Btu/h
150
200 Btuh/person latent
100
50
-
8 RTS Zone Type 1 3 5 7 9 11 13 15 17 19 21 23
MW w
Heat Gain Hour
Sensible Cooling Load
Carpet
50% glass
Non-Solar Total Latent
Input Heat Gain RTS Radiant Sensible Cooling
Usage Convective % Radiant % Zone Type Cooling Cooling Load
Hour Profile Heat Gain 40% 60% 8 Load Load Btuh/
Btuh/person Btuh/pers person
1 0% - - - 49% 18 18 -
2 0% - - - 17% 18 18 -
3 0% - - - 9% 17 17 -
4 0% - - - 5% 15 15 -
5 0% - - - 3% 14 14 -
6 0% - - - 2% 12 12 -
7 100% 250 100 150 2% 84 184 200
8 100% 250 100 150 1% 108 208 200
9 100% 250 100 150 1% 120 220 200
10 100% 250 100 150 1% 126 226 200
11 100% 250 100 150 1% 129 229 200
12 100% 250 100 150 1% 131 231 200
13 100% 250 100 150 1% 132 232 200
14 100% 250 100 150 1% 132 232 200
15 100% 250 100 150 1% 134 234 200
16 100% 250 100 150 1% 135 235 200
17 100% 250 100 150 1% 137 237 200
18 100% 250 100 150 1% 138 238 200
19 0% - - - 1% 66 66 -
20 0% - - - 1% 42 42 -
21 0% - - - 0% 30 30 -
22 0% - - - 0% 24 24 -
23 0% - - - 0% 21 21 -
24 0% - - - 0% 20 20 -
Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236
Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554
WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85
DB 2 45.1 46.7 52.8 59.0 66.1 71.3 73.0 73.0 68.8 59.4 51.1 46.7
WB 2 44.7 44.7 49.0 54.7 61.9 66.4 68.7 68.7 64.4 56.5 49.8 46.7
WBR 2 504.37 504.37 508.67 514.37 521.57 526.07 528.37 528.37 524.07 516.17 509.47 506.37
PWS 2 0.145877 0.145877 0.171584 0.211773 0.274220 0.320981 0.347473 0.347473 0.299400 0.226079 0.176784 0.157377
WST 2 0.006236 0.006236 0.007348 0.009094 0.011826 0.013888 0.015062 0.015062 0.012935 0.009718 0.007573 0.006733
W 2 0.006145 0.005782 0.006482 0.008108 0.010855 0.012748 0.014058 0.014058 0.011914 0.009051 0.007276 0.006733
DB 3 44.5 46.0 52.1 58.3 65.5 70.7 72.4 72.4 68.3 58.8 50.4 46.1
WB 3 44.3 44.3 48.7 54.4 61.7 66.2 68.5 68.5 64.2 56.2 49.5 46.1
WBR 3 503.97 503.97 508.37 514.07 521.37 525.87 528.17 528.17 523.87 515.87 509.17 505.77
PWS 3 0.143668 0.143668 0.169669 0.209468 0.272288 0.318763 0.345096 0.345096 0.297314 0.223637 0.174818 0.153846
WST 3 0.006141 0.006141 0.007265 0.008994 0.011742 0.013790 0.014957 0.014957 0.012843 0.009611 0.007488 0.006580
W 3 0.006095 0.005755 0.006490 0.008100 0.010863 0.012744 0.014046 0.014046 0.011892 0.009014 0.007282 0.006580
DB 4 43.9 45.4 51.5 57.6 64.9 70.1 71.8 71.8 67.7 58.2 49.8 45.5
WB 4 43.9 43.9 48.3 54.1 61.5 66.0 68.3 68.3 64.0 56.0 49.1 45.5
WBR 4 503.57 503.57 507.97 513.77 521.17 525.67 527.97 527.97 523.67 515.67 508.77 505.17
PWS 4 0.141489 0.141489 0.167145 0.207185 0.270368 0.316559 0.342733 0.342733 0.295240 0.222022 0.172226 0.150385
WST 4 0.006046 0.006046 0.007155 0.008894 0.011657 0.013693 0.014852 0.014852 0.012752 0.009541 0.007376 0.006431
W 4 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
DB 5 43.5 45.0 51.0 57.2 64.5 69.7 71.4 71.4 67.3 57.8 49.4 45.1
WB 5 43.5 43.6 48.1 53.9 61.3 65.9 68.2 68.2 63.9 55.8 48.9 45.1
WBR 5 503.17 503.27 507.77 513.57 520.97 525.57 527.87 527.87 523.57 515.47 508.57 504.77
PWS 5 0.139339 0.139874 0.165895 0.205675 0.268460 0.315462 0.341556 0.341556 0.294208 0.220418 0.170943 0.148116
WST 5 0.005954 0.005977 0.007101 0.008828 0.011573 0.013644 0.014800 0.014800 0.012706 0.009471 0.007320 0.006333
W 5 0.005954 0.005659 0.006441 0.008072 0.010834 0.012760 0.014053 0.014053 0.011917 0.009011 0.007206 0.006333
