Chapter 9 Function Parameters Table

Function Factory
Illustration Setting Range Minimum
Code Default
Unit
0:Panel control
Control channel 1:Terminal control
F0.00 1 0
selection 2:Communication
control
0: Two-wire 1
Terminal control 1: Two-wire 2
F0.01 1 0
mode 2: Three-wire 1
3: Three-wire 2
0:Digital setting for
UP,DOWN
adjustment

1:AI1

Selection of 2:AI2
F0.02 main frequency 1 0
3:PULSE setting (X6)
source A
4: Multi-speed

5:PLC

6:PID
7:Communication
setting
0:Digital setting for
UP,DOWN
adjustment
Selection of
auxiliary 1:AI1
F0.03 1 1
frequency
source B 2:AI2

3:PULSE setting (X6)


4: Multi-speed
5:PLC

6:PID

7: Communication
setting

Range selection
0: Relative to
of auxiliary
F0.04 1 0
frequency maximum frequency
source B 1: Relative to
frequency source A
Range of 1% 100%
auxiliary
F0.05 0~100%
frequency
source B

0:Main frequency

source A
1: Main frequency
source A + auxiliary
frequency source B
2: Switch main
Frequency frequency source A
F0.06 1 0
source selection
and auxiliary
frequency source B
3: Switch main
frequency source A
and main frequency
source A + auxiliary
frequency source B

0:Non-memory
Digital setting
F0.07 for memory 1 1
1:Shutdown memory
selection
2:Shutdown,power-off
memory
Lower frequency limit
F0.08 Preset frequency – Upper limiting 0.01Hz 50.00Hz
frequency
Maximum
F0.09 50.00 - 300.0HZ 0.01Hz 50.00Hz
frequency
Upper limiting Lower frequency limit
F0.10 0.01Hz 50.00Hz
frequency - Maximum frequency
Lower 0.00Hz - Upper
F0.11 0.01Hz 00.00Hz
frequency limit limiting frequency

0:Positive direction
Running
F0.12 1 0
direction
1:Negative direction

0.00 - Maximum
Inching
F1.00 0.01Hz 5.00Hz
frequency frequency(F0.09)
Inching
F1.01 acceleration 0.0s – 3200.0s 0.1s 1.0s
time
Inching
F1.02 deceleration 0.0s - 3200.0s 0.1s 1.0s
time
0.00hz –Maximum
Hopping
F1.03 0.01Hz 0.00Hz
frequency frequency(F0.09)
Range of 0.00hz –Maximum
F1.04 hopping 0.01Hz 0.00Hz
frequency(F0.09)
frequency
Positive and
F1.05 negative 0.0s – 200.0s 0.1s 0.0s
dead-zone time
Acceleration
F1.06 0.0s - 3200.0s 0.1s 20.0s
time 1
Deceleration
F1.07 0.0s - 3200.0s 0.1s 20.0s
time 1
Acceleration
F1.08 0.0s - 3200.0s 0.1s 20.0s
time 2
Deceleration
F1.09 0.0s - 3200.0s 0.1s 20.0s
time 2
Acceleration and 0: Straight-line
F1.10 1 0
deceleration acceleration and
mode selection deceleration
1: S curve
acceleration and
deceleration
S curve start
F1.11 0.0 - 40.0% 0.1% 30.0%
time
F1.12 S curve end time 0.0 - 40.0% 0.1% 30.0%
0: Permit reversal
F1.13 Reversal control 1 0
1: Inhibit reversal

0:Direct start
F2.00 Starting mode 1 0
1 : Speed tracking
mode

0 : Start from zero


speed
Speed tracking 1 : Start from
F2.01 1 0
mode
downtime frequency
2 : Start from
maximum frequency
Start frequency 0.00hz –Maximum
F2.02 0.01Hz 0.00Hz
frequency
Start frequency
F2.03 0.0s – 60.0s 0.1s 00.0s
hold time
Start DC braking
F2.04 0% - 100% 1% 100%
current

0:Slowdown
F2.05 Stop mode 1 0
1:Stop immediately
0: Running at lower
frequency limit
Below lower
F2.06 1 0
frequency limit 1 : Stop after Delay
stop time(F2.07)
F2.07 Delay stop time 0.0s – 600.0s 0.1s 300.0s
DC brake
0.00hz –Maximum
F2.08 frequency when 0.01Hz 0.00Hz
frequency
machine halts
DC brake
electric current
F2.09 0% - 100% 1% 0%
when machine
halts
DC brake
waiting time
F2.10 0.0s – 600.0s 0.1s 0.0s
when
machine halts
DC brake
waiting time
F2.11 0.0s – 600.0s 0.1s 0.0s
when
machine halts
F2.12 Brake usage rate 0% - 100% 1% 50%
F2.13 reserved
F2.14 reserved
F2.15 reserved
F2.16 reserved

