Documente Academic
Documente Profesional
Documente Cultură
Outline
• Introduction
• Types of overcurent relays
• Inverse, time-delay overcurrent relays
• Instantaneous overcurrent relays
• Directional overcurrent relays
Page 2
1
11/8/2019
Introduction
• The most obvious effect of a shunt fault is a sudden build up of current. Therefore, it
is only natural that the magnitude of current be utilized as a positive indication of
existence of a fault.
• An overcurrent (OC) relay is a type of protective relay which operates when the
current exceeds a pickup value.
Page 3
Page 4
2
11/8/2019
Page 5
Page 6
3
11/8/2019
Page 7
Page 8
4
11/8/2019
Page 9
Page 10
5
11/8/2019
Page 11
• It is often desirable to adjust the pick-up current to any required value. This is usually
achieved by the use of tappings on the relay operating coil.
• The taps are brought out to a plug bridge as shown in figure. The plug bridge permits
to alter the number of turns on the relay coil. This changes the torque on the disc and
hence, the time of operation of the relay.
• The current plug settings usually range from 50% to 200% in steps of 25% for
overcurrent relays.
Page 12
6
11/8/2019
Page 13
• The values assigned to each tap are expressed in terms of percentage full-load
rating of C.T. with which the relay is associated and represents the value above
which the disc commences to rotate and finally closes the trip circuit.
Pick-up current = Rated secondary current of C.T. × Current setting
• For example, suppose that an overcurrent relay is connected to a supply circuit
through a current transformer of 400/5 A has current setting of 125% . The rated
secondary current of C.T. is 5 A. Therefore, the pick-up value will be 25% more than
5 A i.e. 5 × 1.25 = 6.25 A. It means that with above current setting, the relay will
actually operate for a relay coil current equal to or greater than 6.25 A.
Page 14
7
11/8/2019
Page 15
Time-delay setting
• The operating time of a relay mainly depends upon two factors :
˗ How long distance to be travelled by the moving parts of the relay for closing
relay contacts
˗ How fast the moving parts of the relay cover this distance.
• To adjust the operating time of relay, both of the factors to be adjusted.
• The adjustment of travelling distance of an electromechanical relay is commonly
known as time dial setting (or time setting multiplier) of relay.
• In electromechanical relays, a time dial is provided that positions the moving contact
relative to a fixed contact. The dial is marked from a setting of ½ to 10, fastest to
slowest operating times, respectively.
Page 16
8
11/8/2019
10
½
10
Page 17
• By adjusting only the time dial setting, we cannot set the actual time of operation of a
relay because the time of operation of a relay also depends upon the speed of
operation.
• The speed of moving parts of relay depends upon the force due to current in the
relay coil. Hence, it is clear that the speed of operation of a relay depends upon the
level of fault current. In other words, time of operation of relay depends upon plug
setting multiplier.
• The relation between time of operation and plug setting multiplier (in terms of
multiples of the pickup (× pu value)) is plotted on a log-log graph paper.
• This allows the same curves to be used, regardless of the actual input value
corresponding to a specific tap setting.
Page 18
9
11/8/2019
Page 19
Page 20
(or PSM)
10
11/8/2019
• From this graph one can determine, the total time taken by the moving parts of an
electromechanical relay, to complete its total travelling distance for different PSM.
• This is an inverse time–current relationship, that is, the greater the operating current,
the less time it takes to travel from the reset position to the operating position.
• In solid-state relays, timing is achieved by electrical circuits using R–L–C timing
circuits.
• In digital relays, the time delays are established within the algorithm using the
internal clocks or by accessing external timers.
• The purpose of the time-delay setting is to enable relays to coordinate with each
other.
• A family of curves must be provided; so two or more relays, seeing the same fault as
defined by the multiples of pickup, can operate at different times.
Page 21
Example 1:
• Referring to figure, determine the operating time for a relay with a 4.0 A pickup,
time dial setting of 1.0, and 12.0 A operating current.
• The input current of 12 A corresponds to a value of 12/4 = 3 × pu, that is, PSM =
3. Using this value from the curve and the corresponding curve for the time dial
setting of 1.0 gives us an operating time of 1.375 s.
Example 2:
• As another example, for a relay with 5.0 A pickup, time dial setting of 2.0 and 15.0
A operating current, the operating current is 3 × pu, that is, PSM = 3 and the
operating time corresponding to a time dial setting of 2 is 2.25 s.
Page 22
11
11/8/2019
Example 3
• Determine the time-delay lever setting to achieve an operating time of 1.0 s for a
relay set at 10.0 A pickup and an operating current of 50.0 A.
• The input current of 50.0 A corresponds to a value of 50/10 = 5 × pu, that is, PSM =
5. Using this value on the abscissa and the operating time of 1.0 s on the ordinate,
the corresponding time dial curve is 2.0.