DB 6 43.9 45.4 51.5 57.6 64.9 70.1 71.8 71.8 67.7 58.2 49.8 45.5
WB 6 43.9 43.9 48.3 54.1 61.5 66.0 68.3 68.3 64.0 56.0 49.1 45.5
WBR 6 503.57 503.57 507.97 513.77 521.17 525.67 527.97 527.97 523.67 515.67 508.77 505.17
PWS 6 0.141489 0.141489 0.167145 0.207185 0.270368 0.316559 0.342733 0.342733 0.295240 0.222022 0.172226 0.150385
WST 6 0.006046 0.006046 0.007155 0.008894 0.011657 0.013693 0.014852 0.014852 0.012752 0.009541 0.007376 0.006431
W 6 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
DB 7 45.3 46.9 53.0 59.2 66.3 71.5 73.2 73.2 69.0 59.6 51.3 46.9
WB 7 44.8 44.8 49.1 54.8 62.0 66.5 68.7 68.7 64.5 56.6 50.0 46.9
WBR 7 504.47 504.47 508.77 514.47 521.67 526.17 528.37 528.37 524.17 516.27 509.67 506.57
PWS 7 0.146434 0.146434 0.172226 0.212547 0.275190 0.322095 0.347473 0.347473 0.300448 0.226898 0.178106 0.158569
WST 7 0.006260 0.006260 0.007376 0.009128 0.011869 0.013938 0.015062 0.015062 0.012981 0.009754 0.007630 0.006784
W 7 0.006146 0.005783 0.006487 0.008119 0.010875 0.012774 0.014012 0.014012 0.011937 0.009064 0.007334 0.006784
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75
Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236
Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554
WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85
DB 8 48.6 50.4 56.9 62.9 69.7 74.9 76.7 76.5 72.3 63.1 54.8 50.2
WB 8 47.1 47.1 51.0 56.4 63.3 67.6 69.8 69.8 65.7 58.1 51.9 49.2
WBR 8 506.77 506.77 510.67 516.07 522.97 527.27 529.47 529.47 525.37 517.77 511.57 508.87
PWS 8 0.159770 0.159770 0.184845 0.225262 0.288081 0.334573 0.360805 0.360805 0.313278 0.239501 0.191101 0.172871
WST 8 0.006836 0.006836 0.007923 0.009682 0.012436 0.014490 0.015655 0.015655 0.013548 0.010304 0.008195 0.007404
W 8 0.006495 0.006086 0.006577 0.008191 0.010955 0.012791 0.014043 0.014090 0.012015 0.009154 0.007531 0.007175
DB 9 52.3 54.4 61.1 67.1 73.5 78.7 80.5 80.2 75.9 67.0 58.8 53.9
WB 9 49.7 49.6 53.1 58.2 64.7 68.9 70.9 70.9 67.0 59.8 54.2 51.7
WBR 9 509.37 509.27 512.77 517.87 524.37 528.57 530.57 530.57 526.67 519.47 513.87 511.37
PWS 9 0.176127 0.175471 0.199732 0.240362 0.302554 0.349864 0.374583 0.374583 0.327715 0.254524 0.207944 0.189695
WST 9 0.007545 0.007516 0.008570 0.010342 0.013074 0.015168 0.016268 0.016268 0.014186 0.010962 0.008927 0.008133
W 9 0.006951 0.006422 0.006742 0.008297 0.011035 0.012885 0.014025 0.014094 0.012118 0.009303 0.007873 0.007630
DB 10 55.6 58.0 65.0 70.8 77.0 82.2 83.9 83.5 79.1 70.4 62.4 57.2
WB 10 52.0 51.8 54.9 59.8 66.0 70.0 72.0 71.9 68.1 61.3 56.2 54.0
WBR 10 511.67 511.47 514.57 519.47 525.67 529.67 531.67 531.57 527.77 520.97 515.87 513.67
PWS 10 0.191807 0.190397 0.213322 0.254524 0.316559 0.363277 0.388819 0.387506 0.340384 0.268460 0.223637 0.206429
WST 10 0.008225 0.008164 0.009161 0.010962 0.013693 0.015765 0.016903 0.016845 0.014748 0.011573 0.009611 0.008861
W 10 0.007402 0.006748 0.006851 0.008432 0.011142 0.012921 0.014120 0.014132 0.012189 0.009475 0.008189 0.008128
DB 11 58.5 61.1 68.3 74.1 80.0 85.2 87.0 86.4 82.0 73.5 65.5 60.1
WB 11 54.1 53.8 56.6 61.2 67.1 71.0 72.9 72.8 69.1 62.7 57.9 56.0
WBR 11 513.77 513.47 516.27 520.87 526.77 530.67 532.57 532.47 528.77 522.37 517.57 515.67
PWS 11 0.207185 0.204924 0.226898 0.267511 0.328850 0.375859 0.400816 0.399467 0.352270 0.282067 0.237786 0.222022
