Documente Academic
Documente Profesional
Documente Cultură
USER MANUAL
Note:
Important!
Warning!
SECURITY WARNING
Users shall read safety instructions available in Section 1 of User manual.
SECTION 1:
Introduction
SECTION 2:
Technical Data
SECTION 3:
Installation
SECTION 4:
Operating Instructions
SECTION 5:
Protection & Diagnostic
SECTION 6:
Maintenance & Safety
6.1 INTRODUCTION
This section describes:
• Maintenance of the MV7000 power stacks, fans and control boards.
• Safety procedures to be carried out prior to servicing MV7000.
No component level maintenance is described. If either power stacks or control boards require
component level maintenance, a request for assistance should be made to CONVERTEAM.
Note: This document provides help for maintenance operation, but does not provide practical
training for the described operations. In addition, maintenance staff shall attend a
dedicated CONVERTEAM training session.
6.2.1 General
Medium voltage capacitors are used in MV7000
• to provide the two voltage levels of the DC link.
• as an integral part of the optional filter circuits (output dv/dt, sinus, …).
• as snubber capacitors in the rectifier.
These capacitors are provided with passive discharge resistors, which allow the stored energy in
each capacitor to be discharged. The discharge circuit is designed to discharge the stored energy
to less than 50V, within 10 minutes after the main AC supply and the auxiliary supply are
disconnected.
WARNING
• To ensure that the equipment is safe to work on, it is mandatory that all external supply
sources be disconnected and locked out, the stored energy in the capacitors
discharged, the absence of voltage verified, and the equipment grounded. Failure to do
so may result in personal injury and/or death.
The minimum required equipment and the procedure to make the drive safe to work on are
described further in this document.
Note: A warning label on the grounding switch cabinet door summarizes the various
requirements for a safe access to the equipment.
Nb of locks = N
ORDER OF THE
OPERATIONS
SYMBOLS
Nb of locks = N
WARNING
For safety reasons, it is prohibited to reproduce duplicate interlock keys.
Wait 10 minutes
Voltage yes
> 50 V DC?
no
no
Voltage yes
> 50 V
AC or DC?
no
Abnormal condition
yes during grounding procedure.
Voltage
> 50 V DC? Damage probably!
Call CONVERTEAM
no
Grounding finished
Figure 6-2 Drive Shutdown and Grounding Flow Chart (main steps only)
Step 5: Isolate the MV supply circuit breaker by racking it out. Lock out in accordance with local
codes and with installation specific lockout procedures.
Lock out the precharge circuit breaker.
Lock out the excitation supply circuit breaker, if applicable.
Step 6: Close and lock the grounding switch corresponding to the MV supply circuit breaker.
Step 8: Wait 10 minutes to allow for capacitor discharge. You may use the keypad display to
watch the DC link voltage decreasing. However, from a safety viewpoint, this is not a safe
voltage indicator.
After 10 minutes, proceed to the grounding procedure.
Step 9: Get the key(s) to operate the grounding switch(es) from the Kirk key interlocking system.
(Refer to Section 6.2.3.)
Step 11: Get the keys to open the doors of the drive cubicles from the Kirk key interlocking system.
(Refer to Section 6.2.3.)
Open the door of the cubicle with the grounding switch at first.
WARNING
• Be aware of possibly live parts in your proximity.
Step 14: Open and lock out all remaining auxiliary supplies:
• 3AC 400V for cooling pumps,
• 1AC 230V for cubicle fans,
• 1AC 230V UPS-buffered supply for the controller,
• 1AC 230V for receptacles (socket outlets),
• and others (project specific).
Verify the absence of voltage in all these low-voltage circuits.
measure at the
copper plates
Measure the voltage at the input terminals of MV7000. Proceed as follows for each 3-phase system
of the input voltage, starting with the rearmost system.
Step 19: Measure the phase-to-phase voltages and the phase-to-ground voltages.
If any of the voltages is > 50 V DC or AC, stop the grounding procedure and proceed to
Section 6.2.4.3.
Step 20: If all voltages of this 3-phase system are < 50 V DC or AC, connect the ground clamp of
the grounding lead for the input terminals to the copper ground bar.
WARNING
• For handling the ball head caps, always use the isolating handle.
Step 21: Connect the grounding lead to the 3 fixed ball points of the input terminals for this
3-phase system.
Step 22: Repeat Step 19 to Step 21 for the other 3-phase systems of the input voltage. (2 systems
for 12-pulse, 4 systems for 24-pulse configuration.)
Step 23: Open the doors to get access to the MV7000 output terminals:
If the drive is equipped with a filter, the output terminals U, V, W are located in the filter
cubicle; otherwise they are located in the inverter cubicle (AC output section).
For parallel drives, there may be two filter cubicles with 3 output terminals each; start with
one filter cubicle then.
Step 24: Measure the voltage at the output terminals of MV7000: Measure the phase-to-phase
voltages and the phase-to-ground voltages.
If any of the voltages is > 50 V DC or AC, stop the grounding procedure and proceed to
Section 6.2.4.3.
Step 25: If all voltages are < 50 V DC or AC, connect the ground clamp of the grounding lead for
the output terminals to the copper ground bar.
Step 26: Connect the grounding lead to the 3 fixed ball points of the output terminals U, V, W.
Step 27: For parallel drives with two filter cubicles (3 output terminals each), repeat Step 24 to
Step 26 for the other set of output terminals.
+ 0 –
clamp capacitors
(behind inverter stack)
inverter stack
+ 0 –
(at center heatsink)
inverter stacks
+ 0 0 –
(at heatsink between (at heatsink between
diode and isolation) diode and isolation)
U1,V1,W1
U,V,W
M
U2,V2,W2
Prior to working on MV7000, ensure that the drive has been safely grounded in accordance with
the Drive Grounding Procedure. Refer to Section 6.2 of this manual.
