COOLING LOAD COMPONENTS PEOPLE

2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06


21-Sep-17
COOLING LOAD - PER PERSON

INPUT DATA: People Load


300

250 Btuh/person sensible 250


40% % Convective
200
60% % Radiant

Btu/h
150
200 Btuh/person latent
100

50

-
8 RTS Zone Type 1 3 5 7 9 11 13 15 17 19 21 23
MW w
Heat Gain Hour
Sensible Cooling Load
Carpet
50% glass
Non-Solar Total Latent
Input Heat Gain RTS Radiant Sensible Cooling
Usage Convective % Radiant % Zone Type Cooling Cooling Load
Hour Profile Heat Gain 40% 60% 8 Load Load Btuh/
Btuh/person Btuh/pers person
1 0% - - - 49% 18 18 -
2 0% - - - 17% 18 18 -
3 0% - - - 9% 17 17 -
4 0% - - - 5% 15 15 -
5 0% - - - 3% 14 14 -
6 0% - - - 2% 12 12 -
7 100% 250 100 150 2% 84 184 200
8 100% 250 100 150 1% 108 208 200
9 100% 250 100 150 1% 120 220 200
10 100% 250 100 150 1% 126 226 200
11 100% 250 100 150 1% 129 229 200
12 100% 250 100 150 1% 131 231 200
13 100% 250 100 150 1% 132 232 200
14 100% 250 100 150 1% 132 232 200
15 100% 250 100 150 1% 134 234 200
16 100% 250 100 150 1% 135 235 200
17 100% 250 100 150 1% 137 237 200
18 100% 250 100 150 1% 138 238 200
19 0% - - - 1% 66 66 -
20 0% - - - 1% 42 42 -
21 0% - - - 0% 30 30 -
22 0% - - - 0% 24 24 -
23 0% - - - 0% 21 21 -
24 0% - - - 0% 20 20 -

3,000 1,200 1,800 100% 1,800 3,000


COOLING LOAD COMPONENTS
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06
This spreadsheet was prepared in conjunction with development of
the ASHRAE Example Building for Chapter 30, Nonresidential
Cooling and Heating Load Calculations, of the 2005 ASHRAE
Handbook—Fundamentals (sometimes abbreviated as “2005F”). It
has been updated with new procedures defined in the 2009, 2013
and 2017 Handbooks (the chapter has been renumbered as Chapter
18 in the new volume).

This spreadsheet’s purpose is to demonstrate the calculation


techniques described in that chapter for internal and external cooling
load components using the radiant time series (RTS) method.

Worksheets are included for Design Weather Profile generation


based on monthly design data provided in the 2017 Fundamentals
volume. The location and design basis (0.4%, 2%, 5% or 10%) is
selected via a dropdown box. A 24 h profile for outdoor dry
bulb/humidity is generated for each month and the sensible and
latent cooling load to condition a unit of outside air infiltration flow
rate (one cfm or one L/s) to room conditions is calculated.

Worksheets are included for internal heat gain components (people,


lights, and equipment) to calculate cooling loads based on usage
schedules and the room construction mass as approximated by RTS.

Worksheets are included for external heat gain components (wall,


roof, and window) based on the Design Weather Profile generated in
that worksheet. The wall and roof worksheets include dropdown
boxes for selection of the most similar construction from Chapter 18
tables. Those determine conduction time series (CTS) profiles use
to approximate the time delay of heat gain from external to internal
surfaces of massive elements.

The worksheets for internal and external components can be


RTS COOLING LOAD CALCULATIONS REVISION NOTES September 21, 2017
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 Page: 1

These spreadsheets were prepared by TC 4.1 volunteers as examples of load calculations


for use with the 2005 Fundamentals volume of the ASHRAE Handbook. They have been
updated with data and procedure changes included in the 2017 Handbook.
If you would like notice of future revisions/corrections or have questions, send an email to:
mowen@ashrae.org

Changes Made in 2005 July 2 Revision


1 Updated comments to 2005 ASHRAE Handbook references.
2 Deleted weather stations missing wet bulb data.
3 Corrected solar altitude calculation for noon - previously returned wrong sign.
4 Corrected overhang shading calculation surface-solar azimuth for angles >270 or <-270
- previously considered fully shaded when should have been sunlit
- primarily affected north elevations at early morning solar angles in summer
5 Negative outside air latent load (due to very dry climates) zeroed out
- previously added latent to sensible to determine total cooling
- when outside humidity below room design conditions, incorrectly reduced total cooling
6 Eliminated rounding of calculated sol-air temperatures to improve accuracy
7 Modified SHGC data to two significant digits to match printed data in Handbook

Changes Made in 2009 May 25 Revision


1 Updated comments to 2009 ASHRAE Handbook references.
2 Updated weather data to 2009 HoF data, including worldwide sites, not just USA-CAN
3 Updated weather profile to 2009 HoF procedures, including new wet bulb procedures
4 Updated clear sky solar radiation model to new 2009 HoF model
5 Updated indoor shading procedure for 2009 HoF model
6 Updated radiant/convective fractions in examples to data from 2009 HoF

Changes Made in 2013 Oct 21 Revision


1 Updated comments to 2013 ASHRAE Handbook references.
2 Updated weather data to 2013 HoF data
3 Updated clear sky solar radiation model to new 2013 HoF model
4 Updated examples to renovated ASHRAE HQ as included in 2013 HoF

Changes Made in 2015-09-24 Revision


1 Corrected cell range error in weather data which caused incorrect weather data
selection for countries alphabetically past Russia - Objacevo site.