WST 11 0.008894 0.008796 0.009754 0.011532 0.014237 0.016325 0.017439 0.017379 0.015275 0.012172 0.010229 0.009541
W 11 0.007886 0.007126 0.007074 0.008562 0.011243 0.013012 0.014140 0.014197 0.012273 0.009678 0.008483 0.008599
DB 12 60.5 63.2 70.6 76.3 82.0 87.2 89.0 88.4 83.9 75.5 67.6 62.1
WB 12 55.4 55.2 57.7 62.2 67.8 71.6 73.5 73.4 69.8 63.5 59.1 57.3
WBR 12 515.07 514.87 517.37 521.87 527.47 531.27 533.17 533.07 529.47 523.17 518.77 516.97
PWS 12 0.217239 0.215665 0.236081 0.277140 0.336887 0.383589 0.408993 0.407620 0.360805 0.290111 0.248241 0.232705
WST 12 0.009332 0.009264 0.010155 0.011955 0.014593 0.016670 0.017805 0.017744 0.015655 0.012526 0.010687 0.010007
W 12 0.008162 0.007431 0.007198 0.008706 0.011296 0.013029 0.014177 0.014232 0.012371 0.009754 0.008731 0.008904
DB 13 62.0 64.9 72.4 78.1 83.6 88.8 90.6 89.9 85.4 77.2 69.3 63.6
WB 13 56.5 56.2 58.6 62.9 68.4 72.2 74.0 73.9 70.4 64.3 60.0 58.3
WBR 13 516.17 515.87 518.27 522.57 528.07 531.87 533.67 533.57 530.07 523.97 519.67 517.97
PWS 13 0.226079 0.223637 0.243836 0.284060 0.343912 0.391458 0.415917 0.414524 0.368265 0.298355 0.256345 0.241227
WST 13 0.009718 0.009611 0.010494 0.012259 0.014904 0.017021 0.018116 0.018053 0.015987 0.012889 0.011042 0.010380
W 13 0.008455 0.007617 0.007328 0.008755 0.011374 0.013145 0.014228 0.014306 0.012492 0.009907 0.008901 0.009160
DB 14 63.0 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
WB 14 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59.0
WBR 14 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS 14 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST 14 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W 14 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
DB 15 63.0 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
WB 15 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59.0
WBR 15 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75
Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236
Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554
WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85
PWS 15 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST 15 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W 15 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
DB 16 61.8 64.6 72.2 77.9 83.4 88.6 90.4 89.7 85.3 77.0 69.0 63.4
WB 16 56.4 56.1 58.4 62.8 68.4 72.1 73.9 73.8 70.3 64.2 59.9 58.2
WBR 16 516.07 515.77 518.07 522.47 528.07 531.77 533.57 533.47 529.97 523.87 519.57 517.87
PWS 16 0.225262 0.222828 0.242094 0.283062 0.343912 0.390137 0.414524 0.413135 0.367012 0.297314 0.255433 0.240362
WST 16 0.009682 0.009576 0.010418 0.012215 0.014904 0.016962 0.018053 0.017991 0.015931 0.012843 0.011002 0.010342
W 16 0.008442 0.007628 0.007253 0.008735 0.011420 0.013110 0.014190 0.014268 0.012437 0.009884 0.008907 0.009145
DB 17 60.3 63.0 70.4 76.1 81.8 87.0 88.8 88.2 83.7 75.3 67.4 61.9
WB 17 55.3 55.0 57.6 62.1 67.8 71.6 73.4 73.4 69.7 63.5 59.0 57.2
WBR 17 514.97 514.67 517.27 521.77 527.47 531.27 533.07 533.07 529.37 523.17 518.67 516.87
PWS 17 0.216451 0.214101 0.235233 0.276163 0.336887 0.383589 0.407620 0.407620 0.359575 0.290111 0.247354 0.231867
WST 17 0.009298 0.009195 0.010118 0.011912 0.014593 0.016670 0.017744 0.017744 0.015600 0.012526 0.010648 0.009971
