Sunteți pe pagina 1din 112

manual

Installation and operating instructions

ϑ ϑ

M M M M
O2
PE X6-03 X6-02 X6-01 X7-03 X7-02 X7-01 PE

module
X5-01

min
Start
L

PE
L
N
PE
L
N
PE

N
L
N
PE
L
N
PE

H0-Start

Start
L

X8-03

L V1
PE L
V3

V2
SV
X5-02

min PE
M

L N
X8-02

ON/OFF V1
X5-03

3 L
2 OIL L
X8-01

L GAS L

INT L min.
P

max.
X9-03

GAS
P

LT
X4-01

OIL (CPI)
P

L
X9-02

RESET PE
PE IGNITION N
X4-02

N V1 L
X9-01

L V2 L
PE PV L
P
X4-03

N SV L
L (START)
X10-03
W-FM 200

ION
FSV/QRI
PE
FLAME

X10-02

N
X3-01 X3-02 X3-03

L MOTOR
L
L ALARM
Power QRI
P

QRB
L
L
FLANGE LINE
X10-01

N
L
G0
SAFETY 12VAC
G
L LOOP
X3-04

PE
L LINE
VOLTAGE
N

F1/T6,3 F2/T4 F3/T4


IEC 127-2/V IEC 127-2/V IEC 127-2/V

info esc

Weishaupt Combustion Manager W-FM 83054802 - 1/2004


1 General instructions 4 8 Load controller
8.1 Set operating mode
38
38
8.2 Configure sensors 39
8.3 Set point (external) 40
2 Safety instructions 5 8.4 Set point (internal)
8.5 Modulating load control
41
42
8.5.1 Parameter internal load control 42
8.5.2 Optimise internal load control 43
3 Technical description
3.1 Function
6
6
8.6 Multi-stage load control
8.7 Cold start function
44
45
3.2 Display and programmer unit ABE 7

9 Parameter and functions 46


4 Installation
4.1 Safety instructions for installation
8
8
9.1 Menu structure (ABE)
9.2 Operating display
46
54
4.2 Installation of components 8 9.3 Operation 54
4.3 Electrical connection diagram 9.4 Manual operation 55
(principle drawing) 10 9.5 Burner control 56
9.5.1 Times 56
9.5.2 Configuration 56
9.5.3 Product identification and
5 Preparation for commissioning
5.1 Safety instructions
16
16
software version
9.6 Ratio control
56
57
5.2 Steps to be taken on burner 9.6.1 Setting gas/oil 57
and frequency converter 16 9.6.2 Times 61
5.3 Preparation steps on 9.6.3 Switch off behaviour 61
combustion manager 16 9.6.4 Programme stop 61
9.7 O2 control and guarding 62
9.7.1 Setting gas/oil 62
9.7.2 Process data 64
6 Commissioning - modulating
6.1 Set fuel and load points on W-FM
18
18
9.8 Load controller
9.8.1 Control parameter
65
65
6.2 Commission burner 19 9.8.2 Temperature switch 66
6.2.1 Set mixing pressure for ignition 19 9.8.3 Cold start 67
6.2.2 Burner ignition 20 9.8.4 Configuration load controller 68
6.2.3 Set load point 1 21 9.8.5 Adaption 71
6.2.4 Start full load 22 9.8.6 SW version 71
6.2.5 Optimise full load 23 9.9 AZL (ABE) 72
6.2.6 Redefine intermediate load points 24 9.9.1 Times 72
6.3 O2 functions - modulating 26 9.9.2 Language 72
6.3.1 Set O2 sensor 26 9.9.3 Date format 72
6.3.2 Set O2 control 27 9.9.4 Physical units 72
6.3.3 Set O2 regulating functions 28 9.9.5 eBus 72
6.3.4 Check and optimise O2 control 28 9.9.6 Modbus 73
6.3.5 Optimise O2 control 29 9.9.7 Display contrast 73
6.4 Concluding work following 9.9.8 Serial number and SW version 73
commissioning 30 9.10 Stepping motors 74
6.4.1 Set ratings range and flue gas 9.10.1 Addressing 74
temperature limit values 30 9.10.2 Rotation direction 74
6.4.2 Concluding work on the burner 31 9.10.3 Serial number and SW version 74
9.11 FC module 75
9.11.1 Configuration 75
9.11.2 Process data 76
7 Commissioning multi-stage
7.1 Set fuel and required rating
32
32
9.11.3 Serial number and SW version
9.12 O2 module
76
77
7.2 Adjust burner 33 9.12.1 Configuration 77
7.2.1 Pre-set curve parameters 33 9.12.2 Display values 77
7.2.2 Burner ignition 34 9.12.3 Serial number and SW version 77
7.2.3 Start full load 35 9.13 System configuration 78
7.2.4 Set switch off point(s) 36 9.14 Operating hours 78
7.2.5 Check operating, switch on 9.15 Start counter 79
and off points 36 9.16 Fuel meter 79
7.2.6 Check start behaviour 37 9.17 Updating 80
7.2.7 Define full load as required load 37 9.17.1 Parameter back-up 80
9.17.2 Load SW from PC 80
9.18 Password 80
9.19 TÜV test 80
9.20 Sequence of operation diagrams 81

2
10 O 2 sensor 86

11 Frequency converter
11.1 Programming and display unit frequency
88

converter VLT series 88


11.2 Parametering VLT 2800 90
11.3 Parametering VLT 5000 92

12 Cause and rectification of faults 94

13 Maintenance
13.1 Safety information for maintenance
105
105
13.2 Maintenance plan 105

14 Technical data
14.1 Combustion manager W-FM
106
106
14.2 Servomotor SQM45.../48... 107
14.3 Flame guarding 108
14.4 Display and operating unit (ABE) 109

A Appendix
Notes 110

3
1 General information
These installation and operating instructions Hand-over and operating instructions
• are an integral part of the equipment and must be The contractor is responsible for passing the operating
kept permanently on site. instructions to the plant operator prior to hand-over. He
should also inform the plant operator that these instruc-
• are to be used by qualified personnel only. tions should be kept with the heating appliance. The
address and telephone number of the nearest service
• contain the relevant information for the safe assembly, centre should be entered on the reverse of the operating
commissioning and servicing of the equipment. instructions. The plant operator must note that an agent of
the contractor or other suitably qualified person must
• are for the attention of all personnel working with the inspect the plant at least once a year. To ensure regular
equipment. inspections, -weishaupt- recommends a service contract.

• in addition to this installation and operating manual, The contractor should instruct the plant operator in the use
the documentation for the relevant burner and the of the equipment prior to hand-over and inform him as and
type of frequency converter must be observed. when necessary of any further inspections that are required
before the plant can be used.

Explanation of notes and symbols Guarantee and liability


This symbol is used to mark instructions, Weishaupt will not accept liability or meet any guarantee
which, if not followed, could result in death or claims for personal injury or damage to property arising as
serious injury. a result of one or more of the causes below:
DANGER • Failure to use the equipment as intended
• Improper assembly, commissioning, operating or
This symbol is used to mark instructions, servicing of the equipment.
which, if not followed, could result in life • Operating the appliance with defective safety
threatening electric shock. equipment, or with non-recommended or non-
functioning safety and protection devices
DANGER • Failure to follow the information in the Installation and
Operating Instructions
• Alterations made to the construction of the equipment
This symbol is used to mark instructions, by the plant operator
which, if not followed, could result in damage • Fitting additional components not tested or approved
to, or the destruction of the equipment and for use with the equipment.
environmental damage. • Alterations made to the equipment by the plant
ATTENTION operator (e.g. motor ratio - rating and speed)
• Alterations made to the combustion chamber, which
hinders constructive, predetermined flame formation
• Inadequate guarding of parts liable to wear and tear
☞ This symbol is used to mark procedures, • Improperly executed repairs
which you should follow. • Acts of God
• Damage caused by continued use despite the
1. Procedures with more than one step are occurrence of a fault
2. numbered. • Use of incorrect fuel
3. • Obstruction or damage of the supply lines
• Use of non-original -weishaupt- spare parts
❑ This symbol is used when you are required to
carry out a test.

• This symbol is used to list points.

➩ This symbol indicates detailed information

Abbreviations
Tab. Table
Ch. Chapter

4
2 Safety information 2
Dangers when using the equipment Electrical safety
Weishaupt products are manufactured in accordance with • Before starting work - isolate plant and protect against
the relevant existing standards and guidelines and the reactivation, check voltage is isolated, the unit is
recognised safety laws. However, improper use of the earthed, and protected from adjacent equipment that
equipment could endanger life of the user or a third party, might still be under voltage!
or result in damage to the plant. • Work on the electrical supply should be carried out by
a qualified electrician
To avoid unnecessary danger, the equipment is only to be • Electrical components should be checked during
used: servicing. Loose connections and heat damaged
• for its intended purpose cables should be dealt with immediately.
• under ideal safety conditions • The control panel should be locked at all times. Access
• with reference to all the information in the installation should be restricted to authorised button holder
and operating instructions personnel.
• in accordance with inspection and service work. • Should it be necessary to carry out work on live parts,
country specific safety regulations must be observed
Faults, which could affect the safe operation of the burner, and tools to EN 60900 must be used. A second
should be rectified immediately. person should be present to switch off the mains
supply in an emergency.

Personnel training
Only competent personnel may work on the appliance. Maintenance and fault rectification
Competent personnel according to this operating manual • Necessary installation, service and inspection work
are persons who are familiar with the installation, should be carried out at the specified time.
mounting, setting and commissioning of the product and • Inform the operator before beginning any service
have the necessary qualifications such as:- work.
• Training, instruction or authorisation to switch electrical • For all service, inspection and repair work, electrically
circuits and electrical devices on and off, to earth them isolate the equipment and ensure the mains switch
and to mark them in accordance with the safety cannot be accidentally switched back on. Cut off the
standards. fuel supply.
• Training, instruction or authorisation to carry out • Flame guarding devices, limit controls, correcting
installation, alteration and maintenance work on gas elements and all other safety devices must be
installations in buildings and on site. commissioned by, and may only be replaced by, the
manufacturer or an authorised agent.
• Following service work, all safety devices should be
Organisational measures tested to ensure they are functioning correctly.
• Everyone working on the plant should wear the
necessary protective clothing.
• All safety devices should be checked regularly. Alterations to the construction of the equipment
• No alterations to the equipment are to be made without
the approval of the manufacturer.
Informal safety measures All conversions require written confirmation from Max
• In addition to the installation and operating instructions, Weishaupt GmbH.
local codes of practice should also be adhered to. • Any parts not in perfect working order should be
Special attention should be paid to the relevant replaced immediately.
installation and safety guidelines given. • No additional components may be fitted, which have
• All safety and danger notices should be kept in a not been tested for use with the equipment.
legible condition. • Use only -weishaupt- replacement and connection
• Furthermore, all safety documentation and danger parts. Parts from other manufacturers are not
notes covering the frequency converter and burner guaranteed to be suitable to meet the necessary
must be observed. operational and safety requirements.

Safety measures in normal operation


• Only use the equipment when all the safety devices are
fully functional.
• The moving parts of the burner should not be touched
during operation.
• At least once a year the equipment, including the safety
devices, should be checked for signs of visible damage
and to ensure that the safety devices are operating
correctly.
• More frequent safety check may be required
depending on plant conditions.

5
3 Technical description
The combustion manager W-FM contains all functions Functions
required for safe and efficient operation of multi-stage or • Burner control
modulating single fuel and dual fuel burners. • Electronic compound regulation for up to a max of
The display and programming unit shows the conditions 5 1 stepping motors
and allows programming via dial knob and function • Speed control
buttons. • O2 control
• Valve proving
• True dual fuel operation
• Integral load/ratings controller 2
• Flame guarding
• Separate ABE programmer

3.1 Function
Combustion manager Load controller 2
The combustion manager: The optional, integrated PID load controller can be used as
• controls the sequence of operation a temperature or pressure controller for multi-stage or
• guards the flame modulating burners, depending on the connection and
• communicates with the stepping motors parametering. Furthermore the load controller contains a
• controls and guards the frequency converter control reaction damper which protects the stepping
• carries out valve proving of the gas valves motors from unnecessary drive impulses, thus protecting
• has: – an integrated load controller 2 the stepping motors and increases their life span.
– Speed control 1 The load controller can be operated with one external
– O2 control 1 setting value or set point input, or with two internal set
points.
The internal set points can be selected using an external,
Operating elements potential free contact.
The system can be controlled by several operating units: Switchover from an external operation to the internal load
• a plug-in programmer ABE controller is via a contact.
• PC module for guard control A separate start up programme is incorporated for boiler
• Remote main control system (Building Management cold start if required.
System)

Speed control 1
Flame sensor The frequency converter of the fan motor is started by a set
Guards the flame during all phases of operation. If the point output (0/4 - 20 mA) and the speed is matched to
flame signal does not correspond to the sequence of the current burner rating required. The speed and the
operations, a safety lockout will occur. rotation are determined and guarded using an inductive
Flame sensors used: proximity switch in conjunction with an asymmetrical
• QRI for continuous or intermittent operation for oil, transmitter disc. In compound with the stepping motors
gas and dual fuel burners. the required combustion air is automatically adjusted and
• Ionisation electrode only for gas for continuous or the electrical consumption is reduced to a minimum.
intermittent operation. If the air supply fails or becomes insufficient, an air
pressure switch initiates lockout.
Stepping motors
Separate stepping motors (as appropriate) on: O2 Trim control 1
• Air damper The residual O2 content in the flue gas is determined by a
• Oil controller sensor, which compares it to the set points calculated
• Gas butterfly valve during commissioning. Depending on the control
• Mixing head deviations from the set points, the combustion manager
Providing precise, direct control of the correcting elements re-adjusts the air regulating devices and corrects the
in the compound. burner’s aeration.
Individual setting values are transmitted via CAN BUS from
the combustion manager to the stepping motors, the
stepping motors are electronically adjusted and the Low gas programme
combustion manager constantly guards their position If the control gas pressure falls below the setting of the low
return signals. gas pressure switch during operation, the combustion
manager starts a low gas programme.
If the gas pressure is below the set point prior to start, the
burner start is inhibited.

1
only W-FM 200
2
optional on W-FM 100

6
3
Valve proving (only on gas operation) Sequence diagram valve proving
Following each controlled shutdown, the combustion
1st. Test phase 2nd. Test phase
manager carries out a valve proving test of the gas
solenoid valves.
Following lockout or power failure, the valve proving test is Valve V1
carried out prior to the next burner start. 3 secs.
sek. 10
10sek.
secs. 3 secs.
sek. 10
10sek.
secs.
Valve V2
Function
1st. Test phase:
During a controlled shutdown valve V1 closes P between
V1 and V2
immediately, and valve V2 has a slight delay in closing
which permits the volume between the valve seats to Gas press.
depressurise. The section between V1 and V2 must switch VP
remain depressurised once the second valve has
closed.
Setting pressure gas pressure switch
2nd. Test phase:
Valve V1 opens and immediately closes again, PR + PV
allowing gas pressure build-up between V1 and V2 = setting pressure
valve seats. During the test phase, the pressure 2
between the valve seats must not fall below the
pressure setting of the gas pressure switch XX. PR = Control pressure into V1 (reduce impact pressure)
PV = Maximum pressure during pre-purge downstream of V2

3.2 Display and programmer unit ABE


Setting without tools Display and programmer unit ABE
The advantage of electronic ratio control provided by the
W-FM lies in the simple setting via display menus. The
positioning for fuel, air, and auxiliary actuators is selected
digitally. With only a few input ratings-positions being
entered, the intermediate firing positions are automatically
interpolated.

Display
4 lines with scroll function

ESC button
Cancel or return
Info button
Return to operating display
Enter button
Execution
Scroll knob
Cursor control and value change

RS 232 interface (COM1)


For PC or Laptop connection
CAN Bus
Connection to W-FM
RJ45 interface for eBus/Mod Bus (COM2)

Emergency - Off function


Simultaneous pressing of the ESC and Enter buttons
immediately initiates lockout. The Emergency - Off function
is saved in the lockout history.

Contrast adjustment
To change the contrast of the display, press Enter button
and hold down whilst changing the contrast using the
scroll knob (+/–). (Only possible in menu Normal
operation, contrast adjustment with saving see Ch. 9.9.7).
7
4 Installation
4.1 Safety instructions for installation
Electrically isolate the plant Note Due to the frequency converters used it is
Prior to installation switch off the mains switch possible for some of the electrical
and the safety switch. components to continue to be energised
Failure to comply could cause death or following mains isolation. The waiting time
serious injury by electric shock. given must therefore be observed prior to
DANGER starting work.

4.2 Installation of components


The electrical connections should be carried out to the
wiring diagram supplied with the burner. All country and
local codes of practice (i.e. EN, DIN, VDE, BS, etc.) must
be observed.

Line length Gas valve train


The line length of the individual components to the W-FM The pre-wired gas valve train should be connected as per
can be a maximum of 100 m. the wiring diagram supplied with the burner. Cable entry is
When installing the stepping motors and the ABE it is via the cable entry access on the right of the burner.
particularly important that the total line length of all Bus
connections (CAN-Bus) does not exceed 100 m.

External connections
Mains voltage carrying lines (230V; 50 Hz) should be
Display and programmer unit ABE flexible and have a minimum cross section of 0.75 mm. The
The installation of the ABE to the W-FM is carried out with PE terminals on the fixing plate of the W-FM should be
a special CAN-Bus cable. This cable supplies voltage to used for earth wire connection.
the ABE and transmits the BUS signals.

O2 sensor / O2 module (only W-FM 200)


Stepping motors The electrical connection of the O2 sensor or O2 module
The installation is carried out as a serial Bus system. should be carried out to the wiring diagram supplied with
• Air damper the burner. Please note that the screened sensor line of
• Gas butterfly valve the O2 sensor must be connected separately and line
• Oil controller length must not exceed 10 m.
• Mixing head Installation O2 sensor see Ch. 10.
The voltage supply of the stepping motors and the
communication with the W-FM is carried out via CAN-Bus
cable.
Bus connection
On last component of the Bus line, a Bus connection
should be made using the jumper supplied. On all other
Frequency converter (only W-FM 200) components within the Bus, the Bus termination jumper
The electrical connection of the frequency converter has to must not be connected.
be carried out to the wiring diagram supplied with the On the ABE the Bus connection is inbuilt.
burner. When wiring, ensure that the screens of the cable
are connected only once to the W-FM (FE terminal).

Flame sensor
The 1.8 m senor line to the flame sensor can be extended
by up to 100m if installed separately (i.e. for W-FM in a
separate control panel).

Ignition line
The ignition cables should be installed as close as
possible to the ignition electrodes. Ignition cables must
have an adequate spacing away from any other wiring.

8
4
Installation example: W-FM in burner housing Installation example: W-FM in a control panel

O2 module Jumper with Bus (only W-FM 200) O2-Modul Jumper with Bus (only W-FM 200)
connection connection

5 5

Burner Burner
SQM4... SQM4... SQM4... Frequency SQM4...
no Bus
SQM4...
no Bus
SQM4...
no Bus
no Bus no Bus no Bus
con- con- con- converter 2 con- con- con-
ABE nection nection nection nection nection nection

2 AT
5 5 5
5 5

AC1 12V 4 AT

AC2 12V 4 AT

AC2 12V
AC1 12V
CANH
CANL
GND
GND
5 5
AC2 12V
AC1 12V

AC2 12V
AC1 12V
CANH

CANH
CANL

CANL
GND

GND

4 AT

4 AT
ABE

6,3 AT
5

W-FM

AC2 12V
AC1 12V
CANH

CANH
CANL

CANL
GND

GND
Netz
4 AT

4 AT
5

6,3 AT
(only W-FM 200)

W-FM
Frequency Frequency
converter
converter 1
Mains

(only W-FM 200)


Frequency converter

Frequency
converter

W-FM fitted into a control panel


A second supply transformer is required for the Bus supply
if distance between W-FM and burner is an extended
distance. The supply transformer 2 is fitted to the burner
and connected to the burner terminal rail. The voltage
supply of all following Bus components is exclusively via
supply transformer 2.
The voltage supply (AC1 and AC2) must not be connected
to the bus line from W-FM to burner terminal rail.
Bus line W-FM to control panel order number: 743 192.

9
10
T2 F10 S7 T1 Y9 F36 F35 Y7
X30-03 X30-02 1
4
3
2 4
P P< P>

12V
12V
2
1 P 2 3 1 2 3 1
3
2 (F10) X36 PE 2 3 1
X35 PE 2 3 1
2

12V

230V
1 1
X30-01

1
3
4
1
1
1
3
1
1
1
1
3

1
3
4
2
2
2
2
3
2
2
3
2
3
2

X10-01
X52
X3-02
X3-03
X4-02
X4-03
X5-01
X5-02
X6-02
L N L L PE N L L N PE PE L PE L PE N L
L PE N L L L L L N W-FM 200

2
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
1

1
2

1
X60
X61
X62
X63

0
0
0 2

FE
FE
FE 3

FE

X3-01
X3-04
X4-01
X5-03
X6-01
X7-03
X6-03

X8-01
0 - 10V
0 - 10V

4 - 20mA0
4 - 20mA0
4 - 20mA0

SX
Power Sensor
4.3 Electrical connection (principle drawing)

B3
X63
X62

Y10 Pt100

2 1 3

Pre-selection Gas
Pre-selection Oil
Burner on
ext. controller
contacts
P20W/P30W

Burner reset
B3 B3
= Set point

Set point switchover or

FX SX

PE
L

Burner lockout
Start release Oil
Residual oil immediate
start
Start release Gas
Gas operation
Oil operation
KX Pt/Ni1000
X60/X61 = actual value

Function X60 - X63 only


= Plotter output

with internal load controller

FX
KX SX
operating type switchover load controller

Motor start
contactor
Safety circuit
230V 1/N/PE 50-60Hz N
Return signal motor
protection contact
Legend:
A1 Combustion manager
External connections B3 Appliance’s temperature/ pressure sensor
Additional connections F10 Air pressure switch
F35 Max. oil return pressure sensor
F36 Min. oil supply pressure sensor
S7 Burner flange limit switch
T1 Ignition unit
T2 Control transformer
Y7 Magnetic coupling
Y9 Solenoid valve on air pressure switch
Y10 Anti siphon fuel valve
FE certified earth
Y14
(U /2)
Y15
N (UN/2)
Y11 Y12 Y14
(U /2)
Y15
(U /2)
N N

Y11

1
2
3
4

1
2
3

1
2
3
1
2
3
1
2
3
4

X8-03

X7-01
X7-02
X7-01
X8-03

On multi stage
Light-oil burners
size 30 - 40
On modulating
Light-oil burners
sizes 30 - 70
PE N L

Y11 Y12
(UN/2) (UN/2)

Y14
(U /2)
Y15
N (UN/2)

Y12 Y13 Y11 Y14 Y11

(Option)

On multi stage
Heavy-oil burners
size 30 - 50
On modulating
Heavy-oil burners
sizes 30 - 70

1
2
3
1
2
3
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

X7-01
X7-02
X8-02
X8-03
X8-02
X8-03

PE N L PE N L L N PE L N PE L N PE L N PE
W-FM 200

Legend: Y11 Solenoid valve/nozzle solenoid


Y11 Partial load solenoid valve Y12 Solenoid valve (normally open)
Y12 Intermediate load solenoid valve
Y13 Full load solenoid valve Y14 Additional solenoid valve
Y14 Additional solenoid valve Y15 Additional solenoid valve
Y15 Additional solenoid valve
4

11
12
B12
4

BU

BN
BK
B12

BN
BU
1
3
4
5

X70
W-FM 200

DC in
0/4-20
mA out

12-24V

1
2
3
4
1
2
3
4
1
2
3
4
5
6

X71
X72
X73
B20 B21

+24V
Start frequency converter
Lockout frequency converter
Set point
Earth
Screen

BN
BU

BN
BU
5

Connection
B20 B21 frequency converter

Legend:
B12 Proximity switch burner motor
B20 Fuel meter Gas (optional)
B21 Fuel meter Oil (optional)
A2 Y20 Y17 Y19 Y18
B1 QRB B1 1
3 5 M M M M

BK

BN
4/6 Bus interface

1
3
4
5

X10-02.1
5
7 5 5 5
X72
QRI B1 5 5

X70
4
7
2

8
3

braun
blue
black
1
3
4
5
1
3
4
5

1
2
6
2
6

2
4
5
6

X10-03
X10-02.2
X50
X51
L PE N
W-FM 200

2
1
4
1

3
2

4
3
2
1

X9-03
X9-02
X9-01

9
5
3
2

8
7
1
4

PE
Connection control panel
External signalling pressure switch (optional) 10

9
5
3
2

8
7
1
4

PE

2
1
1
1

3
2
4
3
2
1
2
1
4
3
2
Terminal box gas valve train Connection O2 module

Only with O2 control (optional)

X21-01
X21-02
X20-03
X20-02
X20-01
3
2

2
3
2
3
2
3
2
3
2
3
1
4
2
3
2
3

1
1
1
1
1
1
1

X22-01
X22-02
X22-03
X23-01
X23-02
X23-03
X24-01
X24-02
X24-03

2
1
Legend:

A2 Display unit/programmer

PE
L1
PE
L1
PE
L1
PE
N
PE
L1

N
L2
N
L2
N
L2
L1
L2
N

X8 X8B X8A X9 X9A


B1 Flame sensor
1 2 3 1 2 3 1 2 3 2 1 3 1 2
F11 Low gas pressure switch
F12 Valve proving pressure switch
P< P> P> 1 2 F33 High gas pressure switch
Y3 Y1 Ignition gas solenoid valve
Y2 Main gas solenoid valves
F11 F33 F12 Y2 Y1 Y3 Remote solenoid valve
Y17 Oil controller stepping motor
Y18 Gas butterfly stepping motor
Y19 Mixing head stepping motor
Y20 Air damper stepping motor
4

13
14
O2 sensor
Mains voltage QGO20
4

M
B1

U3

PE
B2

Q4
Q5
G2
3

6
5
4
3
2
1
6
2

5
4
3
1

3
2
1
3
2
1
3
2
1

3
2
1
X81

X89-01
X89-02
X82

X83
L N PE L N PE
O2 module

GND
GND

CANL
CANL

CANH
CANH

12VAC1
12VAC2
12VAC1
12VAC2

1
2
3
1
2
3
1
2
3
1
3
4
5
1
3
4
5

2
2

X88
X87
X86
X85
X84 5

Legend:

B10 Combustion air temperature sensor


B11 Flue gas temperature sensor
Connection stepping
motor
B10 B11
Pt/Ni1000 Pt/Ni1000
Usensor FE
2 Wire
Pulse-IN 0

LOAD
3 Wire-PNP

X63
OUTPUT
0 4-20mA
PE X6-03 X6-02 X6-01 X7-03 X7-02 X7-01 PE
Reserve

P
FE

L
L
L

L
L
L
L
N
N

N
N
min

X70
N

PE
PE
PE

PE
PE
FE 0

X5-01
Start

Start

MOTOR SPEED INPUT


L V1

X8-03
Usensor 4-20mA

H0-Start
INPUT
2 Wire PE L
Pulse-IN 0-10V SET POINT

V2

V3

P
SV
M
3 Wire-PNP min
X62
PE
0

X5-02
OIL GAS OIL

X71
L N
FE FE
ON/OFF V1

X8-02
Usensor 0
2 Wire 3 L
Pulse-IN 4-20mA

X5-03
INPUT

3 Wire-PNP 2 OIL L
0 0-10V
TEMP./PRES.

X72
X8-01
L GAS L
X61

FUEL COUNTER INPUT


FE Power Supply
Sensor

FE
Start-OUT
min.