Example 4
• Consider a relay with a pickup setting of 5.0 A and the same operating time of 1.0 s
and fault current of 50 A. The operating current is 50/5 = 10 × pu on the abscissa,
that is, PSM = 10 and 1.0 s operating time on the ordinate, corresponding to the
curve of a time dial setting of 5.0.
Page 23
Example 5
• Finally, consider a relay with the same pickup setting of 5.0 A, the same operating
time of 1.25 s, and an operating current of 35.0 A. The input current is 35/5 = 7 ×
pu, that is, PSM = 7, which at an operating time of 1.25 s, corresponds to a time dial
setting between the curves labelled 3 and 4.
• In electromechanical relay design, the time dial is a continuous adjustment; so
interpolation between two settings is possible, and a setting of 3.5 can be made.
Page 24
12
11/8/2019
• Inverse, time-delay overcurrent relay must be set so it will always operate for faults in
its zone of protection. This will require margins above normal operating currents and
below minimum fault currents.
• Rules for relay setting:
˗ For phase relays, it is necessary to calculate the maximum load current, and
minimum phase fault current through system planning studies.
˗ The relay should then be set somewhere between twice maximum load current
and a third of the minimum fault current value.
˗ The actual setting must be an evaluation of setting closer to the maximum load,
increasing dependability and decreasing security or achieving less than three
times pickup for minimum fault, decreasing dependability, and increasing security.
Page 25
• A ground relay must “see” all phase-to-ground faults within its zone of protection, and
under conditions that give a minimum fault current. Note that in calculating ground
current, it is the zero-sequence current that is of interest (ground current = 3I0).
• There is no concern for load current, but normal phase and load unbalance and CT
errors must be considered and the relays set above these values.
• Again, setting between twice the “normal” ground current and a third of the minimum
fault value is desirable.
• In the absence of any other information, the normal ground current may be taken to
be 10% of the load current.
Page 26
13
11/8/2019
Example:
• Determine the CT ratio, pickup, and time dial settings for the relay at breaker 1,
assuming that no coordination with any other relay is required.
Page 27
• Select a CT ratio to give 5.0 A secondary current for maximum load, that is, 95/5 =
19 : 1. Since this is not a standard CT ratio (refer to Table 3.1), we select the nearest
CT ratio of 20 : 1 or 100 : 5.
• The relay pickup setting should be bracketed by twice the maximum load and one-
third of the minimum fault. Using the actual CT ratio, twice maximum load is 190 A
divided by 20, or a relay current of 9.5 A.
• Assuming the relay has taps 4.0, 6.0, 8.0, 10.0, and 12.0, we would select the 10.0 A
tap, giving a primary current relay pickup of 200 A. Dividing by 95 A load current
results in a margin of 2.1 × pu to prevent false operation (security).
Page 28
14
11/8/2019
• The minimum fault is 600 A divided by the relay pickup of 200 A, which gives 3 × pu
to ensure correct operation (dependability).
• For this configuration, no coordination is required; so one can set the time delay at
the lowest dial setting (fastest time) of ½.
Page 29
Page 30
15
11/8/2019
• A relay must get an adequate chance to protect the zone under its primary
protection. However, if the primary protection does not clear the fault, the back-up
protection should initiate tripping.
• Naturally, the primary protection is the first to operate, its operating time being less
than that of the back-up relay.
• In the light of the above discussion, the correct procedure for the relay coordination
would be to start the setting from the tail end of the feeder system.
• The relay, which is at the end of the radial feeder, can be made to operate without
any delay, as it does not have to coordinate with any other relay.
• The main drawback is that the closer the fault is to the source, the greater the fault
current magnitude, yet the longer the tripping time.
Page 31
Page 32
16
11/8/2019
• Example: Given the magnitudes of all the loads and the fault currents at all the
buses, set the OC relays at buses A, B, C and D so that the entire feeder gets over-
current protection arranged as primary and back-up protection.
Page 33
• For fault F1 at the end farthest from the generating source, relay Rd, tripping breaker
(4), operates first; relay Rcd at breaker (3) has a higher time lever setting which
includes a coordinating time delay S to let breaker (4) trip if it can.
• Similarly, relay Rbc, at breaker (2), coordinates with the relay at breaker (3) by having
a still longer time delay (including the same coordinating time S);
• Finally, relay Rab at breaker (1) has the longest time delay and will not trip unless
none of the other breakers trips, provided it can see the fault, that is, provided the
fault current is greater than its pickup setting.
• If a fault occur between breakers (3) and (4), relay Rd will receive no current and
therefore will not operate; relay Rcd will trip, since its operating time is faster than that
of relay Rb.