0 :Invalid
Water supply
F2.17 1 0
sleep function
1 :Valid
Water supply
wakeup delay
F2.18 0.0s – 600.0s 0.1s 1.0s
time from
sleeping

Duration of start
F2-19 0.0s – 600.0s 0.1s 0.0s
DC braking
0:No function

1:Forward running
2: Reversal running
3: Three-wire mode
4::Terminal UP

5:Terminal down

6:Forward inching

7:Reversal inching
8:Multi-speed
terminal 1
9:Multi-speed
terminal 2
10:Multi-speed
terminal 3
11:Pause running
F3.00 X1 1 0
12:Stop immediately
13:Fault reset
terminal
14:reserved

15 : generating
external fault
when terminal is
closed
16:Remote command
and keyboard
command switch
1
17: Communication
and terminal
command switch
2
F3.01 X2 1 0
18 : Frequency
F3.02 X3 1 0
F3.03 X4 source switches 1 0
F3.04 X5 terminal, refer to 1 0
F3.05 X6 function 1 0
F3.06 description of 1 1
F3.07 reserved F0.06 1 2
F3.08 1 0
19:Clear UP/DOWN
settings

20:PLC state reset

21:PID pauses

22:PID effect negate

23: Reserved

24:Reserved

25:Reserved

26:Reserved

27:Reserved

F3.09 28:High speed pulse 1 0


input
29 : Disable
acceleration and
deceleration
30:Selection terminal
1 of acceleration and
deceleration
31:Selection terminal
2 of acceleration and
deceleration
32:Frequency source
input be AI1
33:Frequency source
input be multi-speed

F3.10 DI filtering time 0.00s – 10.00s 0.01 0.00


F3.11 AI1 minimun 0.0V – F3.13 0.01V 0.0V
value
Settings
corresponding to
F3.12 -100.0% - 100.0% 0.1% 0.0%
AI1 minimum
value
AI1 Maximum
F3.13 F3.11 – 10.0V 0.01V 10.0V
value
Settings
corresponding to
F3.14 -100.0% - 100.0% 0.1% 100.0%
AI1 maximum
value
AI1 filtering
F3.15 0.00s – 50.00s 0.01s 0.00s
time
AI2 minimum
F3.16 0.0V – F3.18 0.01V 0.0V
value
Settings
corresponding to
F3.17 -100.0% - 100.0% 0.1% 0.0%
AI2 minimum
value
AI2 Maximum
F3.18 F3.16– 10.0V 0.01V 10.0V
value
Settings
corresponding to
F3.19 -100.0% - 100.0% 0.1% 100.0%
AI2 maximum
value
AI2 filtering
F3.20 0.00s – 50.00s 0.01s 0.00s
time
PULSE
F3.21 0.00khz – F3.23 0.01kHz 0.00kHz
minimum value
Settings
corresponding to
F3.22 -100.0% - 100.0% 0.1% 0.0%
PULSE
minimum value
PULSE
F3.23 F3.21 – 50.00khz 0.01kHz 50.00kHz
maximum value
Settings
corresponding to
F3.24 -100.0% - 100.0% 0.1% 000.0%
PULSE
maximum value
PULSE filtering
F3.25 0.00s – 50.00s 0.01s 0.20s
time
0: No function
Relay 1 output
1: Forward running
F4.00 function 1 0
selection
2: Reversal running
3: Fault
4: Frequency arrives
Relay 2 output
F4.01 function 5 : Low frequency 1 0
selection
limit arrives
6 : Upper limiting
frequency arrives
Collector Y1 7:In ZERO speed
F4.02 output function 1 0
8: Reserved
selection
9 : PLC frequency
source is effective
10:Reserved

11:Special processing

12 : Ready for
operation
13: Reserved
14 : Pre-alarm for

Collector Y2 motor
F4.03 output function overloading 1 0
selection 15 : Communication
setting
16 : Frequency
reaching the FDT
value
17:Reserved