W 17 0.008151 0.007364 0.007184 0.008687 0.011342 0.013076 0.014139 0.014279 0.012340 0.009800 0.008716 0.008890
DB 18 58.3 60.9 68.1 73.9 79.8 85.0 86.8 86.2 81.8 73.3 65.3 59.9
WB 18 53.9 53.7 56.5 61.1 67.0 70.9 72.8 72.8 69.1 62.6 57.8 55.8
WBR 18 513.57 513.37 516.17 520.77 526.67 530.57 532.47 532.47 528.77 522.27 517.47 515.47
PWS 18 0.205675 0.204175 0.226079 0.266564 0.327715 0.374583 0.399467 0.399467 0.352270 0.281076 0.236932 0.220418
WST 18 0.008828 0.008763 0.009718 0.011490 0.014186 0.016268 0.017379 0.017379 0.015275 0.012128 0.010192 0.009471
W 18 0.007821 0.007116 0.007061 0.008544 0.011216 0.012979 0.014103 0.014243 0.012319 0.009658 0.008469 0.008530
DB 19 55.4 57.7 64.7 70.6 76.8 82.0 83.7 83.3 79.0 70.2 62.1 57.0
WB 19 51.9 51.7 54.8 59.7 65.9 69.9 71.9 71.9 68.0 61.2 56.0 53.9
WBR 19 511.57 511.37 514.47 519.37 525.57 529.57 531.57 531.57 527.67 520.87 515.67 513.57
PWS 19 0.191101 0.189695 0.212547 0.253618 0.315462 0.362039 0.387506 0.387506 0.339215 0.267511 0.222022 0.205675
WST 19 0.008195 0.008133 0.009128 0.010922 0.013644 0.015710 0.016845 0.016845 0.014696 0.011532 0.009541 0.008828
W 19 0.007394 0.006763 0.006863 0.008416 0.011117 0.012889 0.014085 0.014178 0.012138 0.009456 0.008141 0.008118
DB 20 53.3 55.5 62.3 68.2 74.6 79.8 81.5 81.2 76.9 68.0 59.9 54.9
WB 20 50.4 50.3 53.6 58.7 65.1 69.2 71.3 71.2 67.3 60.3 54.8 52.4
WBR 20 510.07 509.97 513.27 518.37 524.77 528.87 530.97 530.87 526.97 519.97 514.47 512.07
PWS 20 0.180775 0.180104 0.203429 0.244712 0.306804 0.353479 0.379706 0.378420 0.331129 0.259097 0.212547 0.194656
WST 20 0.007746 0.007717 0.008731 0.010532 0.013262 0.015329 0.016497 0.016439 0.014337 0.011163 0.009128 0.008349
W 20 0.007084 0.006531 0.006742 0.008349 0.011060 0.012859 0.014112 0.014101 0.012106 0.009388 0.007959 0.007777
DB 21 51.5 53.6 60.2 66.2 72.7 77.9 79.7 79.4 75.1 66.2 58.0 53.1
WB 21 49.2 49.1 52.6 57.8 64.4 68.6 70.7 70.7 66.7 59.4 53.7 51.2
WBR 21 508.87 508.77 512.27 517.47 524.07 528.27 530.37 530.37 526.37 519.07 513.37 510.87
PWS 21 0.172871 0.172226 0.196095 0.236932 0.299400 0.346282 0.372045 0.372045 0.324333 0.250917 0.204175 0.186219
WST 21 0.007404 0.007376 0.008412 0.010192 0.012935 0.015009 0.016155 0.016155 0.014037 0.010804 0.008763 0.007983
W 21 0.006879 0.006350 0.006676 0.008263 0.011012 0.012843 0.014052 0.014122 0.012085 0.009238 0.007778 0.007548
DB 22 49.7 51.7 58.2 64.2 70.9 76.1 77.9 77.6 73.4 64.3 56.1 51.3
WB 22 48.0 47.9 51.6 56.9 63.7 68.0 70.2 70.1 66.1 58.6 52.6 50.0
WBR 22 507.67 507.57 511.27 516.57 523.37 527.67 529.87 529.77 525.77 518.27 512.27 509.67
PWS 22 0.165274 0.164654 0.188995 0.229371 0.292153 0.339215 0.365763 0.364518 0.317659 0.243836 0.196095 0.178106
WST 22 0.007074 0.007048 0.008103 0.009862 0.012616 0.014696 0.015875 0.015820 0.013741 0.010494 0.008412 0.007630
W 22 0.006687 0.006183 0.006597 0.008186 0.010949 0.012810 0.014076 0.014068 0.012046 0.009182 0.007611 0.007334
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75
Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236
Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554
WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85
DB 23 48.4 50.2 56.6 62.7 69.5 74.7 76.5 76.3 72.1 62.9 54.6 50.0
WB 23 47.0 46.9 50.9 56.3 63.2 67.6 69.7 69.7 65.6 58.0 51.8 49.1
WBR 23 506.67 506.57 510.57 515.97 522.87 527.27 529.37 529.37 525.27 517.67 511.47 508.77