P
INT L
12-24VDC Alarm in
TEMP.

max.

P
GAS
0/4-20mA Setpoint OUT
Pt100

LT

X9-03

P
OIL
Pt/Ni1000

(CPI)
X60

X4-01
L

X73
FE PE
RESET

FREQUENCY CONVERTER
X9-02

PE IGNITION N
N V1 L

X4-02
L V2 L
FE
X9-01

P
PE PV L
12VAC2
N SV L
M

X4-03
TRAFO

L (START)
X52

12VAC1
X10-03

ION
FSV/QRI
PE
BUS

N
FLAME

L MOTOR
W-FM
L GND
X10-02

L ALARM
Power QRI CANL

P
QRB CANH
L
L 12VAC2
FLANGE LINE
N 12VAC1

X3-01 X3-02 X3-03


L
X51

G0 Shield
X10-01

SAFETY 12VAC
G GND
L LOOP
CANL
PE
CANH

X3-04
L LINE
VOLTAGE 12VAC2
N
12VAC1
X50

Shield
BUS

F1/T6,3 F2/T4 F3/T4


IEC 127-2/V IEC 127-2/V IEC 127-2/V
4

15
5 Preparation for commissioning
5.1 Safety note
Check installation Safety notes on initial commissioning
All installation work must be completed and The initial commissioning must only be carried out by the
checked prior to commissioning. The burner supplier, manufacturer or their appointed agent. At this
must be mounted on the appliance, ready for time, all the control and safety equipment must be
operation and all control and safety devices checked to ensure correct operation and, if it can be
DANGER must be connected correctly. adjusted, it should be checked that it has been set
correctly.

❏ Burner mounted, including refractory as required Furthermore the correct fusing of the circuits and the
❏ Fuel supply complete measures for contact protection of electrical equipment
❏ Electrical connections and controls complete and of all wiring must be checked

5.2 Preparation on the burner and the frequency converter


Burner Additional data relating to the burner and frequency
Check setting on burner, vent fuel lines and connect converter can be found in the relevant installation and
measuring instruments. operating instructions.
If the burner is fitted with a moving mixing head (with
stepping motor), this should be checked for freedom of
movement.

Frequency converter 1 (only for Danfoss VLT...)


Check parameter settings on frequency converter (see
parameter list Ch. 11).

Carry out automatic motor adaption on frequency


converter using parameter 107 (not possible on all
frequency converters).

Note Due to the automatic motor adaption, the motor-slip


adjustment and the load compensation are set
back. These parameters must be re-set to the -
weishaupt- data (parameter 134, 136 on VLT 2800
or 113, 114 and 115 on VLT 5000).

5.3 Preparation on the combustion manager


1. Burner OFF Burner Off
To be able to carry out the following steps it is necessary
to set the burner to OFF in menu Manual Operation. Manual Operation ➩ Ch. 9.4
Auto/Manual/Off
Auto/Manual/ Off
Curr: Automatic
New: Burner Off

2. Enter password Enter password


By asking for a password it is ensured that only authorised
personnel have access to the configuration and setting Enter PW ➩ Ch. 9.18
parameter. Access SERV
Enter digit or number using the dial knob at the flashing Enter
cursor point and confirm with <ENTER>. password
Corrections can be made using <ESC>, empty data :........
spaces should be filled using <ENTER>. -

1
W-FM 200 only when used with frequency converter
16
5
3. Carry out speed control standardisation 1 Speed standardisation
During speed control standardisation a set point signal of ➩ Ch. 9.11.1
95% is given. The speed is determined and saved in Parm + display
parameter Standardised Speed. If, during standardisation FC module
more than 50Hz is displayed, the motor-slip compensation Configuration
(=0) on the frequency converter has to be checked. Speed control
Standardisation
The rotational direction of the motor should be checked Standardisation
during speed standardisation. Curr: deactivated
New: activated
Note After each speed standardisation, or changes to the
saved values, the combustion quality needs to be
checked.

4. Check configuration of O2 module 1 O2 module configuration


The following parameter should be check and set for ➩ Ch. 9.12.1
operation with O2 trim control. Parm + display
O2 module
• O2-Sensor: QGO20 Configuration
• Supply air sensor:PT1000 (if fitted) O2 sensor
• Flue gas sensor: PT1000 (if fitted) SupAirTempSens
• MaxTempFlueGas: Presetting 400° C FlueGasTempSens
MaxTempFlGas

5. Check O2 sensor temperature 1 Check O2 sensor temperature


The O2 sensor requires an internal operating temperature ➩ Ch. 9.12.2
of 700° C ±(15°C). If the sensor has been connected Param + Display
incorrectly, this can lead to overheating and thus damage O2 module
of the sensor. If the sensor temperature exceeds 750° C, Displayed values
the sensor should be isolated and the electrical QGOSensorTemp
connection should be checked. QGOHeatingLoad

Note The QGOSensorTemp and QGOHeatingLoad


should be guarded regularly during the heat up
process.

HeatingLoad: Start heating load to 100° C ___approx. 13%


Heat up process ____________approx. 60%
Operating temperature: __approx. 15… 25%

6. Deactivate O2 trim control 1 Automatic O2 trim control deactivate


For commissioning the O2 trim control for the individual ➩ Ch. 9.7.1
fuels, the O2Ctrl should initially be deactivated. Param + Display
The O2 controller and the O2 guard have no influence on O2Ctrl/GuardDeac
the burner operation at this setting. t Setting ...
OperatingMode
Note On dual fuel burners the O2 trim control should be OperatingMode
deactivated on both fuels. Curr: man deact
New: man deact

7. Enter fuel type Enter fuel type


To be able to calculate the combustion efficiency it is
necessary to define the type of fuel used. Param + Display ➩ Ch. 9.7.1
If a fuel is used which is not available for selection, its fuel O2Ctrl/Guard
specific values can be entered under Fuel type def. Setting ...
Fuel type
Note On dual fuel burners both the oil and gas type must Fuel type def.
be entered.

1
only W-FM 200 in connection with frequency
converter or O2 module
17
6 Commissioning - modulating
6.1 Set fuel and load limits on W-FM
Select fuel (only on dual fuel burners) Select fuel
Select the required fuel using the external fuel selection
switch. If an external fuel selection switch is not available, Operation ➩ Ch.9.3
fuel selection is made using the ABE or BMS. Fuel
Fuel selection or:
Note The external fuel selection switch takes priority. That Fuel selection Fuel selection
means the commissioning can only be carried out Curr: Oil switch on Oil
with the fuel set at this switch. New: Gas

Check load limits Load limits


To ensure that the whole ratings range is available for
commissioning, check load points and adjust if necessary. Param + Display ➩ Ch. 9.6.1
MinRating: _______________________________ 0,0 % RatioControl
MaxRating: _______________________________ 100 % GasSettings
LoadLimits
Note On dual fuel burners the load points for oil and gas MinLoadGas
should be checked. On single fuel oil and gas MaxLoadGas
burners only one fuel appears in the display.

18
6
6.2 Commissioning the burner
6.2.1 Set mixing pressure for ignition
Set Program stop 36 Program stop 36: Ignition position without ignition
Prior to the first ignition trial, the program stop must be set
to 36 IgnitionPos. After burner start the burner runs to the RatioControl ➩ Ch. 9.6.1
ignition position without actual ignition occurring. ProgramStop
ProgramStop
Note In its delivered condition the program stop has Curr: 36 IgnitionPos
already been factory pre-set to 36. New: 36 IgnitionPos

Open manual fuel shut off devices and the burner is Burner On
ready to start
After the fuel shut off devices have been opened the RatioControl ➩ Ch. 9.3
burner should be started in manual operation. Auto/Manual/Off
Auto/Manual/Off
Note For burner start all safety devices, pressure and Curr: Burner Off
temperature controllers should be in operating New: Burner ON
position.
Ensure sufficient heat requirement for the duration
of the commissioning procedures.

Set ignition position Ignition positions (example gas operation 3LN multiflam®)
Set the ignition positions whilst observing the mixing
pressure. RatioControl ➩ Ch. 9.6.1
The speed during ignition should not be less than 80% for GasSettings
oil and 70% for gas (only when using a frequency SpecialPositions
converter / W-FM200). IgnitionPos IgnitionPosGas
If the measured mixing pressure is too high, this can be IgnitionPosGas Curr: 10.5°
adjusted by reducing the air damper position. IgnitionPosAir New: 15°
IgnitionPosAux
The relevant ignition pre-settings should be taken from the IgnitionPosFC
installation and operating instructions of the burner or its IgnitionPosAir
test data sheet. Curr: 13°
New: 10°
Note The auxiliary motor position on 3LN burners
(multiflam®) in ignition position and during burner IgnitionPosAux
operation must be a minimum of 18°. Curr: 18°
New: 19°

IgnitionPosFC
Curr: 100%
New: 70%

19
6
6.2.2 Burner ignition
Set program stop 52 Program stop 52: ignition after safety time
To ignite the burner the program stop should be set from
36 to 52. Fuel is released following SpecialPositions ➩ Ch. 9.6.1
pre-ignition. The motors remain in the ignition positions ProgramStop
setting. ProgramStop
Curr: 36 IgnitionPos
New: 52 Interv 2

Pre-set fuel pressure


On oil and dual fuel burners the oil throughput for full load
has been measured, that means the pump pressure has
been factory pre-set (20-30 bar) and should only be
adjusted if starting problems occur.

The gas setting pressure can be found in the installation


and operating instructions of the burner.

Carry out combustion analysis


Determine CO, O2 values and carry out smoke
measurement. If necessary, optimise combustion by
adjusting the ignition positions.

20
6
6.2.3 Set load point 1
Deactivate program stop Deactivate program stop
To continue with commissioning the program stop has to
be deactivated. If the program stop is not deactivated, the RatioControl ➩ Ch. 9.6.1
burner remains in the position set and setting of additional ProgramStop
load points is not possible. ProgramStop
Curr: 52 Interv 2
New: deactivated

Set load point 1 Take over Ignition load point as load point 1
In setting oil, the first load point has been programmed by
the factory. GasSettings ➩ Ch. 9.6.1
If the first load point has been deleted, the ignition load CurveParams
values will be taken over automatically as the first load Point Load :15.0
P Point Load :15.0
point just as with Setting Gas. Burn:15.0 : 1 Burn :15.0
In both cases the values should be matched and a ManualAir :10.0 O2 Air :10.0
combustion analysis should be carried out. Aux1 :19.0 4.9 Aux1 :19.0
FC :70.0 FC :70.0

At the first load point the fuel dependent minimum speed1 Change load point 1
should be aimed for whilst observing the combustion ➩ Ch. 9.6.1
quality and flame stability. Point Load: 10.5
Point I Point
Procedure: : 1 C
Change?
1. Drive up the air damper stepping motor until a residual Point Load:15.0 Point Load :15.0
O2 content in the flue gas of max. 8% has been 1 Burn:15.0 1 Burn:15.0
achieved (on 3LN burners multiflam® max. 7% residual O2 Air :10.0
A O2 Air :223.6
O2 content in the flue gas). 4.9 Aux1 :19.0 4.9 Aux1 :19.0
FC :70.0 FC 50.2
:5
2. Reduce speed1 (not below minimum speed). To
achieve minimum speed it may be necessary to repeat
steps 1 and 2. Point esc
save- >ENTER
3. Carry out combustion analysis and if necessary delete- >ESC
optimise combustion by adjusting the air damper
position.

4. Leave point 1 by pressing <ESC> and save by Point Load :15.0


pressing <ENTER>. : 1 Burn :15.0
O2 Air :23.6
5. Leave programming of point 1 by pressing <ESC>. 6.4 FC :50.2
Note If the burner is fitted with an auxiliary motor and
speed control the value selected by the turn knob is
displayed in the last line. Minimum speed

Fuel Setting Frequency


FC at transformer

Oil (pump separate) 60 % approx. 30 Hz

Oil (pump fitted) 70 % approx 35 Hz

Gas 50 % approx 25 Hz

1
only W-FM 200 with speed control
21
6
6.2.4 Start full load
Drive to full load via intermediate load points Increase load manually
Starting from the first load point, drive to full load via the
intermediate load points. Point Load:15.0 ➩ Ch. 9.6.1
Burn :15.0
Procedure: Hanual Air :23.6
M
1. Set cursor to Manual and press <ENTER>. Aux1 :19.0

2. Increase burner rating using the dial knob, whilst


guarding the combustion quality (excess air, flame O2 Load :15.0 O2 Load:25.0
stability). 6.4 Burn :15.0 6.1 Burn :23.8
Manual Air :23.6 Manual Air :31.4
3. Set intermediate point before reaching the combustion . Aux1 :19.0
:15.0 :19.8 Aux1 :27.3
limit by pressing <ENTER> (on 3LN multiflam max. 7%
residual O2 content in the flue gas).
Setting intermediate load points, correcting and saving
4. Carry out combustion analysis and correct intermediate
load point values. O2 Load :25.0 O2 Load :25.0
L
6.1 Burn :23.8 roint18.7
Punkt Load:25.0
5. Leave load point by pressing <ESC> and save with Manual Air :31.4 : 2uft :28.4
2 Burn :21.9
<ENTER>. :19.8 Aux1 :27.3 8O2 Hilfs:60.1
Air :228.8
26.0
5.9 Aux1 :2
Repeat procedure until full load (Load: 100) has been
reached. FC :56.0

Point esc
Save- >ENTER
enter->ESC

Point Load:100
:5 Burn:73.6
O2 Air :67.8
3.8 Aux1 :78.5

22
6
6.2.5 Optimising full load
Optimising full load
In the last load point (load = 100%) the exact fuel quantity
throughput for the required full load should be set.

Note Observe load data supplied by the appliance


manufacturer and the capacity graph of the burner.

Procedure:
1. Set fuel throughput
Optimising full load
Gas: At 65° to 70° gas butterfly setting, determine ➩ Ch. 9.6.1
gas throughput and adjust using the setting Point Load :100
screw on the pressure controller. 5 Burn 68.7
:6
O2 Air :67.8
Oil: Set pump pressure required, determine oil 4.5 Aux1 :78.5
throughput and adjust using stepping motor
setting of the oil controller (see burner test data
sheet: Indicator setting oil controller).

2. Determine combustion limit at full load and set excess


air. Point Load :100
The fan speed should be selected as low as possible 5 Burn:68.7
whilst observing NOx and flame stability, however it O2 Air :776.2
should not be below 40 Hz / 80% (only when using 3.8 78.0
Aux1 :7
frequency converter / W-FM 200).
FC 88.8
:8
3. Re-determine fuel quantity throughput and if necessary
adjust.
Once this step has been completed, the pump and gas
setting pressure must not be altered.

4. Save full load point.

23
6
6.2.6 Re-define intermediate load points
Re-define load point 1 Drive to load point 1 and optimise combustion
To later allow O2 control across the whole ratings range,
point 1 must be a minimum 30% below the required partial Point Load :100
load (only when using an O2 module / W-FM 200). :5 Burn:68.7
O2 Air:76.2
Procedure: 3.8 Aux1 :78.2
1. Select point 1 with dial knob, press <ENTER>, confirm
Change point with <ENTER>, point 1 is started.

2. Check combustion quality, and optimise if necessary. Point Load :15.0 Point Point
Drive to combustion limit, note down and set excess air :1 Burn:15.0 : 1 c
vhange?
required for combustion limit. O2 Air :23.6 löschen?
Point Load:15.0
Excess air: • without O2 control approx. 15% to 20% 6.4 Aux1 :19.0 11.9
: 1 Burn:1
• with O2 control approx. 20% to 25% O2 Air :2 22.2
6.3 Aux: 18.6
Please observe the minimum speed and the mixing FC 50.0
:5
pressure required.

3. Determine fuel quantity throughput and carry out


ratings distribution.

4. Save load point 1.

Delete intermediate points Delete intermediate load points


Delete intermediate load points and re-define.
To achieve an even speed reference line, the fan speed at Point Load:15.0
the newly set intermediate load points should not be : 1 Burn:11.9
altered (only when using a frequency converter / W-FM O2 Air :22.2
200). 6.3 Aux :18.6

Procedure;
Select Point 2 with dial knob, press <ENTER>, confirm
Delete point with <ENTER>, point 2 is deleted and the Point Load:19.8 Point Point
setting values for the next intermediate load point : 2 Burn :19.3 : 2 change?
below point 2 appear automatically. O2 Air :25.5 Manual d
lelete?
Repeat procedure, until full load settings appear under 5.9 Aux1 :23.2 Point Load :449.6
point 2. : 2 Burn: 35.9
Do not delete the full load point (Load: 100) and point Manual Air: 47.3
1. 47.1 Aux1 :444.2

Check
Select point 3 with dial knob. If all intermediate load
points have been deleted, no values are defined in
point 3 and the following display is shown.
Point Load: 100
:2 Burn: 68.7
Point Load :XXXX O2 Air :76.2
: 3 Burn: XXXX 3.8 Aux1 :78.2
Manual Air :XXXX
Aux1 :XXXX

24
6
Set new intermediate load points and carry out ratings Reduce rating and optimise combustion
distribution in percentages
For burner operation 5 load points are required, this means Point Load: 100 ➩ Ch. 9.6.1
at least 3 intermediate load points must be set. Burn :68.7
depending on the installation, more intermediate load Hanual Air :76.2
M
points may be required (maximum 15 load points). Aux1 :78.2

Note When using O2 trim control, partial load cannot be


set below point 2, this means point 2 should be set O2 Load :100 O2 Load :90.0
smaller or equal to the eventual partial load. 3.8 Burn :68.7 3.9 Burn :62.0
Manual Air :76.2 Hand Air :69.7
Procedure 0 Aux1 :78.2
100 .
:90.0 Aux1 :71.2
1. Leave load point by pressing <ESC>, select manual Point Load :89.7
function using the dial knob and confirm with : 3 Burn: 62.0
<ENTER>. O2 Air: 68..8
70.7
4.0 Aux1 :7
2. Whilst observing the combustion quality, reduce the
FC :84.2
burner rating using the dial knob.
Recommendation: 10% steps
Point esc
3. Optimise combustion quality and set excess air
Save- >ENTER
required for the combustion limit
Delete->ESC
Excess air: • without O2 control approx. 15% to 20%
• with O2 control approx. 20% to 25%

To maintain an even speed reference line, the speed Point Load :100
should not be adjusted after this process if at all : 3 Burn :68.7
possible (only when using a frequency converter / W- O2 air :76.2
FM 200). 4.0 Aux1 :78.2
4. Determine fuel quantity throughput, calculate rating esc
and carry out ratings distribution.
P
Point Load :89.7
Burn :62.0
5. Leave point using <ESC> and save with <ENTER>.
HAnd Air :68.8
Aux1 :70.7
6. Repeat procedure for all curve points.
FC :84.2

Example ratings distribution


➩ Ch. 9.6.1
Throughput intermediate load point
Rating [%] = • 100
Throughput full load

Gas:

305 m3/h
Rating [%] = • 100 = 89.7 %
340 m3/h

Oil:

260 kg/h
Rating [%] = • 100 = 89.7 %
290 kg/h

Point .
Load:90.0 Punkt Load 89.7
:8
: 3 Burn:62.0 : 3 Burn :62.0
O2 Air :68.8 O2 Air :68.8
4.0 Aux1 :70.7 4.0 Aux1 :70.7

25
6
6.3 O2 functions modulating
The settings for the O2 trim control must only be carried
out if a W-FM 200 with O2 trim control is to be used.

6.3.1 Set O2 guard


The combustion limit has to be determined for each ‘P’ O2 guard
point, and saved in the guard function as the O2 minimum
value. The operating type for O2 control / guard or must be Param + Display ➩ Ch. 9.7.1
deactivated during setting. O2Ctlr/Guard
If the O2 limit values are already known, these can be Setting
entered directly as O2 minimum values. O2 Guard
It is also possible to drive to the combustion limit of each
load point and to copy over the determined O2 set points
as O2 min. values.

Direct entry of known O2 limit values: Direct entry O2 min value


1. Select point to be set using the dial knob and confirm
with <ENTER>. Point:1
: 13.9% ➩ Ch. 9.7.1
:9
Point:9 100%
2. Select O2 min value using dial knob and confirm with Point:9 100% Point:9 100%
<ENTER>. 02-Minval: 0.0. 02-Minval: 0..7
P-Airman : 0.0 P-Airman: 0.0
3. Enter the O2 min value using the dial knob and save
with <ENTER>.

