 14362 8181 8581 4790.5 4790.5 0 4791
3 2127 18616 10308 10708 5854 5854 0 5854
4 2658.75 22870 12435 12835 6917.5 6917.5 0 6918
5 3190.5 27124 14562 14962 7981 7981 0 7981
6 3722.25 31378 16689 17089 9044.5 9044.5 0 9045
7 4254 35632 18816 19216 10108 10108 0 10108
8 4785.75 39886 20943 21343 11171.5 11171.5 0 11172
Hole face 0 1600 1600 1600 1600 1600 0 1600
Col face 0 1600 1600 0 1600

ENCLOSED AREAS LINK REQUIREMENTS within


Per No Corner Per No v Asv Total No Location Band?
1 3.433 1 0.507 2413 0.0 0.00 d 0
2 5.697 2 0.361 3101 0.0 0.00 d 0
3 8.527 3 0.261 3790 0.0 0.00 d 0
4 11.923 4 0.186 4478 0.0 0.00 d 0
5 15.884 5 0.126 5166 0.0 0.00 d 0
6 20.411 6 0.076 5855 0.0 0.00 d 0
7 25.503 7 0.032 6543 0.0 0.00 d 0
8 31.161 8 -0.007 7232 0.0 0.00 d 0
Hole face 0.120 Hole face 1.328
Col face 0.120 Col face 1.328

LINK PERIMETERS 0
Per No a Internal Edge C Edge D Corner Choose m deduct Final m No Spacing
1 354.5 4436 3218 3618 2709 2709 0 2709 4 900
2 886.25 8690 5345 5745 3772.5 3772.5 0 3773 5 940
3 1418 12944 7472 7872 4836 4836 0 4836 6 965
4 1949.75 17198 9599 9999 5899.5 5899.5 0 5900 7 980
5 2481.5 21452 11726 12126 6963 6963 0 6963 8 990
6 3013.25 25706 13853 14253 8026.5 8026.5 0 8027 9 1000
7 3545 29960 15980 16380 9090 9090 0 9090 10 1010
8 4076.75 34214 18107 18507 10153.5 10153.5 0 10154 11 1015
9 4608.5 38468 20234 20634 11217 11217 0 11217 12 1015
Project G+1

Location COLUMN NO. 4 RE-ENTRANT CORNER COLUMN


PUNCHING SHEAR to BS8110:1997 Made by 0 Job No 0
Originated from RCC13.xls on CD © 1999 BCA for RCC Date 30-Dec-99

DETAILED CALCULATIONS
Veff/Vt 1.2500 (enhancement factor) link leg area 78.5
Hole deduction ? NO
CRITICAL PERIMETERS ENCLOSED AREAS
Per No a Internal Corner deduct Final m Per No Internal Corner
1 298.5 6388 5791 0 5791 1 2.550 1.686
2 447.75 7582 6686.5 0 6687 2 3.593 2.096
3 597 8776 7582 0 7582 3 4.814 2.550
4 746.25 9970 8477.5 0 8478 4 6.213 3.049
5 895.5 11164 9373 0 9373 5 7.790 3.593
6 1044.75 12358 10268.5 0 10269 6 9.545 4.181
7 1194 13552 11164 0 11164 7 11.479 4.814
8 1343.25 14746 12059.5 0 12060 8 13.590 5.491
Hole face 0 4000 4000 0 4000 Hole face 1.000 1.000
Col face 0 4000 0 4000 Col face 1.000

LINK REQUIREMENTS within


Per No v Asv Total No Location Band?
1 0.9166 1052 13.40 1.50 d 0
2 0.7848 1215 15.47 2.25 d 0
3 0.6833 1378 0.00 3.00 d 0
4 0.6025 1540 0.00 0.00 d 0
5 0.5364 1703 0.00 0.00 d 0
6 0.4812 1866 0.00 0.00 d 0
7 0.4343 2028 0.00 0.00 d 0
8 0.3938 2191 0.00 0.00 d 0
Hole face 1.3522
Col face 1.3522

LINK PERIMETERS 0
Per No a Internal Corner deduct Final m No Spacing
1 99.5 4796 2597 0 2597 11 285
2 248.75 5990 3492.5 0 3493 14 290
3 398 7184 4388 0 4388 17 290
4 547.25 8378 5283.5 0 5284 20 290
5 696.5 9572 6179 0 6179 23 290
6 845.75 10766 7074.5 0 7075 26 290
7 995 11960 7970 0 7970 29 295
8 1144.25 13154 8865.5 0 8866 32 295
9 1293.5 14348 9761 0 9761 35 295
Disclaimer
All advice or information from the British Cement Association and/or Reinforced Concrete Co
will evaluate the significance and limitations of its contents and take responsibility for its u
(including that for negligence) for any loss resulting from such advice or information is acc
subcontractors, suppliers or advisors. Users should note that all BCA software and publicati
time to time and should therefore ensure that they are in possession of the latest version.

This spreadsheet should be used in compliance with the accompanying publication 'Spreads
8110 & EC2' available from British Cement Association, Telford Avenue, Crowthorne, Berkshir

Status of spreadsheet
Public release version.

Revision history RCC13 Punching Shear

Date Version
03-Aug-99 RCC13 v1.0
ation from the British Cement Association and/or Reinforced Concrete Council is intended for those who
nificance and limitations of its contents and take responsibility for its use and application. No liability
egligence) for any loss resulting from such advice or information is accepted by the BCA, RCC or their
pliers or advisors. Users should note that all BCA software and publications are subject to revision from
ould therefore ensure that they are in possession of the latest version.

ould be used in compliance with the accompanying publication 'Spreadsheets for concrete design to BS
le from British Cement Association, Telford Avenue, Crowthorne, Berkshire RG45 6YS.

RCC13 Punching Shear

Action
First public release.
Includes b version comments
ouncil is intended for those who
use and application. No liability
cepted by the BCA, RCC or their
ons are subject to revision from

sheets for concrete design to BS


e RG45 6YS.

Size (kB)
309

S-ar putea să vă placă și