PWS 23 0.159169 0.158569 0.184161 0.224448 0.287071 0.334573 0.359575 0.359575 0.312190 0.238642 0.190397 0.172226
WST 23 0.006810 0.006784 0.007893 0.009647 0.012392 0.014490 0.015600 0.015600 0.013500 0.010267 0.008164 0.007376
W 23 0.006492 0.006034 0.006593 0.008178 0.010934 0.012837 0.014012 0.014058 0.011990 0.009139 0.007524 0.007170
DB 24 47.0 48.8 55.1 61.2 68.1 73.3 75.0 74.9 70.7 61.5 53.2 48.6
WB 24 46.0 46.0 50.1 55.6 62.7 67.1 69.3 69.3 65.1 57.4 51.0 48.2
WBR 24 505.67 505.67 509.77 515.27 522.37 526.77 528.97 528.97 524.77 517.07 510.67 507.87
PWS 24 0.153264 0.153264 0.178770 0.218823 0.282067 0.328850 0.354691 0.354691 0.306804 0.233545 0.184845 0.166519
WST 24 0.006555 0.006555 0.007659 0.009401 0.012172 0.014237 0.015383 0.015383 0.013262 0.010044 0.007923 0.007128
W 24 0.006327 0.005919 0.006519 0.008117 0.010922 0.012794 0.014052 0.014075 0.011962 0.009101 0.007420 0.007037
HUMIDITY RATIOS
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 0.006221 0.005834 0.006480 0.008095 0.010868 0.012780 0.014025 0.014048 0.011937 0.009103 0.007352 0.006915
2 0.006145 0.005782 0.006482 0.008108 0.010855 0.012748 0.014058 0.014058 0.011914 0.009051 0.007276 0.006733
3 0.006095 0.005755 0.006490 0.008100 0.010863 0.012744 0.014046 0.014046 0.011892 0.009014 0.007282 0.006580
4 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
5 0.005954 0.005659 0.006441 0.008072 0.010834 0.012760 0.014053 0.014053 0.011917 0.009011 0.007206 0.006333
6 0.006046 0.005706 0.006427 0.008092 0.010871 0.012739 0.014035 0.014035 0.011893 0.009035 0.007216 0.006431
7 0.006146 0.005783 0.006487 0.008119 0.010875 0.012774 0.014012 0.014012 0.011937 0.009064 0.007334 0.006784
8 0.006495 0.006086 0.006577 0.008191 0.010955 0.012791 0.014043 0.014090 0.012015 0.009154 0.007531 0.007175
9 0.006951 0.006422 0.006742 0.008297 0.011035 0.012885 0.014025 0.014094 0.012118 0.009303 0.007873 0.007630
10 0.007402 0.006748 0.006851 0.008432 0.011142 0.012921 0.014120 0.014132 0.012189 0.009475 0.008189 0.008128
11 0.007886 0.007126 0.007074 0.008562 0.011243 0.013012 0.014140 0.014197 0.012273 0.009678 0.008483 0.008599
12 0.008162 0.007431 0.007198 0.008706 0.011296 0.013029 0.014177 0.014232 0.012371 0.009754 0.008731 0.008904
13 0.008455 0.007617 0.007328 0.008755 0.011374 0.013145 0.014228 0.014306 0.012492 0.009907 0.008901 0.009160
14 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
15 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
16 0.008442 0.007628 0.007253 0.008735 0.011420 0.013110 0.014190 0.014268 0.012437 0.009884 0.008907 0.009145
17 0.008151 0.007364 0.007184 0.008687 0.011342 0.013076 0.014139 0.014279 0.012340 0.009800 0.008716 0.008890
18 0.007821 0.007116 0.007061 0.008544 0.011216 0.012979 0.014103 0.014243 0.012319 0.009658 0.008469 0.008530
19 0.007394 0.006763 0.006863 0.008416 0.011117 0.012889 0.014085 0.014178 0.012138 0.009456 0.008141 0.008118
20 0.007084 0.006531 0.006742 0.008349 0.011060 0.012859 0.014112 0.014101 0.012106 0.009388 0.007959 0.007777
21 0.006879 0.006350 0.006676 0.008263 0.011012 0.012843 0.014052 0.014122 0.012085 0.009238 0.007778 0.007548
22 0.006687 0.006183 0.006597 0.008186 0.010949 0.012810 0.014076 0.014068 0.012046 0.009182 0.007611 0.007334
23 0.006492 0.006034 0.006593 0.008178 0.010934 0.012837 0.014012 0.014058 0.011990 0.009139 0.007524 0.007170