Changes Made in 2017 April 06 Revision


1 Updated weather data to 2017 HoF data
2 Updated CTS data to 2017 HoF data
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75

Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236

Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554

WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85

DRY BULB/WET BULB TEMPERATURE PROFILES AND HUMIDITY RATIOS


MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
DB 1 45.8 47.5 53.7 59.8 66.9 72.1 73.8 73.7 69.6 60.2 51.9 47.4
WB 1 45.2 45.2 49.4 55.0 62.2 66.7 68.9 68.9 64.7 56.9 50.3 47.4
WBR 1 504.87 504.87 509.07 514.67 521.87 526.37 528.57 528.57 524.37 516.57 509.97 507.07
PWS 1 0.148680 0.148680 0.174167 0.214101 0.277140 0.324333 0.349864 0.349864 0.302554 0.229371 0.180104 0.161586
WST 1 0.006357 0.006357 0.007460 0.009195 0.011955 0.014037 0.015168 0.015168 0.013074 0.009862 0.007717 0.006915
W 1 0.006221 0.005834 0.006480 0.008095 0.010868 0.012780 0.014025 0.014048 0.011937 0.009103 0.007352 0.006915

DB 2 45.1 46.7 52.8 59.0 66.1 71.3 73.0 73.0 68.8 59.4 51.1 46.7
WB 2 44.7 44.7 49.0 54.7 61.9 66.4 68.7 68.7 64.4 56.5 49.8 46.7
WBR 2 504.37 504.37 508.67 514.37 521.57 526.07 528.37 528.37 524.07 516.17 509.47 506.37
PWS 2 0.145877 0.145877 0.171584 0.211773 0.274220 0.320981 0.347473 0.347473 0.299400 0.226079 0.176784 0.157377
WST 2 0.006236 0.006236 0.007348 0.009094 0.011826 0.013888 0.015062 0.015062 0.012935 0.009718 0.007573 0.006733
W 2 0.006145 0.005782 0.006482 0.008108 0.010855 0.012748 0.014058 0.014058 0.011914 0.009051 0.007276 0.006733

DB 3 44.5 46.0 52.1 58.3 65.5 70.7 72.4 72.4 68.3 58.8 50.4 46.1
WB 3 44.3 44.3 48.7 54.4 61.7 66.2 68.5 68.5 64.2 56.2 49.5 46.1
WBR 3 503.97 503.97 508.37 514.07 521.37 525.87 528.17 528.17 523.87 515.87 509.17 505.77
PWS 3 0.143668 0.143668 0.169669 0.209468 0.272288 0.318763 0.345096 0.345096 0.297314 0.223637 0.174818 0.153846
WST 3 0.006141 0.006141 0.007265 0.008994 0.011742 0.013790 0.014957 0.014957 0.012843 0.009611 0.007488 0.006580
W 3 0.006095 0.005755 0.006490 0.008100 0.010863 0.012744 0.014046 0.014046 0.011892 0.009014 0.007282 0.006580

DB 4 43.9 45.4 51.5 57.6 64.9 70.1 71.8 71.8 67.7 58.2 49.8 45.5
WB 4 43.9 43.9 48.3 54.1 61.5 66.0 68.3 68.3 64.0 56.0 49.1 45.5
WBR 4 503.57 503.57 507.97 513.77 521.17 525.67 527.97 527.97 523.67 515.67 508.77 505.17
PWS 4 0.141489 0.141489 0.167145 0.207185 0.270368 0.316559 0.342733 0.342733 0.295240 0.222022 0.172226 0.150385
WST 4 0.006046 0.006046 0.007155 0.008894 0.011657 0.013693 0.014852 0.014852 0.012752 0.009541 0.007376 0.006431
W 4 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431

DB 5 43.5 45.0 51.0 57.2 64.5 69.7 71.4 71.4 67.3 57.8 49.4 45.1
WB 5 43.5 43.6 48.1 53.9 61.3 65.9 68.2 68.2 63.9 55.8 48.9 45.1
WBR 5 503.17 503.27 507.77 513.57 520.97 525.57 527.87 527.87 523.57 515.47 508.57 504.77
PWS 5 0.139339 0.139874 0.165895 0.205675 0.268460 0.315462 0.341556 0.341556 0.294208 0.220418 0.170943 0.148116
WST 5 0.005954 0.005977 0.007101 0.008828 0.011573 0.013644 0.014800 0.014800 0.012706 0.009471 0.007320 0.006333
W 5 0.005954 0.005659 0.006441 0.008072 0.010834 0.012760 0.014053 0.014053 0.011917 0.009011 0.007206 0.006333

DB 6 43.9 45.4 51.5 57.6 64.9 70.1 71.8 71.8 67.7 58.2 49.8 45.5
WB 6 43.9 43.9 48.3 54.1 61.5 66.0 68.3 68.3 64.0 56.0 49.1 45.5
WBR 6 503.57 503.57 507.97 513.77 521.17 525.67 527.97 527.97 523.67 515.67 508.77 505.17
PWS 6 0.141489 0.141489 0.167145 0.207185 0.270368 0.316559 0.342733 0.342733 0.295240 0.222022 0.172226 0.150385
WST 6 0.006046 0.006046 0.007155 0.008894 0.011657 0.013693 0.014852 0.014852 0.012752 0.009541 0.007376 0.006431
W 6 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431

DB 7 45.3 46.9 53.0 59.2 66.3 71.5 73.2 73.2 69.0 59.6 51.3 46.9
WB 7 44.8 44.8 49.1 54.8 62.0 66.5 68.7 68.7 64.5 56.6 50.0 46.9
WBR 7 504.47 504.47 508.77 514.47 521.67 526.17 528.37 528.37 524.17 516.27 509.67 506.57
PWS 7 0.146434 0.146434 0.172226 0.212547 0.275190 0.322095 0.347473 0.347473 0.300448 0.226898 0.178106 0.158569
WST 7 0.006260 0.006260 0.007376 0.009128 0.011869 0.013938 0.015062 0.015062 0.012981 0.009754 0.007630 0.006784
W 7 0.006146 0.005783 0.006487 0.008119 0.010875 0.012774 0.014012 0.014012 0.011937 0.009064 0.007334 0.006784
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75

Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236

Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554

WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85

DB 8 48.6 50.4 56.9 62.9 69.7 74.9 76.7 76.5 72.3 63.1 54.8 50.2
WB 8 47.1 47.1 51.0 56.4 63.3 67.6 69.8 69.8 65.7 58.1 51.9 49.2
WBR 8 506.77 506.77 510.67 516.07 522.97 527.27 529.47 529.47 525.37 517.77 511.57 508.87
PWS 8 0.159770 0.159770 0.184845 0.225262 0.288081 0.334573 0.360805 0.360805 0.313278 0.239501 0.191101 0.172871
WST 8 0.006836 0.006836 0.007923 0.009682 0.012436 0.014490 0.015655 0.015655 0.013548 0.010304 0.008195 0.007404
W 8 0.006495 0.006086 0.006577 0.008191 0.010955 0.012791 0.014043 0.014090 0.012015 0.009154 0.007531 0.007175

DB 9 52.3 54.4 61.1 67.1 73.5 78.7 80.5 80.2 75.9 67.0 58.8 53.9
WB 9 49.7 49.6 53.1 58.2 64.7 68.9 70.9 70.9 67.0 59.8 54.2 51.7
WBR 9 509.37 509.27 512.77 517.87 524.37 528.57 530.57 530.57 526.67 519.47 513.87 511.37
PWS 9 0.176127 0.175471 0.199732 0.240362 0.302554 0.349864 0.374583 0.374583 0.327715 0.254524 0.207944 0.189695
WST 9 0.007545 0.007516 0.008570 0.010342 0.013074 0.015168 0.016268 0.016268 0.014186 0.010962 0.008927 0.008133
W 9 0.006951 0.006422 0.006742 0.008297 0.011035 0.012885 0.014025 0.014094 0.012118 0.009303 0.007873 0.007630

DB 10 55.6 58.0 65.0 70.8 77.0 82.2 83.9 83.5 79.1 70.4 62.4 57.2
WB 10 52.0 51.8 54.9 59.8 66.0 70.0 72.0 71.9 68.1 61.3 56.2 54.0
WBR 10 511.67 511.47 514.57 519.47 525.67 529.67 531.67 531.57 527.77 520.97 515.87 513.67
PWS 10 0.191807 0.190397 0.213322 0.254524 0.316559 0.363277 0.388819 0.387506 0.340384 0.268460 0.223637 0.206429
WST 10 0.008225 0.008164 0.009161 0.010962 0.013693 0.015765 0.016903 0.016845 0.014748 0.011573 0.009611 0.008861
W 10 0.007402 0.006748 0.006851 0.008432 0.011142 0.012921 0.014120 0.014132 0.012189 0.009475 0.008189 0.008128

DB 11 58.5 61.1 68.3 74.1 80.0 85.2 87.0 86.4 82.0 73.5 65.5 60.1
WB 11 54.1 53.8 56.6 61.2 67.1 71.0 72.9 72.8 69.1 62.7 57.9 56.0
WBR 11 513.77 513.47 516.27 520.87 526.77 530.67 532.57 532.47 528.77 522.37 517.57 515.67
PWS 11 0.207185 0.204924 0.226898 0.267511 0.328850 0.375859 0.400816 0.399467 0.352270 0.282067 0.237786 0.222022
WST 11 0.008894 0.008796 0.009754 0.011532 0.014237 0.016325 0.017439 0.017379 0.015275 0.012172 0.010229 0.009541
W 11 0.007886 0.007126 0.007074 0.008562 0.011243 0.013012 0.014140 0.014197 0.012273 0.009678 0.008483 0.008599

DB 12 60.5 63.2 70.6 76.3 82.0 87.2 89.0 88.4 83.9 75.5 67.6 62.1
WB 12 55.4 55.2 57.7 62.2 67.8 71.6 73.5 73.4 69.8 63.5 59.1 57.3
WBR 12 515.07 514.87 517.37 521.87 527.47 531.27 533.17 533.07 529.47 523.17 518.77 516.97
PWS 12 0.217239 0.215665 0.236081 0.277140 0.336887 0.383589 0.408993 0.407620 0.360805 0.290111 0.248241 0.232705
WST 12 0.009332 0.009264 0.010155 0.011955 0.014593 0.016670 0.017805 0.017744 0.015655 0.012526 0.010687 0.010007
W 12 0.008162 0.007431 0.007198 0.008706 0.011296 0.013029 0.014177 0.014232 0.012371 0.009754 0.008731 0.008904

DB 13 62.0 64.9 72.4 78.1 83.6 88.8 90.6 89.9 85.4 77.2 69.3 63.6
WB 13 56.5 56.2 58.6 62.9 68.4 72.2 74.0 73.9 70.4 64.3 60.0 58.3
WBR 13 516.17 515.87 518.27 522.57 528.07 531.87 533.67 533.57 530.07 523.97 519.67 517.97
PWS 13 0.226079 0.223637 0.243836 0.284060 0.343912 0.391458 0.415917 0.414524 0.368265 0.298355 0.256345 0.241227
WST 13 0.009718 0.009611 0.010494 0.012259 0.014904 0.017021 0.018116 0.018053 0.015987 0.012889 0.011042 0.010380
W 13 0.008455 0.007617 0.007328 0.008755 0.011374 0.013145 0.014228 0.014306 0.012492 0.009907 0.008901 0.009160

DB 14 63.0 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
WB 14 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59.0
WBR 14 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS 14 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST 14 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W 14 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358

DB 15 63.0 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
WB 15 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59.0
WBR 15 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75

Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236

Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554

WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85

PWS 15 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST 15 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W 15 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358

DB 16 61.8 64.6 72.2 77.9 83.4 88.6 90.4 89.7 85.3 77.0 69.0 63.4
WB 16 56.4 56.1 58.4 62.8 68.4 72.1 73.9 73.8 70.3 64.2 59.9 58.2
WBR 16 516.07 515.77 518.07 522.47 528.07 531.77 533.57 533.47 529.97 523.87 519.57 517.87
PWS 16 0.225262 0.222828 0.242094 0.283062 0.343912 0.390137 0.414524 0.413135 0.367012 0.297314 0.255433 0.240362
WST 16 0.009682 0.009576 0.010418 0.012215 0.014904 0.016962 0.018053 0.017991 0.015931 0.012843 0.011002 0.010342
W 16 0.008442 0.007628 0.007253 0.008735 0.011420 0.013110 0.014190 0.014268 0.012437 0.009884 0.008907 0.009145

DB 17 60.3 63.0 70.4 76.1 81.8 87.0 88.8 88.2 83.7 75.3 67.4 61.9
WB 17 55.3 55.0 57.6 62.1 67.8 71.6 73.4 73.4 69.7 63.5 59.0 57.2
WBR 17 514.97 514.67 517.27 521.77 527.47 531.27 533.07 533.07 529.37 523.17 518.67 516.87
PWS 17 0.216451 0.214101 0.235233 0.276163 0.336887 0.383589 0.407620 0.407620 0.359575 0.290111 0.247354 0.231867
WST 17 0.009298 0.009195 0.010118 0.011912 0.014593 0.016670 0.017744 0.017744 0.015600 0.012526 0.010648 0.009971
W 17 0.008151 0.007364 0.007184 0.008687 0.011342 0.013076 0.014139 0.014279 0.012340 0.009800 0.008716 0.008890

DB 18 58.3 60.9 68.1 73.9 79.8 85.0 86.8 86.2 81.8 73.3 65.3 59.9
WB 18 53.9 53.7 56.5 61.1 67.0 70.9 72.8 72.8 69.1 62.6 57.8 55.8
WBR 18 513.57 513.37 516.17 520.77 526.67 530.57 532.47 532.47 528.77 522.27 517.47 515.47
PWS 18 0.205675 0.204175 0.226079 0.266564 0.327715 0.374583 0.399467 0.399467 0.352270 0.281076 0.236932 0.220418
WST 18 0.008828 0.008763 0.009718 0.011490 0.014186 0.016268 0.017379 0.017379 0.015275 0.012128 0.010192 0.009471
W 18 0.007821 0.007116 0.007061 0.008544 0.011216 0.012979 0.014103 0.014243 0.012319 0.009658 0.008469 0.008530

DB 19 55.4 57.7 64.7 70.6 76.8 82.0 83.7 83.3 79.0 70.2 62.1 57.0
WB 19 51.9 51.7 54.8 59.7 65.9 69.9 71.9 71.9 68.0 61.2 56.0 53.9
WBR 19 511.57 511.37 514.47 519.37 525.57 529.57 531.57 531.57 527.67 520.87 515.67 513.57
PWS 19 0.191101 0.189695 0.212547 0.253618 0.315462 0.362039 0.387506 0.387506 0.339215 0.267511 0.222022 0.205675
WST 19 0.008195 0.008133 0.009128 0.010922 0.013644 0.015710 0.016845 0.016845 0.014696 0.011532 0.009541 0.008828
W 19 0.007394 0.006763 0.006863 0.008416 0.011117 0.012889 0.014085 0.014178 0.012138 0.009456 0.008141 0.008118

DB 20 53.3 55.5 62.3 68.2 74.6 79.8 81.5 81.2 76.9 68.0 59.9 54.9
WB 20 50.4 50.3 53.6 58.7 65.1 69.2 71.3 71.2 67.3 60.3 54.8 52.4
WBR 20 510.07 509.97 513.27 518.37 524.77 528.87 530.97 530.87 526.97 519.97 514.47 512.07
PWS 20 0.180775 0.180104 0.203429 0.244712 0.306804 0.353479 0.379706 0.378420 0.331129 0.259097 0.212547 0.194656
WST 20 0.007746 0.007717 0.008731 0.010532 0.013262 0.015329 0.016497 0.016439 0.014337 0.011163 0.009128 0.008349
W 20 0.007084 0.006531 0.006742 0.008349 0.011060 0.012859 0.014112 0.014101 0.012106 0.009388 0.007959 0.007777

DB 21 51.5 53.6 60.2 66.2 72.7 77.9 79.7 79.4 75.1 66.2 58.0 53.1
WB 21 49.2 49.1 52.6 57.8 64.4 68.6 70.7 70.7 66.7 59.4 53.7 51.2
WBR 21 508.87 508.77 512.27 517.47 524.07 528.27 530.37 530.37 526.37 519.07 513.37 510.87
PWS 21 0.172871 0.172226 0.196095 0.236932 0.299400 0.346282 0.372045 0.372045 0.324333 0.250917 0.204175 0.186219
WST 21 0.007404 0.007376 0.008412 0.010192 0.012935 0.015009 0.016155 0.016155 0.014037 0.010804 0.008763 0.007983
W 21 0.006879 0.006350 0.006676 0.008263 0.011012 0.012843 0.014052 0.014122 0.012085 0.009238 0.007778 0.007548