4. Enter O2 min value in the O2 graph on the right.

Determine O2 value of combustion limit and note it: Determine combustion limit
1. Select the point to be set using the dial knob and
confirm with <ENTER>. Point:1
: 13.9% ➩ Ch. 9.7.1
:9
Point:9 100%
2. Select P air manual using dial knob and confirm with Point:9 100% Point:9 100%
<ENTER>. 02-Setpoint: 3.8 02-Setpoint: 0.7
P-AirHand: 0.0. 10.4 .
P-AirMan:1
3. Turn dial knob to the right. The air rating is reduced on
the curve flow line in relation to the ratings setting of P
air manual. The fuel quantity throughput remains
unchanged.
Reduce air rating until the combustion limit (CO or O2 graph
soot) has been reached. 8

4. Leave setting level with <ESC> and save the O2 value 7


as min value for the guard function using <ENTER>. 6
O2 content [%]

5
5. Enter O2 min value in the graph on the right.
4
3
2
1
0
0 10 20 30 40 50 60 70 80 90 100

Burner rating [%]

26
6.3.2 Set O2 trim control
6
For subsequent O2 trim settings, a standardisation has to O2 trim
be carried out at each point.
Param Display ➩ Ch. 9.7.1
O2Ctlr/Guard
Setting ...
O2 trim

Procedure: Standardisation
1. Select point to be set using the dial knob and confirm
with <ENTER>. Point:2
: 21.1% ➩ Ch. 9.7.1
02-Verbund
: :xxxx
Point:2 21.1% Point :221.1%
2. As soon as the O2 value is stabilised confirm with 02-Sollwert:xxxx
O2 RatioCon: 6.0 O2 RatioCon: 6.0
<ENTER>. Normierert :xxxx
If the value is stable O2 SetPoint:3.9
continue with ENTER StandardVal:11.3
.
3. Turn dial knob to the right. The air rating is reduced on
the curve flow line in relation to the ratings setting of
Point esc
standardisation value. The fuel quantity throughput
remains unchanged. save- >ENTER
The standardised O2 value should be 1 to 1.5% points delete->ESC
above the combustion limit (O2 min value of guard
function) and minimum of 1 % point below the O2 ratio.

4. Leave setting level with <ESC> and save the O2 value delay time is
using <ENTER>. measured O2 Actual
value: 4.2
Note At point 2 and with 100% the time (Tau) between Measurem success
the air quantity change and its recognition at the O2 ControlParam has
sensor is determined. This results in the controller been determined
parameters for subsequent O2 control. continiue with ESC

Example: O2 set points


Following completion of the O2 standardisation the ratio
curve points should not be altered, otherwise the 8
standardisation for the point altered will be deleted and 7
O2 control will not be possible. If a curve point is altered, O2
6 ratio
Con
the standardisation for this point will have to be repeated.
O2 Content [%]

trol
5
O2 S
4 etP
oint
3 O2 G
Control limit uard
At burner ratings in the lower load range, the flue gas 2
velocity at the O2 sensor may not be sufficient for correct 1
and problem free control. In this case the O2 control limit
0
must be increased accordingly. 0 10 20 30 40 50 60 70 80 90 100

Flue gas velocity [v]: min. = 1 m/s Burner load [%]


max. = 10 m/s or sensor temperature
min. 680°C
O2 control limit
T+273
QB · L · λ Param + Display ➩ Ch. 9.7.1
273 O2Ctrl/Guard
v=
d2 · 0.785 · 3600 Setting ...
O2CtrlThreshold
QB = Fuel throughput (kg/h) (m3/h)
L = Stoichiometric air requirement (m3/kg) (m3/m3)
λ = Air number
T = Flue gas temperature °C
d = Flue gas pipe diameter (m2)

QB · 0,0046 T+273
General formula: v = 2 ·
d 273
27
6
6.3.3 Set O2 controlling functions
The O2 trim control function is set using OptgMode. O2 operating mode

man deact Param + Display ➩ Ch. 9.7.1


The O2 control and O2 guard are deactivated. The burner O2Ctrl/Guard
starts with cold sensor (only for commissioning, not Setting ...
recommended for normal operation). OptgMode
OptgMode
O2 guard Curr: man deact
Only the O2 guard is active. New: conAutoDeac
Start-up only when the operating temperature of the
sensor has been reached.
If the O2 guard reacts, or if an error is detected during
measuring, lockout occurs, if there is no possibility of
repetition.

O2 controller
The O2 controller and O2 guard are active.
Start-up only when the operating temperature of the
sensor has been reached.
If the O2 guard reacts, or if an error is detected during
measuring, lockout occurs, if there is no possibility of
repetition.

conAutoDeact
The O2 controller and O2 guard are active.
Start-up before operating temperature of the sensor has
been reached.
If the O2 guard reacts, or if an error is detected during
measuring the function auto deact is initiated.

auto deact (not recommended)


The O2 controller and the O2 guard have been deactivated
automatically by the function

conAutoDeact.
The burner remains in operation, however without O2
control and O2 guard.
6.3.4 Check and optimise O2 control
Check O2 control If the O2 sensor has reached its operating temperature,
Procedure: and the controller’s damping time (10 x Tau in partial load)
1. Re-start burner in automatic operation. The start has elapsed, pre-control starts and the O2 value goes
behaviour can be checked again. close to the set point. If within the delay time (approx. 2 x
Tau in full load) no load changes occur, control goes to the
2. Change rating with external signal, so that the O2 value O2 set point. The actual O2 value should then be equal to
can be checked on the display of the ABE • i.e. the O2 set point.
connect a 3 pole switch to X5-03 and change over the
LC operating type to ExtLC X5-03. When a load change occurs the O2 controller is locked at
the existing value, and the air motors are re-adjusted with
3. In menu “OperationalStat” select “NormalOperation” the pre-control starting from the previous differential value
and change over to the second display using setting. This means that the O2 set point is almost
<ENTER>. maintained even during pre-control.

4. Carry out various load changes across the whole Note The O2 control can also be guarded using
ratings range whilst observing the O2 controller’s recording software.
behaviour.

28
6
6.3.5 Optimise O2 control
Depending on site specific requirements it may be O2 control parameters
necessary to adjust the O2 control parameters in the
SERV level. Param + Display ➩ Ch. 9.7.1
O2Ctlr/Guard
Setting ...
ControllerParams

O2 actual value fluctuates


If the control fluctuates parameter I and P should be
optimised.

In the lower ratings range:


I-Partial reduce increase
or
PP-Partial load reduce

In the upper ratings range


I-Full load load increase
or
P-Volllast P-Full load

O2 control remains locked


If a ratings change occurs prior to the end of the locking
times the controller remains stationary.

LoadCtrlSuspend increase
FilterTmeLoad reduce

O2 guard reacts at ratings change


A rapid ratings change will result in lockout by the O2
guard.

LoadCtrlSuspend increase
O2Offset increase

29
6
6.4 Concluding work following commissioning
6.4.1 Lower load limit (partial load)

Observing the instructions given in the installation and Set lower load limit
operating instructions of the burner and the instructions
given by the appliance manufacturer, partial load and the GasSettings ➩ Ch. 9.6.1
control range should be set in menu Load limits. Here, LoadLimits
partial load is defined with parameter MinLoad. MinLoadGas
MinLoadGas
Curr: 0.0%
New: 22.8%

Flue gas temperature limit value Set flue gas temperature limit values
If the limit value is exceeded the warning Flue gas
temperature too high is given. A prerequisite for this is a Param + Display ➩ Ch. 9.12.1
configured flue gas temperature sensor on the O2 module O2 Module
(only W-FM 200). Configuration
The limit value should be set approx. 20% above the flue MaxTempFlueGas
gas temperature at nominal load.

Overheating due to flue gas temperatures


above 300°C can damage the O2 sensor.

ATTENTION

Select second fuel (only on dual fuel burners) Fuel Selection


Select required fuel using the external fuel selection
switch. If an external selection switch is not available fuel Operation ➩ Ch. 9.3
selection is made with the ABE or BMS. Fuel
Curr fuel or:
Note The external fuel selection switch has priority, this Fuel selection Fuel selection
means commissioning can only be carried out with Curr: Oil switch set
the fuel selected with this switch. New: Gas to oil

30
6
6.4.2 Concluding work on the burner
Following commissioning the following, concluding work
has to be carried out on the burner.
• Set air pressure switch.
• Set gas and oil pressure switches.
• Remove measuring devices,
• etc ...

More detailed information can be obtained from the


installation and operating instruction of the burner.

31
7 Commissioning multi-stage
Prior to commissioning the preparations necessary for
commissioning (Ch. 5) must be completed.

7.1 Set fuel and required load


Burner OFF Burner OFF
To be able to carry out the following steps the burner has
to be set to OFF in menu Manual Operation. Manual operation ➩ Ch. 9.4
Auto/Manual/Off
Auto/manual/Off
Curr: Automatic
New:: Burner Off

Select fuel Oil (only on dual fuel burners) Select fuel


Select fuel Oil using the external fuel selection switch. If an
external fuel selection switch is not available, fuel is Operation ➩ Ch. 9.3
selected using the ABE or BMS. Fuel
Curr fuel or:
Note The external fuel selection switch has priority, this Fuel selection Fuel selection
means commissioning can only be carried out with Curr: Gas switch is set
the fuel selected with this switch. New: Oil to Oil

Select required rating S1 Select fuel


In menu Manual operation call up the function required
load and set to S1. Manual operation ➩ Ch. 9.3
Required load
Required load
Curr: S3
New: S1

32
7
7.2 Adjust burner
7.2.1 Preset curve parameter

For commissioning the fan speed1 and air damper setting Call up stepping motor positions
of each operating point as well as the On/Off switch points ➩ Ch. 9.6.1
must be checked and if necessary adjusted. Param + Display
RatioControl
Procedure; Oil Settings
1. Call up stepping motor positions. CurveParams
Curve Settings
2. Select option Without start Stepping motor
positions
3. Call up operating, the on and off stage switch points With start
one by one using the dial knob and compare air damper Without start
setting (air stepping motor) and fan speed1 (FC) with
table values. If they deviate, overwrite the parameter
by Activate option ‘without start’
• calling up operating, on and off switch points with
<ENTER>, ➩ Ch. 9.6.1
• selecting parameter using dial knob and confirming Stepping motor Point Air :40.0
with <ENTER>, positions ::BS1 FC :80.0
• inputting parameter value (dial knob +/-) and saving With start O2
with <ENTER>. W
Without start xxxx
• Continue procedure until all parameters are the same
as the table values.
Call up operating, on and off switch points
1
two Air damper [°<] Speed [%] ➩ Ch. 9.6.1
operating stages Air PC Point Air :40.0 Point Air :40.0
::BS1 FC :80.0 ES2 FC
::E :90.0
Operating point BS1 40 80 O2 O2
Switch on point ES2 xxxx xxxx
Switch off point AS2 70 100
Operating point BS2
Overwrite parameters

three Air damper [°<] Speed [%]1 Point Air :40.0


operating stages Air motor Auxiliary motor ES2 Point
::E FU ALir
ir0 :40.0
:ES2 FC :90.0
Operating point BS1 30 80 O2
Switch on point ES2 xxxx

Switch off point AS2 change values with dial knob


Operating point BS2 50 90
Switch on point ES2 Point Air :40.0 Point Air :40.0
:ES2 FFC :90.0 :ES2 FC 80.0
:8
Switch off point AS3 70 100 O2 O2
Operating point BS3 xxxx xxxx

Point Air :40.0


4. Exit level with <ESC>. :ES2 FFC :80.0 save values
O2
xxxx

Exit level

Without start SSpecialPositions


Operating point S3
esc
CurveParams
Air motor: 70.0 LoadLimits
AAux motor: 100

1
Only W-FM200 in connection with frequency
converter
33
7
7.2.2 Burner ignition
Set programme stop 36 Programme stop 36: Ignition position without ignition
Prior to first ignition the programme stop has to be set to
36 IgnitionPos. After burner start, the burner then drives to SpecialPositions ➩ Ch. 9.6.1
ignition position without igniting (with long pre-ignition, ProgramStop
ignition is carried out without fuel release). ProgramStop
Curr: 36 IgnitionPos
Note In its delivered condition the programme stop has New: 36 IgnitionPos
already been factory pre-set to 36.

Open manual fuel isolation devices and start burner Burner On


Once the fuel shut off devices have been opened the
burner should be started in manual operation. RatioControl ➩ Ch. 9.4
Auto/Manual/Off
Note For the burner start all safety devices, pressure and Auto/Manual/Off
temperature controllers must be in operating Curr: Burner Off
position. New: Burner On
Sufficient heat demand must be ensured for the
duration of commissioning.

Setting ignition position Set air damper fan speed and ignition position
The fan speed and the ignition position of the air damper
should be set whilst observing the mixing pressure. The RatioControl ➩ Ch. 9.6.1
ignition speed1 should not be below 80%. Depending on OIlSettings
the burner, the mixing pressure for ignition should be SpecialPositions
between 3 and 5 mbar. The mixing pressure can be IgnitionPos
adjusted with the air damper and diffuser positions. * The IgnitionPosOil does
IgnitionPosOil* not need to be set for
It is recommended to note down the IgnitionPos set IgnitionPosAir multi-stage operation, as
values.. IgnitionPosAux no oil throughput regu-
IgnitionPosFC lator valve and thus no
stepping motor is fitted.

Set programme stop 44 Programme stop 44: ignition position after safety time
To be able to ignite the burner the programme stop has to
be set from 36 to 44. Once the pre-ignition time has SpecialPositions ➩ Ch. 9.6.1
elapsed fuel is released. The stepping motors remain in the ProgramStop
ignition position setting. Programmstopp
Curr: 36 IgnitionPos
New: 44 Interv 1

Check fuel pressure


The atomising pump pressure is factory pre-set and can be
determined from the burner test data sheet.

Deactivate programme stop Deactivate programme stop


The programme stop has to be deactivated to continue
commissioning. If the programme stop is not deactivated, ProgramStop ➩ Ch. 9.6.1
the burner remains in the existing position, the setting of Curr: 44 Interv 1
new load points is therefore not possible. New: deactivated

1
only W-FM 200 in connection with frequency
converter
34
7
7.2.3 Start full load
Activate option “With start” Activate option “With start”
In stepping motor positions activate the option “With start”
by pressing <ENTER>. CurveParams ➩ Ch. 9.6.1
Curve Settings
Stepping motor Point Air :40.0
Note Operation of the switch off points should be positions ::BS1 FC :80.0
avoided during commissioning, as this can lead to With start O2
excessive air deficiency. Without start xxxx

Pre-set operating point S1 Pre-set operating point and set switch on point
1. Select operating point S1 using the dial knob and
confirm with <ENTER>. Point Air :40.0 ➩ Ch. 9.6.1
2. Call up parameter values using the dial knob and ::BS1 FC :80.0
<ENTER> and adjust operating point BS1 whilst O2
observing the combustion quality. xxxx

Note The burner motor speed XX should not be selected


below 70% (30 Hz).
Lir
Point A :36.0 Point Air 36.0
:3
3. Exit parametering with <ESC>. :BS1 F C :80.0 :BS1 FC 74.0
:7
O2 O2
xxxx xxxx
Set switch on point S2
1. Select switch on point S2 using the dial knob and esc
confirm with <ENTER>.
Start next operating or
2. Call up parameter values using the dial knob and Point Air :33.0 switch on point and set
<ENTER> and increase excess air whilst observing the ::BS1 FC :63.0 parameter.
flame stability. O2
3. Note down values. Do not operate switch off
xxxx point
4. Exit parametering with <ESC>.

Note When using a three stage burner the procedure has


to be repeated for operating point BS2 and switch
on point ES3.

Set Full Load


1. Select full load point using the dial knob and confirm
with <ENTER> .
2-stage burner: operating point BS2
3-stage burner: operating point BS3

2. Determine fuel throuhput and adjust if necessary.

3. Call up the parameter values using the dial knob and


<ENTER> , and optimise combustion (carry out a
combustion test)

4. After saving with <ENTER> exit parametering with


<ESC> .

1
only W-FM 200 in connection with frequency
converter 35
7
7.2.4 Set switch off point(s)
Change over to option “Without start” Activate option “Without start”
Exit option With start in stepping motor positions with
<ESC> and re-enter Curve setting to select option Curve Settings ➩ Ch. 9.6.1
Without start and activate with <ENTER>. Stepping motor Point Air :33.0
positions ::BS1 FC :63.0
With start O2
W
Without start xxxx

Set switch off point S2 Set switch off point(s)


1. Using the dial knob select switch off point AS2 and
confirm with <ENTER>. Point Air :50.0 ➩ Ch. 9.6.1
2. The air damper and motor speed of switch on point of AS2 FC
::A :90.0
ES2 should also be set for the switch off point of AS2. O2
and save with <ENTER>. xxxx
3. Exit parametering with <ESC>.

Note When using three stage burners repeat procedure


and transfer values from switch on point ES3 to iir
Point A :50.0 Point Air 42.0
:4
switch off point AS3. :AS2 F C :90.0 :AS2 FC 69.0
:6
O2 O2
xxxx xxxx

esc

On three stage burners:


Point Air :42.0 Call up switch off point AS3
::AS2 FC :69.0 and transfer the values
O2 from switch on point ES3.
xxxx

7.2.5 Check operation of, on and off switch points


If the pump pressure has been changed during full load
adjustment the operating and switchover points has to be
checked.

Carry out combustion check Note With 3-stage operation an additional combustion
• activate option With start. quality check for stage 2 (operating point BS2) is
required.
• Drive to operating point BS1 and check combustion
quality.

• If necessary, optimise combustion quality by changing


the air damper setting and burner motor speed.
During this procedure, the pump pressure must not be
altered.

Check on and off switch points


Drive to operating points several times, whilst checking the
on and off switching behaviour of the second or third
stages and optimise if necessary.

36
7
7.2.6 Check start behaviour
Procedure: Programme stop
1. Set ProgramStop to phase 44.
SpecialPositions ➩ Ch. 9.6.1
2. Re-start burner in manual operation. ProgramStop
ProgramStop
3. Check start behaviour and if necessary correct ignition Curr: deactivated
load setting. New: 44 Interv 1

Note If the ignition load setting has been altered, the start
behaviour has to be rechecked.
Restart burner
4. Deactivate programme stop.
Auto/Maual/Off ➩ Ch. 9.4
Auto/Manual/Off
Curr: Burner Off
New: Burner Off
Auto/Manual/Off
Curr: Burner On
New: Burner On

7.2.7 Define full load as required load


Call up function required load in menu ‘Manual operation’ Set required load
and set to full load.
Manual operation ➩ Ch. 9.4
two stage operation: BS2 Required load
three stage operation: BS3 Required load
Curr: BS1
New: BS3

37
8 Load controller
The controller has to be configured relevant to the
installation to ensure safe and reliable load control. On the
W-FM100 the load controller is optional.

8.1 Set operating mode


The operating mode determines if and how the internal Set operating mode
load controller is used and if an external load controller is
connected. Param + Display ➩ Ch. 9.8.4
If the internal load controller is deactivated in menu LoadController
SystemConfig, it can only be reactivated in this menu. Configuration
LC-OptgMode
Note As an emergency function switchover from the LC-OptgMode
external load controller to the Int LC can be carried Curr: Int LC
out with a switch contact on input X62. The Int LC New: Int LC
must be configured for this and must be equipped
with a process condition (temperature/pressure)
sensor.

ExtLC X5-033 point step input signal of external load


controller to X5-03
.
Int LC Internal load controller with 2 set points.

Int LC Bus Digital set point signal from building


management system via eBus or Modbus.
The ABE acts as interface.

Int LC X62 Analogue set point signal from the


building management system on input
X62
(4 to 20 mA or 0 to 10V).
switchover to the internal set point W1 is
possible with an external switch contact
on terminal X62:1/2.

Ext LC X62 Analogue setting signal from the building


management system on input X62 (4 to
20 mA or 0 to 10V).

Ext LC Bus Load control is carried out by the building


management system.
Signal transfer is carried out with eBus or
Modbus, the ABE acts as interface.

38
8
8.2 Configure sensors
Sensors used Configure sensors
Sensor selection has to be configured depending on
whether the actual value is determined by a temperature Param + Display ➩ Ch. 9.8.4
sensor (input X60) or a temperature or pressure sensor LoadController
(input X61). Configuration
Sensor selection
PT 100 PT 100 sensor on terminal X60:1/2/4, Sensor selection
temperature limit (TL) function is active. Curr: PT 100
New: PT 100
PT 1000 PT 1000 sensor on terminal X60:3/4,
temperature limit (TL) function is active.

Ni 1000 Ni 1000 sensor on terminal X60:3/4,


temperature limit (TL) function is active.

PT100 PT1000 PT 100 sensor on terminal X60:1/2/4


for temperature controller function.
PT 1000 sensor on terminal X60:3/4
for temperature limit (TL) function.

PT 100 Ni 1000 PT 100 sensor on terminal X60:1/2/4


for temperature controller function.
Ni 1000 sensor on terminal X60:3/4 for
temperature limit (TL) function.

TempSensor Temperature sensor on input X61, no


(thermocouple) temperature limit (TL) function.

PressureSens Pressure sensor on input X61, no limit


(TL) function.

None No sensor fitted to W-FM.

Sensor measuring range Set measuring range


To allow correct actual value determination the measuring
range of the sensor has to be defined. Param + Display ➩ Ch. 9.8.4
LoadController
MeasR PtNi : 150°C/302°F or 400°C/752°F Configuration
MeasureRange PtNi MeasureRange
MeasR TempSensor : 0 to 2000°C MRange TempSens Curr: 150°C/302°F
MRange PressSens New: 400°C/752°C
MeasR PressSens : 0 to 99.9 bar

The measuring range is also the setting range for the


external set point.

Sensor signal Set analogue signal at input X61


If the actual value is determined by a sensor’s connection
to input X61, the relevant analogue signal has to be set. Param + Display ➩ Ch 9.8.4
LoadController
4 to 20 mA : Current signal on terminal X61:3 Configuration
with load limit (TL) Ext Inp X61 U/I
Ext Inp X61 U/I
2 to 10 V : Voltage signal on terminal X61:2 Curr: 0 ... 10 V
with load limit (TL) New: 4 ... 20 mA
0 to 10 V : Voltage signal on terminal X61:2
without load limit.

39
8
8.3 Set point (external)
External load / set point signal Define analogue signal at input X62
If a load controller is connected to input X62 (Ext LC X62),
or if the set point signal for the internal load controller (Int Param + Display ➩ Ch. 9.8.4
LC X62) is given by this input, the type of analogue signal LoadController
must be defined. Configuration
Ext Inp X62 U/I
Ext LC X62 (load signal) : 4 to 20 mA or 2 to 10 V Ext Inp X62 U/I
Curr: 4 ... 20 mA
Int LC X62 (set point signal) : 4 to 20 mA or o to 10 V New: 0 ... 10V

Set limit values for external set point Set limit values
The set point signal for the internal load controller (Int LC
X62) can be limited in parameter Ext MinSetPoint and Ext Param + Display ➩ Ch. 9.8.4
MaxSetPoint. LoadController
The percentages given for the limit relate to the value set Configuration
under MeasureRange PtNi. Ext MinSetPoint Ext MaxSetPoint
Ext MinSetPoint Ext MaxSetPoint
Example: Curr: 0% Curr: 100%
New: 33% New 5 3%
Upper set point limit required = 80°C

MeasureRange PtNi = 150°C

Calculation

80°C
• 100 ≈ 53,3%
150°C

40
8
8.4 Set point (internal)
Internal set points (W1 / W2) Internal set points (W1 / W2)
Two internal set points can be stipulated.
Switchover is with potential free contact on the terminals Param + Display ➩ Ch. 9.8.1
X62:1/2. LoadController
The set points cannot be set above the temperature limit ControlParam
value already entered. ContParamList
Setpoint W1
Setpoint W2
Setpoint W1
Curr: 80°C
New: 70°C

Switching differential Switch differential


The on and off switch point is given in percent relating to
the set point. Param + Display ➩ Ch. 9.8.1
LoadController
ControlParam
Set point70°C Sd_ModOn Sd_ModOn
Sd_ModOff 10% (from 70°C = + 7.0K) Sd_ModOff Curr: 3%
Sd_ModOn- 5% (from 70°C = - 3.5K) New: - 5%

Installation Off 70°C + 7.0K = 77.0°C


Installation On 70°C - 3.5K = 66.5°C

Note If a positive Sd_ModOn is defined, the switch on


point will be above the set point.

