Sunteți pe pagina 1din 9

<<Contents>> <<Index>>

General Field Device Connection


Specifications (for N-IO)

GS 32P06K10-01EN

 GENERAL
This General Specifications (GS) provides the hardware specifications of the connection between the N-IO I/O unit
and a field device.

SIGNAL CONNECTIONS
n
l Variation of Signal Connections
The field signal can be connected directly to the pressure clamp terminal or the spring clamp terminal on the base
plate of N-IO I/O unit. It can be also connected to the base plate via a dedicated cable and a terminal board. The
following shows the variation of the signal connections of the base plates for N-IO I/O.

Table Signal Connections of N-IO I/O Units

Terminal board
Signal connection
Number of connection
Model Field Cable
Module name I/O channels Pressure Spring
name Cable Terminal specification
per module clamp clamp Cable
connector board
terminal terminal
S2BN1D-
16 X — — — — (*3)
1
S2BN1D- Base Plate with
16 — X — — — (*3)
2 disconnecting terminal
(for N-IO, 16-channel)
AKB331
S2BN1D- A2BM4
16 — — X AKB651 (*3)
9 (*2)
(*1)
Base Plate for Barrier
S2BN4D 16 X — — — — (*4)
(for N-IO, MTL Barrier)
Base Plate for Barrier
S2BN5D 16 — X — — — (*4)
(for N-IO, P+F Barrier)
X: Connectable —: Not connectable

*1: Refer to the GS “Cablels (for ProSafe-RS)” (GS 32Q06M10-31E).


*2: Refer to the GS “Terminal Board (for N-IO)” (GS 32P06L20-01EN).
*3: Refer to “Cables” section of this document.
*4: Refer to the GS “Base plate (for N-IO)” (GS 32P06K20-01EN).

Yokogawa Electric Corporation GS 32P06K10-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Nov. 2015 (YK)
3rd Edition Nov. 15, 2019 (YK)
<<Contents>> <<Index>> 2
 CABLES
l Field Cable for S2BN1D
Applicable Cables
Refer to the TI “ProSafe-RS Installation Guidance” (TI 32P01J10-01EN), and use the proper cable appropriate for its
installation environment.
Recommended Cable Thickness
Terminal Sleeve Cable nominal cross sectional area (mm2)
Unused
Pressure clamp terminal
Used 0.5 to 2.5 (AWG 20 to 14)
Unused
Spring clamp terminal
Used 0.5 to 1.5 (AWG 20 to 16)

Cable Termination Process


• Without a Sleeve
Cable nominal cross
Terminal Peel-off length (mm)
sectional area (mm2)
Pressure clamp terminal 0.5 to 2.5 (AWG 20 to 14) 8
Spring clamp terminal 0.5 to 2.5 (AWG 20 to 14) 7

• With a Sleeve
If a sleeve is used, terminate the cable according to the instructions of the sleeve manufacturer.
It is recommended to use any one of the following sleeves.
Sleeve without insulating cover (DIN 46 228/1)
Sleeve with insulating cover (DIN 46 228/4)
The following shows an example of a Weidmuller sleeve.

Cable nominal When using a sleeve with insulating cover When using a sleeve (without insulating cover)
cross sectional Peel-off Sleeve dimensions Sleeve dimensions
area Weidmuller Peel-off length Weidmuller
length Total length Contact section Total length
(mm2) model No. (mm) model No.
(mm) (mm) length (mm) (mm)
0.5 10 14 8 H0.5/14 6 6 H0.5/6
0.75 10 14 8 H0.75/14 6 6 H0.75/6
1.0 10 14 8 H1/14 6 6 H1/6
1.5 10 14 8 H1.5/14 7 7 H1.5/7
2.5 11 14 8 H2.5/14D 7 7 H2.5/7

l Field wiring to base plate relaying terminal board

Dedicated cable (AKB331 or AKB651)

Base plate (S2BN1D)


Terminal board for analog
digital I/O (A2BM4)

Field cable F07E.ai


Figure Field wiring to base plate relaying terminal board

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 3
Applicable cables
An appropriate cable that matches the installation environment must be used by referring to the TI “ProSafe-RS
installation guidance” (TI 32P01J10-01EN).
Dedicated cable
AKB331 or AKB651
Recommended Cable Thickness
Terminal Sleeve Cable nominal cross sectional area (mm2)
Not used
Pressure clamp terminal 0.5 to 2.5 (AWG 20 to 14)
Used

Cable termination processing


• Without a sleeve
Cable nominal cross
Terminal Peel-off length (mm)
sectional area (mm2)
Pressure clamp terminal 0.5 to 2.5 (AWG 20 to 14) 8

• With a sleeve
When using a sleeve, a cable must have terminal processing in accordance with the instructions of the
sleevemanufacturer. Use one of the following sleeves is recommended.
Sleeve without insulating cover (DIN 46 228/1) Sleeve with insulating cover (DIN 46 228/4)
The table below shows examples of Weidmuller sleeves.