DB 22 49.7 51.7 58.2 64.2 70.9 76.1 77.9 77.6 73.4 64.3 56.1 51.3
WB 22 48.0 47.9 51.6 56.9 63.7 68.0 70.2 70.1 66.1 58.6 52.6 50.0
WBR 22 507.67 507.57 511.27 516.57 523.37 527.67 529.87 529.77 525.77 518.27 512.27 509.67
PWS 22 0.165274 0.164654 0.188995 0.229371 0.292153 0.339215 0.365763 0.364518 0.317659 0.243836 0.196095 0.178106
WST 22 0.007074 0.007048 0.008103 0.009862 0.012616 0.014696 0.015875 0.015820 0.013741 0.010494 0.008412 0.007630
W 22 0.006687 0.006183 0.006597 0.008186 0.010949 0.012810 0.014076 0.014068 0.012046 0.009182 0.007611 0.007334
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75

Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236

Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554

WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85

DB 23 48.4 50.2 56.6 62.7 69.5 74.7 76.5 76.3 72.1 62.9 54.6 50.0
WB 23 47.0 46.9 50.9 56.3 63.2 67.6 69.7 69.7 65.6 58.0 51.8 49.1
WBR 23 506.67 506.57 510.57 515.97 522.87 527.27 529.37 529.37 525.27 517.67 511.47 508.77
PWS 23 0.159169 0.158569 0.184161 0.224448 0.287071 0.334573 0.359575 0.359575 0.312190 0.238642 0.190397 0.172226
WST 23 0.006810 0.006784 0.007893 0.009647 0.012392 0.014490 0.015600 0.015600 0.013500 0.010267 0.008164 0.007376
W 23 0.006492 0.006034 0.006593 0.008178 0.010934 0.012837 0.014012 0.014058 0.011990 0.009139 0.007524 0.007170

DB 24 47.0 48.8 55.1 61.2 68.1 73.3 75.0 74.9 70.7 61.5 53.2 48.6
WB 24 46.0 46.0 50.1 55.6 62.7 67.1 69.3 69.3 65.1 57.4 51.0 48.2
WBR 24 505.67 505.67 509.77 515.27 522.37 526.77 528.97 528.97 524.77 517.07 510.67 507.87
PWS 24 0.153264 0.153264 0.178770 0.218823 0.282067 0.328850 0.354691 0.354691 0.306804 0.233545 0.184845 0.166519
WST 24 0.006555 0.006555 0.007659 0.009401 0.012172 0.014237 0.015383 0.015383 0.013262 0.010044 0.007923 0.007128
W 24 0.006327 0.005919 0.006519 0.008117 0.010922 0.012794 0.014052 0.014075 0.011962 0.009101 0.007420 0.007037

HUMIDITY RATIOS
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 0.006221 0.005834 0.006480 0.008095 0.010868 0.012780 0.014025 0.014048 0.011937 0.009103 0.007352 0.006915
2 0.006145 0.005782 0.006482 0.008108 0.010855 0.012748 0.014058 0.014058 0.011914 0.009051 0.007276 0.006733
3 0.006095 0.005755 0.006490 0.008100 0.010863 0.012744 0.014046 0.014046 0.011892 0.009014 0.007282 0.006580
4 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
5 0.005954 0.005659 0.006441 0.008072 0.010834 0.012760 0.014053 0.014053 0.011917 0.009011 0.007206 0.006333
6 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
7 0.006146 0.005783 0.006487 0.008119 0.010875 0.012774 0.014012 0.014012 0.011937 0.009064 0.007334 0.006784
8 0.006495 0.006086 0.006577 0.008191 0.010955 0.012791 0.014043 0.014090 0.012015 0.009154 0.007531 0.007175
9 0.006951 0.006422 0.006742 0.008297 0.011035 0.012885 0.014025 0.014094 0.012118 0.009303 0.007873 0.007630
10 0.007402 0.006748 0.006851 0.008432 0.011142 0.012921 0.014120 0.014132 0.012189 0.009475 0.008189 0.008128
11 0.007886 0.007126 0.007074 0.008562 0.011243 0.013012 0.014140 0.014197 0.012273 0.009678 0.008483 0.008599
12 0.008162 0.007431 0.007198 0.008706 0.011296 0.013029 0.014177 0.014232 0.012371 0.009754 0.008731 0.008904
13 0.008455 0.007617 0.007328 0.008755 0.011374 0.013145 0.014228 0.014306 0.012492 0.009907 0.008901 0.009160
14 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
15 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
16 0.008442 0.007628 0.007253 0.008735 0.011420 0.013110 0.014190 0.014268 0.012437 0.009884 0.008907 0.009145
17 0.008151 0.007364 0.007184 0.008687 0.011342 0.013076 0.014139 0.014279 0.012340 0.009800 0.008716 0.008890
18 0.007821 0.007116 0.007061 0.008544 0.011216 0.012979 0.014103 0.014243 0.012319 0.009658 0.008469 0.008530
19 0.007394 0.006763 0.006863 0.008416 0.011117 0.012889 0.014085 0.014178 0.012138 0.009456 0.008141 0.008118
20 0.007084 0.006531 0.006742 0.008349 0.011060 0.012859 0.014112 0.014101 0.012106 0.009388 0.007959 0.007777
21 0.006879 0.006350 0.006676 0.008263 0.011012 0.012843 0.014052 0.014122 0.012085 0.009238 0.007778 0.007548
22 0.006687 0.006183 0.006597 0.008186 0.010949 0.012810 0.014076 0.014068 0.012046 0.009182 0.007611 0.007334
23 0.006492 0.006034 0.006593 0.008178 0.010934 0.012837 0.014012 0.014058 0.011990 0.009139 0.007524 0.007170
24 0.006327 0.005919 0.006519 0.008117 0.010922 0.012794 0.014052 0.014075 0.011962 0.009101 0.007420 0.007037
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75

Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236

Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554

WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85

OUTSIDE AIR AND INFILTRATION SENSIBLE COOLING LOAD - BTUH PER CFM
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 -32.12 -30.25 -23.43 -16.72 -8.91 -3.19 -1.32 -1.43 -5.94 -16.28 -25.41 -30.36
2 -32.89 -31.13 -24.42 -17.60 -9.79 -4.07 -2.20 -2.20 -6.82 -17.16 -26.29 -31.13
3 -33.55 -31.90 -25.19 -18.37 -10.45 -4.73 -2.86 -2.86 -7.37 -17.82 -27.06 -31.79
4 -34.21 -32.56 -25.85 -19.14 -11.11 -5.39 -3.52 -3.52 -8.03 -18.48 -27.72 -32.45
5 -34.65 -33.00 -26.40 -19.58 -11.55 -5.83 -3.96 -3.96 -8.47 -18.92 -28.16 -32.89
6 -34.21 -32.56 -25.85 -19.14 -11.11 -5.39 -3.52 -3.52 -8.03 -18.48 -27.72 -32.45
7 -32.67 -30.91 -24.20 -17.38 -9.57 -3.85 -1.98 -1.98 -6.60 -16.94 -26.07 -30.91
8 -29.04 -27.06 -19.91 -13.31 -5.83 -0.11 1.87 1.65 -2.97 -13.09 -22.22 -27.28
9 -24.97 -22.66 -15.29 -8.69 -1.65 4.07 6.05 5.72 0.99 -8.80 -17.82 -23.21
10 -21.34 -18.70 -11.00 -4.62 2.20 7.92 9.79 9.35 4.51 -5.06 -13.86 -19.58
11 -18.15 -15.29 -7.37 -0.99 5.50 11.22 13.20 12.54 7.70 -1.65 -10.45 -16.39
12 -15.95 -12.98 -4.84 1.43 7.70 13.42 15.40 14.74 9.79 0.55 -8.14 -14.19
13 -14.30 -11.11 -2.86 3.41 9.46 15.18 17.16 16.39 11.44 2.42 -6.27 -12.54
14 -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
15 -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
16 -14.52 -11.44 -3.08 3.19 9.24 14.96 16.94 16.17 11.33 2.20 -6.60 -12.76
17 -16.17 -13.20 -5.06 1.21 7.48 13.20 15.18 14.52 9.57 0.33 -8.36 -14.41
18 -18.37 -15.51 -7.59 -1.21 5.28 11.00 12.98 12.32 7.48 -1.87 -10.67 -16.61
19 -21.56 -19.03 -11.33 -4.84 1.98 7.70 9.57 9.13 4.40 -5.28 -14.19 -19.80
20 -23.87 -21.45 -13.97 -7.48 -0.44 5.28 7.15 6.82 2.09 -7.70 -16.61 -22.11
21 -25.85 -23.54 -16.28 -9.68 -2.53 3.19 5.17 4.84 0.11 -9.68 -18.70 -24.09
22 -27.83 -25.63 -18.48 -11.88 -4.51 1.21 3.19 2.86 -1.76 -11.77 -20.79 -26.07
23 -29.26 -27.28 -20.24 -13.53 -6.05 -0.33 1.65 1.43 -3.19 -13.31 -22.44 -27.50
24 -30.80 -28.82 -21.89 -15.18 -7.59 -1.87 0.00 -0.11 -4.73 -14.85 -23.98 -29.04

OUTSIDE AIR AND INFILTRATION LATENT COOLING LOAD - BTUH PER CFM
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 -14.60 -16.46 -13.34 -5.52 7.90 17.15 23.18 23.29 13.07 -0.65 -9.12 -11.24
2 -14.96 -16.72 -13.33 -5.46 7.84 17.00 23.34 23.34 12.96 -0.90 -9.49 -12.12
3 -15.20 -16.85 -13.29 -5.50 7.87 16.98 23.28 23.28 12.85 -1.08 -9.46 -12.86
4 -15.44 -17.09 -13.60 -5.54 7.91 16.95 23.23 23.23 12.86 -0.97 -9.78 -13.58
5 -15.89 -17.31 -13.53 -5.63 7.73 17.06 23.31 23.31 12.98 -1.09 -9.83 -14.05
6 -15.44 -17.09 -13.60 -5.54 7.91 16.95 23.23 23.23 12.86 -0.97 -9.78 -13.58
7 -14.96 -16.71 -13.31 -5.41 7.93 17.12 23.11 23.11 13.07 -0.83 -9.21 -11.87
8 -13.27 -15.25 -12.87 -5.06 8.32 17.20 23.27 23.49 13.45 -0.40 -8.25 -9.97
9 -11.06 -13.62 -12.07 -4.54 8.71 17.66 23.18 23.51 13.95 0.33 -6.60 -7.77
10 -8.88 -12.04 -11.54 -3.89 9.22 17.83 23.64 23.69 14.29 1.16 -5.07 -5.36
11 -6.53 -10.21 -10.47 -3.26 9.71 18.28 23.73 24.01 14.70 2.14 -3.65 -3.08
12 -5.20 -8.74 -9.87 -2.57 9.97 18.36 23.91 24.18 15.17 2.50 -2.44 -1.61
13 -3.78 -7.84 -9.23 -2.33 10.34 18.92 24.16 24.54 15.76 3.25 -1.62 -0.37
14 -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
15 -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
16 -3.84 -7.79 -9.60 -2.43 10.57 18.75 23.98 24.35 15.49 3.14 -1.59 -0.44
17 -5.25 -9.06 -9.93 -2.66 10.19 18.58 23.73 24.41 15.02 2.73 -2.52 -1.67
18 -6.85 -10.26 -10.53 -3.35 9.58 18.12 23.56 24.23 14.92 2.04 -3.71 -3.42
19 -8.91 -11.97 -11.49 -3.97 9.10 17.68 23.47 23.92 14.04 1.07 -5.30 -5.41
20 -10.42 -13.09 -12.07 -4.29 8.83 17.54 23.60 23.55 13.89 0.73 -6.18 -7.06
21 -11.41 -13.97 -12.39 -4.71 8.60 17.46 23.31 23.65 13.79 0.01 -7.06 -8.17
22 -12.34 -14.78 -12.78 -5.08 8.29 17.30 23.43 23.38 13.60 -0.26 -7.87 -9.21
23 -13.28 -15.50 -12.79 -5.12 8.22 17.43 23.11 23.34 13.33 -0.47 -8.29 -10.00
24 -14.08 -16.06 -13.15 -5.42 8.16 17.22 23.31 23.42 13.19 -0.65 -8.79 -10.64
Table 28 Cooling Load Component: Lighting, Btu/h
Non-Solar
RTS Total % Lighting Room
Heat Gain Zone Type Radiant Sensible to Sensible
Usage Convective % Radiant % 8 Cooling Cooling Return Cooling
Hour Profile Heat Gain 43% 57% % Load Load 0% Load