Temperature limit (TL) Temperature limit


If the temperature limit is exceeded, the installation
switches off and the message internal Param + Display ➩ Ch. 9.8.2
temperature limit (TL_ThreshOff) has reacted is displayed. LC-OptgMode
The switch on threshold is given in percent relative to the TempLimiter
set point temperature. TL_ThreshOff TL_ThreshOff
If a thermocouple or pressure sensor has been configured, TL_SD On Curr: 95
the limit function is inactive. New: 90

TL Threshold Off 90°C


TL SwDiff On - 10% (from 80°C = 9.0K)

Installation Off 90°C


Switch on threshold 90°C - 9.0K = 81°C

41
8
8.5 Modulating load control
8.5.1 Parametering internal load control
Adaption Filter time
During adaption, the internal load controller recognises the
control section and calculates the PID parameter. Param + Display ➩ Ch. 9.8.1
Adaption can be started in manual or automatic operation LC-OptgMode
independent of the operating phase (standby or Regelparameter
operation). SW-FilterTmeCon
During adaption, the parameter SW-FilterTmeCon should SW-FilterTmeCon
be between 2 and 4 seconds. If the value selected is too Curr: 3 s
high, this can stop the adaption or lead to insufficient New: 3 s
control parameters.

Adaption rating Adaption Load


If during adaption insufficient heat demand is available, full
load can be limited to up to 40% in parameter Param + Display ➩ Ch. 9.8.5
AdaptionLoad. LC-OptgMode
However, if the AdaptionLoad selected is too low, this can Adaption
stop the adaption. AdaptionLoad
AdaptionLoad
Curr: 100%
New: 80%

Start adaption Start adaption


Select parameter StartAdaption and confirm with
<ENTER>. The respective phases of adaption are Param + Display ➩ Ch. 9.8.5
displayed alternately with the actual value and load signal. LC-OptgMode
Adaption
Phases of adaption: Start adaption Start adaption
• Decreasing of temperature (Temp decrease) with ENTER 12
Before the adaption can be started, the actual Set point 80°C
temperature (or pressure) must be 5% below the set Actual value 79°C
point temperature (or steam pressure).

• Determine actual value (stabilising phase)


The direction of the actual value is determined for 5 min.
During this time the actual value should be constant.
If strong fluctuations occur the time is increased to
maximum 10 min, and anything greater leads to
termination.

• Start-up (heating)
The direction of the actual value during the heat up
phase is determined.
Adaption complete
• calculation of control parameter (Adaption ok)
Using the measured values of the stabilising phase, Adaption ok Adaption ok
the heat input and reaction times and the PID P-content (Xp) P-content (Tu)
parameter are calculated. 11.2% 53s
The values calculated can be called up using the dial continue with <> continue with <>
knob.

Standard control parameters Standard control parameters


If an adaption is not possible or not necessary, standard
parameters can be used as PID values. Various settings ➩ Ch. 9.8.1
Param + Display
are available depending on the behaviour of the control LC-OptgMode
section. ControllerParam
ContrlParamList
P (Xp) I (Tn) D (Tv) StandardParam
very slow 30 % 400 s 10 s SW-FilterTmeCon
slow 15 % 320 s 40 s Curr: XXX
normal 7% 90 s 50 s New: Normal
fast 4% 35 s 17 s
very fast 40 % 55 s 15 s
42
8
8.5.2 Optimising internal load control
Control behaviour Adapt PID parameters
Observe load control for some time during operation and if
necessary optimise the PID parameter. Param + Display ➩ Ch. 9.8.1
LC-OptgMode
ControllerParam
ControlParamList
P-Part (Xp)
I-Part (Tn)
D-Part (Tv)

Setting adjustment stability Setting adjustment stability


With the MinActuatorStep unnecessary drive impulses of
the stepping motors can be reduced and thus their Param + Display ➩ Ch. 9.8.1
longevity increased. LC-OptgMode
However, the MinActuatorStep adjustment affects the ControllerParam
precision control and stability of the load control. MinActuatorStep
MinActuatorStep
Curr: 1.0%
New: 2.0%

Erroneous signal filter Fault signal Filter


Using a filter with time constants (SW_FilterTmeCon),
signals which affect the D-Part can be weakened. Param + Display ➩ Ch. 9.8.1
However, a time filter that is too long will have a negative LC-OptgMode
effect on the control. ControllerParam
SW_FilterTmeCon
Recommendation: 2 to 4 seconds SW_FilterTmeCon
Curr: 3 s
New: 4 s

43
8
8.6 Multi-stage load control
Switching differentials Switching differentials
The switching differentials are formed in percentages
depending on the current set point. Param + Display ➩ Ch. 9.8.1
LC-OptgMode
SD_SStage1On: ControllerParam
At this switching differential the control circuit is closed SD_Stage1On SD_Stage1On
and the burner is switched on. SD_Stage1Off Curr: 1.0%
SD_Stage2Off New: 1.0%
SD_SStage1Off: SD_Stage3Off
As this switching differential is exceeded the control circuit
is opened and the burner is switched off.

SD_SStage2Off:
As this switching differential is exceeded the system is
switched from stage 2 to stage 1.

SD_SStage3Off:
As this switching differential is exceeded the system is
switched from stage 3 to stage 2.

Switch thresholds Switch thresholds


This is the integral (I) from the control devitation multiplied
by the time. Param + Display ➩ Ch. 9.8.1
This function monitors the behaviour of the installation. LC-OptgMode
depending upon demand the next higher load stage is ControllerParam
selected. ThresholdStage2On ThresholdStage2On
The control devitation refers to the set point (W1 or W2). ThresholdStage3On Curr: 300
New: 300
ThresholdStage2On:
Switch criteria for the release of second stage.

ThresholdStage3On:
Switch criteria for the release of third stage.

Notes for 2 stage operation


If a burner with 3 nozzles is only to be operated in two
stage mode, the ThresholdStage2On should be set to “0”.
This means that with the release of the load control the
second nozzle is immediately switched on. The burner is
then in partial load. To ensure correct switch off behaviour,
SD_Stage2Off and SD_Stage1Off should be set to the
same value.

44
8
8.7 Cold start function
Activate cold start function Activate cold start function
In order to avoid the appliance operating at its maximum
loading before the required minimum appliance Param + Display ➩ Ch. 9.8.3
temperature or pressure has been reached, the cold start LC-OptgMode
function has to be activated. LC OptgMode Cold start On
Curr: deactivated
New: activate

Additional sensor Configure additional sensor


A separate temperature sensor (terminal X60) for the cold
start function must only be activated if either a temperature Param + Display ➩ Ch. 9.8.3
or pressure sensor on terminal X61 is used for the load LC-OptgMode
control. ColdStartOn
The switch thresholds then relate to the set point for the Additional Set point add sens
additional sensor. Additional sensor Set point add sens
Curr: deactivated Curr: 60°C
New: Pt 1000 New: 70°C

Switch thresholds Switch thresholds


The thresholds relate to the current set point (W1/W2) or
if an additional sensor is fitted to the Set point add sens. Param + Display ➩ Ch. 9.8.3
LC -OptgMode
ThresholdOn: ColdStartOn
If the actual temperature falls below the switch on ThresholdOn ThresholdOn
threshold the burner starts in the cold start function. ThresholdOff Curr: 20%
New: 25%
ThresholdOff:
If the actual temperature exceeds the switch off threshold
the cold start function is deactivated. Set switch
thresholds

Load steps (only with modulating operation) Set StageLoad


At parameter, StageLoad the load increase can be set up
to that of the ThresholdOff value. Param + Display ➩ Ch. 9.8.3
LC-OptgMode
ColdStartOn
StageLoad StageLoad
Curr: 15%
New: 15%

StageSetp_Mod Setting StageSetp_Stage


StageSetp_Mod (stage set point modulating):
If the actual temperature exceeds the next stage set point , Param + Display ➩ Ch. 9.8.3
the cold start load increases by the value set under LC-OptgMode
StageLoad. ColdStartOn
StageSetp Mod StageSetp Mod
StageSetp_Stage: (stage set point multi-stage): StageSetp Stage Curr: 5%
If the actual temperature exceeds the next stage set point , New: 5%
the next stage is released

Time controlled load increase Setting StageSetp_Stage


If the actual temperature does not reach the
StageSetPoint ..., the cold start load (StageLoad) is Param + Display ➩ Ch. 9.8.3
increased following the MaxTmeStage... LC OptgMode
ColdStartOn
MaxTmeMod MaxTmeMod
MaxTmeStage Curr: 3 min
New: 3 min

45
9 Parameters and functions
9.1 Menu structure (ABE)
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
OperationalStat NornalOperation
esc
Status/Reset
FaultHistory
LockoutHistory
Alarm Act/deact

Operation Boiler setpoint Setpoint W1


esc esc
Setpoint W2

Fuel CurrentFuel
esc
FuelSelect

Date/TimeOfDay DisplayClock Date


esc esc
TimeOfDay
Weekday

SetClock Date
esc
TimeOfDay
Weekday

HoursRun GasFiring
esc
OilStage1/Mod
OiStage2
OilStage3
TotalHoursreset
TotalHours
SystemOnPower

StartCounter GasStartCount
esc
OilStartCount
TotalStartCountR
TotalstartCount

Fuel meter Curr Flow Rate


esc
Volume Gas
Volume Oil
Volume Gas R
Volume Oil R
Reset Date Gas
Reset Date Oil

LockoutCounter

O2 Module Current O2 value


esc
only W-FM200 O2 Setpoint
SupplyAirTemp
FlueGasTemp
CombEfficiency

BurnerID

OptgModeSelect InterfacePC
esc
GatewayBASon
GatewayBASoff
Type of Gateway

O2Ctr Activate
only W-FM200

ManualOperation SetLoad
esc
Auto/Manual/Off
End user: Access without password
Engineer: Access with SERV password
46
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
Param & Display BurnerControl Times Times Startup1 FanRunup Tme
esc esc esc esc Prepurge TmeGas
Prepurge TmeOil

TimesStartup2 Interval1Gas
esc
Interval1Oil
Interval2Gas
Interval2Oil

TimesShutdown MaxTmeLowFire
esc
Postpurge3Gas
Postpurge3Oil

TimesGeneral AlarmDelay
esc
DelayStartPrev

Configuration Configuration AlarmStartprev


esc
General esc ForcedIntermit
ConfigFlameSens

ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

SW version

RatioControl GasSettings SpecialPositions HomePos


esc esc esc
PrepurgePos
IgnitionPos
PostpurgePos
ProgramStop
ResetignitPos

CurveParams

LoadLimits MinLoadGas
esc
MaxLoadGas

OilSettings SpecialPositions HomePos


esc esc
PrepurgePos
IgnitionPos
PostpurgePos
ProgramStop
ResetignitPos

CurveParams Curve Settings


esc

LoadLimits MinLoadOil
esc
MaxLoadOil

Auto/Manual/Off

Times OperatRampMod
esc
OperatRampStage
DriveRamp

ShutdownBehav

ProgramStop End user: Access without password


Engineer: Access with SERV password
47
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5

O2Contr/Guard GasSettings OptgMode


esc esc esc
Param & Display (only W-FM 200) O2 Control
O2 guard

Control Param P Low-Fire


esc
I Low-Fire
Tau Low-Fire
P High-Fire
I High-Fire
Tau High-Fire

O2CtrlThreshold
Type of fuel

Fuel user-def V_Lnmin


esc esc
V_afNmin
V_atrNmin
A2
B / 1000

Control param like theory


esc
like P air

OptgMode
O2 Control
O2 Guard

OilSettings OptgMode
esc esc
O2 Control
O2 Guard

Control param P Low-Fire


esc
I Low-Fire
Tau Low-Fire
P High-Fire
I High-Fire
Tau High-Fire

O2CtrlThreshold
Type of fuel

Fuel user-def V_Lnmin


esc esc
V_afNmin
V_atrNmin
A2
B / 1000

Control param like theory


esc
like P air

O2 OffsetOil
LoadCtrlSuspend
Filter TimeLoad

Process Data CombEfficiency


esc
ManVar O2 Ctrl
State O2 Ctrl
Air-related Load
Diag Reg State

End user: Access without password


Engineer: Access with SERV password
48
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
LoadController ControllerParam ContrlParamList StandardParam
esc esc esc esc
Param & Display (optional on W-FM P-Part (Xp)
100) I- Part (Tn)
D-Part (Tv)

MinActuatorStep
SW_FilterTmeCon
SetpointW1
SetpointW2
SD_ModOn
SD_ModOff
SD_Stage1On
SD_Stage1Off
SD_Stage2Off
SD_Stage3Off
ThreshStage2On
ThreshStage3On

TempLimiter TL_ThreshOff
esc
TL_SD_On

ColdStart ColdStartOn
esc
ThresholdOn
StageLoad
StageSetp_Mod
StageSetp_Stage
MaxTmeMod
MaxTmeStage
ThresholdOff
AdditionalSens
Setp AddSensor
Release Stages

Configuration LC_OptgMode
esc
Sensor Select
MeasureRangePtNi
Ext Inp X61 U/I
MRange TempSens
MRange PressSens
Ext Inp X62 U/I
Ext MinSetpoint
Ext MaxSetpoint

Adaption StartAdaption
esc
AdaptionLoad

SW version

End user: Access without password


Engineer: Access with SERV password
49
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
Times Sum/WinterTime
esc AZL(ABE) esc esc
Time EU/US
Param & Display

Language
DateFormat

PhysicalUnits UnitTemperature
esc
UnitPressure

eBus Address
esc
SendCycleBU

ModBus Address
esc
Baudrate
Parity
Timeout
Local/Remote
Remote Mode
W3

Display Contrast

ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

SW Version

End user: Access without password


Engineer: Access with SERV password
50
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
Actuators Addressing 1 AirActuator
esc esc esc
Param & Display 2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
5 AuxActuator2
6 AuxActuator3

DirectionRot Delete curves


esc

ProductID 1 Air Actuator ASN


esc esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

2 Gas Actuator ASN


esc
(Oil) ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

3 Oil Actuator ASN


esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

4 Auxiliary Actuator ASN


esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

5 Auxiliary ASN
esc
Actuator 2 ProductionDate
(only on W-FM 200) SerialNumber
ParamSet Code
ParamSet Vers

5 Auxiliary ASN
esc
Actuator 3 ProductionDate
(only on W-FM 200) SerialNumber
ParamSet Code
ParamSet Vers

SW Version 1 AirActuator
esc
2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
5 AuxActuator2
6 AuxActuator3

End user: Access without password


Engineer: Access with SERV password
51
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
Configuration Speed Num Puls per R
esc FC Module esc esc esc
Standardisation
Param & Display
(VSD Module) StandardisedSp
(optional on Setpoint Output
W-FM 100)

Fuel meter PulseValueGas


esc
PulseValueOil

Process Data Max Stat Dev


esc
Max Dyn Dev
Num Dev >0.3%
Num Dev >0.5%
Absolute Speed

ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

SW Version

O2 module Configuration O2 Sensor


esc esc esc
(only W-FM 200) SupAirTempSens
FlueGasTempSens
MaxTempFlGasGas
MaxTempFlGasOil

Displayed Values Current O2 Value


esc
O2 Setpoint
SupplyAirTemp
FlueGasTemp
CombEfficiency
QGO SensorTemp
QGO HeatingLoad
QGO Resistance

ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers

SW Version

SystemConfig LC_OptgMode
esc
Inp3Config..I/U

TempLimiter TL_Thresh_Off
esc
TL_SD_On
Sensor Select
MeasureRangePtNi

O2Ctrl/LimitrGas
O2Ctrl/LimitrOil

End user: Access without password


Engineer: Access with SERV password
52
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
HoursRun GasFiring
esc esc
Param & Display OilStage1/Mod
OilStage2
OilStage3
TotalHoursReset
TotalHours
SystemOnPower

Reset GasFiring
esc
OilStage1/Mod
OilStage2
OilStage3
TotalHoursReset

StartCounter GasStartCount
esc
OilStartCount
TotalStartCountR
TotalStartCount

Reset GasStartCount
esc
OilStartCount
TotalStartCountR

Fuel Meter Curr Flow Rate


esc
Volume Gas
Volume Oil
Volume Gas R
Volume Oil R
Reset DateGas
Reset DateOil

Updating ParamBackup BackupInfo Date


esc esc esc
TimeOfDay
BU included?
AZL(ABE) included?
LC included?
ACT1 included?
ACT2 included?
ACT3 included?
ACT4 included?
ACT5 included?
ACT6 included?
VSD included?
O2 included?

LMV5… -> AZL


AZL -> LMV5…

PW Login Load_SW_from_PC
PW Logout

SafetyCheckFunct LossFlameTest
esc
SLT Test

End user: Access without password


Engineer: Access with SERV password
53
9
9.2 Operating display
The operating display is accessible by pressing the Info
button, by pressing ESC you return to the previous menu.

NormalOperation FaultHistory

Display of: Fault memory with the last 21 faults.


• Phases during start up Display of:
• Set points and actual values • Fuel at onset of fault
• Current burner rating • Fault group
• Flame signal • Fault and diagnostic codes (C/D) ☞ see Ch. 12
• by pressing ENTER the stepping motor positions, • Phase, in which the fault occurred
speed and the O2 value can be displayed. • Load position and start No.

Status/Reset LockoutHistroy

If a lockout is present at display “NormalOperation”, this Memory of the last 9 faults, which caused lockout.
can only be reset using parameter “Status/Reset”. Display of:
The display alternates between displaying fault information • Date and time when lockout occurred
and clear text description of the fault. The display is exited • Fault and diagnostic codes (C/D) ☞ see Ch. 12
using ESC and the plant can be reset by pressing ENTER. • Phase, in which lockout occurred (P)
• Load position and fuel

Alarm act/deact

With this function the lockout signal output on terminal


X3-)1:2 can be reactivated or deactivated. Deactivation
of the output remains active until reset, the next start or a
system reset.

9.3 Operation
BoilerSetpoint

Two set points (W1/W2) can be entered for the internal Set point switchover W1/W2
load controller. The set points cannot be set using the
current guarding temperature (optional on W-FM 100).

Switchover from set point W1 to W2 is carried out with


X62

potential free contact at input X62:1/2 Activation 2


2nd set point W2
1

Fuel

Fuel determination with “CurrentFuel” (read only) External fuel selection switch

If an external fuel selection switch has been fitted, this has


priority.
X4-01

Pre-selection
If an external fuel selection switch is not fitted, or if this Oil
2
switch has been set to W-FM internal the current fuel can Pre-selection
1
be changed with the ABE using “FuelSelect”. Gas
W-FM internal
012

Fuel selection with ABE or eBus (BMS) have equal


preference, this means the option selected last is valid.

Date/TimeOfDay

In this menu the date, time and weekday are shown and
can be adjusted if required.

54
9
HoursRun BurnerID

HoursRun is read only. Reset of the individual counters is Here, the burner specific serial number is saved at the
only possible in level Param & Display in menu HoursRun factory. Using the serial number it is possible to replace a
(see Ch. 9.14). failed unit with one that has the same factory pre-settings.
BurnerID also acts as copy protection; this means burner
specific data in the memory of the ABE cannot be
transferred to another W-FM.
StartCounter

The burner starts are read only. Reset of the individual start
counters is only possible in level Param & Display in menu OptgModeSelect
StartCounter (see Ch. 9.15).
Here, the operating mode of ABE for serial interface is set.

InterfacePC
Fuel meter The ABE acts as PC interface. The W-FM is set using a
PC and software.
see Ch. 9.16 Param & Display - fuel meter
GatewayBASon
Access by building management (BMS) to the W-FM
LockoutCounter using the ABE. The ABE remains functioning.
Total number of lockouts since commissioning (cannot be GatewayBASoff
reset). Operation without building management. Access to the
W-FM only with ABE.
CombEfficiency
Type of Gateway
Display of the current efficiency during burner operation Stipulated by the relevant bus protocol (eBus or Modbus).
(see Ch. 9.7.1).

9.4 Manual operation


Target rating

0-100%
Load started in manual operation (burner On). if not
specified, partial load is started.

S1-S3
Highest stage which can be started in manual operation
(burner On).

Auto / Manual / Off

Burner operation is set using this parameter.


This menu is also accessible from level RatioControl.

Automatic
The burner is regulated by an external or the internal load
controller to set point. Regulation can be two stage, three
stage or modulating.

Manual On
The burner starts and is switched of by the external or
internal temperature guard. Prerequisite is a closed control
circuit or bridge at input X5-03 terminals 1 and 4.

Manual Off
Burner switches off. Even if the switch on hysteresis is not
reached, the burner remains off.

55
9
9.5 Burner control
Depending on the password entry the relevant parameter
for the operator or the engineer is displayed.

9.5.1 Times

Time start up 1 Time general

Fan run up time Alarm delay time


Duration of fan start up to start of stepping motors. This time stipulates how soon the combustion manager
signals lockout. The self-test of the system can take up to
Pre-purge time gas/oil 35 seconds. If the fault has been rectified during this test
Duration after reaching the pre-purge positions up to drive phase, the installation re-starts.
to ignition positions.
Delay Start Prevention
This stipulates after how many seconds the display
message is shown if start prevention is active during heat
Time start up 2 demand.

The interval times act as stabilisation periods following


flame formation. The interval time 2 is only active with pilot
ignition.

Time shutdown

MaxTime_LowFire
If the burner is shut down, or if fuel change over is initiated,
the shutdown program starts at the latest after completion
of this time. If low fire is reached prior to this time elapsing,
the shutdown program starts when low fire is reached.

Post-purge time 3
Duration of post-purge.

9.5.2 Configuration

Configuration general ConfigFlame Sensor

Alarm start prevention Flame signal


Stipulates if start preventions are signalled by the alarm Display of the current signal at the flame sensor.
output (terminal X3-01:2)

ForcedIntermit
With ForcedIntermit active, a controlled shutdown with
immediate restart is carried out after 23 h 50 mins.

9.5.3 Product ID and software version

Product ID SW version

The “ProductID” gives information about: The “SW Version” gives information about the software
• Type description (LMV...) version of the burner control.
• Production date
• Serial number
• Parameter set codes
• Parameter set version

56
9
9.6 Ratio control
The setting parameters in menu “RatioControl” can only be
accessed with the password for the engineer.

9.6.1 Settings gas/oil

SpecialPositions

The special positions are fuel specific and can be entered Ignition positions
individually for oil and gas. This parameter is used to set the stepping motor positions
and speed for ignition. Ignition (phase 38) is only carried
Home positions out when all motors have reached their ignition positions.
This parameter is used to set the stepping motor positions
or speed control in Standby.
HomePosFC = 0 Frequency converter deactivated IIgnPosGas : Ignition must be carried out with excess
HomePosFC > 0 Start release frequency converter air. The gas pressure has to be set to the
Fan motor starts with relevant instructions given in the installation and
speed set (in %). operating instructions of the burner.
Gas butterfly opening during ignition:
Pre-purge positions – with ignition pilot 10 to 20°<)
This parameter is used to set the air determining stepping – without ignition pilot approx. 10°<)
motor positions or the motor speed for pre-purge.
Pre-purge only starts once all motors have reached their IgnPosOil : Position of the oil controller. The ignition
pre-purge positions. position for oil can be found on the burner
test data sheet. The indicator position
Post-purge positions given is the same as the data given for the
The parameter PostpurgePos allows separate setting of degree of angle. If an oil controller is not
the individual stepping motors. fitted (multi-stage) the ignition position of
Pre-set values have been entered at the factory. Generally, oil has no influence.
setting values are required, which ensure sufficient cooling
of the mixing head whilst still maintaining adequate heat in IgnPosAir : When the fuel is ignited a pressure
the heat exchanger. increase occurs in the combustion
The speed of the frequency converter must not be set chamber. The burner must create a
below 10%. resistance against this to avoid a back
flow of flue gases. Therefore ignition with
Program stop open air damper and matching of the
In menu, ProgramStop the start of the burner can be mixing pressure by speed only is not
stopped at 7 defined positions and adjustments to the possible. A setting of approx. 30°<) for the
burner settings can be made. air damper is recommended. The actual
air damper opening will be determined
24 PrePurgPos : Nominal load pre-purge position later by the mixing pressure measurement.
32 PreP FGR : Nominal load pre-purge for FGR
36 IgnitPos : Ignition position without ignition IgnPosAux : The position of the adjustable mixing head
44 Interv 1 : End of first safety time can be found in the installation and
52 Interv 2 : End of second safety time operating instructions of the burner. If an
72 PostPPos : Air damper in post-purge position adjustable mixing head is not fitted, the
(shutdown) fixed sleeve or the adjustable flame head
76 PostPFGR : Air damper in post-purge position must be pre-set to the operating points in
for FGR the capacity graph.