Cable nominal When using a sleeve with insulating cover When using a sleeve (without insulating cover)
cross sectional Peel-off Sleeve dimensions Sleeve dimensions
area Weidmuller Peel-off length Weidmuller
length Total length Contact section Total length
(mm2) model No. (mm) model No.
(mm) (mm) length (mm) (mm)
0.5 10 14 8 H0.5/14 6 6 H0.5/6
0.75 10 14 8 H0.75/14 6 6 H0.75/6
1.0 10 14 8 H1/14 6 6 H1/6
1.5 10 14 8 H1.5/14 7 7 H1.5/7
2.5 11 14 8 H2.5/14D 7 7 H2.5/7

 TERMINAL CONNECTION SPECIFICATIONS


l S2BN1D

Terminal number Signal type


A Analog Digital I/O (AI_/AO_/DI_/DO_)
B Common (COM)
: Channel number

l A2BM4

Terminal number Signal type


A Analog Digital I/O (AI_/AO_/DI_/DO_)
B Common (COM)
C Field power supply (F24V) or unused (*1)
: Channel number
*1: Terminal-C is used as field power supply (F24 V) in case of analog input function (3-wire). In other cases, terminal-C is
unused.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 4
 TERMINAL ARRANGEMENT
l S2BN1D
For the Base Plate with disconnecting terminal (S2BN1D), select either the pressure clamp terminal, spring clamp
terminal, or cable connector to connect the field wiring. For the pressure clamp terminal and the spring clamp terminal,
connect the field wiring directly to the terminal. For a cable connector, connect the field wiring through the analog
digital I/O terminal board (A2BM4). The following figures show the terminal arrangement.

Pressure clamp Spring clamp


terminals Terminal terminals Terminal
for 16 channels numbers for 16 channels numbers
1A 1A
1B 1B
2A 2A
2B 2B
3A 3A
3B 3B
4A 4A
4B 4B

5A 5A
5B 5B
6A 6A
6B 6B
7A 7A
7B 7B
8A 8A
8B 8B

9A 9A
9B 9B
10A 10A
10B 10B
11A 11A
11B 11B
12A 12A
12B 12B

13A 13A
13B 13B
14A 14A
14B 14B
15A 15A
15B 15B
16A 16A
16B 16B

F01E.ai

l A2BM4

1A 2A 3A 4A 5A 6A 7A 8A 9A 10A 11A 12A 13A 14A 15A 16A


Terminal
numbers 1B 2B 3B 4B 5B 6B 7B 8B 9B 10B 11B 12B 13B 14B 15B 16B
1C 2C 3C 4C 5C 6C 7C 8C 9C 10C 11C 12C 13C 14C 15C 16C A2BM4

I/O channels CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16

Pressure clamp
terminals
for 16 channels

F08E.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 5
 CIRCUIT DIAGRAMS
 S2BN1D-1, -2
Analog input function (2-wire)
Base Plate I/O Module

A AI_

Current
Transmitter →AI

B COM

: Channel number
F02E.ai

Analog input function (4-wire)


Base Plate I/O Module

A AI_

Current

Transmitter →AI

B COM

: Channel number
F03E.ai

Analog output function


Base Plate I/O Module

A AO_
Current
←AO
Load

B COM

: Channel number
F04E.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 6
Digital input function
Base Plate I/O Module

A DI_
Current
→DI

B COM

: Channel number
F05E.ai

Digital output function


Base Plate I/O Module

EP+ F24V

Load A DO_ ←DO

Current
24 V DC

B

EP- COM

: Channel number
F06E.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 7
 S2BN1D-9
Analog input function (2-wire)
Dedicated cable
and
terminal board Base Plate I/O Module

A AI_

Current
Transmitter →AI

B COM

C

: Channel number
F09E.ai

Analog input function (3-wire)


Dedicated cable
and
terminal board EP+ Base Plate I/O Module
C F24V

A AI_

Current 24 V DC
Transmitter →AI

B COM

: Channel number EP-


F10E.ai

Analog input function (4-wire)


Dedicated cable
and
terminal board Base Plate I/O Module

A AI_

Current
Transmitter →AI

B COM

C

: Channel number
F11E.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 8
Analog output function

Dedicated cable
and
terminal board Base Plate I/O Module

A AO_
Current
←AO
Load

B COM

C

: Channel number
F12E.ai

Digital input function


Dedicated cable
and
terminal board Base Plate I/O Module

A DI_
Current
→DI

B COM

C

: Channel number F13E.ai

Digital output function

Dedicated cable
and
terminal board EP+ Base Plate I/O Module

F24V

Load A DO_ ←DO

Current
24 V DC

B

COM
C

EP-

: Channel number
F14E.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 9
 TRADEMARKS
• ProSafe, CENTUM, PRM, STARDOM, FAST/TOOLS, Exaopc, FieldMate, and Vnet/IP are either registered
trademarks or trademarks of Yokogawa Electric Corporation.
• Other company and product names appearing in this document are registered trademarks or trademarks of their
respective holders.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P06K10-01EN Oct. 5, 2018-00
Subject to change without notice.