1 0% - - - 49% 26 26 - 26
2 0% - - - 17% 26 26 - 26
3 0% - - - 9% 24 24 - 24
4 0% - - - 5% 21 21 - 21
5 0% - - - 3% 19 19 - 19
6 0% - - - 2% 17 17 - 17
7 100% 375 161 214 2% 120 281 - 281
8 100% 375 161 214 1% 154 315 - 315
9 100% 375 161 214 1% 171 332 - 332
10 100% 375 161 214 1% 180 341 - 341
11 100% 375 161 214 1% 184 345 - 345
12 100% 375 161 214 1% 186 347 - 347
13 100% 375 161 214 1% 188 349 - 349
14 100% 375 161 214 1% 188 349 - 349
15 100% 375 161 214 1% 190 352 - 352
16 100% 375 161 214 1% 192 354 - 354
17 100% 375 161 214 1% 195 356 - 356
18 100% 375 161 214 1% 197 358 - 358
19 0% - - - 1% 94 94 - 94
20 0% - - - 1% 60 60 - 60
21 0% - - - 0% 43 43 - 43
22 0% - - - 0% 34 34 - 34
23 0% - - - 0% 30 30 - 30
24 0% - - - 0% 28 28 - 28
COOLING LOAD COMPONENTS EQUIPMENT
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06
21-Sep-17
COOLING LOAD - PER EQUIPMENT PEAK WATT

INPUT DATA: 4 Equipment Load


1.00 watt peak equipment 3.5
3.41 btu/h sensible peak gain 3
2.5

Btu/h
70% % Convective 2
30% % Radiant 1.5
1
0.5

8 RTS Zone Type 0


1 3 5 7 9 11 13 15 17 19 21 23 25
MW w
Carpet Hour
50% glass
Heat Gain Sensible Cooling Load

Non-Solar Total
Input Heat Gain RTS Radiant Sensible
Usage Convective % Radiant % Zone Type Cooling Cooling
Hour Profile Heat Gain 70% 30% 8 Load Load
Btuh/equipment watt
1 0% - - - 49% 0.12 0.12
2 0% - - - 17% 0.12 0.12
3 0% - - - 9% 0.11 0.11
4 0% - - - 5% 0.10 0.10
5 0% - - - 3% 0.09 0.09
6 0% - - - 2% 0.08 0.08
7 100% 3.41 2.39 1.02 2% 0.57 2.96
8 100% 3.41 2.39 1.02 1% 0.74 3.12
9 100% 3.41 2.39 1.02 1% 0.82 3.21
10 100% 3.41 2.39 1.02 1% 0.86 3.25
11 100% 3.41 2.39 1.02 1% 0.88 3.27
12 100% 3.41 2.39 1.02 1% 0.89 3.28
13 100% 3.41 2.39 1.02 1% 0.90 3.29
14 100% 3.41 2.39 1.02 1% 0.90 3.29
15 100% 3.41 2.39 1.02 1% 0.91 3.30
16 100% 3.41 2.39 1.02 1% 0.92 3.31
17 100% 3.41 2.39 1.02 1% 0.93 3.32
18 100% 3.41 2.39 1.02 1% 0.94 3.33
19 0% - - - 1% 0.45 0.45
20 0% - - - 1% 0.29 0.29
21 0% - - - 0% 0.20 0.20
22 0% - - - 0% 0.16 0.16
23 0% - - - 0% 0.14 0.14
24 0% - - - 0% 0.13 0.13

40.92 28.64 12.28 100% 12.28 40.92


1 1 1 49% 15 15.92
-4 -2 -2 17% 12 9.61
-8 -5 -4 9% 10 5.10
-12 -6 -5 5% 8 1.74
-14 -8 -7 3% 7 (1.18)
-15 -8 -7 2% 6 (2.45)
-7 -4 -3 2% 6 2.54
13 7 6 1% 11 17.52
41 22 19 1% 18 40.10
70 38 32 1% 27 64.81
97 52 45 1% 36 87.93
120 65 55 1% 43 108.33
150 81 69 1% 53 133.98
211 114 97 1% 70 183.80
278 150 128 1% 91 241.38
325 175 149 1% 111 285.97
337 182 155 1% 122 304.65
311 168 143 1% 122 290.15
238 129 110 1% 108 236.70
134 72 62 1% 80 152.85
56 30 26 0% 53 83.83
28 15 13 0% 36 51.40
16 9 7 0% 26 34.73
8 4 4 0% 20 24.10
Table 29A Conduction: Wall Component of Solar Irradiance

DIRECT BEAM SOLAR DIFFUSE SOLAR HEAT GAIN


Beam Surface Diffuse Total
Local Apparent Hour Solar Solar Solar Normal Incident Surface Horizontal Ground Sky Sub-total Surface
Standard Solar Angle Altitude Azimuth Air Mass Btuh/sf Angle Direct Btuh/sf Diffuse Y Diffuse Diffuse Irradiance
Hour Time, H ² Æ m Eb ¸ Btuh/sf Ed Btuh/sf Ratio Btuh/sf Btuh/sf Btuh/sf