Reset ignition position IgnPosAux2 : Auxiliary motors for special applications.


The values of ignition position for oil, air and auxiliary motor IgnPosAux3 : For example: Second fuel Kerosene or
are deleted, existing programming points remain. Liquid Petroleum Gas, flue gas damper
The burner without ignition position data can no longer etc.
start. (only W-FM 200)

Note: In its delivered condition a provisional ignition IgnPosFC : The ignition speed depends on the fuel
position has been set, for fuel oil also the program and should not be below 70% for gas and
point P1 (these values are needed for burner 80% for oil. If the mixing pressure for
testing). ignition is outside of the limit, correction
To ensure that the burner does not start at the must be made using the air damper or
installation, a program has been set in phase 36. mixing head position (only in connection
with a frequency converter / W-FM 200).

57
9
Curve parameters (modulating)

Increase load manually Manual load increase starting from point P1


Due to burner testing load point 1 (P1) has been factory
90 100
pre-programmed for fuel oil. If P1 has been deleted the

Motor positions °<)

Speed %
W-FM suggests the ignition position as load point 1. 80 90

Starting at the first load point reference lines for the 70


80
maximum stepping motor position are created up to full
4 70
load (100%), if no other load point is defined. 60
60
If the load is now increased in menu curve 50
parameter/manual, the stepping motors and the frequency 50
converter are driven by the predetermined reference lines. 40
40

Set intermediate load points 30


3 30
When nearing the combustion limit, a further load point has 2
20 P2
to be set and combustion optimisation has to be carried out. 1 20

10 10
Once the new load point has been saved, a new reference P1
line is created. The reference lines are drawn between the 0 0
previous and the new load point and are further extra- 0 10 20 30 40 50 60 70 80 90 100
polated. in manual load increase, the stepping motors are Rating %
now driven on the basis of the new reference lines.

This procedure is repeated until full load has been Curve lines after saving P2
reached.
90 100
Motor positions °<)

Speed %
80 90
Optimising full load
The required nominal load in full load has to be set with the 80
70
fuel throughput.
4 70
60
Gas: Due to the control characteristic of the gas butterfly
60
this should be set to 65° to 70°. The gas throughput 50
has to be determined and adjusted using the setting 50
screw on the pressure controller. 40
40
Oil: Set required pump pressure in accordance with the 30 3
30
information given in the installation and operating
instructions or the burner test data sheet. Determine 20 2
20
oil throughput and adjust using the setting of the oil 1 P2
controller’s stepping motor. 10 10
P1
0 0
Determine combustion limit at full load and set excess air. 0 10 20 30 40 50 60 70 80 90 100
Rating %
Excess air:
• without O2 control approx. 15 to 20%
• with O2 control approx. 20 to 25% Drive to full load and optimise
For the air quantity setting this means, that the speed is set 90 100
Motor positions °<)

Speed %

to a minimum, depending on the load and the emissions,


90
however not below 40Hz (80%). If at all possible, the 80
position of the mixing head should be set for maximum 80
mixing energy and the air damper should be set to the 70
effective point. With additional O2 control, this will ensure 4 70
60
an effective involvement of the air damper. P5
60
50
Due to the changes made to the mixing pressure and the
P4 50
speed the fuel quantity throughput should be checked and 40
adjusted if required. 40
The pump or gas setting pressure must not be alter once 30 3
this process has been completed. P3
30

20 2
20
1 P2
10 10
P1
0 0
0 10 20 30 40 50 60 70 80 90 100
Rating %

58
9
Deleting points Delete intermediate load points
If a curve point is deleted, the numbering is automatically
90 100
changed to the next point. The reference line will then run

Motor positions °<)

Speed %
linear with the neighbouring points. 80 90

80
70
Insert load points
4 70
If a new load point is inserted, its number is always the 60
P4
number of existing load points plus one. In setting P5 60
“Manual” the load is set with the burner in operation to the 50
value at which the load point is required (recommendation: P3 50
P4
all 10%). 40
40
Carry out combustion optimisation and once the fuel
throughput has been determined, carry out load 30
3 30
P2
apportionment. To achieve an even speed curve line, the P3
20 2
speed should not be adjusted during combustion 20
1
optimisation. P2
10 10
P1
When saving the intermediate load point, an automatic “re- 0 0
sorting” of the load points is carried out according to the 0 10 20 30 40 50 60 70 80 90 100
load. Rating %
This means: The new point 8 now becomes point 7,
point 7 becomes point 8.
Enter intermediate load points
It is possible to optimise ratio control with up to 15 points.
90 100
Motor positions °<)

Speed %
Note: If O2 control is used, point P2 forms the minimum 90
80
O2 control load.
For loads below P2, the O2 control is deactivated 80
70
and the burner runs on the normal ratio control
curve. 60
4 70
Point P1 is important for the air ratings reduction of P7
P8 60
the O2 control. This must have sufficient distance 50
to P2. 50
Recommendation: P1 minimum 30% below P2 40
P8 40
P7
30 P6
3 30
Load assignment P5
Once the curve points have been saved, they automatically 20
2
P4 20
sort themselves according to the load assigned to them. 1 P3

The percentage load assignment depends on the current 10 P2 10


P1
and full load fuel throughput.
0 0
0 10 20 30 40 50 60 70 80 90 100
Current throughput Rating %
Load [%] = –––––––––––––––––––––––––––––––– x 100%
Full load throughput 1 – Air damper
2 – Fuel
If the calculated load deviates too much from the load 3 – Mixing head
point, the fuel throughput can be matched by adjusting the 4 – Speed
stepping motor position.
– manually started load points
Example; – Saved load points
3
Current throughput at point 7 (70%): 250m /h – Deleted load points
Throughput full load: 340 m3/h

250 m3/h
Load [%] = ––––––––––––––––––––––––––––––– x 73,5%
340 m3/h

In this case the fuel throughput (P7) can be reduced with


the fuel motor, the combustion optimisation now has to be
repeated.

59
9
Curve parameter (multi-stage)

The operating mode “multi-stage” is only possible in oil On and off switch point - 2 stage operation
operation. Depending on burner version two or three stage
operation is available. A three stage burner can also BS2
operate in two stage mode with low impact start.

Set operating and switch points


The setting of the operating and switch points can be
carried out with or without starting up. By turning the dial
knob the positions of all operating and switch points
entered can be viewed. This does not have any effect on Solenoid valve
the system. Even if “with start up” is selected the stepping AS2 stage 2 opens
motors do not follow! ES2 Solenoid valve
stage 2 closes
Without start-up
The stepping motor positions can be set without the
motors following; they remain in the required load set
under manual operation. BS1

With start-up
By pressing the ENTER button the point called up is
started and the motors follow the current settings made
with the dial knob.
The on and off switch points are also started, however the
valve does not yet switched at the on and off switch point.
This procedure is required to optimise the air quantity to
the fuel quantity.

If the burner is set to “Off” in manual operation, only the


stepping motors follow, the solenoid valves of the
individual stages, however, are not operated.

Operating points
BS1: Stipulates the air quantity for fuel quantity for
stage 1 (excess air approx. 20 to 25%).

BS2: Stipulates the air quantity for fuel quantity for


stage 2 (excess air approx. 15 to 20%).

BS3: Stipulates the air quantity for fuel quantity for


stage 3 (excess air approx. 15 to 20%).

Switch on point
Only once the switch on point has been exceeded will the
solenoid valve for the next stage open. This means the
solenoid valve of the next stage remains closed at the
direct start of the point. This allows the flame stability can
be checked prior to switching to the next stage.

Switch off point


If the burner is reset by one stage, the relevant solenoid
valve will close when the switch off point has been
exceeded (stage 3 or stage 2).
A direct start of the switch off point is not recommended,
as the solenoid valve of the higher stage will remain open,
which leads to soot due to insufficient air.

60
9
Load limits

Using the parameter min and max load, the burner can be
limited fuel specific in its load range within the
programmed curve lines.

MinLoad_Gas/Oil
Limits the load range downwards (low fire).
The min load cannot be set below point 1 and if used with
O2 control not below point 2.

MaxLoad_Gas/Oil
Limits the load range upwards (full load).

9.6.2 Times
The duration of the slowest motor across a setting section
of 90° is important for parametering the drive times.

OptgRampMod DriveRamp

Gives the run time of the motors in modulating operation. Gives the run time of the motors during the operating
phase without flame.
OptgRampStage

Gives the run time of the motors in multi-stage operation.

9.6.3 Switch off behaviour

Using the parameter Switch off behaviour it is stipulated,


how the ratio control behaves during lockout.

SM stopped HomePos

The stepping motors remain in the position at the time of At lockout the motors drive to the given home positions.
lockout.

Post purge

If lockout occurs the combustion manager carries out a


post purge.

9.6.4 Programme stops

In menu programme stop the commissioning of the burner


can be interrupted at 7 pre-defined positions and the
burner setting adjustments can be made.

24 PrePurgP : Nominal load pre-pre purge position


32 PreP FGR : Nominal load pre-purge for FGR
36 IgnitPos : Ignition position without ignition
44 Interv 1 : End first safety time
52 Interv 2 : End second safety time
72 PostPPos : Air damper in post purge position
(shutdown)
76 PostPFGR : Air damper in post purge position for
FGR

61
9
9.7 O2 control and guarding
Here, the relevant parameters for the operator or the
engineer are displayed depending on the password
entered (only W-FM 200).

9.7.1 Setting Gas/Oil


The following parameters are fuel specific and can be
entered separately for oil and gas.

Operating mode
auto deact O2 controller
Is activated automatically, if the O2 control is switched off The O2 controller and guard are active. The same data
in operating mode “RegAuto deact”. applies as for O2 guard.
O2 controller and guard are deactivated and ratio control
drives on the curve lines programmed. At the same time a conAutodeact
warning message appears in the display. Manual activation The O2 controller and guard are active. Start-up is carried
of operating mode is not recommended. out prior to the operating temperature of the O2 sensor
being reached. Activation of the O2 control in operation is
man deact only carried out once the operating temperature has been
O2 controller and guard are deactivated. The systems reached and the sensor test has been successful.
drives on the parametered ration control curve lines. The
burner starts with cold sensor (only for commissioning, not If the O2 guard reacts, or if a fault occurs in connection
recommended for normal operation). with the O2 measurement, the O2 module, the O2 sensor
or the sensor test, the O2 controller and O2 guard are
O2 guard deactivated automatically.
Only the O2 guard is active.
If the O2 sensor has not reached operating temperature, The system drives to the O2 ratio control setting. The
start is prevented. operating mode is set to “auto deact”. The ABE displays
If the O2 guard reacts, or if a fault occurs in connection the note about the automatic deactivation. The fault code
with the O2 measurement, the O2 module or the O2 sensor, remains until the operating mode is changed.
a safety shutdown is initiated. If repetition is not possible
lockout occurs.

O2 control
Using this parameter an O2 set point standardisation has
to be carried out at each point.
The air determining stepping motors are driven down on
the programmed ration control curve lines in line with the
standard values given. The air load this reduced, but the
fuel quantity remains unchanged.

During standardisation of point 2 and the last load point


(full load) the PI control parameters are determined. In
these two points the O2 ratio control value is started after
the standardised value has been saved and the
reactivation time (Tau) is determined. This means the delay
time between changes to the air stepping motor positions
and the actual value at the O2 sensor are determined.

62
9
O2 Guard
Using this parameter, an O2 limit value has to be set for O2 min limit
each point (CO/soot).
If during operation, the O2 min limit is not reached for 3,0
3 secs. this leads to either a safety shutdown or an
automatic deactivation of the O2 control / guarding 2,5
function, depending on the operating mode selected.
2,0

O2 content [%]
The O2 min limit can be entered directly if the combustion
limit has already be determined, or it can be determined by 1,5
reducing the air load.
1,0
Direct input:
If the O2 values on the combustion limit are already known
these can be assigned as O2 min value for the Guard 0,5
function.
0
Determination: 0 10 20 30 40 50 60 70 80 90 100
Burner rating [%]
Using P-Air manual reduce air load until the combustion
limit (CO/soot) has been reached and save the O2 actual O2 min limit for guard function
value displayed as limit value. Increased O2 min value with steep CO increase at the
combustion limit (+0.2 to 0.3 % points)
Note If the CO increases sharply at the combustion limit,
the O2 min value for the guard function can be
selected 0.2 to 0.3% points higher.

Control parameter
The O2 control is supported by the pre-control function. O2 control behaviour
If equal ambient conditions are present, the pre-control
calculates the air load reduction for the total load range. If O2 Currual value
O2 content [%]

the load signal changes, a setting size alteration (air) of the O2 set point
ratio control is carried out by the pre-control. This means,
the O2 control only has to adjust deviations in ambient
conditions (temperature, air pressure, ...).

Pre-control becomes active at entry into the load control


after 10 x Tau low fire. If during the delay time full load no
load changes occur, the O2 control becomes active. 4
1
5
At each load change the actual load is calculated. If the
difference of the reference line exceeds the LoadContLock
value the O2 control is stopped.
If the load signal remains constant and the difference is not 1
Load [%]

exceeded, the O2 control becomes active again once the 2 3


delay time full load has elapsed.
1 parameter LoadContLock
Using the control parameter the behaviour of the O2 2 locked range
control can be influenced. 3 Delay time full load ( 2 x Tau full load)
4 Burner load
5 Following actual load

P Low/high fire Tau high fire


Proportional part of O2 control. Reaction time at 100% determined during standardisation.

I Low/high fire LoadContLock


Integral part of O2 control. Limit value of the load difference from which the O2 control
is locked.
Tau low fire
Reaction time in point 2 determined during FilterTimeLoad
standardisation. Lock time after which a load change in the size of the
LoadContLock can be made.

O2 Offset Gas/Oil
Increase of O2 content before a load increase is carried
out.
63
9
O2 control limit
For burner ratings below the set value, the O2 control is
deactivated and the system drives on the programmed
curve lines of the ratio control. If the burner rating
increases to 5% points above the control limit, the O2
control is reactivated.

Type of Fuel
To calculate the combustion efficiency the fuel currently The values
used must be set. V_Lnmin = Air volume under normal conditions at λ 1
V_afNmin = Flue gas volume wet under normal cond. λ 1
If the fuel is not available, its fuel values can be entered V_atrNmin = Flue gas volume dry under normal cond. λ 1
under FuelUseDef. are required for converting O2 wet to O2 dry
In parameter FuelUseDef the calculation values for the
combustion efficiency will be displayed. A2 = Adjustable constancies for ηF
B/1000 = Adjustable constancies for ηF
are constancies depending on the fuel.

Type air change


Influences the calculation procedure for pre-control. In theory:
A change in air density (temperature pressure) will not
As P Air: affect the fuel throughput.
A change in air density (temperature pressure) will affect Recommended setting for fuel Oil.
the fuel throughput.
Recommended setting for fuel Gas.

LoadContLock
Limit value of the load difference from which the O2 control
is locked.

FilterTimeLoad
Lock time after which a load change in the size of the
LoadContLock can be made.

O2 Offset gas/Oil
Increase of O2 content before a load increase is carried
out.

9.7.2 Process data


The menu process data is read only:
– about the current combustion efficiency
– about the setting size of the O2 controller
– release of O2 controller (activated/deactivated)
– current load of the air determining motors
– diagnostic codes if the controller is locked

64
9
9.8 LoadController
Here, the relevant parameters for the operator or the
engineer are displayed depending on the password
entered.
On W-FM 100 the load controller is optional.

Note: To set the internal load controller this must be


activated in SystemConfig (Ch. 9.13).

9.8.1 ControlParam Select

ReglerParam Wahl
Under (StandardParam) 5 standard parameter sets and Adapt control parameters
the adaption PID values can be accessed. Each one of
these parameter sets can be copied direct into the PID Xp too small Xp too large
memory, the existing values will be overwritten.

StandardParam P (Xp) I (Tn) D (Tv)


very slow 30 % 400 s 10 s
slow 15 % 320 s 40 s
normal 7% 90 s 50 s
fast 4% 35 s 17 s
very fast 40 % 55 s 15 s Tn, Tv too small Tn, Tv too large
Adaption values determined during adaption

The control parameters can also be entered manually:

P-Part (Xp): Proportional band


I-Part (Tn): Integral action
D-Part (Xv): Derivative action

MinActuatorStep
The smallest possible correcting element step is used for
setting value damping.
If the difference between the new calculated setting size
and the current setting size is smaller than
MinActuatorStep, the current setting size is maintained.

SW FilterTmeCon
Using the filter time actual value fault signals, which
predominantly affect the D content, can be weakened.
However, if the filter time is too long this influences the
actual value determination and has a negative effect on the
control accuracy.

A filter time of 2 to 4 seconds should be set for automatic


adaption. If the time selected is too long this can lead to
automatic adaption being stopped.

Set points W1/W2


Two set points (W1/W2) can be set for the internal load Set point switchover W1/W2
controller. The set points can not be set above the current
limit temperature.

Switchover from set point W1 to W2 is by potential free


X62

contact at input X62:1/2 Activation 2


2. set point W2
1
65
9
SD_M
ModOn/Off
Switch difference in percent for modulating operation.
With positive SD_ ModOn the switch difference is above
the set point, with negative below.

SD_S
Stage On/Off
Switch difference in percent for modulating operation.
With positive SD_Stage1On the switch difference is
above the set point, with negative below.

ThresholdStage... On
If control deviations occur an integral is created over the Switch ThresholdStage... On
time.
Actual
If the integral drops below the ThresholdStage...On the value
next stage is switched. This can influence the switching
Set point
frequency of the individual stages.
SD_Stage
1 On

Stage 2
Q2 Q2
Stage 3
Q3

O2 = switch threshold stage 2 (ThresholdStage2On)


O2 = switch threshold stage 3 (ThresholdStage3On)

9.8.2 Temperature switch


The temperature switch is only active in connection with
the relevant sensors (see Ch. 9.8.4).

The TL_ThresholdOff stipulates the temperature at which


the installation is switched off. Once the switch on
hysteresis TL_SD_On is reached, the installation is
released again.

66
9
9.8.3 Cold start

ColdStartOn Cold start function


Activates/deactivates the cold start function. The cold start
function ensures that the boiler is not operated at its
maximum loading if the preset minimum boiler temperature
has not been reached. Set point
This operating mode protects the material of the boiler.

Threshold
Threshold On Off

Switch on threshold in percent relating to the set point StepSetpoint


(W1/W2) or Setpoint AddSens. Threshold
The cold start function is started if the boiler temperature is On
below this switch on threshold at heat demand. Actual
value
appliance

Step Load (modulating)


Cold start load modulating
The cold start load increases by this value, when the boiler
temperature has reached the next set point step. If the set
point step is not reached, the cold start load is increased
after completion of the parametered MaxTmeMod.

Step load
Step Setpoint m/s
Low fire
Stipulates the cold start set point increase.
If the boiler temperature reaches the current cold start set
MaxTmeMod
point, this is increased by the given value.

Cold start load multistage


MaxTime
MaxTimeMod: Stage 3
Time after which a load increase is carried out (modulating
operation). Stage 2

MaxTimeStage:
Time after which the next stage is released. Pre-requisite is Stage 1
that Release Stages is activated.

ThresholdOff MaxTmeStage

Switch off threshold in percent relating to the set point


(W1/W2) or Setpoint AddSens. Once the switch off
threshold has been reached the installation switches to Release Stages
control operation.
Not released:
Cold start only in the first burner stage. Stage 2 and stage
Additional sensor 3 are locked during the cold start.
Activates the temperature sensor on terminal X60. Released:
The additional sensor is required if a pressure sensor has Cold start is carried out in the first burner stage. Once the
been fitted to terminal X61 and if start-up is to be carried boiler temperature reaches the current cold start set point,
out with media temperatures below 100° C. the next stage is released.

Setpoint AddSens
If the additional sensor has been activated this set point is
the reference size for the on and off switch threshold of the
cold function.

67
9
9.8.4 Configuration load controller

LC operating mode
The load controller setting (internal/external) in
SystemConfig has priority. This means that if an external
load controller has been activated in SystemConfig,
operating mode selection is not possible.

extLC X5-3 External LC on input X5-03


Load control is via three-point step signal of an external
controller at input X5-03. The input must not be switched LC
ϑ
P
1 Stage 1 On
with radio interference suppressors.
2 Stage 3 Closed

X5-03
°C

3 Stage 2 Open
int LC
4
Activates the internal load controller. Set point (W1/W2) L

are set using the ABE.


If a different operating mode is selected, the int LC
operating mode can be activated using one of the switch
contacts on terminal X62:1/2. In this case, control is to set Ext. analogue signals and switchover to int. LC
point W1.
The internal load controller must be configured and 0
optimised to carry out this function. 4 BMS

X62
4…20 mA
3
0…10 V
2
int LC Bus ext. switch contact Int LC
1
The building management system stipulates the set point
for the internal load controller. Signal switchover is carried
out by the ABE and an additional eBus interface. For this
the gateway has to be activated in menu Operation,
parameter Select operating mode (Ch. 9.3) and the Bus External set point / load input via Bus
protocol (Gateway type) has to be entered. If the Gateway
type ModBus has been selected, the ModBus must be set
to local in menu AZL(ABE) (Ch. 9.9.6).
BMS
int LC X62
The building management system stipulates an analogue
signal as set point for the internal load controller. The
setting range automatically matches itself to the
parametered measuring range of the sensor
(MeasureRange PtNI). Additionally, it is possible to limit
the set point range both up and down (Ext SetPoint ...). eBus
Interface
W-FM 200
ext LC X62
The building management system stipulates an analogue
load signal (tab. External load input). The W-FM converts
the signal and starts the relevant motors or the frequency
converter.
Load signal output - only with internal load controller -

External load input


Modulating Multistage
Analogue
X63

0
signal Low fire High fire Stage 1 Stage 2 Stage 3 2
4…20 mA
1
I (mA) 4 20 5 10 15
For the operating modes with internal load controller a load
U (V) 2 10 2,5 5 7,5 signal of 4 to 20 mA is given to output X63:1/2.

Ext LC Bus 4 mA ➙ 0% load


Load control is carried out by the building management 20 mA ➙ 100% load
system. Start-up is carried out by the ABE and an
additional eBus interface. For this the gateway has to be
activated in menu Operation, parameter Select operating
mode (Ch. 9.3) and the Bus protocol (Gateway type) has
to be entered. If the Gateway type ModBus has been
selected, ModBus must be set to remote in menu AZL
(ABE) (Ch. 9.9.6).
68
9
Senor selection
PT100 Sensor connection
PT 100 sensor on terminal X60:1/2/4 (three core switching)
➔ temperature limiting function is active.
Pt 100 Pt/Ni 1000
4
PT1000

X60
3
PT 1000 sensor on terminal X60:3/4
2
➔ temperature limiting function is active.
1

Ni 1000
Ni 1000 sensor on terminal X60:3/4
➔ temperature switch function is active.

PT100 PT1000
PT 100 sensor on terminal X60:1/2/4 (three core switching)
for temperature switch function.
PT1000 sensor on terminal X60:3/4 for temperature
limitng function.

PT100 Ni 1000
PT 100 sensor on terminal X60:1/2/4 (three core switching)
for temperature switch function.
Ni 1000 sensor on terminal X60:3/4 for temperature
limiting function.

