Sunteți pe pagina 1din 5

<<Contents>> <<Index>>

General Safety Lifecycle Management


Specifications Support Function

GS 32P01B40-01EN

 GENERAL
Safety Lifecycle Management Support Function provides necessary functions to correctly design, implement, and
operate ProSafe-RS safety instrumented system. This function is obtained by combining Automation Design Suite
(AD Suite) of the ProSafe-RS and iDefine for ProSafe-RS (provided by Trinity Integrated Systems).

 FUNCTIONAL SPECIFICATIONS
Functional safety management (FSM) is to reduce risks of causing hazards over “human beings, physical assets and
environments” to a tolerable level throughout the plant lifecycle of design, operation, maintenance, modification, and
decommissioning. The international standard IEC 61511 defines the requirements of the FSM at each phase of the
plant lifecycle.
The safety lifecycle management support function integrally manages information of the requirement specifications,
design, engineering, and maintenance in “Safety requirements specifications for the safety instrumented system” and
later phases in the following figure. This function enables to perform consistent FSM throughout the entire lifecycle of
the plant. In order to achieve highly efficient FSM, functions such as FSM support, design and engineering, and frame
work test are provided.

Hazard and risk assessment


Management of functional safety and functional safety assessment and auditing

Allocation of safety functions to protection layers

Safety requirements
Safety lifecycle structure and planning

specifications for the safety


instrumented system Design and development
of other means of risk
reduction
Design and engineering of
Verification

safety instrumented system

Installation , commissioning and validation

Operation and maintenance

Modification

Decommissioning

: Typical direction of information flow


F01E.ai

Figure IEC 61511 SIS safety lifecycle phases

Yokogawa Electric Corporation GS 32P01B40-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Sep. 2016 (YK)
5th Edition Nov. 15, 2019 (YK)
<<Contents>> <<Index>> 2
 FSM support function
In the phases of “Management of functional safety and functional safety assessment and auditing” and “Safety
life-cycle structure and planning,” organizational and engineers’ responsibilities, authorization, and skills must be
clearly defined. The FSM support function provides the following functions.
• Defining safety and project lifecycle phases
• Resource assignment
• Planning activities
• Identifying functional assessment and verification milestones
• Remote monitoring of FSM status
• Automatic configuration of documentation

 Application logic engineering


The following functions of the iDefine for ProSafe-RS support creation of application logics.
• Cause & effect
• State analysis
• IEC 61131 FBD logic editor
• Typical logic editor
• Change management function
The cause & effect function automatically generates the application logic in the format of IEC 61311 FBD style
by defining the relationship of input and output variables in matrix. The state analysis function also automatically
generates the application logic by the drawing the state management modules.
Since the verification of partial or overall operations of the application can be performed by the cause & effect function
or the state analysis function, the specifications and its validations can be confirmed by step by step.

 Test function
The iDefine for ProSafe-RS consists of the following test functions.
• Test case editor
• Test viewer
• Emulator
The test function allows the user to test the application logic and automatically generate the test report by using the
test scripts that the test case editor generates. The test scripts enable to perform these tests repeatedly until the
application logic becomes error-free.
The test function executes not only the logic test using the emulator but also simulation test and target test in
association with the ProSafe-RS’s test functions. The test status and results can be confirmed visually and in real time
by using the test viewer assigned with the cause & effect function and the state analysis function.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 32P01B40-01EN Sep. 28, 2016-00
<<Contents>> <<Index>> 3
 SYSTEM CONFIGURATION
The following shows an example of system configuration with safety lifecycle management support function. (*1)
*1: The iDefine for ProSafe-RS can be installed in the computer where ProSafe-RS R4.03.00 or later is installed from R4.03.00
or later.
However, the CENTUM software and the iDefine for ProSafe-RS cannot be installed in the same computer.

AD Suite

iDefine for ProSafe-RS AD Server

Ethernet

SENG ENG/HIS

Vnet/IP

SCS

F02E.ai
AD Suite: Automation Design Suite
AD Server: Automation Design Server
SENG: Safety engineering station
SCS: Safety control station
ENG: CENTUM VP Engineering station
HIS: CENTUM VP Human interface station
Figure Example of system configuration

 iDefine for ProSafe-RS


This is a functional safety lifecycle management tool exclusively developed for ProSafe-RS by Trinity Integrated
Systems. Functional modules such as the cause & effect and the state analysis are provided. Note that the functions
dedicatedly developed for the ProSafe-RS is not available from the iDefine of Trinity Integrated Systems sold in the
market.

iDefine for ProSafe-RS runs on a single computer.


When installing on a computer with ProSafe-RS, ProSafe-RS R4.03 or later is required.
When installing on a computer with CENTUM VP, CENTUM VP R6.07 or later is required.
When installing on a computer with ProSafe-RS and CENTUM VP, ProSafe-RS R4.05 or later and CENTUM VP
R6.07 or later are required.