24 0.006327 0.005919 0.006519 0.008117 0.010922 0.012794 0.014052 0.014075 0.011962 0.009101 0.007420 0.007037
COOLING LOAD COMPONENTS DESIGN WEATHER PROFILES
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06 21-Sep-17
OUTSIDE AIR PROFILES - PEAK DRY BULB AND MEAN COINCIDENT WET BULB Hours Standard
USA - GA - ATLANTA HARTSFIELD-JACKSON - 5% Latitude Longitude Elevation,ft +/- UTC Time Zone Meridian
Index = 1951 33.64 -84.43 1027 -5 Eastern -75
Inside Heating Design Temperature, F = 72 Design OA heating: Inside Cooling Design Conditions:
Outside Heating Design Temp, F (99.6%) = 21.9 55.11 Btuh/cfm DB, F RH DBR PWS PW W
Outside Heating Design Temp, F (99%) = 26.5 50.05 Btuh/cfm 75 50% 534.67 0.4300745 0.2150373 0.009236
Month = 1 2 3 4 5 6 7 8 9 10 11 12
Monthly Design DB = 63 65.9 73.5 79.2 84.6 89.8 91.6 90.9 86.4 78.2 70.3 64.6
Mean Coincident WB = 57.2 56.9 59.1 63.4 68.8 72.5 74.3 74.2 70.7 64.7 60.6 59
Daily Range, DB = 19.5 20.9 22.5 22 20.1 20.1 20.2 19.5 19.1 20.4 20.9 19.5
Daily Range, WB = 13.6 13.3 11 9.5 7.5 6.6 6.1 6 6.8 8.9 11.7 13.2
SOLAR TAU-B 0.31 0.315 0.347 0.386 0.44 0.473 0.515 0.515 0.417 0.363 0.333 0.311
SOLAR TAU-D 2.538 2.521 2.453 2.324 2.213 2.168 2.066 2.052 2.312 2.46 2.484 2.554
WBR = 516.87 516.57 518.77 523.07 528.47 532.17 533.97 533.87 530.37 524.37 520.27 518.67
PWS = 0.231867 0.229371 0.248241 0.289095 0.348667 0.395445 0.420121 0.418716 0.372045 0.302554 0.261875 0.247354
WST = 0.009971 0.009862 0.010687 0.012481 0.015115 0.017199 0.018304 0.018241 0.016155 0.013074 0.011284 0.010648
W = 0.008638 0.007797 0.007382 0.008837 0.011444 0.013159 0.014252 0.014329 0.012496 0.009953 0.009050 0.009358
Peak Design OA cooling load,
sensible, Btuh/cfm = -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
latent, Btuh/cfm = -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
Total, Btuh/cfm = -16.10 -16.98 -10.62 2.69 21.25 35.27 42.54 42.14 28.32 6.99 -6.07 -10.85
OUTSIDE AIR AND INFILTRATION SENSIBLE COOLING LOAD - BTUH PER CFM
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 -32.12 -30.25 -23.43 -16.72 -8.91 -3.19 -1.32 -1.43 -5.94 -16.28 -25.41 -30.36
2 -32.89 -31.13 -24.42 -17.60 -9.79 -4.07 -2.20 -2.20 -6.82 -17.16 -26.29 -31.13
3 -33.55 -31.90 -25.19 -18.37 -10.45 -4.73 -2.86 -2.86 -7.37 -17.82 -27.06 -31.79
4 -34.21 -32.56 -25.85 -19.14 -11.11 -5.39 -3.52 -3.52 -8.03 -18.48 -27.72 -32.45
5 -34.65 -33.00 -26.40 -19.58 -11.55 -5.83 -3.96 -3.96 -8.47 -18.92 -28.16 -32.89
6 -34.21 -32.56 -25.85 -19.14 -11.11 -5.39 -3.52 -3.52 -8.03 -18.48 -27.72 -32.45
7 -32.67 -30.91 -24.20 -17.38 -9.57 -3.85 -1.98 -1.98 -6.60 -16.94 -26.07 -30.91
8 -29.04 -27.06 -19.91 -13.31 -5.83 -0.11 1.87 1.65 -2.97 -13.09 -22.22 -27.28
9 -24.97 -22.66 -15.29 -8.69 -1.65 4.07 6.05 5.72 0.99 -8.80 -17.82 -23.21
10 -21.34 -18.70 -11.00 -4.62 2.20 7.92 9.79 9.35 4.51 -5.06 -13.86 -19.58
11 -18.15 -15.29 -7.37 -0.99 5.50 11.22 13.20 12.54 7.70 -1.65 -10.45 -16.39
12 -15.95 -12.98 -4.84 1.43 7.70 13.42 15.40 14.74 9.79 0.55 -8.14 -14.19
13 -14.30 -11.11 -2.86 3.41 9.46 15.18 17.16 16.39 11.44 2.42 -6.27 -12.54
14 -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
15 -13.20 -10.01 -1.65 4.62 10.56 16.28 18.26 17.49 12.54 3.52 -5.17 -11.44
16 -14.52 -11.44 -3.08 3.19 9.24 14.96 16.94 16.17 11.33 2.20 -6.60 -12.76
17 -16.17 -13.20 -5.06 1.21 7.48 13.20 15.18 14.52 9.57 0.33 -8.36 -14.41