TempSensor Sensor connection


temperature sensor at input X61
➔ no temperature limiting function. P/ϑ
0
4
PressSens
X61
4…20 mA
3
Pressure sensor at input X61 0…10 V
2
➔ no limiting function. 20V DC
1

none
No sensor connected to W-FM (i.e. external ratings input
without temperature guarding function).

Measuring range PtNi


The start of the measuring range is fixed at 0° C or 32° F
and cannot be altered.

The end of the measuring range can be configured.


Two possibilities are available:

150° C/302° F or 400° C/752° F

Valid for Pt100:


Load balancing of the three core switching is not required,
if the resistance of the connecting lines are equa

Ext Input X61 U/I


Input X61 has to be configured depending on the sensor
used.

4...20 mA : Current signal to terminal X61:3


with line guarding

2...10 V : Voltage signal to terminal X61:2


with line guarding

0...10 V : Voltage signal to terminal X61:2


without line guarding

The supply voltage (20V DC) on terminal X61:1 cannot be


altered.

69
9
MeasureRange TempSens / PressSens
The measuring range of the temperature or pressure sensor
can be parametered freely within the preset limits.

MeasureRange TempSens: 0 to 2000° C or 32 to 3632° F

MeasureRange PressSens: 0 to 99.9 bar or 0 to 1450 psi

Values 105 outside of the measuring range are interpreted as


sensor short circuit or as line break.

Ext Input X62 U/I


If an external load or set point signal is switched at terminal
X62, the analogue signal has to be defined.

4...20 mA : Current signal on X62-/4


Load or set point signal with line monitoring

2...10 V : Voltage signal on X62:2/4


Load input with line monitoring

0...10 V : Voltage signal on X62:2/4


Set point input without line monitoring

Ext Setpoint min/max


The external analogue set point signal is applied as a Measure Range Set point input
percentage in the internal load controller to the
temperature range set under MeasureRange PtNi. PtNi Current signal Voltage signal
Temperature inputs outside of this limit will not be included
into the control by the load controller, even if the external 4 mA 20 mA 0V 10 V
input does not reach or exceeds these values.
0…150°C 0°C 150°C 0°C 150°C

0…400°C 0°C 400°C 0°C 400°C

Example 1 (set point signal in mA): Example 2 (set point signal in Volt):

Upper set point limit required = 80° C Lower set point limit required = 50° C

MeasureRange PtNi MeasureRange PtNi


150° C 400° C

ExtInput X62 U/I ExtInput X62 U/I


40 to 20 mA; corresponds to analogue range of 16 mA 0 to 10 V; corresponds to analogue range of 10 volt

Calculation Calculation:

80°C 50°C
• 100 ≈ 53,3% • 100 = 12,5%
150°C 400°C

Corresponds to a set point signal of Corresponds to a set point signal of

16 mA 10 V
• 80°C + 4mAOffset ≈ 12,53 mA • 50°C = 1,25 V
150°C 400°C

70
9
9.8.5 Adaption

Start adaption
The adaption allows the load controller to automatically
identify the control section and to create the PID
parameter from the data determined. Adaption is available
for both temperature and pressure control. The adaption
can be started in manual or automatic operation; the
installation can be in operation or standby.
Adaption is not possible in multi-stage operation.

Adaption Load
With this parameter, the adaption load can be reduced by
up to 40%. This could be necessary, if the heat demand
during adaption for full load (100%) is insufficient and the
installation switches off during the adaption process.
If the adaption load is selected so low that the set
temperature is not reached this leads to interruption of the
adaption.

9.8.6 SW version
The “SW Version” supplies details about the software
version of the load controller.

71
9
9.9 ABE
9.9.1 Times

Sum/Winter time Time EU/US


Manual or automatic changeover from Summer to Winter European or American Summer / Winter times can be
time can be selected. selected.

9.9.2 Language
Six languages are available for selection.
If the required language is not available the language
group can be overwritten with PC software. A total of 4
language groups, each with 6 languages, are available in
the software.

9.9.3 Date format


Available for selection are the European format: DD, MM,
YY or the international format: MM, DD, YY.

9.9.4 Physical units


Temperature can be selected as degrees Celsius or
degrees Fahrenheit, pressure in bar or psi.

9.9.5 eBus

Adress Send Cycle


Here the eBus address of the W-FM is set, which the Here the cycle time for sending operating data of the
building management uses to communicate with the combustion manager to the BMS is set.
combustion manager.

72
9
9.9.6 Modbus

Adress Local / Remote


Here the Modbus address of the W-FM is set, which the In Local setting the internal load controller of the
building management uses to communicate with the combustion manager becomes active.
combustion manager. In remote setting, the building management system is
active.
Baudrate Remote Modus
The baudrate stipulates the transfer speed. The parameter is read only, input is by BMS.
The baudrate of the combustion manager and the BMS
must be identical. Remote Auto : Set point input W3 by BMS
Remote on : Set degree input by BSM
Remote off : The internal load controller is active
Parity
Parity is a safety feature for data words during transfer.
The parity of the combustion manager and the BMS must W3
be identical.
Set point input press or temperature by BMS.

Timeout
This time stipulates, after what time the ABE automatically
switches from remote to local if Modbus communication
fails.
This means the building management system is
deactivated and the internal load controller of the W-FM
takes over control.

9.9.7 Display contact


With this selection the dial knob is active and the required
contrast can be set and saved.

The display contrast can also be altered without saving it.


To do this turn the dial knob left or right whilst holding
down the ENTER button (only possible in the operating
display normal operation).

9.9.8 Product ID and SW Version

Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (ABE) version of the display and operating unit (ABE).
• Production date
• Serial number
• Parameter set code
• parameter set version

73
9
9.10 Stepping motors (Actuators)
9.10.1 Addressing
If only one stepping motor is changed the addressing and Addressing stepping motor
the rotational direction will remain the same. If more than
one stepping motor is changed, a new address has to be
entered for each new motor.

Bus connection
If the stepping motor is the last unit in the bus line,
a bus connection has to be made using a jumper. The bus
connection on all other units must be deactivated (the ABE
has a fixed bus connection).

Addressing stepping motors Address button


Select relevant motor in the menu and confirm with Enter.
Then start the address assignment by pressing Enter and
press the address button on the stepping motor to be LED
addressed.
Following addressing the LED shows the flashing code
and the display shows a confirmation message. Jumper

Delete address
If a wrong address has been entered, this can be deleted
by pressing the push button on the stepping motor for 10
seconds, if necessary disconnect the mains voltage whilst
holding down the button. The LED will return to continuous without bus with bus
illumination. connection connection
Flashing codes
Air stepping motor 1 impulse
Gas stepping motor (Oil) 2 impulses LED continuous illumination = no address
Oil stepping motor 3 impulses
Auxiliary motor 4 impulses
Auxiliary motor 2 5 impulses
Auxiliary motor 3 6 impulses LED continuous flashing = addressing in progress

LED flashing codes = addressed

9.10.2 Rotation direction

DeleteCurves
Deletes curve lines of all stepping motors, only required to
change the rotation direction in menu level OEM.

9.10.3 Product ID and SW Version

Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (stepping motor) version of the stepping motor.
• Production date
• Serial number
• Parameter set code
• Parameter set version

74
9
9.11 FC-Modul
Depending on the password entered this displays the
parameters for the operator or the engineer (only W-
FM200).

9.11.1 Configuration

Speed
Number of impulses per rotation Set point output
Speed determination is carried out with an asymmetrical The output signal (0/4 to 20 mA) at terminal X73 of the
transmitter (3 impulses per rotation) at input X70. The W-FM and the input signal of the frequency converter must
asymmetrical transmitter construction (60°, 120°, 180°) is have been matched to one another.
used for recognising the rotation direction, motor start with To guard the signal line, the setting 4 to 20 mA should be
the wrong direction is therefore not possible. selected on the W-FM and frequency converter.

Standardisation
During standardisation a set point signal of 95% is given
at open air or auxiliary stepping motor. This means that Speed determination
there is a shortfall of 5% of the max. frequency set at the 180°
transformer (52.5 Hz x 0.95 = 50 Hz). The speed reached 60°
1 10 V DC
at the standardised 50 Hz is saved in parameter 2 core
Standardised Speed as 100% value for the speed control. 2 Pulse
3 core PNP
X70
If more than 50 Hz is shown during standardisation, the 3 GND
120°
motor slip adjustment (=0) on the frequency converter has 4 Reserve
to be checked. 5 Screen Pulse sequence: 60°, 120°, 180°
If the standardised speed is not reached during operation
at 100%, a reserve of 5% is available to the system.
Connection Frequency converter
Note Following speed standardisation or changes to the
speed saved, the combustion values should be 24 V
checked. 1 FC
2 Start FC
12…24 V DC in (Alarm)
X73

Standardised speed 3
The speed determined during standardisation is saved in 4 0/4…20 mA out (Setpoint)
this parameter and can be altered if necessary (not 5 GND
recommended). 6 Screen

Fuel meter
Fuel meters with Namur or Reed output and Open Impulse value Gas
Collector (pnp) can be used. Depending on the type of gas meter, m3 or ft3 can be
The system continually calculates the current fuel selected.
throughput for the fuel selected. Calculation time
is dynamic and is between 1 and 10 seconds. Impulse value Oil
If the meter does not supply an impulse for 10 seconds, Depending on the type of oil meter, l or gal can be
throughput “Zero” is displayed. This means that the selected.
transmitter should have a minimum impulse frequency of
0.1 Hz at minimum throughput.
At maximum throughput the maximum frequency is 300 Hz. Fuel meters
Gas 10 V DC Fuel meter
1
2 core
Example: Pulse Oil
X71

2
Data on gas meter: 250 impulses per m3 3 core PNP
3 GND
Throughput full load: 20 m3/h ^
= 5000 Imp./h ^
= 1,388Hz 4 Screen
Throughput partial load: 4 m3/h ^
= 1000 Imp./h ^
= 0,277Hz

Oil 1 10 V DC Fuel meter


2 core Oil
Pulse
X72

2
3 core PNP
3 GND
4 Screen

75
9
9.11.2 Process data
The process data is located in the volatile memory and is
reset automatically following lockout.

Max Stat Dev Num Dev>...


The “maximum static deviation” shows the largest speed Shows the frequency of static deviations at the end of a
deviation at the end of value input alteration. value input alteration, which were > 0.3% or > 0.5%.

Max Dyn Dev Absolute Speed


The “maximum dynamic deviation” shows the largest Shows the actual speed.
speed deviation between actual speed and set speed in
multistage operation.

9.11.3 Product ID and SW Version

Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (FC module) version of the FC module.
• Production data
• Serial number
• Parameter set code
• Parameter set version

76
9
9.12 O2-Module
Depending on the password entered this displays
the parameters for the operator or the engineer (only
W-FM200).

9.12.1 Configuration

O2 sensor MaxTempFlueGas ...


To determine O2 the O2 sensor QGO20 has to be If the flue gas temperature set is exceeded a warning
activated. message is given. The set limit can be set individual for oil
and gas and indicates increased appliance losses. The set
value should be approx. 20% above the nominal flue gas
Supply air sensor / flue gas sensor temperature of the appliance manufacturer.
To be able to determine the combustion efficiency the
supply air sensor and the flue gas sensor must be
connected and configured.

9.12.2 Display values

Current O2 value QGO Heating Load


Current O2 value measured by the sensor QGO20. Display of the actual heat rating in %.
The heat rating is in the range of 0 to 60%. The percentage
displayed corresponds to an impulse/pause ratio relating
Supply air temperature to 2 seconds and 230 V.
60% heat rating corresponds to 1.2 seconds impulse and
Air intake temperature measured by the Pt/Ni sensor. 0.8 seconds pause.
Used to determine combustion efficiency. After approx. 15 minutes the sensor has reached the set
point of 700° C (pre-requisite for release of the O2 control).

Heating Load:
Flue gas temperature Start heat load up to 100° C ______________approx. 13%
Flue gas temperature measured by the Pt/Ni sensor. Used Heat up process approx. 60%
to determine combustion efficiency. Operating temperature ______________approx. 15 to 25%

QGO Resistance
The internal resistance is a measure for the function ability
QGO SensorTemp of the sensor. It changes during the operating time.
Current operating temperature of the O2 sensor. If the internal resistance is < 5 Ω or > 150 Ω the sensor is
ageing.

9.12.3 Product ID and SW version

Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives details about the software version
• Type description (O2 module) of the O2 module.
• production date
• Serial number
• Parameter set code
• Parameter set version

77
9
9.13 SystemConfig
LC operating mode TempLimit
The configuration of the load controller operating mode is The configuration of the TL_ThresholdOff and TL_SD_Off
identical to that in menu LoadController (Ch. 9.8.4). is identical to that in menu LoadController (Ch. 9.8.2).
However, the setting in SystemConfig has priority.
This means that if an external load controller is selected in The configuration for SensSelect and for MeasureRange
menu SystemConfig you cannot change over to internal is identical to that in menu LoadController (Ch. 9.8.4).
operating mode in menu LoadController.

Ext Input X62 U / I


O2Ctrl/Guard.....
The configuration of the external input X62 is identical to
that in menu LoadController (Ch. 9.8.4). The configuration is identical with that in menu
O2Ctrl/Guard (Ch. 9.7.1).

9.14 Operating hours


Gas operation TotalOperHoursR
Operating hours for fuel Gas since last reset. Total operating hours oil and gas since last reset.

Stage 1 / Mod TotalOperHours


Operating hours of stage 1 or modulating (oil) since last Total operating hours oil and gas.
reset. This value cannot be reset.

Stage 2 Unit under voltage


Operating hours of stage 2 (oil) since last reset. Total hours the W-FM has been connected to mains
voltage.
This value cannot be reset.
Stage 3 Reset
Operating hours of stage 3 (oil) since last reset. Here all parameters, which can be reset, can be set to
“Zero”.

78
9
9.15 Start counter
Start counter Gas TotalStartCounterR
Burner starts with fuel gas since last reset. Total burner starts with fuel oil and gas since last reset.

Start counter Oil TotalStartCounter


Burner starts with fuel oil since last reset. Total burner starts with fuel oil and gas.
This value cannot be reset.

Reset
Here all parameters, which can be reset, can be set to
“Zero”.

9.16 Fuel meters


If an oil or gas meter is installed and configured (Ch.
9.11.10), the fuel quantities determined can be called up
and reset here.

Current throughput Volume Gas R

Displays the current throughput for gas in m3/h or oil in l/h. Fuel throughput for gas in m3 since last reset. Reset by
pressing the ENTER button.

Volume Gas
Reset date gas
Total gas throughput in m3.
This value cannot be reset. Date of last reset for fuel gas.

Volume Oil Reset date oil


Total oil throughput in litres. Date of last reset for fuel oil.
This value cannot be reset.

Volume Gas R
Fuel throughput for oil in litres since last reset. Reset by
pressing ENTER button.

79
9
9.17 Updating
9.17.1 Parameter backup

Backup-Info ABE -> LMV5...


Displays information about the date and time of the last Loads the data from the display and operating unit (ABE)
parameter backup as well as their system components. to the base unit (W-FM). Pre-requisite is that the burner
identification of the ABE and the W-FM are identical or
that burner identification of the W-FM is still in its delivery
condition.
LMV5... -> ABE The data in the W-FM are overwritten and can no longer
be reproduced.
Loads the data from the base unit (W-FM) to the display
and operating unit (ABE).
Any data in the ABE is overwritten and can no longer be
reproduced.

9.17.2 Load SW from PC


Updates the software of the display and operating unit
(ABE) with PC-Tool using a serial interface.

9.18 Password
PW login Deactivate PW (PW Logout)
After entering the engineer’s password additional access Using this parameter the password protected level can be
to the engineer’s level is available. The password is protected at an earlier stage.
deactivated 120 minutes after the last input.

9.19 TÜV test


LossFlameTest SLT Test
The flame failure test interrupts the flame sensor signal and During the SLT Test the control circuit as well as the
it can be checked if the W-FM will go to lockout. temperature guard are bridged and the burner is operated
at maximum load, allowing the response of the safety
temperature limiters to be checked.

80
Start up Operation Shutdown Valve proving

tv TSA1 TSA2

ON

Safety

Standby
Fuel valve

Home run
Pre-purge

Fan = ON
Press test

Safety fuel
Post purge

relay = ON
Direct start

valve = ON
Pre-ignition
Ignition OFF

Safety phase
Fill valve train

Test no press

Interval time 2

Lockout phase
ignition position
Ignition position
Low fire position

Flame signal ON
After burner time
Empty valve train

Stepping motor in

pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2
post purge position

Air stepping motor in


Air stepping motor in
tn1
V1 = Closed, V2 = Open
V1 = Open, V2 = Closed

Gas direct ignition

tn3 5
6
V1 = Closed, V2 = Closed
V1 = Closed, V2 = Closed

Operating phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
Timer-Event- Link und und or and
Timer 1 t0 t10 t21 t22 t30 t34 t38 t42 t44 t52 t62 t70 t74 t78 t80 t81 t82 t83
Timer 2 9 tv TSA

Times
Timer 3 = Phase max. time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch GAS X4-01: 1 C B B B B B B B B B F F F F G B
Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B w D D D D
Sequence diagram gas with direct ignition

Temperature guard internal C B B B B B B B B B F F F F F F F F E B


Controller ON C B B B B B B B B B F F F F G m 5 7
Flame signal X10-02: 6 q c k i i i i L L L L L L k k k k k i i i i
9.20 Sequence of operation diagrams

Air press. switch APS X3-02: 1 1 A/c A/c c C A A A A A A A A A A A A A A A A A A c A A A A

Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A A A A A

Inputs
or FGR- Fan-PS X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c A A A A
CPI or VP-PS X9-03: 2 C A A A A A A A A A a a A A A A A
Low gas press.sw. LGPS X9-03: 4 3t G B B B B B B B D D D D D D D D H w D D D D
Release Gas X7-03: 1 3w G B B B B B B B D D D D D D D D H w D D D D

Gas
Lockout HGPS. X9-03: 3 3 A A A A A A A A
Gas pressure switch GPSVP X9-03: 2 A a
Burner motor / Fan X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 N N
3-way solenoid X4-03 u 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N 4 4 4 4
Alarm X3-01: 2 i N 8

Gas + Oil
Safety relay internal X3-04: 1/2 N N N N N N N N N N N N N N N N N N N N N N N N N N N

Output
Safety relay Gas X9-01: 1 N N N N N N N N N N N N N N N N N N N N N
Valve pilot ignition Gas X9-01: 2

Gas
Fuel valve 1 Gas X9-01: 4 N N N N N N N N N
Fuel valve 2 Gas X9-01: 3 N N N N N N N N N

90° (Full load)


Pre-purge position
Post-purge position

Fuel
Partial load
Ignition position
Standby position

Actuators
90° (Full load)
Pre-purge position
Post-purge position

Air
Partial load
Ignition position
Standby position
9

81
82
Start up Operation Shutdown Valve proving

tv TSA1 TSA2
9

ON

Safety

Standby
Fuel valve

Home run
Pre-purge

Fan = ON
Press test

Safety fuel
Post purge

relay = ON
Direct start

valve = ON
Pre-ignition
Ignition OFF

Safety phase
Fill valve train

Test no press

Lockout phase
ignition position
Ignition position
Low fire position

Flame signal ON
After burner time
Empty valve train

pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2

Stepping motors in
post purge position
Air stepping motor in

Air stepping motors in


tn1

Pilot ignition valve OFF


V1 = Closed, V2 = Open
V1 = Open, V2 = Closed

Gas pilot ignition

tn3 5
6
V1 = Closed, V2 = Closed
V1 = Closed, V2 = Closed

Operating phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
Timer-Event- Link und und or and
Timer 1 t0 t10 t21 t22 t30 t34 t38 t42 t44 t52 t62 t70 t74 t78 t80 t81 t82 t83
Timer 2 9 tv TSA

Times
Timer 3 = Phase max. time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch GAS X4-01: 1 C B B B B B B B B B F F F F G B
Sequence diagram gas with pilot ignition

Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B w D D D D


Temperature limit internal C B B B B B B B B B F F F F F F F F E B
Controller ON C B B B B B B B B B F F F F G m 5 7
Flame signal X10-02: 6 q c k i i i i L L L L L L k k k k k i i i i
Air press. switch APS X3-02: 1 1 A/c A/c c C A A A A A A A A A A A A A A A A A A c A A A A

Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A A A A A

Inputs
Or FGR-Fan-PS X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c A A A A
CPI or VP-PS X9-03: 2 C A A A A A A A A A a a A A A A A
Low gas press. sw. LGPS X9-03: 4 3t H B B B B B B B D D D D D D D D H w D D D D
Release Gas X7-03: 1 3w H B B B B B B B D D D D D D D D H w D D D D

Gas
Lockout HGPS. X9-03: 3 3 A A A A A A A A
Gas press. switch GPSVP X9-03: 2 A a
Burner fan motor X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 N N
3-way solenoid valve X4-03 u 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N 4 4 4 4
Alarm X3-01: 2 i N 8

Gas + Oil
Safety relay internal X3-04: 1/2 N N N N N N N N N N N N N N N N N N N N N N N N N N N

Output
Safety relay Gas X9-01: 1 N N N N N N N N N N N N N N N N N N N N N
Valve pilot ignition Gas X9-01: 2 N N N N

Gas
Fuel valve 1 Gas X9-01: 4 N N N N N N N N N
Fuel valve 2 Gas X9-01: 3 N N N N N N

90° (Full load)


Pre-purge position
Post-purge position

Fuel
Partial load
Ignition position
Standby position

Actuators
90° (Full load)
Pre-purge position
Post-purge position

Air
Partial load
Ignition position
Standby position
Start up Operation Shutdown

tv TSA1 TSA2

ON

Safety

Standby
Fuel valve

Home run
Pre-purge

Fan = ON
Safety fuel
Post purge

relay = ON
Direct start

valve = ON
Pre-ignition
Ignition OFF

Safety phase
Interval time 2

Lockout phase
ignition position
Ignition position
Low fire position

Flame signal ON
After burner time

pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2

Stepping motors in
post purge position
Air stepping motor in

Air stepping motors in


tn1

Oil direct ignition


tn3 5
6

Operating phase 00 01 10 12 20 21 22 24 36 38 40 30 32 34 42 44 50 52 54 60 62 70 72 74 76 78 79
Timer-Event-Link und und und und or and
Timer 1 t10 t21 t22 t30 t34 t36 t38 t42 t44 t52 t62 t70 t74 t78 tmx1
Timer 2 9 tv TSA1

Times
Timer-Event- Link t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx3 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch OIL X4-01: 2 C B B B B B B B B B D D D D G B
Sequence diagram oil with direct ignition

Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B


Temperature limit internal C B B B B B B B B B D D D D D D D D E B
Controller ON C B B B B B B B B B D D D D G m 5
Flame signal X10-02: 6 q c k i i i i L L L L L L k k k k k
Air press. switch APS X3-02: 1 1 A/c A/c c C A A A A A A A A A A A A A A A A A A c

Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A

Inputs
or FGR-Fan-PS X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c
CPI or VP-PS X9-03: 2 C A A A A A A A A A A A A A A A A A A A A A A A
Low oil press. sw. LOPS X5-02: 1 3 r C A A A A A A A A
High oil press. sw. HOPS X5-02: 2 3

Oil
C A A A A A A A A A A A A A A A
Start release Oil X6-01: 1 3 H B B B B B B B D D D D D D D D H
Burner fan motor X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 2 2 2 2 2 2 N N
3-way solenoid on APS X4-03 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N
Alarm X3-01.2 u N 8

Gas + Oil
Safety relay internal X3-01: 1/2 i N N N N N N N 2
N N N N N N N N N N N N N N N N
Safety relay Oil X6-03: 3 N N N N N N N N N N N N N N N N N N

Output
Fuel valve 1 Oil X8-02/-03 N N N N N N N N

Oil
Fuel valve 2 Oil X7-01 N
Fuel valve 3 Oil X7-02 N
Magnetic clutch/sep. Pump X6-02: 3 z 2 2 2 2 2 2 N N N N N N N N N

90° (Full load)