 Automation Design Suite (AD Suite)


The AD Suite provides an engineering environment for configuring and maintaining control systems overall, including
plant instrumentation, safety instrumentation, and maintenance management. In the ProSafe-RS, the AD Suite is
consisted of an AD Server and an SENG.
The AD Server is a station to manage project data created by the SENG. The AD Server manages not only
ProSafe-RS projects but also configuration data of the iDefine for ProSafe-RS.
The SENG is the ProSafe-RS’s engineering and maintenance station. By using “RS4E5210 I/O list engineering
package” and “RS4E5810 iDefine interface package” (*1), safety I/O lists generated by the SENG can be exported to
the iDefine for ProSafe-RS, and the application logic generated by the iDefine for ProSafe-RS can be imported to the
SENG. Furthermore, the target test or the simulation test can be executed by the test case of the iDefine for
ProSafe-RS.
For defining tag names or executing SCS simulation test, “RS4E5600 CENTUM VP integration package” is required.
For defining tag names to integrate with FAST/TOOLS, “RS4E5700 FAST/TOOLS integration package” is required.
*1: Supported by ProSafe-RS R4.02 or later.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 32P01B40-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 4
 Safety control station (SCS)
An SCS is a station to perform safety control in a safety control system. This function runs on the following SCSs.
S2SC70S Safety control unit (for N-IO/FIO, rack mountable type)
S2SC70D Duplexed safety control unit (for N-IO/FIO, rack mountable type)
SSC60S Safety control unit (for FIO, rack mountable type)
SSC60D Duplexed safety control unit (for FIO, rack mountable type)
SSC50S Safety control unit (for FIO, rack mountable type)
SSC50D Duplexed safety control unit (for FIO, rack mountable type)
SSC57S Safety control unit (for Vnet/IP-Upstream, rack mountable type)
SSC57D Duplexed safety control unit (for Vnet/IP-Upstream, rack mountable type)

 OPERATING ENVIRONMENT
iDefine for ProSafe-RS (*1)
OS: Windows 7 SP1 32-bit/64-bit, Windows 8.1 32-bit/64-bit, Windows Server 2012 R2,
Windows 10 32-bit/64-bit (*2), Windows Server 2016 (*3)
CPU: Duo Core 1 GHz (or equivalent and above)
Memory: Minimum 8 GB
HDD: Minimum 10 GB of free space
For using this software, “ST1TD10 iDefine for ProSafe-RS License” is needed.
For more details, refer to the instruction manual for ST1TD10.This software installer is available from the website.
*1: As for the operating environment, refer to the “ProSafe-RS Safety instrumented system overview (for Vnet/IP)”
(GS 32P01B10-01EN) when the ProSafe-RS software and the iDefine for ProSafe-RS are installed in the same computer.
*2: Supported by ProSafe-RS R4.03.00 (iDefine for ProSafe-RS: 1.16.2) or later.
*3: Supported by ProSafe-RS R4.04.00 (iDefine for ProSafe-RS: 1.16.4) or later

To use iDefine for ProSafe-RS in virtual environment, Dongle Gateway of Windows Service is also required. Dongle
Gateway should be installed on a thin client, real environment SENG, or virtual machine installed SENG software.
USB dongle (software use right of iDefine for ProSafe-RS) should be plugged into a computer where the Dongle
Gateway is installed.
If Dongle Gateway is installed on virtualized SENG, USB Device Server is needed. The USB dongle should be
plugged into the USB Device Server.
The ST1TD10 software installer and Dongle Gateway software are available from the website. For USB Device
Server, contact YOKOGAWA.
AD Suite
As for the operating environment of the AD Suite, refer to the general specifications of “ProSafe-RS Safety
instrumented system overview (for Vnet/IP)” (GS 32P01B10-01EN), or “ProSafe-RS Safety Instrumented System
Overview (for Vnet/IP-Upstream)” (GS 32P01B30-01EN).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 32P01B40-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 5
 MODEL AND SUFFIX CODES
iDefine for ProSafe-RS License

Description
Model ST1TD10 iDefine for ProSafe-RS License
-V Basic software license
1 Single 1 license (*1) (*2)
2 Multi. 2 licenses ( only for Virtualization) (*2)
3 Multi. 3 licenses ( only for Virtualization) (*2)

Suffix 4 Multi. 4 licenses ( only for Virtualization) (*2)


Codes 5 Multi. 5 licenses ( only for Virtualization) (*2)
6 Multi. 6 licenses ( only for Virtualization) (*2)
7 Multi. 7 licenses ( only for Virtualization) (*2)
8 Multi. 8 licenses ( only for Virtualization) (*2)
1 English version

*1: In a real environment, ST1TD10 - V11 is required for each computer using iDefine for ProSafe-RS. For each computer, a
software license is provided with a USB dongle.
*2: For virtual environments, software licenses for the number of virtual machines using iDefine for ProSafe-RS are required.
Multiple software licenses are provided in one USB dongle.

SENG’s virtual machine on Vnet/IP requires the Vnet / IP interface package (RS4C3300).
For virtualization, refer to “IA System Product Virtualization Platform” (GS 30A05B10-01EN).

Limited warranty of product


The USB dongle is provided with the limited warranty as same as other ProSafe-RS’s software media.
For the details of the warranty, refer to the article 4 (Limited Warranty/Maintenance Services) of the “Software License
Agreement.”

ProSafe-RS release 4 software license agreement:


http://www.yokogawa.com/product/system/EndUserLicenseAgreement.htm

 ORDERING INFORMATION
Specify the model and suffix code(s).

 TRADEMARKS
• ProSafe, CENTUM, PRM, STARDOM, FAST/TOOLS, Exaopc, FieldMate, and Vnet/IP are either registered
trademarks or trademarks of Yokogawa Electric Corporation.
• Other products and company names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 32P01B40-01EN July 24, 2018-00
Subject to change without notice.

S-ar putea să vă placă și