18 -18.37 -15.51 -7.59 -1.21 5.28 11.00 12.98 12.32 7.48 -1.87 -10.67 -16.61
19 -21.56 -19.03 -11.33 -4.84 1.98 7.70 9.57 9.13 4.40 -5.28 -14.19 -19.80
20 -23.87 -21.45 -13.97 -7.48 -0.44 5.28 7.15 6.82 2.09 -7.70 -16.61 -22.11
21 -25.85 -23.54 -16.28 -9.68 -2.53 3.19 5.17 4.84 0.11 -9.68 -18.70 -24.09
22 -27.83 -25.63 -18.48 -11.88 -4.51 1.21 3.19 2.86 -1.76 -11.77 -20.79 -26.07
23 -29.26 -27.28 -20.24 -13.53 -6.05 -0.33 1.65 1.43 -3.19 -13.31 -22.44 -27.50
24 -30.80 -28.82 -21.89 -15.18 -7.59 -1.87 0.00 -0.11 -4.73 -14.85 -23.98 -29.04
OUTSIDE AIR AND INFILTRATION LATENT COOLING LOAD - BTUH PER CFM
MONTH
HOUR 1 2 3 4 5 6 7 8 9 10 11 12
1 -14.60 -16.46 -13.34 -5.52 7.90 17.15 23.18 23.29 13.07 -0.65 -9.12 -11.24
2 -14.96 -16.72 -13.33 -5.46 7.84 17.00 23.34 23.34 12.96 -0.90 -9.49 -12.12
3 -15.20 -16.85 -13.29 -5.50 7.87 16.98 23.28 23.28 12.85 -1.08 -9.46 -12.86
4 -15.44 -17.09 -13.60 -5.54 7.91 16.95 23.23 23.23 12.86 -0.97 -9.78 -13.58
5 -15.89 -17.31 -13.53 -5.63 7.73 17.06 23.31 23.31 12.98 -1.09 -9.83 -14.05
6 -15.44 -17.09 -13.60 -5.54 7.91 16.95 23.23 23.23 12.86 -0.97 -9.78 -13.58
7 -14.96 -16.71 -13.31 -5.41 7.93 17.12 23.11 23.11 13.07 -0.83 -9.21 -11.87
8 -13.27 -15.25 -12.87 -5.06 8.32 17.20 23.27 23.49 13.45 -0.40 -8.25 -9.97
9 -11.06 -13.62 -12.07 -4.54 8.71 17.66 23.18 23.51 13.95 0.33 -6.60 -7.77
10 -8.88 -12.04 -11.54 -3.89 9.22 17.83 23.64 23.69 14.29 1.16 -5.07 -5.36
11 -6.53 -10.21 -10.47 -3.26 9.71 18.28 23.73 24.01 14.70 2.14 -3.65 -3.08
12 -5.20 -8.74 -9.87 -2.57 9.97 18.36 23.91 24.18 15.17 2.50 -2.44 -1.61
13 -3.78 -7.84 -9.23 -2.33 10.34 18.92 24.16 24.54 15.76 3.25 -1.62 -0.37
14 -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
15 -2.90 -6.97 -8.97 -1.93 10.69 18.99 24.28 24.65 15.78 3.47 -0.90 0.59
16 -3.84 -7.79 -9.60 -2.43 10.57 18.75 23.98 24.35 15.49 3.14 -1.59 -0.44
17 -5.25 -9.06 -9.93 -2.66 10.19 18.58 23.73 24.41 15.02 2.73 -2.52 -1.67
18 -6.85 -10.26 -10.53 -3.35 9.58 18.12 23.56 24.23 14.92 2.04 -3.71 -3.42
19 -8.91 -11.97 -11.49 -3.97 9.10 17.68 23.47 23.92 14.04 1.07 -5.30 -5.41
20 -10.42 -13.09 -12.07 -4.29 8.83 17.54 23.60 23.55 13.89 0.73 -6.18 -7.06
21 -11.41 -13.97 -12.39 -4.71 8.60 17.46 23.31 23.65 13.79 0.01 -7.06 -8.17
22 -12.34 -14.78 -12.78 -5.08 8.29 17.30 23.43 23.38 13.60 -0.26 -7.87 -9.21
23 -13.28 -15.50 -12.79 -5.12 8.22 17.43 23.11 23.34 13.33 -0.47 -8.29 -10.00
24 -14.08 -16.06 -13.15 -5.42 8.16 17.22 23.31 23.42 13.19 -0.65 -8.79 -10.64
Table 28 Cooling Load Component: Lighting, Btu/h
Non-Solar
RTS Total % Lighting Room
Heat Gain Zone Type Radiant Sensible to Sensible
Usage Convective % Radiant % 8 Cooling Cooling Return Cooling
Hour Profile Heat Gain 43% 57% % Load Load 0% Load
1 0% - - - 49% 26 26 - 26
2 0% - - - 17% 26 26 - 26
3 0% - - - 9% 24 24 - 24
4 0% - - - 5% 21 21 - 21
5 0% - - - 3% 19 19 - 19
6 0% - - - 2% 17 17 - 17
7 100% 375 161 214 2% 120 281 - 281
8 100% 375 161 214 1% 154 315 - 315
9 100% 375 161 214 1% 171 332 - 332
10 100% 375 161 214 1% 180 341 - 341
11 100% 375 161 214 1% 184 345 - 345
12 100% 375 161 214 1% 186 347 - 347
13 100% 375 161 214 1% 188 349 - 349
14 100% 375 161 214 1% 188 349 - 349
15 100% 375 161 214 1% 190 352 - 352
16 100% 375 161 214 1% 192 354 - 354
17 100% 375 161 214 1% 195 356 - 356
18 100% 375 161 214 1% 197 358 - 358
19 0% - - - 1% 94 94 - 94