Page 34
17
11/8/2019
• For the settings shown in figure, relay Rab will not see this fault. Relay Rb must still
provide backup relaying for this fault.
• Thus, the following rule could be established for the overcurrent relay coordination:
TRd = 0.1 sec (fastest)
TRcd = TRd + TCB, Rd + Safety margin
• A fault at the end of the line should be cleared by Rd and CB4. Rcd sees the same
fault as Rd and starts to close its contacts.
• Assuming electromechanical relays, if the circuit breaker clears the fault, Rcd will
reset after some over-travel (or overshoot). Thus, contact over-travel is included in
the margin of safety.
Page 35
Page 36
18
11/8/2019
• Over-travel does not apply to solid-state or digital relays that do not have moving
parts although some safety margin would be provided.
• If the fault is not cleared, Rcd continues to close its contacts and initiates a trip of CB3
at the end of its operating time. To be sure that Rcd does not close its contacts before
the fault is cleared by CB4, it must be set longer than Rd operating time (U), plus CB4
clearing time (V), and a factor of safety (X) (including overtravel, VV).
• It is usual to add 0.3 – 0.5 s coordinating time to the operating time of Rd, which is
calculated at its maximum fault. The same fault current is used to determine the
operating time of relay Rcd.
Page 37
• Assume we have a radial system with two adjacent line segments. The relay
protecting the next line segment closest to the source must protect its own line and,
if possible, back up the relays protecting the next line.
Page 38
19
11/8/2019
• From the previous example, the pickup setting of Rb is 10.0 A, and the time dial
setting is ½.
• Theoretically, to ensure that Rab backs up Rb, it should be set for the same pickup
current, that is, it sees the same faults, but is set at a slower (higher) time dial.
• The operating time of Rb is determined at the maximum fault current at bus B (1500
A) divided by its pickup setting (20 × 10 A) or 7.5×pu and the ½ time dial, resulting
in 0.25 s. Add 0.3 s coordinating time and Rab operating time should be 0.55 s.
• Now, at the same maximum fault current of 1500 A at bus B and pu of 20 × 10 A,
the multiple of the tap setting is 7.5 × pu and the operating time is 0.55 s.
• Interpolating between the time dial setting curves of 1 and 2 gives a setting of 1.5.
Page 39
Page 40
20
11/8/2019
• In order to properly apply the instantaneous overcurrent relay, however, there must
be a substantial reduction of short-circuit current as the fault is moved away from the
relay toward the far end of the line.
• The relay must be set not to overreach the bus at the remote end of the line and
there still must be enough of a difference in the fault current between the near-and
far-end faults to allow a setting for the near-end fault.
• This will prevent the relay from operating for faults beyond the end of the line and, at
the same time, will provide high-speed protection for an appreciable portion of the
circuit.
Page 41
• In simple inverse-time overcurrent relays, the closer the fault is to the source, the
greater the fault current magnitude, resulting in a longer the tripping time.
• Thus, the simple inverse-time overcurrent relays cannot be used without additional
help and the addition of instantaneous overcurrent relays makes this system
protection viable.
• If an instantaneous relay can be set to see almost up to, but not including, the next
bus, all of the fault-clearing times can be lowered.
Page 42
21
11/8/2019
Page 43
Setting Rules
• Since the instantaneous relay must not see beyond its own line section, the values
for which it must operate are very much higher than even emergency loads.
• Therefore, load is not usually a consideration for the instantaneous relay setting. As
a result, there is no need to set an instantaneous overcurrent relay with margins
such as 200% of load and one-third of fault current.
• However, in addition to the inaccuracies of the relay itself, there is a factor called
“transient overreach” that must be considered.
• Transient overreach is the tendency of a relay to instantaneously pick up for faults
farther away than the setting would indicate.
Page 44
22
11/8/2019
• It is therefore common to set an instantaneous relay about 125 – 135% above the
maximum value for which the relay should not operate, and 90% of the minimum
value for which the relay should operate.
• Assignment: For the data specified in previous example, set the instantaneous
relays at buses A and B.
Page 45
Page 46
23
11/8/2019
• Directional relays require two inputs, the operating current and a reference, or
polarizing quantity (voltage or current) that does not change with fault location.
• The operating torque of a two-input relay, which may be used to provide the
directional feature is given by universal relay torque equation.
• Directional overcurrent relaying is necessary for multiple source circuits, when it is
essential to limit relay tripping for faults in only one direction.
• It would be impossible to obtain correct relay selectivity through the use of a non-
directional overcurrent relay in such cases.
• If the same magnitude of the fault current could flow in either direction at the relay
location, coordination with the relays in front of, and behind, the non-directional relay
cannot be achieved except in very unusual system configurations.
Page 47
Page 48
24
11/8/2019
Page 49
Suggested Readings
Page 50
25
11/8/2019
26