1. Technical data
• Netz
- Line data
Voltage 400 V
Frequency 50 Hz
Number of phases 3
Allowance for differing supply voltage No
Allowance for short term supply fluctuations Yes
Maximum temporary undervoltage to the rated voltage 10 %
Undervoltage 360 V

• G150 / Netz
- SINAMICS G150
- Power unit
Order designation 6SL3710-1GE37-5CA3
SINAMICS Safety Integrated No Safety Integrated functionality
Power unit / ambient conditions
Installation altitude 1000 m
Ambient temperature 40 °C
Power unit / catalog data
Type rating 400.00 kW
Rated current 745.00 A
Energy efficiency class -
Dimensions (height x width x depth) 606 x 2005 x 605 mm
Power unit / load-specific data
Available base-load current 745.00 A
Note The dimensioning was performed without checking
the varying load capability at low output frequencies.
Please check the possible effects according to the
SINAMICS configuration recommendations in the
SINAMICS Low Voltage Configuration Manual.
- Accessories
TM31 user terminal block G60
- Motor
Order designation 1LE5603-3BB53-4AB0
Bearing insulation NDE L51
Temperature rise class 155 (F), utilized according to 130 (B), coolant N05
temperature 45° C, derating approx. 4%
Motor / ambient conditions
ATEX zone no EX-Zone (1LA/1LG/1PQ/1LE1)
Installation altitude 1500 m
Ambient temperature 45 °C
Temperature rise class F/105K
Motor / catalog data in relation to line operation
Rated power 500.00 kW
Rated torque 3202.00 Nm
Rated current 870.00 A
Rated speed 1491.00 rpm
Rated voltage 400 V
Frame size 355 L
Type of construction IM B3
Number of poles 4
Winding systems 1
Housing material Cast iron

This configuration data has been created by the SIZER for Siemens Drives program version 3.20.210.1.0. Page 1 From 2
Copyright ©Siemens AG 2001-2019. All rights reserved. (File location: C:\ProgramData\Microsoft\Windows\Templates\Siemens\Sizer\Proj\Sample\M~n^2.szp)
31.10.2019
Customer:
Plant:

Version IE3
Efficiency according to standard IEC 60034-30-1
Efficiency 0.960
Power factor cos phi at 50 Hz 0.86
Star/delta Delta
Motor protection 3 PTC thermistors for trip (2 terminals)
Terminal box top left
Seawater-proof No
Motor data / in relation to specified drive conditions
Interface Delta
Motor frequency 50 Hz
Rated power 442.32 kW
Rated torque 2981.70 Nm
Rated current 817.99 A
Rated speed 1416.45 rpm
Rated voltage 380 V
Motor data / calculated data
Load current 696.31 A
Load data on the motor shaft
Load type Square-law torque
Load torque 2350.00 Nm
Max. load speed 1500.00 rpm

Legend

• /!\ NOTICE

The selection of a brake does not result in the calculation of the physical suitability or the suitability for the application!
Please check the suitability of the selected brake. Please observe the warning and safety notes of the associated product
documentation. If you have any questions with regard to the dimensioning, please contact your local Siemens support.

• Please note:

The overload capability for dimensioning according to load characteristic (e.g. load cycle with constant ON duration)
refers to a temporarily required overload on the motor. With longer or cyclic overloads, a configuration via the
application is required.

With "Simple motor selection without load configuration", the rated data based on 400/460 V will not be attained