18:Reserved
Relay 1 output
F4.04 0.0s – 300.0s 0.1 0.0s
time delays
Relay 2 output
F4.05 0.0s – 300.0s 0.1 0.0s
time delays
Collector Y1
F4.06 output time 0.0s – 300.0s 0.1 0.0s
delays
Collector Y2
F4.07 output time 0.0s – 300.0s 0.1 0.0s
delays
AO1 output
F4.08 0:Running frequency 1 0
selection
AO2 output
F4.09 1:Frequency setting 1 0
selection
2:current(0 – 2times
rated current of
Motor)

3:Output voltage of
frequency
converter , 0 ~
1.2times rated
voltage of
DO(FM) output frequency
F4.10 1 0
selection converter)
4:AI1 Voltage output

5:AI2 Voltage output

6:Reserved

7:Reserved

8:PULSE input

9:Communication set
F4.11 AO1 Gain -10.00 – 10.00 0.01 1.00
AO1 offset
F4.12 -100.0% - 100.0% 0.1% 0.0%
coefficient
F4.13 AO2 Gain -10.00 – 10.00 0.01 1.00
AO2 offset
F4.14 -100.0% - 100.0% 0.1% 0.0%
coefficient
Maximum
F4.15 frequency D0 0.1khz – 50.0khz 0.1kHz 50.0kHz
PULSE outputs

Frequency
0.00hz –Maximum
F5.00 detected value 0.01Hz 50.00Hz
frequency
(FDT)
Frequency
F5.01 detection (FDT) 0.0% - 100.0% 0.1% 5.0%
drop value
Detection rate
0.0% - 100.0%
F5.02 when frequency 0.1% 0.0%
arrives Maximum frequency
Proportion
coefficient when
F5.03 0.000 - 1.5000 0.001 1.000
displaying
rotating speed
Total run time
F5.04 0 - 9999 1 0
record
Display
0 - 9999(refer to
F5.05 parameters of 1 21
schedule)
LED running

Display
0 - 9999(refer to
F5.06 parameters when 1 3
schedule)
LED is
shutdown

0:Invalid

1:Switch of keyboard
and remote
Function
control
selection of
F5.07 1 0
multi-function 2: Switch of positive
key (JOG)
and negative running
3:Forward inching

4:Reversal inching
STOP/RES key
F5.08 0:Valid only under 1 0
function
the control of
keyboard
1: Valid under the
control of other
control mode
F5.09 Software version 0.1 - 999.9 0.1 Factory set

Frequency
F5.10 0 – 100 1 Factory set
converter
temperature

0 : Digital setting

( F6.01 ) (up/down
adjustable)

1:AI1 setting
Multi-speed
F6.00 ZERO given 2:AI2 setting 1 0
mode
3:PULSE setting

4:PID setting

5 : Communication
setting
-100.0% - 100.0%

( 100%
F6.01 Multi-speed 0 corresponding to 0.1% 0.0%
maximum frequency
F0.09)
-100.0% - 100.0%
( 100%
F6.02 Multi-speed 1 corresponding to 0.1% 0.0%
maximum frequency
F0.09)
F6.03 Multi-speed 2 -100.0% - 100.0% 0.1% 0.0%
( 100%
corresponding to
maximum frequency
F0.09)
-100.0%-100.0%
( 100%
F6.04 Multi-speed 3 corresponding to 0.1% 0.0%
maximum frequency
F0.09)
-100.0% - 100.0%
( 100%
F6.05 Multi-speed 4 corresponding to 0.1% 0.0%
maximum frequency
F0.09)
-100.0% - 100.0%
( 100%
F6.06 Multi-speed 5 corresponding to 0.1% 0.0%
maximum frequency
F0.09)
-100.0% - 100.0%
( 100%
F6.07 Multi-speed 6 corresponding to 0.1% 0.0%
maximum frequency

F0.09)
-100.0% - 100.0%

( 100%
F6.08 Multi-speed 7 corresponding to 0.1% 0.0%
maximum

frequencyF0.09)

0:Halt after the single


F6.09 PLC run mode 0 0
run ends
1 : Keep final value
after single run ends
2:Circulating all the
time

0 : Power down
PLC power-fail
without memory
F6.10 memory 1 0
selection 1:Power down with
memory

0:Minute
PLC run time
F6.11 1 0
unit
1:Hour
Run time of
F6.12 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
PLC 0 section

0 : acceleration and
deceleration time 1
1 : acceleration and
Acceleration and
deceleration deceleration time 2
F6.13 1 0
time selection of
2 : acceleration and
PLC 0 section
deceleration time 3
3 : acceleration and
deceleration time 4
Runtime of PLC
F6.14 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
first section