20 0% - - - 1% 60 60 - 60
21 0% - - - 0% 43 43 - 43
22 0% - - - 0% 34 34 - 34
23 0% - - - 0% 30 30 - 30
24 0% - - - 0% 28 28 - 28
COOLING LOAD COMPONENTS EQUIPMENT
2017 ASHRAE FUNDAMENTALS EXAMPLE - IP UNITS rev 2017-04-06
21-Sep-17
COOLING LOAD - PER EQUIPMENT PEAK WATT
Btu/h
70% % Convective 2
30% % Radiant 1.5
1
0.5
Non-Solar Total
Input Heat Gain RTS Radiant Sensible
Usage Convective % Radiant % Zone Type Cooling Cooling
Hour Profile Heat Gain 70% 30% 8 Load Load
Btuh/equipment watt
1 0% - - - 49% 0.12 0.12
2 0% - - - 17% 0.12 0.12
3 0% - - - 9% 0.11 0.11
4 0% - - - 5% 0.10 0.10
5 0% - - - 3% 0.09 0.09
6 0% - - - 2% 0.08 0.08
7 100% 3.41 2.39 1.02 2% 0.57 2.96
8 100% 3.41 2.39 1.02 1% 0.74 3.12
9 100% 3.41 2.39 1.02 1% 0.82 3.21
10 100% 3.41 2.39 1.02 1% 0.86 3.25
11 100% 3.41 2.39 1.02 1% 0.88 3.27
12 100% 3.41 2.39 1.02 1% 0.89 3.28
13 100% 3.41 2.39 1.02 1% 0.90 3.29
14 100% 3.41 2.39 1.02 1% 0.90 3.29
15 100% 3.41 2.39 1.02 1% 0.91 3.30
16 100% 3.41 2.39 1.02 1% 0.92 3.31
17 100% 3.41 2.39 1.02 1% 0.93 3.32
18 100% 3.41 2.39 1.02 1% 0.94 3.33
19 0% - - - 1% 0.45 0.45
20 0% - - - 1% 0.29 0.29
21 0% - - - 0% 0.20 0.20
22 0% - - - 0% 0.16 0.16
23 0% - - - 0% 0.14 0.14
24 0% - - - 0% 0.13 0.13
1 0.26 -176 -36 -175 - 0.0 117.4 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
2 1.26 -161 -33 -159 - 0.0 130.9 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
3 2.26 -146 -27 -144 - 0.0 144.5 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
4 3.26 -131 -19 -132 - 0.0 158.1 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
5 4.26 -116 -9 -122 - 0.0 171.3 0.0 0.0 0.0 0.4500 0.0 0.0 0.0
6 5.26 -101 3 -113 16.91455 8.7 172.5 0.0 6.7 0.7 0.4500 3.0 3.7 3.7
7 6.26 -86 14 -105 3.98235 105.6 159.5 0.0 23.1 4.9 0.4500 10.4 15.3 15.3
8 7.26 -71 27 -98 2.22845 168.6 145.9 0.0 34.0 10.9 0.4500 15.3 26.2 26.2
9 8.26 -56 39 -90 1.58641 205.2 132.3 0.0 41.5 17.1 0.4500 18.7 35.8 35.8
10 9.26 -41 51 -81 1.27776 227.3 118.8 0.0 46.8 22.5 0.4500 21.1 43.5 43.5
11 10.26 -26 63 -67 1.11740 240.4 105.6 0.0 50.2 26.5 0.4553 22.9 49.4 49.4
12 11.26 -11 74 -39 1.04214 247.0 92.6 0.0 52.1 28.9 0.5306 27.6 56.5 56.5
13 12.26 4 76 16 1.02872 248.2 80.2 42.1 52.4 29.4 0.6332 33.2 62.6 104.7
14 13.26 19 69 57 1.07337 244.2 68.7 88.9 51.3 27.9 0.7505 38.5 66.4 155.2
15 14.2647 33.97 57.2 75.05 1.18905 234.4 58.45 122.7 48.6 24.6 0.8644 42.0 66.6 189.3
16 15.26 49 45 86 1.41566 217.0 50.4 138.3 44.3 19.7 0.9555 42.3 62.0 200.3
17 16.26 64 32 94 1.86186 188.2 45.8 131.3 37.9 13.9 1.0073 38.1 52.0 183.3
18 17.26 79 20 102 2.89735 139.7 45.5 97.9 28.7 7.7 1.0100 29.0 36.7 134.6
19 18.26 94 8 109 6.84406 55.0 49.7 35.6 15.3 2.3 0.9631 14.8 17.1 52.6
20 19.26 109 -3 117 - 0.0 57.5 0.0 0.0 0.0 0.8755 0.0 0.0 0.0
21 20.26 124 -14 127 - 0.0 67.5 0.0 0.0 0.0 0.7630 0.0 0.0 0.0
22 21.26 139 -23 138 - 0.0 79.0 0.0 0.0 0.0 0.6452 0.0 0.0 0.0
23 22.26 154 -30 151 - 0.0 91.3 0.0 0.0 0.0 0.5403 0.0 0.0 0.0
24 23.26 169 -35 167 - 0.0 104.2 0.0 0.0 0.0 0.4618 0.0 0.0 0.0
Table 29B Conduction: Wall Component of Sol-air Temperatures, Heat Input, Heat Gain, Cooling Load
Non-Solar
Total CTS Heat Gain RTS Radiant Total
Local Surface Outside Sol-Air Inside Heat Type: Zone Type Cooling Cooling
Standard Irradiance Temp. Temps Temp Input 1 Total Convective Radiant 8 Load Load
Hour Btuh/sf F F F Btuh % Btuh 54% 46% % Btuh Btuh