Water leakage X
Component deterioration X
Prior to working on MV7000, ensure that the drive has been safely grounded in accordance with
the Drive Grounding Procedure. Refer to Section 6.2 of this manual.
Only staff trained by CONVERTEAM must carry out maintenance operation described in this
section.
Metal bolts and screws must never be replaced by an isolating type and vice versa.
4a
2
1 3
0
6
4b
Figure 6-8 IGBT replacement - 1/4 Figure 6-9 IGBT replacement - 2/4
9
5
10
pin (black)
Figure 6-10 IGBT replacement - 3/4 Figure 6-11 IGBT replacement - 4/4
Do not adjust the central nut of the inverter stack. If accidentally it got disturbed, then
this stack should not be installed in MV7000. Contact CONVERTEAM.
Before changing a stack, stop the cooling unit and decrease the hydraulic pressure.
(Refer to Section 6.5)
Figure 6-13 Freewheeling diode stack Figure 6-14 Freewheeling diode stack
replacement - 1/4 replacement - 2/4
3
6
Forklift supporting
Figure 6-15 Freewheeling diode stack Figure 6-16 Freewheeling diode stack
replacement - 3/4 replacement - 4/4
After the replacement, add de-ionized water to the cooling unit. (Refer to Section 6.5.)
Check that there is no leakage in the inverter cubicle before starting MV7000.
Before changing a stack, stop the cooling unit and decrease the hydraulic pressure.
(Refer to Section 6.5)
3
1
Figure 6-17 IGBT stack replacement - 1/5 Figure 6-18 IGBT stack replacement - 2/5
5
8
4
Forklift supporting
Figure 6-19 IGBT stack replacement - 3/5 Figure 6-20 IGBT stack replacement - 4/5
After the replacement, add de-ionized water to the cooling unit. (Refer to Section 6.5.)
Check that there is no leakage in the inverter cubicle before starting MV7000.
Before changing a stack, stop the cooling unit and decrease the hydraulic pressure.
(Refer to Section 6.5.)
1
3 4
2
5 8
Forklift supporting
Figure 6-22 Rectifier diode stack Figure 6-23 Rectifier diode stack
replacement - 1/2 replacement - 2/2
After the replacement, add de-ionized water to the cooling unit. (Refer to Section 6.5.)
Check that there is no leakage in the diode front-end cubicle before starting MV7000.
Filling circuit:
• Filling circuit enables to fill the water circuit with pure water and to add some water after
draining or after a leakage. It is fixed with a screwed type connection of size 3/8’’ and a valve.
VG031
DEIONIZED WATER
MAIN CHARACTERISTICS RAW WATER CIRCUIT
CIRCUIT
Static operating pressure 1.5 bar
Maximum operating pressure (Ps) 6 bar 6 bar
Test pressure 10 bar 10 bar
Pressure drop ≤ 1 bar
Filling circuit pressure 1.5 bar (-0 to +0.5)
Minimal Flow Refer to specific project documents
Initial pressure at empty tank 0.4 bar
Note (1): To convert following calcium hardness units to French degree (°F), use the following
multiplication factors.
X: Deionized water flow alarm and fault settings are defined in project documents, as they depend
on project configuration (MV7000 rating and optional items).
Please refer to cooling unit supplier document for settings and adjustments procedure.
Before starting work on MV7000, ensure that the drive has been safely grounded in accordance
with the Drive Grounding Procedure. Refer to Section 6.2 of this manual.
The deionized water flow circuit can be divided into two sections, which will be prepared
independently:
• Main flow circuit: pump(s), exchanger, rectifier and inverter heat sinks,
• Deionization flow circuit (interfaces at points P0, P1 and P6 in hydraulic diagram): deionization
cartridge, expansion tank and filling circuit.
VD090
Main circuit
VD031
VG040
pumps
To prepare the cooling unit for the maintenance procedures as per Section 6.5.4.2, the following
steps must be performed:
After
Every Every Every Every Every main part
Operation Conditions
month year 2 years 5 years 10 years replacement
(1)
Measurement of motor
3 During operation X
pump current
During operation,
Deionization cartridge
4 no pressure in X
replacement
deionization circuit
During operation,
5 Cleaning of filter FI030 no pressure in X X
deionization circuit
Pressure check in
8 expansion tank and Stopped X
inflate if needed
Note (1): main part replacement means: pump, exchanger, power stack, etc.
To carry out the mentioned operations, please refer to detailed instructions in the cooling
unit supplier documentation.
For replacement of hoses, contact CONVERTEAM. Only qualified personnel must supervise this
operation.
The preventive maintenance schedule shown below is based on raw water quality as per
CONVERTEAM specification (refer to section 6.5.1). Non-compliant water quality may result
in more frequent needs for maintenance operation and possible damage to the cooling unit.
6.6.3.2 Restart
Preparation:
• Close MV7000 cubicle doors.
• Open grounding switch.
• Unlock and switch on main supply and pre-charge supply.
• Select MV7000 normal control mode.
Starting:
• Start auxiliaries, check for no fault and no alarm (1).
• Start drive, check for no fault and no alarm (1).
• Increase the set point slowly to the required operational value, check for no fault and no
alarm.
Note: (1) According to project conditions, these steps are in sequence or both together.
LIMITATION OF LIABILITY
Before following the instructions of this user manual and operating the MV7000 drive, users are
advised to refer to Section 1 of user manual – “limitation of liability”.