0 : acceleration and
deceleration time 1

1 : acceleration and
Acceleration and
deceleration deceleration time 2
F6.15 1 0
time selection of
2 : acceleration and
PLC first section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.16 PLC second 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
section

0 : acceleration and
deceleration time 1
Acceleration and 1 : acceleration and
deceleration
deceleration time 2
F6.17 time selection of 1 0
PLC second 2 : acceleration and
section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.18 PLC third 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
section

0 : acceleration and
deceleration time 1
Acceleration and 1 : acceleration and
deceleration
deceleration time 2
F6.19 time selection of 1 0
PLC third 2 : acceleration and
section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.20 PLC fourth 0.0m(h) - 999.9 m(h) 0.1 m(h) 0.0m(h)
section

0 : acceleration and
deceleration time 1
Acceleration and
1 : acceleration and
deceleration
F6.21 time selection of deceleration time 2 1 0
PLC fourth
2 : acceleration and
section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.22 PLC fifth 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
section

0 : acceleration and
deceleration time 1
Acceleration and 1 : acceleration and
deceleration
deceleration time 2
F6.23 time selection of 1 0
PLC fifth 2 : acceleration and
section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.24 PLC sixth 0.0m(h) - 999.9 0.1m(h) 0.0m(h)
section

0 : acceleration and
deceleration time 1
Acceleration and 1 : acceleration and
deceleration
deceleration time 2
F6.25 time selection of 1 0
PLC sixth 2 : acceleration and
section
deceleration time 3
3 : acceleration and
deceleration time 4
Run time of
F6.26 PLC seventh 0.0m(h) - 999.9 m(h) 0.1m(h) 0.0m(h)
section

0 : acceleration and
Acceleration and deceleration time 1
deceleration
1 : acceleration and
F6.27 time selection of 1 0
PLC seventh deceleration time 2
section
2 : acceleration and
deceleration time 3
3 : acceleration and
deceleration time 4

0:F7.01

1:AI1

2:AI2
PID given
F7.00 0 0
source 3:PULSE

4:Multi-speed

5 : Communication
setting
PID value
F7.01 0.0% - 100.0% 0.1% 50.0%
setting

0:AI1
PID feedback
F7.02 1:AI2 1 0
source
2:PULSE

0:Positive function
PID function
F7.03 1 1
direction
1:Negative function
PID feedback
F7.04 0 - 9999 1 1000
measuring range
Proportional
F7.05 0.1 - 100.0 0.1 20.0
gain P
Integral
F7.06 00.00s – 10.00s 0.01 2.00s
coefficient I
Derivation time
F7.07 00.00s – 10.00s 0.001s 00.00s
D
F7.08 Deviation limit 0.0% - 100.0% 0.1% 0.5%

F8.00 Local address 1 - 127 1 1


0: 1200BPS
1: 2400BPS
Communication 2: 4800BPS
F8.01 1 3
baud rate 3: 9600BPS
4: 192000BPS
5: 384000BPS

0: None check(N,8,

2)

1: Even check(E,8,
F8.02 Data format 1 0
1)

2: Odd check(O,8,

1)
Communication
F8.03 0ms~20ms 1ms 10ms
response delay
Communications
F8.04 timeout fault 0.0s ~ 100.0s 0.1s 10.0s
time

Action when 0:Maintain the status


F8.05 communication 0 0
fault 1:Stop running
Motor rated
F9.00 000.0kw– 900kw 0.1kw
power
Motor rated
F9.01 0V - 480V 1V
voltage
Motor rated
F9.02 0.1A - 999.9A 0.1A
current
Motor rated 0.01HZ - Maximum
F9.03 0.01hz
frequency frequency

0:Straight line V/F


curve
F9.04 v/f curve setting 1:Square V/F curve 1 0

2 : Multi-point V/F
curve
F9.05 Torque upgrade 0.0%- 30.0% 0.1% 5.0%
Torque upgrades
0.00HZ – Maximum
F9.06 and cutoff 0.01hz 30.00HZ
frequency
frequency
Slip
F9.07 compensation 0.0% - 200.0% 0.1% 0.0%
factor
Over excitation
F9.08 0 - 200 1 30
gain