Pre-purge position
Post-purge position

Fuel
Partial load
Ignition position
Standby position

Actuators
90° (Full load)
Pre-purge position
Post-purge position

Air
Partial load
Ignition position
Standby position
9

83
9
Legend for the sequence diagrams
Signal “ON” Signal “OFF” Reaction if relevant signal to sequence diagram is not given

A a Jump to operating phase 01, with repetition counter = 0 on to phase 00 otherwise in Ph 12


B Jump to operating phase 10
C c Stop until completion of Phase max. time (tmx...), then jump to phase 01
D d Jump to operating phase 70
E With heat demand from controller and parametered direct start jump to phase 79,
otherwise to phase 10
F Without valve proving jump to operating phase 70, otherwise to phase 80
G Jump to operating phase 62
H Stop until completion of Phase max. time (tmx...), then jump to phase 10
i 0…3 s Jump to operating phase 01, with repetition counter = 0 on to phase 00 otherwise in Ph 12
k 0…30 s Jump to operating phase 01, with repetition counter = 0 on to phase 00 otherwise in Ph 12
L 0…3 s Jump to operating phase 01, with repetition counter = 0 on to phase 00 otherwise in Ph 12
i With parametered direct start jump to phase 79, otherwise to phase 10
N Output: ON
Output: OFF
Input: no influence

1 Depending on parametering with or without LP

2 Depending on parametering short or long pre-ignition time and pump on time

3 Delayed shutdown in TSA1 + TSA2

4 Depending on parametering output as start signal or PS relief valve

5 Depending on parametering Normal/Direct start

6 Follow on phase 24

7 Only with valve proving during commissioning

8 Depending on parametering with or without alarm at start inhibition

9 With parametered continuous running fan

0 Fan remains driven as before

q Depending on parametering with or without extraneous light test in standby

w With deviation during start up follow on phase 10

e With normal venting: Check for ON in phase 10, stop until completion of phase max. time, then jump to phase 01
With continuous running fan: Check for ON in phase 10 and 12, stop until completion of phase max. time, then jump to
phase 01

r If the min. oil pressure switch input has been parametered to “Act from ts” no check is carried out prior to completion of
TSA 1 time

t If the low gas pressure switch input has been parametered to “deactOgp” no check is carried out with oil with gas pilot
ignition

z If the output is parametered to “DirectCoupl”, the safety valve Oil has to be connected. The output is driven together
with the fan and stops 15 s after the fan in time delay.
u If the output is parametered to “PS relief”, this (output PS relief valve) is inverted logically

i The alarm output can be temporarily deactivated for the current fault

84
9
Assignment times:

Time Description

t0 Post-purge lockout setting


t01 MaxTime_SiPhase
t10 MinTimeHomerun
t21 MinTimeStartrelease
t22 FanRunupTime
t30 Prepurgetime part 1
t34 Prepurgetime part 3
t36 MinOnTimeOilPump
t38 PreIgnTime_Gas / Oil
t42 PreIgnTime_Off
t44 IntervalTime 1 Gas / Oil
t52 IntervalTime 2 Gas / Oil
t62 MaxTime low fire
t70 Afterburn time
t74 PostpurgeTime 1 Gas / Oil (tn1)
t78 PostpurgeTime 3 Gas / Oil (tn3)
t80 Valve proving empty time
t81 Leakage test test time atm. pressure
t82 Leakage test filling test
t83 Leakage test test time gas pressure
tmx1 Max. damper run time
tmx2 MaxTime start release
tmx3 MaxTime venting HO Oil
TSA1 Safety time 1 Gas / Oil
TSA2 Safety time 2 Gas / Oil
tv Prepurge time_Gas / Oil

Actuators
In Standby:
The SA can be moved within the permitted
position range, will however, always be driven
to the standby position, and must be in
standby for phase change.

Abbreviations
FGR Flue gas recirculation
CPI Closed position indicator
PS Pressure switch
VP Valve proving
BrnFan Auxiliary contact burner fan contactor
PL or LF Low fire position
AD Air damper
APS Air pressure switch
PP Post-purge position / post-purge
S Standby
SR Safety relay
STB Safety temperature limiter
TL Temperature guard
PV Pre-purge position / pre-purge
Z Ignition position

85
10 O2 sensor
Installing the O2 sensor

Electrically isolate the plant During operation, the sensor is heated to


Prior to installation, switch off the mains approx. 700°C.
switch and the safety switch.
Failure to comply could cause death or
DANGER serious injury by electric shock. DANGER

• The O2 sensor must only be fitted with the relevant Sensor position
flanges and to the enclosed drawing.

• No infiltrated air must enter before, and at least 2 x


diameters of the flue gas ducting after the sensor.

• The sensor should be fitted as close as possible after


the flue gas outlet terminal of the appliance, but no min.
closer than 1 diameter of the flue gas pipe.
1x
• The sensor must not be fitted vertically from below,
pointing upwards. 10…20°
• The favourable fitting position is vertically from above
or up to 45 ° angle either side of vertical.

• The minimum distance between the inner wall of flue


gas duct and the flue gas sampling outlet hole on the
flange is 10 mm.

Air

up to 45°

Installation instruction

Gas tight (sealed)


welding min. 10 mm

do not insulate

86
10
Electrical connection

The 6 core connection line between the terminal rail X1 of


the O2 module and the sensor is fitted with a screened line
twisted in pairs (3 x 2 x 0.25 mm2).
One side of the screening should be attached to the
mounting plate of the O2 module. There must be no
connection between GND and earth.

The sensor heating L (Q4), N (Q5), PE should be fitted to


the O2 module terminal rail X10 Pin 1, 2, 3 with a minimum
3 x 0.75 mm2.
The line of the sensor heating must be a separate cables.
Outside diameter of the cable = Max. 8 mm.

Connection to O2 module

O2 module
Mains
X10

L (Q4)
N (Q5)
PE 1

Q5
Q4
GND

U3 U3
G2 G2
M
M B2
X1

B2 M
B1
M
B1 1

L, N, PE: Supply voltage sensor heating 230V pulsed Nernst voltage at 700° C sensor temperature
(N switching)
700°C
U3 : Temperature compensation 1 µA/K relating to 120
absolute zero, i.e. 273 µA corresponds to a
sensor temperature of 0° C 100
Nernst voltage [mV]

G2 : Feeder voltage temperature compensation 2 80


to 10V
60
B3 / M : Thermo element 0 to 33 mV
29.1 mV corresponds to approx. 700° C
40

B1 / M : Nernst voltage (0 to 700 mV)


20

0
0,05 0,1 0,2 0,5 1 2 5 10 20
O2 content [%]

87
11 Frequency converter
If the W-FM 200 is used in connection with a frequency Further information and details relating to the frequency
converter VLT 2800 or VLT 5000 (Danfoss),the converter can be found in the manufacturers
parametering of the frequency converter has to be documentation.
checked and if necessary adjusted.

If a frequency converter (Siemens) fitted directly to the


burner motor is used, parametering of the FC is not
required or indeed possible.

11.1 Programming and display unit frequency converter Series VLT


The programming and display unit allows manual access to
the frequency converter during burner operation or
commissioning.

Furthermore the programming and display unit shows


operating values and is used to program the frequency
converter.
Programming the frequency converter with the W-FM or its
ABE is not possible.

Note Please observe the manufacture’s installation and


operating instruction for the frequency converter.

Programming and display unit VLT 2800

Six digit LCD display

+/- Buttons
Selection of parameters and value changes

Quick-Menu
Call up menu or return without changes

Change Data
Confirm value changes
LED display of operating conditions

Stop/Reset
Stop motor / reset lockout

Start
Starts the frequency converter

88
11
Programme and display unit VLT 5000

4 line LCD display 24,3% 30,2% 13,8A

50.0 Hz
Menu
Call up of menus for all parameters Operation
Quick-Menu
Call up of all parameters in the quick menu

Display/Status
Selection of display/change to display mode DISPLAY MENU
OK STATUS
Confirmation of value changes
Cancel
Cancel value changes

Change Data
Changes the parameter selected CANCEL OK
+/- Buttons
Selection of parameters and value changes

Arrow buttons
Selection of parameter groups and value changes

LED display of operating conditions

Stop/Reset
Stop motor/reset lockout STOP FWD. START
JOG RESET JOG REV.
Activate fixed speed / deactivating (parameter 15)
FWD./REV.
Change of rotation direction (parameter 16)
Start
Starts the frequency converter

89
11
11.2 parametering the VLT 2800
In connection with the W-FM 200, certain parameters on
the frequency converter have to be checked and set if
necessary.

No. Description Value Unit Meaning

019 Mains-On-Mode 0 - automatic restart at mains activation

100 Configuration 0 - speed control with motor slip adjustment

101 Torque reference line 1 - constant torque

102 Motor rating xx.yy kW to name plate

103 Motor voltage xx V to name plate

104 Motor frequency xx Hz to name plate

105 Motor current xx.yy A to name plate

106 Motor speed xxxx kW to name plate

123 Frequency stop function 2 Hz activation motor free run if not reached

126 Direct current brake time 2 sec. duration for DC brake

127 Frequency DC brake 2 Hz activation of DC brake if exceeded

128 Thermal motor protection

132 Voltage DC brake 50 % brake voltage

133 Voltage increase 0 V no voltage increase

134 Load compensation 80 % load reference line

136 Slippage adjustment 0.0 % no motor slip adjustment

144 Increase AC brake 1.0 - alternating current brake deactivated

202 Max. frequency 52.5 Hz upper limit value output frequency

204 Min set point 0.0 Hz minimum set point input

205 Max. set point 52.5 Hz maximum set point input

207 Ramp time Open 1 81/152/283 sec. acceleration time from 0 Hz to nominal frequency

208 Ramp time From 1 81/152/283 sec. delay time from nominal frequency to 0 Hz

211 Ramp time Jog 81/152/283 sec. acceleration/delay time fixed speed

212 Ramp time From Quick Stop 81/152/283 sec. delay time quick stop

213 Frequency Jog 0 Hz frequency for fixed speed

226 Warning fmax limit 52.5 Hz

1 up to size 50
2 on sizes 60 to 70
3 WK burners

90
11
No. Description Value Unit Meaning

302 Input 18 digital 7 - Start signal from W-FM200 contact X73:1/2

303 Input 19 digital 0 - No function, input deactivated

304 Input 27 digital 5 - Direct current brake

305 Input 29 digital 0 - No function, input deactivated

307 Input 33 digital 1 - Recording, reset with W-FM 200

308 Input 53 analogue 0- no function, input deactivated

314 Input 60 analogue 1 - set point signal from W-FM200 terminal X73:4

314 Input 60 min. scaling 4.0 m Alower set point signal min.

315 Input 60 max. scaling 20 m Aupper set point signal max.

318 Function after set point fault 0 - off, function deactivated

319 Output 42 analogue 7 - recorder output 0-20 mA

323 Relay output 1 - 38-contacts are switched at alarm

341 Output 46 digital 8 - output reacts at alarm or warning

349 Delay speed comp. 0 m ssystem delay time

400 Brake function 4 - with alternating current brake

405 Type of recording 10 - 10 automatic restart trials after termination

445 Motor hold switching 1 - Holding the motor

91
11
11.3 Parametriering VLT 5000
In connection with the W-FM 200 certain parameters on
the frequency converter have to be checked and set if
necessary.

No. Display Data Meaning

002 Operating mode REMOTE Remote control

013 Setp. Local Mode BLOCKED Set point input only with digital inputs from W-FM

019 Mains ON mode AUTO RESTART Automatic restart when mains switch on

100 Configuration WITH SLIP COMP. Speed control with slippage adjustment

101 Torque ref. line N-CONST-TORQUE Constant torque

102 Motor rating Set nominal rating as per name plate

103 Motor voltage Set nominal voltage as per name plate

104 Motor frequency Set nominal frequency as per name plate

105 Motor current Set nominal current as per name plate

106 Motor nom. speed Set nominal speed as per name plate

113 Load adjust. low 80% Load compensation in lower speed range

114 Load adjust. high 80% Load compensation in upper speed range

115 Slip. adjustment 0.0% no slippage adjustment

122 Stop function DC BRAKE active at shutdown

123 Freq. stop function 2Hz activates motor free run if not reached

124 DC Hold current 0.0% Off

125 DC Brake current 50% corresponds to half motor nominal current

126 DC Brake time 2 sec. Duration DC braking

127 DC br. start freq. 2Hz activates motor free run brake if exceeded

128 Therm. motor protection

202 Max. frequency 52.5 Hz Upper limit value output frequency

204 Min set point 0.0 Hz Minimum set point input

205 Max set point 52.5 Hz Maximum set point input

207 Ramp Open 181/152/283 sec Acceleration time 0 Hz to nominal speed

208 Ramp From 181/152/283 sec Delay time nominal speed to 0 Hz

212 Ramp Q Stop 181/152/283 sec Delay time quick stop

213 Frequency Jog 0.0 Hz Frequency for fixed speed

216 f-max limit 52.5 Hz Warning at speed limit

1 up to size 50
2 on sizes 60 to 70
3 WK burners

92
11
No. Display Data Meaning

300 Input 16 digital NO FUNCTION no function, input deactivated

301 Input 17 digital NO FUNCTION no function, input deactivated

302 Input 18 digital STARTS tart signal from W-FM 200 contact X73:1/2

303 Input 19 digital NO FUNCTION no function, input deactivated

304 Input 27 digital DC BRAKE Direct current brake

305 Input 29 digital NO FUNCTION no function, input deactivated

306 Input 32 digital NO FUNCTION no function, input deactivated

307 Input 33 digital RECORDING Rest by W-FM 200

314 Input 60 analogue SETPOINT Set point signal from W-FM 200

315 Input 60 scale min 4.0 m Alower set point signal min.

316 Input 60 scale max 20.0 m Aupper set point signal max.

318 Funct. foll. setp. fault OFF no function, input deactivated

319 Output 42 d or a 0-I MAX = 0-20 m Aanalogue recorder output 0-20 mA

321 Output 45 d or a ALARM output reacts at alarm

323 Output 1-3 relay ALARM Contacts switched at alarm

400 Brake function OFF no brake resistance

405 Recording 10 x AUTOMATIC 10 automatic restarts after termination

445 Hold switching ACTIVE Holding the motor

93
12 Cause and rectification of faults (fault list)
Faults are displayed alternating as codes and clear text Display - Fault history
information. The following fault possibilities are listed in
order of fault code and diagnostic code. Operating mode
Fault history
Fault rectification: 1 18.06.99 10:35 Stepping motor
• Call up fault history - analyse last fault C:15 D:1 P:81 fault from ECR
• Determine cause, determine reason Start No: 123456
• Rectify fault Load:25.0 Gas
• If necessary, record fault
C: = Fault code
D: = Diagnostic code
P: = Phase

Fault list

Fault Fault Cause Recommended measures


list code

01 01 ROM Fault • 1)
02 01…07 RAM Fault • 1)
03 01…44 Fault at internal data comparison • 1)
04 – Synchronisation fault • 1)
05 01,02 Fault flame signal booster test • 1)
• Replace flame sensor
06 01…04 Fault internal hardware test • 1)
10 01…1B Fault inputs / outputs The number of the diagnostic codes shows
which input is faulty.
01 Load controller on/off • Neutral conductor may be missing, (or not zero V)
02 Fan contact
03 Oil operation selection • The fault could be caused by capacitance loads,
04 Gas operation selection causing longer than 10 ms to reduce the voltage
05 Reset to 0 Volts before the relay switches off.
06 Pressure switch Oil maximum
07 Pressure switch Oil minimum
08 Pressure switch valve proving • Check control wiring
09 Safety valve Oil return signal
0A Fuel valve 1 Oil return signal • 1)
0B Fuel valve 2 Oil return signal
0C Fuel valve 3 Oil return signal
0D Safety valve Gas return signal
0E Fuel valve 1 Gas return signal
0F Fuel valve 2 Gas return signal
10 Fuel valve 3 Gas return signal
11 Safety circuit burner flange
12 Safety relay return signal
13 Pressure switch Gas minimum
14 Pressure switch Gas maximum
15 Ignition transformer return signal
16 Fan pressure switch
17 Start release Oil
18 Residual oil immediate start
19 Load controller open
1A Load controller closed
1B Start release Gas

1) If it occurs sporadically improve EMC measures.


If it occurs permanently replace W-FM

94
12
Fault Fault Cause Recommended measures
list code

11 01 Short circuit contact return signal network • 1)


15 01…3F Stepping motor position or The diagnostic value is made up of the
speed not reached faults listed or their combination.
The individual diagnostic codes are added
hexadecimal.
01 Positioning fault air stepping motor • With sporadic occurrences improve EMC measures.
02 Positioning fault fuel stepping motor
04 Positioning fault auxiliary stepping motor 1 With permanent occurrence, replace relevant
08 Positioning fault auxiliary stepping motor 2 stepping motors (see diagnostic code).
10 Speed not reached
20 Positioning fault auxiliary stepping motor 3 • Check if motor is overloaded
16 00…23 Plausibility fault in ECR The diagnostic code describes the cause
00 Fault ratio curve air stepping motor • Check ratio curve of relevant motor or FC module
01 Fault ratio curve fuel stepping motor and parameter if necessary.
02 Fault ratio curve auxiliary stepping motor 1
03 Fault ratio curve auxiliary stepping motor 2
04 Fault ratio curve auxiliary stepping motor 3
05 Fault ratio curve frequency converter
0A P-content outside of permissible range • Check O2 control parameter and adjust if necessary
0B I-content outside of permissible range
0C Tau outside of permissible range
0D Calculated O2 set point outside • Check if the values entered are valid.
of permissible range If necessary repeat setting for O2 control
0E Calculated O2 min value outside
of permissible range
0F Calculated O2 ratio value outside
of permissible range
13 Load /point number input of the
ABE outside of permissible range
14 Calculated standardisation
value outside of permissible range
20 With hysteresis compensation, exceeding 1)
the permissible adjustment range
21 Load /point number input of the ABE
outside of permissible range
22 At switch command none
of the def. cases was met
23 At switch command no defined
ECR phase was recognised
17 01–03, 3F Internal communication fault ECR
01 TimeOut at programme run 1)
synchronisation of data transfer
02 TimeOut at data transmission
03 CRC fault at data transfer
3F Different values detected at
data synchronisation
18 – Invalid curve data Check curve data for invalid entries.
• For initial commissioning of the unit:
Correct to the valid value range
• If previously operating correctly:
Replace defective base unit

1) With sporadic occurrences improve EMC measures.

With permanent occurrence replace W-FM

95
12
Fault Diagnostic Cause Recommended measures
code code

19 01…2F Fault at comparison pot channel A to B. The diagnostic value is made up of the faults listed
The diagnostic code shows which motor or their combination. The individual diagnostic codes
is faulty. are added hexadecimal.
01 Air stepping motor faulty at comparison • With sporadic occurrences, improve EMC
pot channel A to B measures.
02 Active fuel stepping motor faulty • With permanent occurrence, replace relevant
at comparison pot channel A to B steppingmotors (see diagnostic code).
04 Auxiliary stepping motor 1 faulty
at comparison pot channel A to B
08 Auxiliary stepping motor 2 faulty
at comparison pot channel A to B
20 Auxiliary stepping motor 3 faulty
at comparison pot channel A to B
1A 01 The curve gradient of a partial Max. gradient between two support points:
curve section is too high - 3.6° per 0.1 % (30s ramp)
- 1.8° per 0.1 % (60s ramp)
- 0.9° per 0.1 % (120s ramp)
Alter load matching of the support point until
the conditions are met.
1B – The programming mode remains active Curve parametering should be carried out in manual
in phase 62 and the set positions operation to avoid shutting down the load controller.
(normal operation) have not been However, if the TL reacts this can lead to shutdown.
reached The value (curve point) currently being changed
can however be locked in Standby or lockout

1C 01…3F The relevant ignition positions The diagnostic value is made up of the faults listed
have not been parametered. or their combination. The individual diagnostic
codes are added hexadecimal.
01 Ignition pos. air stepping motor not param. Set ignition position
02 Ignition pos. of active fuel stepping motor
not parametered
04 Ign. pos. auxiliary stepping motor 1 not param.
08 Ign. pos. auxiliary stepping motor 2 not param.
10 Ignition pos. FC not parametered
20 Ign. pos. auxiliary stepping motor 3 not param.
1D 01…3F Run time fault stepping motors / The diagnostic value is made up of the faults listed
frequency converter or their combination. The individual diagnostic
codes are added hexadecimal.
01 Run time fault air stepping motor • Check motor for mechanical overload.
02 Run time fault current fuel stepping motor • Check supply voltage and fuses.
04 Run time fault auxiliary stepping motor 1 • Drive ramp of the stepping motor must be ≤
08 Run time fault auxiliary stepping motor 2 parametered ramp.
10 Run time fault frequency converter • Ramp of the frequency converter must be smaller than the
20 Run time fault auxiliary stepping motor 3 ramp parameter in the WM-F. Recommendation 20%.
1E 01…3F The base unit has detected, that one The diagnostic value is made up of the faults listed
or more stepping motors (incl. FC) have or their combination. The individual diagnostic
not reached the special position codes are added hexadecimal.
required for the phase.
01 Special pos. air stepping motor not reached • Check motor for mechanical overload.
02 Special pos. current fuel stepping motor • Check supply voltage and fuses.
not reached
04 Spec. pos. auxiliary stepping motor 1 not reached
08 Spec. pos. auxiliary stepping motor 2 not reached
10 Spec. pos. FC (speed) not reached
20 Spec. pos. auxiliary stepping motor 3 not reached

96
12
Fault Diagnostic Cause Recommended measures
code code

1F 01…06 Fault detected with FC module With sporadic occurrences:


Check CAN Bus wiring or improve EMC measures.
With permanent occurrence, replace W-FM
01 Fault internal test in FC module
02 Wrong rotation direction of fan • Check rotational direction of motor and transmitter disc.
• Check rotational direction on FC, correct if necessary
03 Impulse sequence and length at speed • Check installation of transmitter disc and transmitter.
input different than expected • Check distance and connection inductive transmitter.
04 Nominal speed not reached stable • Check motor is running
• Check distance and connection inductive transmitter.
05 Air stepping motor(s) did not reach open • Check motor(s) for mechanical overload.
position for standardisation • Check voltage supply to stepping motors
06 Fault internal speed test FC module
21 – Safety circuit opened
22 – Temperature guard value exceeded
23 – Extraneous light during start up
24 – Extraneous light during shutdown
25 – No flame end of safety time ts1
26 – Flame failure during operation
27 – Impermissible air pressure signal “On”
28 – Impermissible air pressure signal “Off”
29 – Impermissible message “On”
from fan relay contact
2A – Impermissible message “Off”
from fan relay contact
2B – Impermissible air pressure signal “On”
flue gas recirculation
2C – Impermissible air pressure signal “Off”
flue gas recirculation
2D 00, 01 Impermissible message “On”
from valve closing contact
2E 00, 01 Impermissible message “Off”
from valve closing contact
2F – Low gas pressure switch has reacted Check gas supply pressure
30 – High gas pressure switch has reacted Check setting gas pressure switch
31 – Gas pressure switch VP has reacted V1 leaking
32 – Gas pressure switch VP not reacted V2 leaking
33 – Unexpected oil pressure present
34 – Low oil pressure switch has reacted Min. permissible oil pressure not reached
35 – High oil pressure switch has reacted Max. permissible oil pressure exceeded
36 No start release oil
37 – No release residual oil immediate start
38 – Low gas programme active Check gas supply pressure
39 01…03 Parameter of safety time faulty
01 Internal fault at timer1
02 Internal fault at timer2
03 Internal fault at timer3
3A – No burner ID defined Parameter burner ID
3B – No engineer’s password defined Enter engineer’s password
40 – Setting internal safety relay With sporadic occurrences, improve EMC
measures.
With permanent occurrence, replace W-FM
41 – Internal ignition contact setting Check wiring of output