1 0.26 -176 -36 -175 - 0.0 117.4 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
2 1.26 -161 -33 -159 - 0.0 130.9 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
3 2.26 -146 -27 -144 - 0.0 144.5 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
4 3.26 -131 -19 -132 - 0.0 158.1 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
5 4.26 -116 -9 -122 - 0.0 171.3 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
6 5.26 -101 3 -113 16.91455 8.7 172.5 0.0 6.7 0.7 0.4500 3.0 3.7 3.7
7 6.26 -86 14 -105 3.98235 105.6 159.5 0.0 23.1 4.9 0.4500 10.4 15.3 15.3
8 7.26 -71 27 -98 2.22845 168.6 145.9 0.0 34.0 10.9 0.4500 15.3 26.2 26.2
9 8.26 -56 39 -90 1.58641 205.2 132.3 0.0 41.5 17.1 0.4500 18.7 35.8 35.8
10 9.26 -41 51 -81 1.27776 227.3 118.8 0.0 46.8 22.5 0.4500 21.1 43.5 43.5
11 10.26 -26 63 -67 1.11740 240.4 105.6 0.0 50.2 26.5 0.4553 22.9 49.4 49.4
12 11.26 -11 74 -39 1.04214 247.0 92.6 0.0 52.1 28.9 0.5306 27.6 56.5 56.5
13 12.26 4 76 16 1.02872 248.2 80.2 42.1 52.4 29.4 0.6332 33.2 62.6 104.7
14 13.26 19 69 57 1.07337 244.2 68.7 88.9 51.3 27.9 0.7505 38.5 66.4 155.2
15 14.2647 33.97 57.2 75.05 1.18905 234.4 58.45 122.7 48.6 24.6 0.8644 42.0 66.6 189.3
16 15.26 49 45 86 1.41566 217.0 50.4 138.3 44.3 19.7 0.9555 42.3 62.0 200.3
17 16.26 64 32 94 1.86186 188.2 45.8 131.3 37.9 13.9 1.0073 38.1 52.0 183.3
18 17.26 79 20 102 2.89735 139.7 45.5 97.9 28.7 7.7 1.0100 29.0 36.7 134.6
19 18.26 94 8 109 6.84406 55.0 49.7 35.6 15.3 2.3 0.9631 14.8 17.1 52.6
20 19.26 109 -3 117 - 0.0 57.5 0.0 0.0 0.0 0.8755 0.0 0.0 0.0
21 20.26 124 -14 127 - 0.0 67.5 0.0 0.0 0.0 0.7630 0.0 0.0 0.0
22 21.26 139 -23 138 - 0.0 79.0 0.0 0.0 0.0 0.6452 0.0 0.0 0.0
23 22.26 154 -30 151 - 0.0 91.3 0.0 0.0 0.0 0.5403 0.0 0.0 0.0
24 23.26 169 -35 167 - 0.0 104.2 0.0 0.0 0.0 0.4618 0.0 0.0 0.0
Table 29B Conduction: Wall Component of Sol-air Temperatures, Heat Input, Heat Gain, Cooling Load
Non-Solar
Total CTS Heat Gain RTS Radiant Total
Local Surface Outside Sol-Air Inside Heat Type: Zone Type Cooling Cooling
Standard Irradiance Temp. Temps Temp Input 1 Total Convective Radiant 8 Load Load
Hour Btuh/sf F F F Btuh % Btuh 54% 46% % Btuh Btuh

1 0.0 73.8 73.8 75 -6 18% 1 1 1 49% 15 16


2 0.0 73.0 73.0 75 -9 57% -4 -2 -2 17% 12 10
3 0.0 72.4 72.4 75 -12 20% -8 -5 -4 9% 10 5
4 0.0 71.8 71.8 75 -15 4% -12 -6 -5 5% 8 2
5 0.0 71.4 71.4 75 -17 1% -14 -8 -7 3% 7 -1
6 3.7 71.8 72.9 75 -10 0% -15 -8 -7 2% 6 -2
7 15.3 73.2 77.8 75 13 0% -7 -4 -3 2% 6 3
8 26.2 76.7 84.6 75 44 0% 13 7 6 1% 11 18
9 35.8 80.5 91.2 75 75 0% 41 22 19 1% 18 40
10 43.5 83.9 97.0 75 101 0% 70 38 32 1% 27 65
11 49.4 87.0 101.8 75 124 0% 97 52 45 1% 36 88
12 56.5 89.0 106.0 75 143 0% 120 65 55 1% 43 108
13 104.7 90.6 122.0 75 217 0% 150 81 69 1% 53 134
14 155.2 91.6 138.2 75 292 0% 211 114 97 1% 70 184
15 189.3 91.6 148.4 75 339 0% 278 150 128 1% 91 241
16 200.3 90.4 150.5 75 349 0% 325 175 149 1% 111 286
17 183.3 88.8 143.8 75 318 0% 337 182 155 1% 122 305
18 134.6 86.8 127.2 75 241 0% 311 168 143 1% 122 290
19 52.6 83.7 99.5 75 113 0% 238 129 110 1% 108 237
20 0.0 81.5 81.5 75 30 0% 134 72 62 1% 80 153
21 0.0 79.7 79.7 75 22 0% 56 30 26 0% 53 84
22 0.0 77.9 77.9 75 13 0% 28 15 13 0% 36 51
23 0.0 76.5 76.5 75 7 0% 16 9 7 0% 26 35
24 0.0 75.0 75.0 75 0 0% 8 4 4 0% 20 24