0:G model
F9.09 Motor model 1 0
1:P model
Oscillation
F9.10 0 - 100 1 0
suppression gain
Carrier
F9.11 0.5khz–16.0khz 0.1 4kHZ
frequency
Multipoint v/f
F9.12 frequency point F9.14- F0.09 0.01hz 0.00Hz
f3
Multipoint v/f
F9.13 F9.15 - 100.0% 0.1% 0.0%
voltage point v3
Multipoint v/f
F9.14 frequency point F9.16 - F9.12 0.01Hz 0.00Hz
f2
Multipoint v/f
F9.15 F9.17 - F9.13 0.1% 0.0%
voltage point v2
Multipoint v/f
F9.16 frequency point 0 –F9.14 0.01Hz 0.00Hz
f1
Multipoint v/f
F9.17 0.0% - F9.15 0.1% 0.0%
voltage point v1

0:Invalid (Starts running directly if


Start protection Start terminal command is
FA.00 function effective) 1 1
1 : Valid(can not start if Start
terminal command is effective)
Fault auto reset
FA.01 0 - 20 1 0
times
Fault relay 0:Inaction
FA.02 action during 1 0
fault auto reset 1:Action
Intervals during
FA.03 000.0s – 600.0s 0.1s 1.0s
fault auto reset
Cleanout time of
FA.04 fault auto reset 0h – 3000h 1h 48h
times
Motor overload 0:Inhibit
FA.05 protection 1 1
selection 1:Permit
Motor overload
FA.06 protection 0.30 - 10.00 0.01 1.00
parameters
Motor overload
FA.07 pre-alarm 50% - 100% 1% 80%
coefficient,
Over-voltage 0:Invalid
FA.08 speed protection 1 1
select 1:Valid
Over-voltage
FA.09 speed protection 550-800V 1 700V
voltage level

0:Disable
Over-current
1 : Valid only when running at
FA.10 speed protection 1 2
select constant speed
2:Valid all the time
Over-current
FA.11 speed protection 50% - 200% 1% 150%
current level
Over-current
speed
FA.12 1.0-600.0s 0.1s 10.s
deceleration
time

0:Invalid
FA.13 AVR select 1 1
1:Valid all the time
2:Valid only when the speed is
decreasing

0:Invalid
Output lacking
FA.14 0 1
phase protection
1:Valid
FA.15 Reservation 0 0 0
The former
FA.16
second fault type
The former first
FA.17
fault type
The last fault
FA.18
type
Frequency when
FA.19
error occurs
Electric current
FA.20 when fault
occurs

DC bus voltage
FA.21
when fault
occurs
Input terminal
FA.22 state when fault
occurs
Output state
FA.23 when fault
occurs
FB Group Reserved
FC Group added parameters
Acceleration
FC.00 0.0s – 3200.0s 0.1s 10.0s
time 3
Deceleration
FC.01 0.0s – 3200.0s 0.1s 10.0s
time3
Acceleration
FC.02 0.0s – 3200.0s 0.1s 10.0s
time 3
Deceleration
FC.03 0.0s – 3200.0s 0.1s 10.0s
time3
FD Group
FD.00 password 0 - 9999 1 0
FD.01 Set run time 0 - 9999 1 0
0:Hour
FD.02 Set run time unit 1 0
1:Minute

Action selection 0:Continue to run


FD.03 when run time 1 0
reaches 1:Halt
FE Group user password parameters

FE.00 User password 0 - 9999 1 0

0:No operation
FE.01
1:Restore the factory parameters 1 0

2:Clear fault history information


FF Group Factory parameters
Factory Factory
FF.00 Factory code Factory setting
setting setting
Factory Factory
FF.01 Machine set Factory setting
setting setting
Temperature Factory Factory
FF.02 Factory setting
curve setting setting
Voltage 50 –
FF.03 1% 100%
correction factor 140%
Current 50.0 –
FF.04 0.1% 100.0%
correction factor 150.0%
Frequency
Factory Factory
FF.05 converter rated Factory setting
setting setting
current
Appendix 1: F5-05 Parameter values display when machine halts
0 Invalid
1 Running frequency
2 Preset frequency
4 DC bus voltage
8 Output voltage
16 Output current
32 Output power
64 AI1 voltage
128 AI2 voltage
256 PID set
512 PID feedback
1024 DI terminal status
2048 DO output status
4096 Motor speed

Appendix 2: F5-06 Parameter values display when machine halts


0 Invalid
1 Preset frequency
2 DC bus voltage
4 AI1 voltage
8 AI2 voltage
16 PID setting
32 PID feedback
64 DI terminal status
128 DO output status

Note: To display multiple parameters, add the corresponding numerical values


together, set corresponding functional code.