97
12
Fault Diagnostic Cause Recommended measures
code code

42 01…FF Contact setting fault of internal The diagnostic value is made up of the faults listed
fuel valve relays or their combination. The individual diagnostic codes
are added hexadecimal.
01 Safety valve - Oil Check wiring of output
02 Fuel valve V1 - Oil
04 Fuel valve V2 - Oil
08 Fuel valve V3 - Oil
10 Safety valve - Gas
20 Fuel valve V1 - Gas
40 Fuel valve V2 - Gas
80 Fuel valve V3 - Gas
43 01…0D Fault during plausibility check
01 No fuel selected
02 No def. fuel train parametered
03 Variable “train” not defined
04 Variable “fuel” not defined
05 Undefined mode of operation with LC
06 Pre-purge time gas too short
07 Pre-purge time oil too short
08 Oil Safety time 1 too long
09 Gas Safety time 1 too long
0A Ignition - Off - Time > ts1 Gas
0B Ignition - Off - Time > ts1 Oil
0C Oil Safety time 2 too long
0D Gas Safety time 2 too long
44 01…0A Deactivated inputs connected
01 Controller input to X62 Activate input or connect nothing
02 Air pressure switch input X3-02
03 Brn Fan / FGR air pressure switch X4-01:3
04 Low gas pressure switch terminal X9-03:4
05 High gas pressure switch terminal X9-03:3
06 Low oil pressure switch terminal X5-01
07 High oil pressure switch terminal X5-02
08 Start signal Oil input X6-01:1/2
09 Residual Oil immediate start input X6-01:3/4
0A Start signal Gas input X7-03
45 – At STB test activated a controlled
shutdown was carried out
46 01…07 A programme stop has been activated
01 Phase 24: Pre-purge If the programme stop (see Ch. 9.6.1) is no longer
02 Phase 32: Pre-purge for FGR required, deactivate it.
03 Phase 36: Ignition positions
04 Phase 44: End first safety time
05 Phase 52: End second safety time
06 Phase 72: Post-purge position
07 Phase 76: Post-purge position FGR
47 – Start release Gas = Off
48 – 1 sensor operation parametered,
but 2 flame signals present

98
12
Fault Diagnostic Cause Recommended measures
code code

50 00…07 Fault in button value check 1)


51 00…07 Time block overrun
52 01…03 Stack fault
53 01 Faulty reset condition
58 – Parameter setting is incorrect Reset unit
59 – Parameter setting is incorrect If this fault occurred during parametering:
5A – Parameter setting is incorrect check parameter last changed for plausibility.
5B – Parameter setting is incorrect If reset does not achieve faultless condition:
5C – Backup restore was carried out Restore parameters from ABE
5D – Internal fault Otherwise replace defective base unit.
5E – Internal fault
5F – Parameter setting is incorrect
60 – Internal fault
61 01…23 Internal fault
70 01…04 Fault at rectification of 1)
lockout information
71 – Manual lockout with contact The lockout by the external contact
is cancelled by re-activating.
72 01…04 Plausibility fault at fault entry 1)
80 01…03 Impermissible cond. auxiliary stepping motor3 With sporadic occurrences, improve EMC measures.
81 01…03 Impermissible condition air stepping motor
82 01…03 Impermissible con. gas stepping motor (Oil) With permanent occurrence, replace relevant motor.
83 01…03 Impermissible condition oil stepping motor
84 01…03 Impermissible cond. auxiliary stepping motor1
85 01…03 Impermissible cond. auxiliary stepping motor2
86 01…03 Impermissible condition of internal LC 1)
87 01…03 Impermissible condition of ABE With sporadic occurrences,
improve EMC measures.
With permanent occurrence, replace ABE
88 01…05 Plausibility fault
01 Non defined fault stepping motors With sporadic occurrences,
02 Non defined fault load controller improve EMC measures.
03 Non defined fault ABE With permanent occurrence replace defective unit
04 Non defined fault FC module (see diagnostic code) or base unit.
01 Non defined fault O2 module
90 – ROM-CRC fault auxiliary stepping motor3
91 – ROM-CRC fault air stepping motor
92 – ROM-CRC fault gas stepping motor (oil)
93 – ROM-CRC fault oil stepping motor
94 – ROM-CRC fault auxiliary stepping motor1
95 – ROM-CRC fault auxiliary stepping motor2
96 – ROM-CRC fault load controller
97 – ROM-CRC fault ABE
98 – Multiple components with the same Check addressing of connected components
address on the CAN Bus and correct if necessary.
99 – CAN is in BusOff Check CAN wiring
9A – CAN Warning Level 1)
9B 01, 02 CAN Queue overrun
1) With sporadic occurrences,
improve EMC measures.
With permanent occurrence, replace W-FM

99
12
Fault Diagnostic Cause Recommended measures
code code

A0 01…1F Auxiliary stepping motor3 has signalled fault With sporadic occurrences,
A1 01…1F Air stepping motor has signalled fault improve EMC measures.
A2 01…1F Gas stepping motor has signalled fault With permanent occurrence,
A3 01…1F Oil stepping motor has signalled fault replace the relevant motor.
A4 01…1F Auxiliary stepping motor1 has signalled fault
A5 01…1F Auxiliary stepping motor2 has signalled fault
01 CRC fault at ROM test
02 CRC fault at RAM test
04 Fault in button value test
05 Time block overrun
07 Sync fault or CRC fault
08 Revolution counter
09 Fault at stack test
0C Temperature warning and shutdown Check housing temperature (max. 60° C)
0D Wrong rotation direction
0E Ramp time for stretch too small • Match ramp time to slowest motor
• Reduce spanning between special positions
10 Timeout at AD change
11 Fault at ADC test
12 Fault at AD change
13 Stepping motor is outside of the valid Check setting range (0-90°)
degree of angle (0-90°)
15 CAN fault Check CAN wiring
16 CRC fault of one parameter section
17 Section was opened too long Reset unit
18 Section is damaged If this fault occurred during parametering:
19 Invalid access to parameter check parameter last changed for plausibility.
1B Fault at copying parameter section If reset does not achieve faultless condition:
Restore parameters from ABE
Otherwise, replace defective base unit.
1E Invalid setting in drive order Check special positions are within valid range
1F Plausibility fault internal
A6 10…FF Internal LC has signalled fault Type of fault: see diagnostic code
10 No actual value increase 1)
12 Invalid XP identified
13 Invalid TN identified
14 TV larger than identification time
15 Invalid TV identified
16 Timeout during observation time
17 Cold start thermal shock protection is active
18 Timeout during adaption load
22 Temp controller Set point larger limit value
30…32 Internal fault load controller
33 Invalid CRC when reading a section Reset unit, poss. repeat Backup Restore
34…3B Internal fault load controller 1)
40 Section open too long Reset unit. If this fault occurred during parametering:
check parameter last changed for plausibility.
If reset does not achieve faultless condition:
Restore parameters from ABE.
Otherwise, replace defective base unit.
41…43 Internal fault load controller 1)

1) With sporadic occurrences, improve EMC measures.


With permanent occurrence, replace W-FM

100
12
Fault Diagnostic Cause Recommended measures
code code

44 Section was set to ABORT Reset unit


45 Section was set to RESTO If this fault occurred during parametering: check para-
46 Section has invalid status meter last changed for plausibility. If reset does not
achieve faultless condition: Restore parameters from ABE
Otherwise, replace defective base unit.
4A…4E CAN fault 1)
50 PT 100 sensor short circuit Check wiring and sensor
on input X60:1/4
51 PT 100 sensor break
on input X60:1/4
52 Break in compensation line
on input X60:2/4
53 PT 1000 sensor short circuit
on input X60:3/4
54 PT 1000 sensor break
on input X60:3/4
55 Ni 1000 sensor short circuit
on input X60:3/4
56 Ni 1000 sensor break
on input X60:3/4
57 Over voltage on input X61
58 Break or short circuit
on input X61
59 Over voltage on input X62
5A Break or short circuit
on input X62
60…6F Internal fault load controller 1)
70 Measurement value variation, PT 100 sensor Check wiring of input
71 Measurement value variation, PT 100 line
72 Measurement value variation, PT 1000
73 Measurement value variation, PWM 1)
74 Measurement value variation, U input X61 • Check wiring of input
75 Measurement value variation, I input X61 • Check signal for ripple voltage
76 Measurement value variation, U input X62
77 Measurement value variation, I input X62
78 Over voltage or wrong polarity Check wiring of input
PT 100 sensor, input X60
79 Over voltage or wrong polarity
PT 100 sensor, input X60
7A Over voltage or wrong polarity
PT 1000 sensor, input X60
7B Over voltage or wrong polarity PWM 1)
7C Over voltage or wrong polarity • Check wiring of input
U measurement input X61 • Check input voltage or current
7D Over voltage or wrong polarity
I measurement input X61
7E Over voltage or wrong polarity
U measurement input X62
7F Over voltage or wrong polarity
I measurement input X62
80…A6 Internal fault load controller 1)
A7 Impermissible selection for the additional A pressure or temperature sensor must
sensor be fitted to X61 (see Ch. 9.8.3 and 9.8.4)
B0…FF Internal fault load controller 1)
1) With sporadic occurrences, improve EMC measures.
With permanent occurrence replace W-FM
101
12
Fault Diagnotic Cause Recommended measures
code code

A7 01…8A The ABE signals faults. With sporadic occurrences, improve EMC measures.
Type of fault, see diagnostic code
With permanent occurrence, replace ABE
01 …08 Internal fault ABE
09 Fault signal Emergency-Off Function ABE
0A Internal fault ABE
0B Service message through burner starts Carry out service, reset start counter
0C Fault parameter backup
0D Fuel changeover from oil to gas Change to menu “Settings Gas”
0E Fuel change over from gas to oil Change to menu “Settings Oil”
15 …1A Internal fault ABE
1B Fault during copying parameter section Reset unit, if necessary repeat parameter backup
1C…28 Interner Fehler ABE
30 Fault during eBus communication
38 Interface mode could not be stopped
40 Parameter fault PC Tool
88…8A Internal fault ABE
A9 01…1F FC module has signalled a fault
01…09 Internal fault FC module 1)
0A Poss. fault on line to speed • Check cabling, use screened
transmitter • 1)
0C Frequency converter has initiated fault Read fault codes of frequency converter
0D FC module could not control speed • Check if current interfaces on frequency converter
difference within its control limit and FC module are set the same (0/4 to 20 mA).
• Carry out speed standardisation incl.
burner adjustment (fuel / air ratio)
0E Fault during speed calculation test 1)
15 F Interrupted CAN Bus transmission • With sporadic occurrence check CAN Bus wiring,
improve EMC measures
• Check closed resistance, correct if necessary
16 CRC fault of a parameter section Reset unit
17 Section was open too long If this fault occurred during parametering:
18 Section has been destroyed check parameter last changed for plausibility.
19 Invalid access to parameter If reset does not achieve faultless condition:
1B Fault during copying parameter section Restore parameters from ABE
Otherwise, replace defective base unit.
1E Invalid entries in drive order Check special positions for valid range
1F Plausibility fault internal 1)
AB 01…3F O2 module has signalled a fault
01…0A Internal fault O2 module 2)
10 Nernst voltage QGO sensor (B1/M) Check connection (poling, short circuit, break)
12 Voltage thermo element (B2/M)
13 Voltage compensation element (G2/U3)
15 Supply air sensor out of range • Check connection (short circuit, break)
16 Flue gas sensor out of range • Check ambient temperature (-20° C to +400° C)
17…1B Internal fault O2 module during test phase 2)
20 Temperature of O2 sensor too low Check heating start up O2 sensor (Q4/Q5)
21 Temperature of O2 sensor too high Check QGO temperature
22 Fault during calculation test 2)
23 Internal resistance of sensor is smaller • Check connection (poling, short circuit)
5 Ohm or larger 150 Ohm • Replace O2 sensor
1) With sporadic occurrences, improve EMC measures. 2) With sporadic occurrences, improve EMC measures.
With permanent occurrence, replace W-FM With permanent occurrence, replace W-FM
102
12
Fault Diagnostic Cause Recommended measures
code code

24 Reaction time O2 sensor more than 5 s • Check position of O2 sensor


• Check soiling of O2 sensor
• O2 sensor
25 Faulty O2 sensor test Check variation of O2 value
24 Reaction time of O2 sensor more than 5 s • Check position of O2 sensor
• Check soiling of O2 sensor
• O2 sensor
25 Faulty O2 sensor test Check variation of O2 value
31 CRC fault of a parameter section Reset unit
32 Section was open too long If this fault occurred during parametering:
33 Section has been corrupted check parameter last changed for plausibility.
34 Invalid access to parameter If reset does not achieve faultless condition:
38 Fault during copying parameter section Restore parameters from ABE
3E Invalid external entry Otherwise, replace defective base unit.
3F Plausibility internal fault 2)
B0 01, 02 Fault during testing port outputs 1)
B1 01 Fault during short circuit testing 1)
from inputs to outputs
B5 01 Fault during O2 guarding 1)
01 O2 min value not reached • Check settings of ratio curve
• Increase differential O2 set point to O2 min value
02 Invalid O2 min value Define all O2 min values
03 Invalid O2 set point Define all O2 set points
04 Adaption fault point 2 or at 100% Repeat standardisation at this point (Ch. 9.7.1)
05 No valid O2 actual value > = 3 s Check connection O2 module and O2 sensor
06 Air oxygen content at pre-purge • Increase pre-purge time
not achieved • Replace O2 sensor
07 O2 value during operation above 15% • Check installation and connection O2 sensor
BA 01 Test O2 sensor not successful 1)
BF – Fault in connection with O2 control In the fault history immediately prior to fault “BF”
or O2 guard the reason for switch off can be read
C5 01…2F ABE has detected old versions during the The diagnostic value is made up of the faults
version comparison of individual units listed or their combination. The individual diagnostic
codes are added hexadecimal.
01 Software version of LC not current Prior to replacing, any units switch on the system
02 Software version of ABE not current and wait for approx. 1 min. (until the display “parameters
04 Software version of stepping motor(s) not current are being updated” disappears when entering the
08 Software version of FC module not current parameter level). Then reset. If the fault still persists,
10 Software version of O2 module not current replace the relevant unit.
20 Software version of O2 module not current
D1 01…03 Impermissible condition frequency converter 1)
D3 01…03 Impermissible condition O2 module 1)
E1 ROM - CRC fault in FC module 1)
E3 – ROM - CRC fault in O2 module 1)
F0 – Plausibility at interpolation calculation 1)
F1 01…07 Fault during pre-control calculation • Check curve setting
• Check setting of fuel parameter depending
on the fuel selected

1) With sporadic occurrences, improve EMC measures. 2) With sporadic occurrences, improve EMC measures.
With permanent occurrence, replace W-FM With permanent occurrence, replace W-FM
103
12
Fault Diagnostic Cause Recommended measures
code code

F2 07…0A Wrong temperature values from


O2 module during calculation of
air load change
07 O2 module transmitted invalid
value
08 Flue gas temperature outside of Increase permitted flue gas temperature
permitted value range
0A QGO sensor not heated Wait until sensor reaches operating temperature
sufficiently
F3 01 The control algorithm is missing Check control parameters
the PID parameters

104
13 Maintenance 13
13.1 Safety information for maintenance
Failure to carry out maintenance and service Endangering operational safety
work properly can have severe consequen- Maintenance work on the following parts may only be
ces, including the loss of life. Pay close carried out by the manufacturer or their appointed agent
attention to the following safety notes. on the individual components.
DANGER • Combustion manager
• Stepping motors
Detailed information and instructions for maintenance can • Flame sensor
be found in the installation and operating instructions of • Gas pressure switch
the burner. • Air pressure switch
• Oil pressure switch
Qualified personnel • Solenoid valves
Only qualified and experienced personnel must carry out
maintenance and service work.

Prior to all maintenance and service work:


1. Electrically isolate the equipment
2. Close all fuel shut off devices

After all maintenance and service work:


1. Function test.
2. Check flue gas analysis i.e. CO2 / O2 / CO values,
smoke No.
3. Complete a test sheet.

13.2 Maintenance plan


The operator should ensure that combustion plant is
serviced at least
once a year by an agent of the supplier or other suitably
qualified person.
During this service all system components with high wear
and tear, or components with a specific life span should be
replaced. Notes to be made of such exchanges.

105
14 Technical data
14.1 Combustion manager W-FM
Mains voltage AC 230V -15% / +10% Ambient conditions for all components:

Transformer AGG5,220 - primary AC 230 V • Transport DIN EN 60 721-3-2


- secondary 2 x AC 12V - climatic conditions Class 2K2
- temperature ranges -20 to + 70° C
Mains frequency 50...60 Hz ± 6% - humidity < 95 % r. h.

Consumption < 30W • Operation DIN EN 60 721-3-3


- climatic conditions Class 3K5
Type of protection housing IP00, IEC 529 - temperature ranges -20 to + 60° C
- humidity < 95 % r. h.
Protection class I with parts according
to II and III to DIN EN 60 730-1 • Mechanical requirements Class 2M2

Mains pre-fusing (external)max. 16 AT Dew point, freezing, water ingress not permitted
Unit fusing (internal) 6.3 AT (IEC 127 2 / 5)
CE Conformity To the guidelines of the EU
Mains supply input currentinstallation specific Electromagnetic compatibility
EMC 89 / 336 EU incl. 92 / 31 EU
Individual contact loading:
Nominal voltage AC 230V + 10% / - 15%, 50-60 Hz Interference transmission To EN 55022
- Fan motor contactor max. 1 A
- Ignition transformer 2A Interference fastness To IEC 1000-4-3
- Fuel valves Gas 2A
- Fuel valves oil 1A
- Oil pump / solenoid valve max. 2 A
- LP test valve max. 0.5 A Housing dimension
- Alarm output 1A
- Ratings factor cosϕ > 0.4

Signal inputs Input currents/input voltages

UeMaxUmains + 10%
UeMinUmains - 15%
200

leMax 1.5 mA peak


182

leMin 0.7 mA peak

Total contact loading (Safety circuit)

Nominal load AC 230V + 10% / - 15%, 50-60 Hz


Unit input current max. 5 A

Cable lengths max. 100 m (100pF/m)


CAN Bus total length max. 100 m
232
250 82,3
CAN Bus special cable Weishaupt No. 743 192

Cable diameters min. 0.75 mm2


(multi-core to VDE 0100)

The cable diameters of the mains supply (L, N, PE) and the
safety circuit (STB, low water, etc.) must be selected for
the nominal currents relative to the selected external pre-
fusing.
The cable diameters of the remaining conductors should
be dimensioned in relative to the internal unit fusing (max.
6.3 AT).

Internal fusing: F1 6.3 AT (IEC 127 2 / 5)


F 24 AT(IEC 127 2 / 5)
F3 4 AT(IEC 127 2 / 5)

Low-voltage transformer
When the W-FM is fitted into a control panel, the burner
must also be fitted with a low-volt transformer for the
control voltage to the stepping motors.

106
14
14.2 Stepping motors SQM45.../48...
Supply voltage AC 2 x 12 V Cable connection
The connection of the screened Bus cable is via plug
Protection class Install low voltage cables with safe screw terminal Rast 3.5. The two connection sockets
separation from mains voltages (x1, X2) on the stepping motor have the same value.

Consumption - SQM45... 9...15VA Cable and cable screening


- SQM48... 26...34 VA Only special cable (Weishaupt No. 743 192) may be used.
Cable screening must be connected to the circuit board
Angular adjustment max. 90 °< with the flat plug provided.

Installation optional Housing cover


The housing cover must only be removed for the short
Degree of protection to EN 60529 IP54 with relevant period during wiring and addressing. Ensure dirt particles
version of cable entry cannot enter the internals of the stepping motor.
The stepping motor contains a printed circuit board with
Torque: - SQM45... up to 3 Nm ‘static’ sensitive components. Its surface is protected
- SQM48... up to 20 Nm against direct contact by a protective cover. Contact with
the underside of the circuit board should be avoided.
Repeat accuracy ± 0.2 ° The protective cover must not be removed!

Rotation direction Can be set in W-FM

Run times: - SQM45... 10 to 120 s


- SQM48... 30 to 120 s

Weight: - SQM45... approx. 1.0 kg


- SQM48... approx. 1.6 kg

Dimensions

90
,4
15 116 76 ø5
2
12
ø1
0 +0
,0 6
0 5

41
+0,1

3N9
33

2,5 0
ø10 h8
ø16

SQM 45
Groove for
25

Woodruff key
3 x 3.7 DIN 6888
122
137

87

50
Prepared for
self tapping screws
+0,1
6 0 M5, 10mm deep,
to DIN 7500
7814m01

25,5
47 2 x M16x1,5
+0,1
0

P9
5
1,9

Groove for parallel


ø18

key 5 x 28

36
SQM 48 39
2 28
ø14 h8

107
14
14.3 Flame supervision
QRI QRI flame sensor
The infrared flame sensor QRI... has the following
characteristics:
• Infrared flame sensor with IR sensitive sensor for gas
and oil flames
• Integrated flame signal amplifier
• Self checking of flame signal for continuous run
• For front or side (90°) viewing
• Fitted to burner body with flange and clamp

Supply voltage: - Operation DC 14 V + 5%


- TestDC 21 V + 5% bl blue wire = reference
br brown wire = supply conductor
Signal voltage: sw black wire = signal conductor
Range DC 0...5V Z Additional conductor
minimum DC 3.5 V; Display flame approx. 50%

Consumption < 0.5 W

Type of protection IP54


Protection class II

Length of sensor connection cable max. 1.8 m


Length of additional sensor line max. 100 m
Installation optional
Vibration to IEC 68-2-6 max. 1g / 10...500 Hz
Weight with cable approx. 0.175 kg

Ionisation electrode
Flame supervision with ionisation electrode for gas
operation is suitable for continuous run.

Idle voltage approx. Umains


Short circuit voltage max. 0.5mA (AC)
Sensor current
minimum 6 µA (DC); display flame approx. 50%
maximum 85 µA (DC); display flame approx. 100%

Sensor line length max. 100m


(core-ground 100 pF (/m)

Note: With increased sensor line (length) the current at


the sensor electrode decreases. For longer line
lengths where very high Ohmic values are
probable, the use of a low capacity sensor line (i.e.
low-loss ignition cable) may be necessary.

108
14
14.4 Display and operating unit (ABE)
Supply voltage via Bus cable AC 12 V Dimensions

Installation optional

Type of protection to EN 60529 IP54


(Viewing side in installed condition)

Ambient conditions see basic unit (Ch. 14.1)

Door cut-out for panel mounting


Height 12,5 ± 1 mm
Width90.5 ± 1 mm
Depth (within panel) 25 mm
Free space for connection cable (below the unit) 50 mm

Cable - line length max. 100 m


Only original -weishaupt- CAN-BUS cable
(order No. 743 192) must be used.

109
A Notizen

110
A

111
Weishaupt products Max Weishaupt GmbH
D-88475 Schwendi

and service Find Weishaupt adresses


and telephone numbers
on www.weishaupt.de

Print No.. 83054802, June 2004


Printed in Germany
All rights reserved

Oil, gas and dual fuel burners types W and WG/WGL


up to 570 kW
They are used mainly in houses and small buildings.
Advantages: fully automatic, reliable operation, individual
components easily accessible, easy to service, quiet operation.

Oil, gas and dual fuel burners types Monarch


R, G, GL, RGL – up to 10.900 kW
These are used on all types and sizes of central heating
plant. The basic model which has proved successful over
many years is the basis for a variety of versions. These
burners have founded the outstanding reputation of
Weishaupt products.

Oil, gas and dual fuel burners types WK –


up to 17.500 kW
WK types are decidedly industrial burners.
Advantages: Built to the modular system, load dependent
variable combustion head, sliding two stage or modulating
operation, easy to service.

Weishaupt control panels, the proven complement to


Weishaupt burners
Weishaupt burners and Weishaupt control panels form
the ideal unit, a combination which has already proved
successful in hundreds of thousands of combustion
installations. The advantages: Cost saving during planning,
installation, servicing and guarantee work. The responsibility
belongs to one manufacturer.

Product and service are the complete


Weishaupt achievement
An extensive service organisation guarantees Weishaupt
customers the greatest possible reliability. In addition
our customers are looked after by heating firms who have
been working with Weishaupt for many years.

S-ar putea să vă placă și